ARP5015B
ARP5015B
Superseding ARP5015A
RATIONALE
Modifications are made within the document for the new generation aircraft electrical systems, update the external
document references and general updates and corrections.
TABLE OF CONTENTS
1. SCOPE.................................................................................................................................................................... 3
3. TECHNICAL REQUIREMENTS.............................................................................................................................. 8
3.1 Equipment Specifications ........................................................................................................................................ 8
3.1.1 Output Rating .......................................................................................................................................................... 8
3.1.2 Alternator Speed ..................................................................................................................................................... 8
3.1.3 Temperature Rise ................................................................................................................................................... 8
3.1.4 Dielectric Tests ....................................................................................................................................................... 8
3.1.5 Power Supply Safety Standards Testing ................................................................................................................. 8
3.1.6 Continuous Rating................................................................................................................................................... 8
3.1.7 Overload Rating ...................................................................................................................................................... 8
3.1.8 Nominal Voltage Rating .......................................................................................................................................... 8
3.1.9 Adjustable Voltage Range....................................................................................................................................... 8
3.1.10 Highest Phase Voltage Limiting .............................................................................................................................. 8
3.1.11 Line Drop Compensation ........................................................................................................................................ 9
3.1.12 Voltage Regulation Steady State ............................................................................................................................ 9
3.1.13 Voltage Transients .................................................................................................................................................. 9
3.1.14 Short-Circuit Current ............................................................................................................................................... 9
3.1.15 Voltage Modulation ................................................................................................................................................. 9
3.1.16 Frequency of Voltage Modulation ........................................................................................................................... 9
3.1.17 Phase Voltage Balance with Balanced Load .......................................................................................................... 9
3.1.18 Phase Voltage Displacement with Balanced Load................................................................................................ 10
3.1.19 Phase Voltage Balance with Unbalanced Load .................................................................................................... 10
__________________________________________________________________________________________________________________________________________
SAE Technical Standards Board Rules provide that: “This report is published by SAE to advance the state of technical and engineering sciences. The use of this report is
entirely voluntary, and its applicability and suitability for any particular use, including any patent infringement arising therefrom, is the sole responsibility of the user.”
SAE reviews each technical report at least every five years at which time it may be revised, reaffirmed, stabilized, or cancelled. SAE invites your written comments and
suggestions.
Copyright © 2018 SAE International
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system or transmitted, in any form or by any means, electronic, mechanical, photocopying,
recording, or otherwise, without the prior written permission of SAE.
TO PLACE A DOCUMENT ORDER: Tel: 877-606-7323 (inside USA and Canada) SAE values your input. To provide feedback
Tel: +1 724-776-4970 (outside USA) on this Technical Report, please visit
Fax: 724-776-0790 http://standards.sae.org/ARP5015B
Email: [email protected]
SAE WEB ADDRESS: http://www.sae.org
Downloaded from SAE International by Cristina Menardi, Monday, October 17, 2022
SAE INTERNATIONAL ARP5015B Page 2 of 16
3.1.20 Phase Voltage Displacement with Unbalanced Load ........................................................................................... 10
3.1.21 Individual Harmonic............................................................................................................................................... 10
3.1.22 Total Harmonic Content ........................................................................................................................................ 10
3.1.23 Crest Factor .......................................................................................................................................................... 10
3.1.24 Frequency Regulation ........................................................................................................................................... 11
3.1.25 Frequency Transients ........................................................................................................................................... 11
3.1.26 Frequency Transient Recovery ............................................................................................................................. 11
3.1.27 Frequency Modulation ........................................................................................................................................... 11
3.1.28 Frequency Modulation Rate .................................................................................................................................. 11
3.1.29 No Break Power Transfer (NBPT) ........................................................................................................................ 11
3.1.30 Phase Rotation...................................................................................................................................................... 12
3.2 Personnel Safety ................................................................................................................................................... 12
3.3 Equipment Protection ............................................................................................................................................ 12
3.3.7 E/F Interlock Circuit ............................................................................................................................................... 12
3.4 Current Quality Check ........................................................................................................................................... 12
