Part3-Bracing Design - Euro Code
Part3-Bracing Design - Euro Code
CODE
Eng.HEBA ADEL
Eng.Heba Adel – Structural Engineer-Alexandria university
Bracing
General
Bracing is required to resist lateral loads, principally wind loads, and
the destabilizing effects of the imperfections defined in Section 5.3
of BS EN 1993-1-1. The equivalent horizontal forces, which cause the
forces in the bracing, do not increase the total load on the whole
structure, because they form a self-equilibrating load case.
Vertical bracing
1|Page
Eng.Heba Adel – Structural Engineer-Alexandria university
at the centre of the building (but this is rarely done due to the
need to begin erection from one braced bay at, or close to, the
end of the building)
in each portion between expansion joints (where these occur).
Where the side wall bracing is not in the same bay as the plan bracing
in the roof, an eaves strut is required to transmit the forces from the
plan bracing into the wall bracing.
2|Page
Eng.Heba Adel – Structural Engineer-Alexandria university
Cross braced angles or flats (within a masonry cavity wall) may be used
as bracing (as shown in Figure 4.31). In this case, it is assumed that
only one of the diagonal members acts in tension under wind load.
3|Page
Eng.Heba Adel – Structural Engineer-Alexandria university
4|Page
Eng.Heba Adel – Structural Engineer-Alexandria university
5|Page
Eng.Heba Adel – Structural Engineer-Alexandria university
6|Page
Eng.Heba Adel – Structural Engineer-Alexandria university
7|Page