Eserver Manual
Eserver Manual
Chapter 1 Introduction
A.3 Compile and Upload / Download Screen & Recipe .......................................... A-8
User Information
Be sure to store this manual in a safe place.
Due to constantly growing product range, technical improvement and alteration or changed
texts, figures and diagrams, we reserve the right of this manual contained information change
without prior notice.
Coping or reproducing any part of this manual, without written consent of Delta Electronics
Inc. is prohibited.
ASIA JAPAN
DELTA ELECTRONICS, INC. DELTA ELECTRONICS (JAPAN) INC.
TAOYUAN Plant/ Sales Office/
31-1, SHIEN PAN ROAD, KUEI SAN DELTA SHIBADAIMON BLDG.
INDUSTRIAL ZONE TAOYUAN 333, TAIWAN 2-1-14 SHIBADAIMON, MINATO-KU,
TEL: 886-3-362-6301 TOKYO, 105-0012, JAPAN
FAX: 886-3-362-7267 TEL: 81-3-5733-1111
FAX: 81-3-5733-1211
eServer is a PC software used to help the customers collect and transfer production
information and history data directly from production site to a PC in the office via Ethernet.
eServer also supports Microsoft Excel (hereinafter “Excel”) software functions, such as
formulas, tables and graphs. This allows that the collected data can be saved in user-defined
Excel file according to various purposes for the customers to easily and quickly create
required production reports. In addition, it also supports ODBC interface which is able to save
the collected data to a database for the purpose of management and use in production sites.
The supported models for eServer Data Collection Software are listed in the table below.
Below are the system requirements to comply with the operating environment of eServer:
In this chapter, it will introduce general functions of eServer with Windows. The users can use
it to design what they want. Detail information for each function will be discussed in the
following chapters.
Step 2. Execute setup.exe from Windows taskbar by clicking “Start” > “Run”. After
pressing OK, the system will setup automatically and the following dialog box
will appear for selecting the desired display language.
Step 3. After pressing OK, the system will setup automatically and the users will get the
following dialog box to choose destination location.
To select a directory other than the default directory, click Browse. A list of
available directories appears. Highlight the desired directory for the Delta
eServer and click OK, then Next> for the next step.
If necessary, click < Back button to take you back through Setup dialog boxes
one by one.
Step 4. After pressing Next, the following dialog box will appear and ask the users to
select the installation software, i.e. DOP eServer. Then click Install button to
start DOP eServer installation.
Step 6. DOP eServer has been installed successfully. Press Close to finish the installation.
Before using eServer, the users need to update HMI firmware and complete PC and HMI
network settings. Please ensure to read the following instructions fully so that the users could
understand how to update HMI firmware and complete PC and HMI network settings correctly.
Remember to update the firmware before using eServer. To select this function, click Start >
Programs > Delta Industrial Automation > HMI > DOP eServer 1.0 > Update Firmware
Tool.
After clicking Update Firmware Tool, the following dialog box will appear for the users to
select the communication interface (the default setting is USB driver). Press Update button to
update HMI firmware automatically.
Power on PC and start Windows. Click Start > Programs, point to Control Panel, and then
Double-click Network Connections icon, the following windows will appear. Right-click
the Local Area Connection icon, and then select Properties from the pop-up menu.
The Local Area Connection Properties dialog box will open. Use General tab to select
Internet Protocol (TCP/IP). Then, press Properties button.
The Internet Protocol (TCP/IP) Properties dialog box will open. Choose Use the
following IP address and enter the IP address numbers of the PC into the field of IP
address and Subnet mask.
Please note that if the IP address numbers of subnet masks of the PC and HMI are
different, HMI may not be displayed in the list when finding node.
Start Screen Editor software program and click Options > Configuration. Use
Communication tab to select Ethernet and complete HMI networking settings shown as
the figure below. Then, press OK button to finish the settings.
Then, click Options > Networking. The following Remote Setting dialog box will appear.
Check the check box before Enable eServer/Remote and set a password for network
communication. After OK button is pressed, HMI networking is completed. Compile the
edited project file at the end of the programming and the edited project file could be
transferred to HMI.