3.5 Personnel Safety ................................................................................................................................................... 13
3.6 Normal Mode ......................................................................................................................................................... 13
3.7 Maintenance By-Pass Mode.................................................................................................................................. 13
3.7.1 Lost/Open Neutral Conductors ............................................................................................................................. 13
3.7.2 Earth/Ground Fault................................................................................................................................................ 13
3.7.3 System Over Temperature.................................................................................................................................... 13
3.8 Interface Requirements ......................................................................................................................................... 13
3.9 Tools and Test Equipment .................................................................................................................................... 13
3.10 Design and Construction ....................................................................................................................................... 13
3.10.1 General Design Features ...................................................................................................................................... 13
3.10.2 Magnetic Devices .................................................................................................................................................. 13
3.10.3 Environmental Conditions ..................................................................................................................................... 14
3.10.4 Life Expectancy ..................................................................................................................................................... 14
3.10.5 Control Panel and Controls ................................................................................................................................... 14
3.10.6 Protective Devices ................................................................................................................................................ 14
3.10.7 Workmanship ........................................................................................................................................................ 14
3.10.8 Adjustments and Repairs ...................................................................................................................................... 14
3.10.9 Lifting Attachments ............................................................................................................................................... 14
3.10.10 Identification and Marking ..................................................................................................................................... 14
3.10.11 Material, Parts, and Processes ............................................................................................................................. 15
3.10.12 Moisture and Fungus Resistance ......................................................................................................................... 15
3.10.13 Corrosion of Metal Parts ....................................................................................................................................... 15
3.10.14 Interchangeability and Replaceability .................................................................................................................... 15
3.10.15 Cabinet .................................................................................................................................................................. 15
3.10.16 Exterior Finish ....................................................................................................................................................... 15
3.10.17 Human Engineering .............................................................................................................................................. 15
3.10.18 Service and Access .............................................................................................................................................. 15
3.10.19 Noise and Vibration ............................................................................................................................................... 15
3.10.20 Emissions (internal combustion engine ground power units only) ........................................................................ 16
3.10.21 Input Current Distortion (solid state equipment only) ............................................................................................ 16
5. NOTES .................................................................................................................................................................. 16
5.1 Revision Indicator .................................................................................................................................................. 16
1.1 This SAE aerospace recommended practice (ARP) covers the requirements for external ground power equipment
supplying 115/200 V, three-phase, 400 HZ output power measured at the aircraft receptacle. All forms of 400 Hz
ground power including mobile and fixed systems are addressed by this document.
1.2 The intent of this document is to provide specifications for engine generators (alternator), motor generators, and
solid-state converters tailored for performance with modern aircraft, applicable to all unless otherwise noted. Modern
aircraft are requiring higher quality power without interruption which places new constraints on the ground power
units (GPUs) such as unity power factor and no-break-power-transfer (NBPT). The protective trip limits are designed
to allow a two-tier protection utilizing both the aircraft's electrical power generating systems (EPGS) and the GPUs
protection. Some of these specifications will place some new design constraints on the manufacturers of GPUs but
will help promote compatibility with old and new generation aircraft with all types of ground power equipment.
1.3 While GPUs are designed to provide the same quality of power as the aircraft's EPGS, there are differences in rated
capacity. Engines powered GPUs must be sized for the peak kw specified which is why a 125% overload is specified
for GPUs. As an example, increasing the size of the prime mover to match the aircraft's EPGS typical 150 to 200%
overload rating would not be practical
2. APPLICABLE DOCUMENTS
The following publications form a part of this document to the extent specified herein. The latest issue of SAE publications
shall apply. The applicable issue of other publications shall be the issue in effect on the date of the purchase order. In the
event of conflict between the text of this document and references cited herein, the text of this document takes
precedence. Nothing in this document, however, supersedes applicable laws and regulations unless a specific exemption
has been obtained.
Available from SAE International, 400 Commonwealth Drive, Warrendale, PA 15096-0001, Tel: 877-606-7323 (inside USA
and Canada) or +1 724-776-4970 (outside USA), www.sae.org.
SAE J1175 Bystander Sound Level Measurement Procedure for Small Engine Powered Equipment
ISO-461-1 Connector for ground electrical supplies - Part 1: Design, performance and test requirements
2.4 UL Publications
Available from UL, 333 Pfingsten Road, Northbrook, IL 60062-2096, Tel: 847-272-8800, www.ul.com.
