The Nonlinear Behavior of The Transformer Insulation
The Nonlinear Behavior of The Transformer Insulation
1140
Authorized licensed use limited to: UNIVERSIDAD POLITECNICA SALESIANA. Downloaded on April 10,2023 at 02:00:42 UTC from IEEE Xplore. Restrictions apply.
(b)
Fig.1. Typical (a) DFR test results and (b) polarization current test result (b)
Fig. 2. DFR results at various test voltages. (a)/ (b) represents the
real/imaginary part of the complex permittivity.
¦I 2
n
THD = n=2 (1)
I1
1141
Authorized licensed use limited to: UNIVERSIDAD POLITECNICA SALESIANA. Downloaded on April 10,2023 at 02:00:42 UTC from IEEE Xplore. Restrictions apply.
appear and becomes more significant. This is the main reason speed is proportional to the field strength that is perpendicular
for the current curve distortion. The harmonics of the test to the interface and the ion accelerating time. In frequency
current are recorded in Table I. domain, applied voltage changes its polarity regularly and
therefore even if the field strength is high, as long as the
TABLE I charging period is not long, the charge accumulation at the
THDI at various test frequencies and voltages interface could be neglected. But if the frequency goes lower,
which means that the charging period is increased, the
Harmonic Test Frequency (mHz) accumulation will occur so the nonlinear phenomenon
Components 1 2.1 4.6 10 appears. In the time domain measurement, the applied voltage
is usually high DC voltage. If the field strength becomes
n = 2 @ 1400V 0.0006 0.0011 0.0023 0.0020 strong enough to make ions in oil move, the test object would
n = 3 @ 1400V 0.0489 0.0306 0.0246 0.0178 always show non-linear behavior.
n = 4 @ 1400V <0.001 <0.0010 <0.0010 <0.0010
n = 5 @ 1400V 0.0165 0.0088 0.0028 0.0029 IV. CASE STUDY
n = 6 @ 1400V <0.001 <0.0010 <0.0010 <0.0010
Few transformers and bushings with different power ratings
n = 7 @ 1400V 0.0060 0.0033 0.0009 0.0005 are also investigated with various test voltages. These
n = 8 @ 1400V <0.001 <0.0010 <0.0010 <0.0010 transformers and bushings represent different structure of the
insulation system, i.e. the size of the oil-paper interface,
THD @ 1400V 0.0520 0.0320 0.0249 0.0181
relative ratio of cellulose and oil.
THD @ 20V 0.0042 0.0034 0.0016 0.0010
A. HVDC Transformer
B. Time domain testing A single phase 800 kV HVDC Transformer made by ABB
is tested by the DFR method. The results in Fig. 5 show that
The PDC measurements with different test voltages also the HVDC transformer is voltage independent at voltages
show different results. The x-axis of Fig. 4 is the time in below 1.4 kVrms. The reason could be that in big
second. The y-axis is the p.u. current. transformers, the field strength is not strong enough to make
The results suggest that the insulation resistance as well as ions in oil move.
the PI/DAR is voltage dependent. As discussed in the above
section, the existence of high polarization voltage and long
period at the same time makes the insulation system not linear
any more.
Fig. 4 Current over time curves (PDC measurement) at various test voltages B. Shell Type Transformer
1142
Authorized licensed use limited to: UNIVERSIDAD POLITECNICA SALESIANA. Downloaded on April 10,2023 at 02:00:42 UTC from IEEE Xplore. Restrictions apply.
Effect is observed with very low influence on the dielectric
response.
(b)
Fig. 7 DFR results of a distribution transformer. (a) – 20 V DFR result ; (b)
– 1.4 kV DFR result. The red curve is the database curve while the green
curve is the test result.
(a)
There is obvious deviation in this case and it is interesting
to see the post analysis by the software which gives the
moisture content information. The moisture contents given by
the software are 2.1% at 20 V and 2.5% at 1.4 kV. The
absolute moisture content error at 1.4 kV is about 0.4%. The
auto-matched geometries of the 1.4 kV curve are quite
different from the other one, from 22/25 at 20 V to 41/15 at
1.4 kV.
D. Bushing
(a)
(a)
1143
Authorized licensed use limited to: UNIVERSIDAD POLITECNICA SALESIANA. Downloaded on April 10,2023 at 02:00:42 UTC from IEEE Xplore. Restrictions apply.
For the oil-paper nonlinear insulation system at very low
frequencies, AC method is preferred because the total
polarization effect is much smaller than the one observed in
the DC method. The dielectric response of cellulose at low
frequency is more sensitive to water. However, for nonlinear
systems, the idea of running a DFR test down to 0.1 mHz in
order to obtain more accurate moisture estimation instead of
only down to 1 mHz is questionable. The reason for going to
very low frequencies should be related to the effect of
temperature [5] on the dielectric response and not the accuracy
of moisture estimation. In cases where it is necessary to use
higher test voltages, such as in HV substations, once the 3rd
harmonic starts to influence the dielectric response, it is
recommended to limit the lowest frequency value of the sweep
(b) which is usually determined by the temperature of the
Fig. 8 (a) -DFR results of the bushing at 20 V and 140 V respectively. (b) - insulation system.
DFR results of the bushing at 140 V and 1.4 kV respectively.
V. CONCLUSION
1144
Authorized licensed use limited to: UNIVERSIDAD POLITECNICA SALESIANA. Downloaded on April 10,2023 at 02:00:42 UTC from IEEE Xplore. Restrictions apply.