To start eServer, click Start > Programs > Delta Industrial Automation > HMI > DOP
eServer 1.0 > eServer.
Please refer to the following steps to complete Excel sampling setting, i.e. how to log data
from HMI to Excel.
4.1.1 Linkage
Start eServer, and click File > New or click New icon After the New dialog box is opened,
select Logging (Excel) icon and press OK button.
Then, the Excel Logging Wizard will be activated and the following dialog box will
appear. Press Next button to continue.
Click icon to link HMI screen project file. There are two methods available for
selection:
1. Select an existing Screen (DOP) file from stored media: Open an existing screen
project file and set the IP address of the connecting HMI.
2. Transfer from Delta – HMI: Transfer the HMI screen project file via network
communication directly.
This step is used to create the desired Excel template sheet. There are two methods
available for selection:
1. Create a new Excel file: When this option is selected, the system will activate Excel
automatically and allow the users to design the desired Excel template sheet.
2. Select an existing Excel file from stored media: When this option is selected, the
system will allow the users to open an existing Excel file.
This step is used to specify the logging range to which the sampling data will be written.
There are three parts in this dialog box.
1. Sampling Direction
There are five different sampling directions could be selected. Please refer to the
following table for explanation.
Sampling Direction Diagram
Multi-Vertical:
When this option is selected, multiple
numbers of different register data could
be logged into each vertical column in
the selecting area simultaneously.
Multi-Horizontal:
When this option is selected, multiple
numbers of different register data could
be logged into each horizontal row in the
selecting area simultaneously.
2. Selection Range
Press Excel button and the system will open the editing Excel template sheet
immediately.
In Excel template sheet, use the mouse to decide the selection range. After the desired
range is selected, press Close button to finish.
When this option is selected, the sampling time and date will be written as well
automatically when the sampling data is recorded. The written position will be
different depending on the setting sampling direction. Generally, the written position
will be at the previous column or row before the selection range. However, if the
following three conditions occur, the function of Stamp Time and Date will be disabled.
a. When the sampling direction is vertical and the selection range includes column
A (the first column).
b. When the sampling direction is horizontal and the selection range includes row
1 (the first row).
The format of the date and time is specified by a string of characters which can be
user-defined and changed freely. Please refer to the table below for the string
representation.
String Format Representation
%m Month
%d Date
%y Year
%H Hour
%M Minute
%S Second
This step is used to set the register address of the sampling data.
This step is used to set the sampling conditions. There are two kinds of options for
selection:
This option is used to determine how long the sampling process is repeated. The time
unit is ms.
This option is used to determine how long the sampling process is repeated when the
trigger conditions are met. The detailed settings are described as follows:
Polling Cycle (Sampling Cycle): It is used to determine how long the sampling process
is repeated. The time unit is ms.
Trigger Conditions:
Setting Item Description Remark
No. Condition number Unchangeable
Choose to activate the trigger conditions.
The users can add many trigger conditions freely.
When all the selected trigger conditions are satisfied,
the system will execute the sampling operation for
one time.
Active
This step is used to set how to output and save the sampling data.
1. Excel Sheet
A. Repeat
When the sampling data has been filled in the selection range to the full, the
system will write the data into the selection range from the first column or row
repeatedly.
When the sampling data has been filled in the selection range to the full, the
system will open a new Excel file automatically and write the data into the new
Excel file.
When the sampling data has been filled in the selection range to the full, the
system will open a new Excel sheet automatically and write the data into the new
Excel sheet.
2. Output Setting
B. Report File Name: Specify the name of the report file. The users can add the date
and time in the end of the file name. The format of the date and time is specified
by a string of characters which can be user-defined and changed freely. Please
refer to the table below for the string representation.
String Format Representation
%m Month
%d Date
%y Year
%H Hour
%M Minute
%S Second
C. Auto Save: When this option is enabled, the system will back up the data in a
period of specified time automatically in case the data will be lost due to
abnormal operation when the power source is cut off unexpectedly or other
accident occurs.
Before creating testing example, make sure to change the upload and download option
(Options > Configuration) on Screen Editor first. The default setting of upload and download
is via USB. If the users need to use Ethernet, please change the default setting by referring to
Appendix A.