Available from National Electrical Manufacturers Association, 1300 North 17th Street, Suite 900, Arlington, VA 22209,
Tel: 703-841-3200, www.nema.org.
NEMA MG-1 NEMA Standards Publication - Motor and Generators (N/A to Solid-State)
Available from IEC Central Office, 3, rue de Varembe, P.O. Box 131, CH-1211 Geneva 20, Switzerland,
Tel: +41 22 919 02 11, www.iec.ch.
IEC/EN 61558-2-6 Safety of Transformers - Reactors, Power Supply Units and Similar Products for Supply Voltages
up to 1,100 V - Part 2-6: Particular Requirements and Tests for Safety Isolating Transformers and
Power Supplying Units Incorporating Safety Isolating Transformers.
IEEE-519 Guide for Harmonic Control and Reactive Compensation of Static Converters
Available from Airlines for America (A4A), 1301 Pennsylvania Avenue, NW, Suite 1100, Washington, DC 20004, Tel: 202-
626-4000, www.airlines.org.
BSI 2G-219 General Requirements for Ground Support Electrical Supplies for Aircraft
DFS-400 Eurostandard 400 Hertz Systems (Obtained from Flughafenverband ADV, Friedrichstrasse 79,
10117 Berlin, Germany, e-mail [email protected] or http://adv.aero/der-verband/ansprechpatner)
This glossary of terms is included as part of this document for use in its interpretation.
The range adjustment, as controlled by the regulator, to enable checking over and under voltage protection devices.
The nominal speed at which the alternator operates to produce 400 Hz.
Downloaded from SAE International by Cristina Menardi, Monday, October 17, 2022
SAE INTERNATIONAL ARP5015B Page 5 of 16
2.9.3 ALTITUDE
The maximum height above sea level at which the unit must operate and maintain characteristics within recommended
limits.
The temperature range in degrees in which the unit must operate and maintain characteristics within recommended limits.
The mode of transferring the aircraft load from aircraft power source to ground power source or vice versa whereby power
to the aircraft is momentarily interrupted.
Constructed so that there are no exposed live parts on the front of the assembly.
The high voltage impressed across the primary and secondary of a transformer and between a component and the
chassis of the unit. This test is used to check insulation characteristics.
The cyclic variation of instantaneous frequency about a mean frequency during any steady state load. Frequency
modulation, in percent, is calculated by taking maximum frequency minus minimum frequency times 100 and dividing this
value by maximum frequency plus minimum frequency. Frequency modulation is a measure of the stability of the power
system’s frequency regulation.
The rate of change of frequency due to frequency modulation when plotted against time.
The band the output frequency stays within except during transients.
The time required for the output frequency to recover to and remain within the prescribed limits after load application or
removal.
The maximum instantaneous deviation of the output frequency from the frequency regulation band.
A rotating or static source supplied by an external ground facility to source electrical power while the aircraft is on the
ground whether it is a point of use or centrally located system.
Downloaded from SAE International by Cristina Menardi, Monday, October 17, 2022
SAE INTERNATIONAL ARP5015B Page 6 of 16
A means of limiting the highest phase voltage of the unit output during any unbalanced load condition.
The rms value of any individual harmonic voltage that is expressed as a percentage of the fundamental.
The total harmonic distortion is a measurement of the harmonic distortion present in a signal and is defined as the ratio of
the sum of the powers of all harmonic components to the power of the fundamental frequency.
A system of increasing the unit output voltage in proportion to the current and power factor in the output cable(s) such that
the voltage is held constant at the aircraft receptacle.
The mode of transferring the aircraft load from aircraft power source to ground power source, or vice versa, whereby the
aircraft and ground power sources are simultaneously connected to the aircraft load and in parallel with each other,
possibly out of synchronization.
The root-mean-square line-to-neutral and line-to-line voltage at which the unit output is rated. The unit is normally set such
that output voltage is maintained at this value.
The terminals on the ground power unit side of the output power feeders. This is considered to be the point of regulation
for the ground power unit.
The normal overload value expressed in kVA at 0.8 power factor for specified time.
The maximum deviation of any of the three phase voltages from the average of the three phase voltages with a designated
three-phase load. The percent unbalance is calculated by taking maximum deviation of any one line-to-neutral voltage
from the average of the three phase voltages times 100 divided by the average of the three phase voltages.
