K-3980 Battery Load Bank
K-3980 Battery Load Bank
Model No.: LB-4811 (48V/110V 100A)
Typical application: Telecom & Power Utility
LB-4811 DC load unit is specially designed for discharge experiment, battery capacity
test, battery maintenance, engineering examination and other tests for DC power with
load. It is specifically designed for nominal voltage of 48V and 110V battery system
with max discharge current of 100A. This makes it applicable for battery discharge in
the areas of telecom and power substation.
With its optional Data Acquisition Case (DAC), you will have a real-time monitoring for
the whole process of discharge with wireless communication in PC.
Our Advantages
1) K-3980 has different customized models to meet requirement of customers from
various industries exactly.
2) Its optional data loggers enables a wireless communication with computer. And it
will monitor the whole process of discharge including voltage of EACH cell.
3) Standard discharge function and other functions like assistant discharge, parallel
load, external load, charge monitor. Compatible with non-Kongter load banks.
4) Rugged, reliable and durable with very good price.
Features
Optional wireless DAC enables real-time PC monitor during measurement
It sets 4 conditions for discharge auto shut-down:
Discharge time, discharge capacity, string voltage and cell voltage
Continued discharge available when previous discharge is stop abnormally
Parallel connection of two units for higher discharge current
Optional DAC
Assistant discharge to add load to even non-Kongter load banks
Can monitor measurement of other load banks or battery charger
Accurate data measurement and vivid waveforms of PC software
Auto sorting for lag-out batteries during discharge
Safe circuits avoids damage to battery during measurement
Powerful management software for data analysis and report generation
Automatic protection upon over-heating and overload
Optional Data Acquisition Case (DAC)
Each DAC is recording voltage of up to 12 cells. It has wireless communication with
Connection with 1.2V or 2V cells:
K-3980 main unit and PC. And it is capable to measure all type of batteries (1.2V, 2V,
6V & 12V). Kongter also offers customized DAC for other battery types.
DAC numbers are easily expandable to cover more battery volumes.
Its Connection:
One DAC is connected with 12 cells of 1.2V, 2V or 4 cells of 12V (or 6V). Therefore, in
Connection with 6V or 12V cells:
different battery systems, they require different amount of DACs. With DAC, K-3980
and Kongter PC software will be able to monitor and record voltage of each cell
together with other parameter like String Voltage, Current, Discharge Capacity and so
on.
For the model of LB-4811, it will require 5 standard DACs for measurement of 2V, 6V
and 12V cells.
K-3980 Battery Load Bank
Composition: Technical Parameters
Standard parts: Power supply AC 220V/110V, 50/60Hz;
1
Main unit of load bank 1) Standard: 1.2V , 2V, 6V and 12V
Carrying case Cell type 2) Customized: 12V ONLY or other uncommon
Data View software battery types.
Set of 3m/10ft load cables 10V-55.2V(nominal: 48V)
3m/10ft voltage test leads 10V-126.5V(nominal: 110V)
Discharge voltage range
PC communication terminal Constant current of 100A in the range of:
Ground cable 43.2-55.2V & 99-126.5V
AC Power cord Single load bank: 10A-100A
Discharge current range
USB with backup info Parallel load: 10A-200A
Antenna Current: 1%
Accuracy
Voltage: 0.5% – 0.8%
Optional: Current: 0.1 A or 0.5%
Resolution
DAC package Voltage: 0.001 V
Current clamp for external loads Sampling Interval 5s –1min
Parallel load cable Discharge pattern Constant current
Display 128*64 pixel LCD
Data transfer USB, Radio Frequency (for DAC to load bank)
Operation Temperature 0℃~40℃ (32 – 104 °F)
Humidity 5%~90% Relative humidity
Standard CE marking, EMC standard
Main Unit Dimension 520 x 202 x 355 mm
Main unit Weight 16 kg
*NOTE:
1) Quantity of DAC and cable in standard DAC package are based on 2V, 6V and
12V. For measurement of 1.2V Ni-cd batteries, you will require some more DACs
and relevant cables.
Kongter PC Software
All standard load units of K-3980 come with PC software. With the software, you have
a real-time data monitoring, analyze the testing data and easily print out the complete
report.
K-3980 PC Software
Kongter Test & Measurement Co., Limited
#405, Bldg 62, Songpingshan, Langshan Rd., Shenzhen China
TEL: +86-755-2691 6832 Web: www.kongter.com Email:
[email protected]