5.1 Example
This example is used to help the users to understand how to use eServer to read the data of
the register addresses $3 and $6 every second, record the data in Excel report file; meanwhile,
calculate the average value of the register addresses $3 and $6 by using Excel formula and
save the collected data in the specified folder (C:\Data).
Start Screen Editor software program and click File > New or click New icon to create a
new project. Then, click Element > Input > Numeric Entry to create two numeric entry
elements ($3 and $6) on the screen. In this case, 10 inches color AE type DOP series HMI
is used.
Use Screen Cycle Macro and enter the following commands in macro command window.
Click Options > Configuration and use Communication tab to select Ethernet and
complete HMI networking settings shown as the figure below. Then, press OK button to
finish the settings.
The following Remote Setting dialog box will appear. Check the check box before Enable
eServer/Remote and set a password for network communication. After OK button is
pressed, HMI networking is completed. Compile the edited project file at the end of the
programming and the edited project file could be transferred to HMI.
1. After eServer is enabled, eServer icon will appear at the bottom right of Windows
screen.
Right-click this icon and select Setting option from the pop-up menu.
3. Click File > New or click icon to create a new project file.
Choose Transfer from Delta – HMI option to transfer the HMI screen project file via
network communication directly. Press OK button to go to next step.
6. Design Excel template sheet. Select Create a new Excel file option and press Next
button to go to next step.
The system will enable Excel automatically. Create a Excel template sheet as the
figure below and enter the following formulas into the cells of E3 ~ E22 in order.
Then, press Close button in the dialog box which appears at the bottom right of
Windows screen to go to next step.
7.2 Press Excel button and the system will open the editing Excel template sheet
immediately.
7.3 In Excel template sheet, the users can drag the mouse to select the selection
range. In this case, C3 ~ D20 is selected. Then, press Close button to finish.
7.4 Check the check box before Enable Stamp Time and Date function and change
the format to %m/%d/%y %H:%M:%S. Once the sampling operation is enabled,
the sampling date and time will be recorded into the cells of B3 ~B20.
Use the following dialog box to set the sampling register addresses.
10. Choose Add a new file in Excel Sheet and define the file location and file name
shown as the figure below. After enabling the function of Auto Save, press Finish
button to complete the settings.
11. Press icon and enter the password. Then, the system will start sampling operation,
i.e. writing data in Excel file.
12. If the users want to pause or stop the sampling operation, only right-click eServer
icon at the bottom right of Windows screen and select Pause or Stop option from the
pop-up menu, the sampling operation will pause and stop immediately. The users
also can use Excel Visible option to decide whether the Excel window displays on the
screen or not.
Please refer to the following steps to complete Excel sampling setting, i.e. how to log data
from HMI to Excel.
5.2.1 Linkage
Start eServer, and click File > New or click New icon After the New dialog box is opened,
select Logging (Excel) icon and press OK button.
Then, the Excel Logging Wizard will be activated and the following dialog box will
appear. Press Next button to continue.
Click icon to link HMI screen project file. There are two methods available for
selection:
1. Select an existing Screen (DOP) file from stored media: Open an existing screen
project file and set the IP address of the connecting HMI.
2. Transfer from Delta – HMI: Transfer the HMI screen project file via network
communication directly.
This step is used to create the desired Excel template sheet. There are two methods
available for selection:
1. Create a new Excel file: When this option is selected, the system will activate Excel
automatically and allow the users to design the desired Excel template sheet.
2. Select an existing Excel file from stored media: When this option is selected, the
system will allow the users to open an existing Excel file.
This step is used to specify the logging range to which the sampling data will be written.
There are three parts in this dialog box.
1. Sampling Direction
There are five different sampling directions could be selected. Please refer to the
following table for explanation.
Sampling Direction Diagram
Multi-Vertical:
When this option is selected, multiple
numbers of different register data could
be logged into each vertical column in
the selecting area simultaneously.
Multi-Horizontal:
When this option is selected, multiple
numbers of different register data could
be logged into each horizontal row in the
selecting area simultaneously.