The maximum deviation in degrees from 120 degrees between phases of the alternator voltages during designated load
conditions.
The means by which the voltage is sensed and fed to the voltage regulator.
The maximum current carrying capacity of the GPU deemed unsafe and detrimental to the GPU’s functionality.
Downloaded from SAE International by Cristina Menardi, Monday, October 17, 2022
SAE INTERNATIONAL ARP5015B Page 7 of 16
The total RMS voltage remaining when the fundamental component is removed. This value is determined by calculating
the square root of the sum of the squares of the individual harmonics and expressing this value as a percentage of the
fundamental.
Defined to be the hours/years of use from time of delivery of the equipment to the using activity until its identity is
destroyed by classifying it as salvage and/or subject to cannibalization.
2.9.32 TRIP
Occurs when the output is turned off or the output contactor is opened.
2.9.34 UNIT
Refers to the complete power package such as the prime mover, alternator, and all associated equipment and systems.
The full load value (rated continuous) expressed in kVA at specified power factor. The unit shall be capable of operating at
any power factor from 0.8 lagging to 1.0 (unity).
The cyclic variation about an average of the AC peak voltage during any steady state load. The modulation envelope is
formed by a continuous curve connecting each sine wave peak. Voltage modulation in percent is calculated by taking
maximum voltage minus minimum voltage times 100 and then dividing this value by maximum voltage plus minimum
voltage.
The band the output voltage stays within except during transients.
The band that the output voltage stays within a fixed load.
The maximum momentary deviation of the output voltage from the steady state voltage as a result of step load changes.
The time required for the output voltage to recover to and remain within the prescribed limits after load application or
removal.
Downloaded from SAE International by Cristina Menardi, Monday, October 17, 2022
SAE INTERNATIONAL ARP5015B Page 8 of 16
3. TECHNICAL REQUIREMENTS
All AC voltage characteristics are in reference to the aircraft receptacle, unless otherwise stated.
The engine generator (alternator), motor generator, or solid-state converter shall be of sufficient capacity to produce the
rated kVA at a power factor ranging from 0.8 lagging to 1.0 (unity), and at specified overload limits, for the altitude and
temperature range in which the equipment will be operated.
The designation shall be based on the continuous operating speed of the prime mover, and design of the alternator, to
produce 400 HZ. Not applicable to solid-state converters.
Components of an alternator shall have insulating properties meeting NEMA MG-1 Standards. solid-state converters shall
utilize a minimum of UL Class 180 Transformer insulation systems in any magnetics greater than 1000 VA.
All magnetic components shall have dielectric strength test performed to check insulation characteristics.
For solid-state converters, where this condition is required by the customer for operational or safety reasons, testing to
meet UL 1012 and CSA 22.2 safety standards.
The continuous kVA rating shall be at a specified power factor ranging from 0.8 to 1.0 (unity). Reference 3.6.4 for details
involving environmental conditions and deratings associated with the equipment rating.
The normal overload rating shall be 125% of rated kVA for 5 minutes at a specified power factor ranging from 0.8 to 1.0
(unity). Reference 3.6.4 for details involving environmental conditions and deratings associated with the equipment rating.
The AC system shall be a three-phase, four-wire Wye system with grounded neutral having a nominal voltage of 115/200
V. The grounded neutral shall be solidly tied to the unit chassis ground with sufficient capacity in the tie to handle
maximum ground fault current for a minimum of 5 seconds.
The adjustable voltage range shall be sufficient, in unloaded condition, for checking over-voltage and under-voltage and
subsequent protective devices.
Regulator sensing shall be enough to provide the specified output voltage levels within this document.
A highest phase voltage limiting system is recommended in the voltage regulator to limit the highest phase voltage to
124 V during unbalanced load conditions.
Downloaded from SAE International by Cristina Menardi, Monday, October 17, 2022
SAE INTERNATIONAL ARP5015B Page 9 of 16
A system of automatic line drop compensation shall be incorporated in the voltage regulator to provide constant voltage at
the aircraft receptacle, based on the cable length, regardless of current. Minimum compensation capability shall be 5% at
rated load for a single output.
The voltage at the aircraft receptacle shall stay within the steady state limits shown in Figure 1 for any rated load condition.
The transient response shall be limited to the operating area shown in Figure 1 with step load changes equivalent to the
full continuous load rating shown in 3.1.6.
The short circuit protection system shall remove power if current exceeds the overload capacity of the GPU. No current
limit voltage fold back mode shall be used.
The modulation of phase voltage (including the effects of frequency modulation) shall not exceed 3.5 V when measured as
the peak-to-valley difference between the maximum and minimum peak voltages reached on the modulation envelope
over a period of at least 1 second.
The frequency components of the voltage modulation envelope waveform shall not exceed 100 Hz.
The maximum deviation of any of the three-phase voltage from the average of the three-phase voltages shall not exceed
1% with a balanced three-phase load.
Downloaded from SAE International by Cristina Menardi, Monday, October 17, 2022
SAE INTERNATIONAL ARP5015B Page 10 of 16
The phase voltage displacement with a balanced three-phase load shall be within the limits of 120 degrees ± 2.5 degrees.
The maximum deviation of any of the phase voltages from the average of the three-phase voltages shall not exceed 4%
with 1/3 rated current at 0.8 power factor lagging on any one phase and no load on the other two phases when measured
at aircraft receptacle.
The phase voltage displacement with a 1/3 rated current unbalanced load under 40-kVA, and 1/6 above 40-kVA, shall be
within the limits of 120 degrees ± 4 degrees between any phase (line to neutral) voltages.
The rms value of any individual voltage harmonic shall not exceed 2% of the fundamental (rms) when measured from line-
to-line and line-to-neutral at no load and rated kVA (linear load) at 0.8 power.
The total harmonic content of the output voltage shall not exceed 3% of the fundamental (rms) when measured from line-
to-line and line-to-neutral at no load and rated kVA (linear load) at 0.8 power factor. The total harmonic content of the
output voltage shall not exceed 4% of the fundamental (rms) when measured from line-to-line and line-to-neutral for a 1/3
rated current unbalanced load.
The output frequency shall stay within 400 Hz ± 5 Hz at all steady state loads up through full rated load.
The instantaneous frequency shall not be greater than 430 Hz or less than 370 Hz during full load application or removal
as shown in Figure 2.
Output frequency shall recover to and stay within 400 Hz ± 5 Hz in 2 seconds as shown in Figure 2.
The output frequency modulation shall not exceed 0.25% of the steady state frequency for all loads up to and including full
rated load.
The rate of frequency modulation rate shall not exceed 13 Hz per second.
The unit must be able to operate in an uninterrupted fashion during NBPT and maintain voltage and frequency within
specified limits with onboard and ground power sources out of synchronization by as much as ±30 degrees, ±2 Hz
frequency, ±10 Vrms for maximum time duration of 100 ms. If the NBPT conditions are more severe, the unit's protection
device(s) may be activated.
Downloaded from SAE International by Cristina Menardi, Monday, October 17, 2022
SAE INTERNATIONAL ARP5015B Page 12 of 16
3.2.1 Where necessary, the system shall include personnel and equipment protection from contact to exposed hot
surfaces, exhaust gases and possible exposure to volatile elements (i.e., fuel, oil, grease, etc.) within the
equipment.
3.2.2 For prime movers, the fuel tank and exhaust shall be located appropriately and shielded to prevent exposure to
electrical or engine components during filling or operating conditions.
3.2.3 Each unit shall offer safety to personnel operating or in vicinity of an operating unit. control panel doors should
require a tool or key to open to prevent entrance by anyone other than authorized personnel when practical. inside
the control panel, any voltage over 30 Vrms shall be located, guarded, or enclosed to prevent accidental contact.
suitable warning labels shall be provided if internal voltages decay slowly after shutdown.
3.2.4 All rotating or moving parts shall be shielded to prevent accidental contact while unit is in normal operating mode.
Labels or safety signs shall be provided. Where applicable to local and national standards, fire suppression
systems shall made available.
3.2.5 Control panel shall have unrestricted access to operating personnel and be adequately illuminated for both day
and night operation. All control functions to be clearly identified and grouped according to their function. The
controls to be designed for easy operation while wearing foul weather clothing.
The facility shall automatically remove the power from the output terminals when the AC line-to-neutral exceeds curve of
Figure 1 at output terminals.