2. Selection Range
Press Excel button and the system will open the editing Excel template sheet
immediately.
In Excel template sheet, use the mouse to decide the selection range. After the desired
range is selected, press Close button to finish.
When this option is selected, the sampling time and date will be written as well
automatically when the sampling data is recorded. The written position will be
different depending on the setting sampling direction. Generally, the written position
will be at the previous column or row before the selection range. However, if the
following three conditions occur, the function of Stamp Time and Date will be disabled.
a. When the sampling direction is vertical and the selection range includes column
A (the first column).
b. When the sampling direction is horizontal and the selection range includes row
1 (the first row).
The format of the date and time is specified by a string of characters which can be
user-defined and changed freely. Please refer to the table below for the string
representation.
String Format Representation
%m Month
%d Date
%y Year
%H Hour
%M Minute
%S Second
This step is used to set the register address of the sampling data.
This step is used to set the sampling conditions. There are two kinds of options for
selection:
This option is used to determine how long the sampling process is repeated. The time
unit is ms.
This option is used to determine how long the sampling process is repeated when the
trigger conditions are met. The detailed settings are described as follows:
Polling Cycle (Sampling Cycle): It is used to determine how long the sampling process
is repeated. The time unit is ms.
Trigger Conditions:
Setting Item Description Remark
No. Condition number Unchangeable
Choose to activate the trigger conditions.
The users can add many trigger conditions freely.
When all the selected trigger conditions are satisfied,
the system will execute the sampling operation for
one time.
Active
This step is used to set how to output and save the sampling data.
1. Excel Sheet
A. Repeat
When the sampling data has been filled in the selection range to the full, the
system will write the data into the selection range from the first column or row
repeatedly.
When the sampling data has been filled in the selection range to the full, the
system will open a new Excel file automatically and write the data into the new
Excel file.
When the sampling data has been filled in the selection range to the full, the
system will open a new Excel sheet automatically and write the data into the new
Excel sheet.
2. Output Setting
B. Report File Name: Specify the name of the report file. The users can add the date
and time in the end of the file name. The format of the date and time is specified
by a string of characters which can be user-defined and changed freely. Please
refer to the table below for the string representation.
String Format Representation
%m Month
%d Date
%y Year
%H Hour
%M Minute
%S Second
C. Auto Save: When this option is enabled, the system will back up the data in a
period of specified time automatically in case the data will be lost due to
abnormal operation when the power source is cut off unexpectedly or other
accident occurs.
Before creating testing example, make sure to change the upload and download option
(Options > Configuration) on Screen Editor first. The default setting of upload and download
is via USB. If the users need to use Ethernet, please change the default setting by referring to
Appendix A.
6.1 Example
This example is used to help the users to understand how to use eServer to read the data of
the register addresses $3 and $6 every second, record the data in Microsoft Access database
via ODBC interface, and save the collected data into the specified folder (C:\Data).
1. Installing MSDE
First download the free software MSDE from the Microsoft web site. To download it, go
to http://www.asp.net/downloads/archived/msde/ and a download link will redirect
the users to download it.
After running the self-extracting file, open setup.ini file within MSDE subdirectory for
editing.
SAPWD=”0000”
SECURITYMODE=”SQL”
The SAPWD is the password required for the system administrator (SA) login account. In
this case, the SA login password is set to 0000. The users can set the desired password
freely. Once the setup.ini file is saved, double-click setup.exe to complete MSDE
installation.
2. Enabling MSDE
Click Start and then click Control Panel. In the Control Panel, click Windows Security
Center > Windows Firewall. Then, click on the Exceptions tab.
Click Add Port button and the following Add a Port dialog box will appear.
In the Add a Port dialog box, type SQL in the Name text field and type the port number
of the instance of the Database Engine, such as 1433 for the default instance in the
Port number text field. Ensure that TCP is selected and click OK to complete the
settings. When SQL port is shown and selected in Windows Firewall dialog box, it
indicates that SQL Server port will not be blocked and the incoming connections to SQL
Server will be allowed.
Double-click the located at the bottom right of Windows screen to open the
following SQL Server Service Manager dialog box and click Start/Continue button.
Start Microsoft Access by clicking Start > Programs > Microsoft Office > Microsoft
Office Access.
Then, click New icon and choose Project using new data to open a new database file
and set the directory to C:\Data.
User’s name: sa
User’s password: 0000
Then, click Design in the following pop-up window to create a database table in
Design view.
In the Table dialog box, create a database like the following figure shown below.
After editing the table, close the window to give a name for this table such as Table 1.
6. ODBC Setup
In the ODBC Data Source Administrator dialog box, select System DSN tab and click
on Add button to add system data source.
In the Create a New Data Source to SQL Server dialog box, do the following:
Enter the name of the data source and select the SQL Server that the users want to
access.
Choose how SQL Server should verify the authenticity of the login ID. Enter the user’s
name and the password. In this case, the user’s name is sa and the password is 0000.
Start Screen Editor software program and click File > New or click New icon to create a
new project. Then, click Element > Input > Numeric Entry to create two numeric entry
elements ($3 and $6) on the screen. In this case, 10 inches color AE type DOP series HMI
is used.
Use Screen Cycle Macro and enter the following commands in macro command window.
Click Options > Configuration and use Communication tab to select Ethernet and
complete HMI networking settings shown as the figure below. Then, press OK button to
finish the settings.
The following Remote Setting dialog box will appear. Check the check box before Enable
eServer/Remote and set a password for network communication. After OK button is
pressed, HMI networking is completed. Compile the edited project file at the end of the
programming and the edited project file could be transferred to HMI.
1. After eServer is enabled, eServer icon will appear at the bottom right of Windows
screen.
Right-click this icon and select Setting option from the pop-up menu.
3. Click File > New or click icon to create a new project file.
Choose Transfer from Delta – HMI option to transfer the HMI screen project file via
network communication directly.
6. ODBC Data Source Setting: Create an ODBC Data Source pointing to your database.
Please refer to the following settings.
8. Set the sampling conditions to constant 1000ms. Press Next button to continue.
9. Press icon. After the password is entered, the system will start sampling operation,
i.e. writing data in Microsoft Access.
10. If the users want to pause or stop the sampling operation, only right-click eServer
icon at the bottom right of Windows screen and select Pause or Stop option from the
pop-up menu, the sampling operation will pause and stop immediately.
Please refer to the following steps to complete ODBC sampling setting, i.e. how to log data
from HMI to a database.
6.2.1 Linkage
Start eServer, and click File > New or click New icon After the New dialog box is opened,
select Logging (ODBC) icon and press OK button.
Then, the ODBC Logging Wizard will be activated and the following dialog box will
appear.
Click icon to link HMI screen project file. There are two methods available for
selection:
1. Select an existing Screen (DOP) file from stored media: Open an existing screen
project file and set the IP address of the connecting HMI.
2. Transfer from Delta – HMI: Transfer the HMI screen project file via network
communication directly.
This step is used to create an ODBC Data Source pointing to your database.
Item Explanation
ODBC Data Source Name of ODBC Data Source
User Name Login Username
Password Login Password
Table Name of Sampling Data Table
Item Explanation
Time and Date Choose if Time and Date Stamp function is enabled.
Table Table which the time and date will be written.
Field Field which the time and date will be written.
Detail The format of the date and time is specified by a string of
characters which can be user-defined and changed freely.
Please refer to the table below for the string representation.
String Format Representation
%m Month
%d Date
%y Year
%H Hour
%M Minute
%S Second
This step is used to set the register address of the sampling data.
This step is used to set the sampling conditions. There are two kinds of options for
selection:
This option is used to determine how long the sampling process is repeated. The time
unit is ms.
This option is used to determine how long the sampling process is repeated when the
trigger conditions are met. The detailed settings are described as follows:
Polling Cycle (Sampling Cycle): It is used to determine how long the sampling process
is repeated. The time unit is ms.
Trigger Conditions:
Setting Item Description Remark
No. Condition number Unchangeable
Choose to activate the trigger conditions.
The users can add many trigger conditions freely.