3.3.1 The facility shall automatically remove the power from the output terminals when the average AC line-to-neutral
voltage drops below curve of Figure 1 at output terminals.
3.3.2 The facility shall automatically remove the power from the output terminals when the frequency drops below the
limits shown in Figure 2.
3.3.3 The facility shall automatically remove the power from the output terminals when the frequency exceeds the limits
shown in Figure 2.
3.3.4 The facility shall automatically remove the power from the output terminals when the output exceeds the overload
rating of the GPU. Overload protective should have an inverse time characteristic and should operate to protect
the unit if a short-circuit occurs within the GPU or its distribution system. No current limiting voltage foldback
practices shall be used.
3.3.5 The facility shall be provided to prevent the GPU from being connected to the aircraft when the rotation is not
consistent with a ABC, three-phase, Y configuration.
3.3.6 The protective system shall include fault indication that shall be easily identified.
When commanded on by the operator, the facility power shall be provided to the aircraft for a period of 2.5 s without the
aircraft providing the returned interlock signal on Pin F. This will allow time for on-board aircraft controls. It shall not be
possible for the facility to supply power to the aircraft through the interlock connections.
Downloaded from SAE International by Cristina Menardi, Monday, October 17, 2022
SAE INTERNATIONAL ARP5015B Page 13 of 16
The E/F interlock circuit shall remove the power from the output within 2.5 s upon removal or absence of 28 V DC interlock
signal from the aircraft, Pin F. This prevents a plug from staying powered while it is not connected to the aircraft. A
maintenance mode shall be provided to allow servicing and testing the GPU in absence of the 28 V DC interlock signal.
Use of this 28 V DC interlock source should be limited to 1/2 A per cable. An accessible switch or control shall allow
selection of either of the following two modes:
For dummy loads, or no load, or for use with aircraft with no 28 VDC. Shall be clearly identified on the GPU.
Where this condition is required by the facility for operational or safety reasons the GPU shall include protection from open
neutral conductors and remove power from the aircraft upon loss of the neutral.
Where this condition is required by the facility for operational or safety reasons it should be fitted and easily demonstrated.
The over temperature protection system shall cause the unit to be shut down before the critical component temperature
reaches a maximum temperature rating determined by the manufacturer of the GPU or the component manufacturer
incorporated into the GPU.
3.8.1 Each aircraft feeder cable (AS5756/2A) and assembly (AS90362) shall be compatible with an AS90362A
receptacle. Feeder cables shall be dielectrically rated for 115/200 V rms 400 Hz power.
3.8.2 Each output circuit on a multiple output GPU shall be rated at 90 kVA maximum. Each output shall have suitable
over-current protection which will function independently of other outputs. Outputs shall be marked A-B-C-N.
3.9.1 Only standard tools shall be required for maintenance of any parts of the equipment.
Adequate guards shall be provided to prevent entry of foreign debris as a result of cooling air suction or accidental acts of
operating or maintenance personnel.
Protection of personnel from accidental contact with electrical parts shall be provided.
All wound magnetic devices insulation class shall be appropriate for the environmental conditions.
Downloaded from SAE International by Cristina Menardi, Monday, October 17, 2022
SAE INTERNATIONAL ARP5015B Page 14 of 16
The unit shall be capable of withstanding or operating satisfactorily when exposed to the following conditions with suitable
derating, unless otherwise specified:
Ambient temperature ranging -30 to +52 °C (-22 to +125 °F) when operating.
Altitude: Operating at any altitude up to 3050 m (10000 feet) above sea level without derating unless otherwise noted.
The unit shall be designed for a minimum life expectancy of 15 years with routine servicing and periodic adjustment.
3.10.5.1 The wiring shall be brought to terminal blocks and/or suitable connectors and each conductor identified in
accordance with a wiring diagram by means of numbers and/or color coding. The wiring shall be formed and
restrained to give a neat appearance.
3.10.5.2 All meter panels and any components containing printed circuit boards or solid-state electronics used in
engine driven equipment shall be shock mounted.
3.10.5.3 There shall be accessibility to controls and instruments and all equipment relative to starting, stopping,
indicating, protecting, and load controlling. All controls, instruments, and wiring shall be mounted in a dead
front enclosure. All shall be adequately identified including the wiring, terminals, and controls.