When all the selected trigger conditions are satisfied,
the system will execute the sampling operation for
one time.
Active
Please refer to the following steps to complete ODBC sampling setting, i.e. how to log data
from HMI to a database.
7.1.1 Linkage
Start eServer, and click File > New or click New icon After the New dialog box is opened,
select Logging (ODBC) icon and press OK button.
Then, the ODBC Logging Wizard will be activated and the following dialog box will
appear.
Click icon to link HMI screen project file.There are two methods available for selection:
1. Select an existing Screen (DOP) file from stored media: Open an existing screen
project file and set the IP address of the connecting HMI.
2. Transfer from Delta – HMI: Transfer the HMI screen project file via network
communication directly.
This step is used to create an ODBC Data Source pointing to your database.
Item Explanation
ODBC Data Source Name of ODBC Data Source
User Name Login Username
Password Login Password
Table Name of Sampling Data Table
Item Explanation
Time and Date Choose if Time and Date Stamp function is enabled.
Table Table which the time and date will be written.
Field Field which the time and date will be written.
Detail The format of the date and time is specified by a string of
characters which can be user-defined and changed freely.
Please refer to the table below for the string representation.
String Format Representation
%m Month
%d Date
%y Year
%H Hour
%M Minute
%S Second
This step is used to set the register address of the sampling data.
This step is used to set the sampling conditions. There are two kinds of options for
selection:
This option is used to determine how long the sampling process is repeated. The time
unit is ms.
This option is used to determine how long the sampling process is repeated when the
trigger conditions are met. The detailed settings are described as follows:
Polling Cycle (Sampling Cycle): It is used to determine how long the sampling process
is repeated. The time unit is ms.
Trigger Conditions:
Setting Item Description Remark
No. Condition number Unchangeable
Choose to activate the trigger conditions.
The users can add many trigger conditions freely.
When all the selected trigger conditions are satisfied,
the system will execute the sampling operation for
one time.
Active
Before creating testing example, make sure to change the upload and download option
(Options > Configuration) on Screen Editor first. The default setting of upload and download
is via USB. If the users need to use Ethernet, please change the default setting by referring to
Appendix A.
8.1 Example
This example is used to help the users to understand how to use eServer to read the data of
the register addresses $3 and $6 every second, record the data in MySQL via ODBC interface,
and save the collected data into the specified folder (C:\Data).
1. AppServ Introduction
AppServ is a free and full-featured software of Apache HTTP Server, MySQL, PHP, and
phpMyAdmin. To download it, go to http://www.appservnetwork.com.
Package of AppServ
After double clicking the appserv-win32-2.5.10.exe file downloaded from the website
exe file, the following dialog box will appear.
The users must read license agreement before installation. Click on I Agree button to
continue.
Select the default directory C:\AppServ, and click on Next button for the next step.
Then, select the AppServ Package Components to install, and click on Next button for
the next step.
Specify Server Name, Administrator’s Email Address and Apache HTTP port for Apache
Web Server. When perform testing, the Servo Name can be specified as localhost
directly. Click on Next button for MySQL Server Configuration settings
Enter root password for MySQL database and complete the settings for MySQL Server.
Character Sets and Collations: The users can select data storage language and
collations from the drop-down menu.
Old Password Support (PHP MySQL API function): When this option is selected, the users
can code PHP code with old MySQL API.
After installing AppServ, the users can view the web site by pointing a web browser to
http://localhost/. If the following screen displays, it indicates that Apache has been
installed successfully.
2. MySQL Settings
Use phpMyAdmin built-in AppServ to perform the relevant MySQL settings. Open the
browser, type: http://localhost/phpMyAdmin/, a Connect to localhost dialog box will
display. Enter root for username and your password for password (The default
administrator account is root, but depending on your setup it may be a different user
name.)
Enter the name of the new database. In this case, the name of the new database is
entered as test. Click on Create button for the next step.
Click on Structure link to create new table on database. In this case, the new table is
named as table1 and the number of fields is set to 3. After Go button is pressed, a new
table on database will be created.
Complete the settings by referring to the figure below and press Save button to save
changes.
After the table1 has been created, the screen will be shown as follows.
Click on Add a new User link to display the add new user page
Login Information:
User name: Enter user name root
Host: Select Any host from the drop down menu and insert a % code.
Password: Enter the desired password
Re-type: Re-enter the desired password
General Password:
Click on Generate button to automatically generate a password.
Click on Copy button to insert the password into the fields of Password
and Re-type.
Scroll the screen down and click on Check All link to select all privileges. Then, click on
GO button to create a new user.
Click Start and then click Control Panel. In the Control Panel, click Windows Security
Center > Windows Firewall. Then, click on the Exceptions tab.
Click Add Port button and the following Add a Port dialog box will appear.
In the Add a Port dialog box, type MySQL in the Name text field and type the port
number of the instance of the Database Engine, such as 3306 for the default instance
in the Port number text field. Ensure that TCP is selected and click OK to complete the
settings.
4. Connector/ODBC Installation
5. ODBC Setup
In the ODBC Data Source Administrator dialog box, select System DSN tab and click
on Add button to add system data source.
Select MySQL ODBC 5.1 Driver and then click on Finish button.
Connection Parameters:
Data Source Name: Enter ODBC data source name eServer or enter the name of
the data source you want to access.
Description: Enter some text to identify the connection.
Server: Enter the default localhost or the name of MySQL server host that the
users want to access.
User: Enter user name root to use for this connection.
Password: Enter the corresponding password for this connection.
Database: The list of databases that the user has permissions to access will be
shown automatically.
Click on Test button to verify the connection. If the test succeeds, the figure shown
below will appear on the screen to indicate that MySQL connection is now available to
use. At this time, click on OK button to complete the settings. If the test does not
succeed, please review the settings.
Start Screen Editor software program and click File > New or click New icon to create a
new project. Then, click Element > Input > Numeric Entry to create two numeric entry
elements ($3 and $6) on the screen. In this case, 10 inches color AE type DOP series HMI
is used.
Use Screen Cycle Macro and enter the following commands in macro command window.
Click Options > Configuration and use Communication tab to select Ethernet and
complete HMI networking settings shown as the figure below. Then, press OK button to
finish the settings.
The following Remote Setting dialog box will appear. Check the check box before Enable
eServer/Remote and set a password for network communication. After OK button is
pressed, HMI networking is completed. Compile the edited project file at the end of the
programming and the edited project file could be transferred to HMI.
1. After eServer is enabled, eServer icon will appear at the bottom right of Windows
screen.
Right-click this icon and select Setting option from the pop-up menu.
3. Click File > New or click icon to create a new project file.
Choose Transfer from Delta – HMI option to transfer the HMI screen project file via
network communication directly.
6. ODBC Data Source Setting: Create an ODBC Data Source pointing to your database.
Please refer to the following settings.
8. Set the sampling conditions to constant 1000ms. Press Next button to continue.
9. Press icon. After the password is entered, the system will start sampling operation,
i.e. writing data in MySQL Server.
10. If the users want to pause or stop the sampling operation, only right-click eServer
icon at the bottom right of Windows screen and select Pause or Stop option from the
pop-up menu, the sampling operation will pause and stop immediately.
11. Open the browser, type: http://localhost/phpMyAdmin/, and select the test database
from the Database drop-down menu.
13. The recorded data will be shown at the bottom of the window.
Please refer to the following steps to complete Excel sampling setting, i.e. how to log data
from HMI to Excel.
Start eServer, and click File > New or click New icon
After the New dialog box is opened, select Recipe Access icon and press OK button.
Click icon to link HMI screen project file. There are two methods available for
selection:
1. Select an existing Screen (DOP) file from stored media: Open an existing screen
project file and set the IP address of the connecting HMI.
2. Transfer from Delta – HMI: Transfer the HMI screen project file via network
communication directly.
This step is used to set the register addresses of the database. There are two modes,
Import and Export available for selection. After selecting the desired mode, choose Fixed
or Variance from the drop-down list and complete the settings.
Import - Fixed
Import - Variance
Export - Fixed
Export - Variance
This step is used to set the sampling conditions. There are two kinds of options for
selection:
This option is used to determine how long the sampling process is repeated. The time
unit is ms.