3.10.5.4 Instruments shall be highest industrial quality with demonstrated reliability consistent with the equipment life
expectancy. The operator's control panel must permit easy and accurate observation of meters, indicators,
and operation of all manual controls from a normal standing position.
3.10.7 Workmanship
The unit, including all parts and accessories, shall be fabricated and finished with the proper degree of skill necessary.
Particular attention shall be given to freedom from blemishes, defects, burrs, and sharp edges; accuracy of dimensions,
radii of fillets, and marking of parts and assemblies; thoroughness of soldering, welding, brazing, painting, wiring, and
riveting; and alignment of parts and tightness of assembly screws, bolts, etc.
The unit shall be so constructed that adjustments and repairs can be easily made by maintenance personnel.
The complete unit shall be designed for lifting and transporting by suitable means.
3.10.10.1 All instruments and controls shall be suitably identified. Adequate operating instruction placards shall be
permanently affixed in proximity to all control panels.
Downloaded from SAE International by Cristina Menardi, Monday, October 17, 2022
SAE INTERNATIONAL ARP5015B Page 15 of 16
3.10.10.2 A permanent nameplate shall be affixed to the equipment specifying vendor's name and/or trademark,
vendor's part or model number, vendor's serial number, date of manufacture, rating as specified in 3.1.6, and
environmental restrictions as specified in 3.6.3.
3.10.10.3 All GPUs shall have a warning label permanently affixed to service panel where high voltages are present.
3.10.11.1 All materials shall be new and suitable for the purpose intended.
3.10.11.2 No components shall be used in the assembly of the unit which will be subjected to conditions in excess of the
original manufacturer's recommended operating limits. Components shall be suitably de-rated to ensure rated
service life.
3.10.11.3 No hidden or inaccessible fasteners shall be used unless adequately secured to prevent turning examples:
rivets, tapped threads, tack welded nuts, or studs).
3.10.11.4 Fire resistant and non-moisture absorbing materials shall be used whenever possible.
Equipment and controls that are exposed to the weather shall be weather resistant type.
Suitable and adequate corrosion protection shall be applied throughout the equipment.
All parts having the same manufacturer's part number shall be directly and completely interchangeable with each other
with respect to installation and performance.
3.10.15 Cabinet
The cabinet enclosure shall be designed to be suitable for the intended environmental conditions. The components and
subassemblies shall be mounted in such a manner that no damage will occur as a result of transportation. Means shall be
provided for easy access to the component part contained therein.
Solid state cabinet enclosure rating shall have an appropriate environmental NEMA or IP rated enclosure.
The unit shall be easily operated by personnel after being given minimum training on the equipment. All operator controls
and instruments shall be conveniently grouped at one location.
Major assemblies and components shall be easily disconnected and removed from the equipment without the necessity for
extensive disassembly of the other components. Lifting eyes, forklift channels, or other devices shall be provided where
required.
3.10.19.1 Noise attenuated (insonorisation) units shall not exceed 85 dBA at 10 feet (3 m) or the local code where
applicable. A measurement shall be taken in accordance with SAE J1175.
Downloaded from SAE International by Cristina Menardi, Monday, October 17, 2022
SAE INTERNATIONAL ARP5015B Page 16 of 16
3.10.19.2 The unit shall be designed and constructed so that no parts will work loose in service. It shall be built to
withstand the stresses, shocks, vibrations, and other conditions incident to shipping, storage, installation, and
service.
All GPU emissions requirements shall be specified by the user to the vendor as part of the initial tender document or meet
the local emission code for the location’s intended use.
All GPU input current distortion requirements shall be specified by the user to the vendor as part of the initial tender
document. Input current distortion requirement shall be based on a full load rating.
4.1 A complete manual shall be provided with each unit containing the following information:
The manual shall be in accordance with AS4828 or Acceptable Manufacturer's Manual as submitted to the purchaser for
approval. Approved manuals shall be provided concurrent with delivery of first production unit.
5. NOTES
A change bar (l) located in the left margin is for the convenience of the user in locating areas where technical revisions, not
editorial changes, have been made to the previous issue of this document. An (R) symbol to the left of the document title
indicates a complete revision of the document, including technical revisions. Change bars and (R) are not used in original
publications, nor in documents that contain editorial changes only.