This option is used to determine how long the sampling process is repeated when the
trigger conditions are met. The detailed settings are described as follows:
Polling Cycle (Sampling Cycle): It is used to determine how long the sampling process
is repeated. The time unit is ms.
Trigger Conditions:
Setting Item Description Remark
Name. Condition number Unchangeable
HMI Name Name of connecting HMI
Address Register Address
1. When the register address is set to Bit, the
selectable options are:
A. Level: Current status
B. Rising edge: Triggered by rising-edge. At
this time, the functions of Operator and
Value are disabled.
C. Falling edge Triggered by falling-edge. At
this time, the functions of Operator and
Value are disabled.
Condition 2. When the register address is set to Word, the
selectable options are:
A. BCD: Setting range of trigger condition is 0
~ 9999
B. Signed: Setting range of trigger condition is
-32768 ~ +32767
C. Unsigned: Setting range of trigger
condition is 0 ~ 65535
D. Hex: Setting range of trigger condition is 0
~ 65535
Operator settings:
1. When the register address is set to Bit, the
selectable operator are:
A. = : equal to
B. != : not equal to
2. When the register address is set to Word, the
Operator selectable operator are: Unchangeable
A. >= : greater than or equal to
B. <= : smaller than or equal to
C. > : greater than
D. = : equal to
E. < : smaller than
Before creating testing example, make sure to change the upload and download option
(Options > Configuration) on Screen Editor first. The default setting of upload and download
is via USB. If the users need to use Ethernet, please change the default setting by referring to
Appendix A.
Update Firmware
Remember to update the firmware before using eServer. To select this function, click Start >
Programs > Delta Industrial Automation > HMI > DOP eServer 1.0 > Update Firmware
Tool. After clicking Update Firmware Tool, the following dialog box will appear for the users
to select the communication interface (the default setting is USB driver). Press Update button
to update HMI firmware automatically.
Start eServer
To start eServer, click Start > Programs > Delta Industrial Automation > HMI > DOP
eServer 1.0 > eServer.
Start eServer, and click File > New or click New icon
After the New dialog box is opened, select Recipe Access icon and enter the file name
exmple for the Recipe Access database. Then, press OK button.
10.1.2 Node
Click icon to link HMI screen project file. There are two methods available for
selection. Here choose Select an existing Screen (DOP) file from stored media option to
create a new node.
Open an existing screen project file (HMI-recipe.dpb) and set the IP address of the
connecting HMI. The IP address is set to 172.16.190.11
After selecting the recipe file and setting the IP address, press OK button to go to next
step.
When the node is set correctly, click Setting and complete the settings next. There are
two modes, Import and Export available for selection. Each mode provides two options,
Fixed or Variance from the drop-down list for use.
Import – Fixed
Setting :
a. Select Fixed.
c. User-define the Name (recipe display name) and File Name (file name of the imported
file).
d. Set Destination Path (destination location) where the imported file is located.
a.
b. c. d.
Condition :
As for the method of sampling condition, select Const (execute sampling repeatedly in
a certain span of time).
a. Select Const.
b. Choose Import.
a.
b.
c.
After completing all the settings on eServer, use the most updated Screen Editor program
editing software to open the selected .dpb file which just has been modified on eServer.
Then, compile it and download the recipe data to HMI. The screen data will be shown as
the figure below:
After downloading the recipe data, please make sure that the IP address numbers of
subnet masks of the PC (172.16.190.1) and HMI (172.16.190.11) are the same; otherwise,
HMI may not be displayed in the list when finding node.
Networking Settings
Setting PC Network
Power on PC and start Windows. Click Start > Programs, point to Control Panel, and then
Double-click Network Connections icon, the following windows will appear. Right-click
the Local Area Connection icon, and then select Properties from the pop-up menu.
The Local Area Connection Properties dialog box will open. Use General tab to select
Internet Protocol (TCP/IP). Then, press Properties button.
The Internet Protocol (TCP/IP) Properties dialog box will open. Choose Use the
following IP address and enter the IP address numbers of the PC into the field of IP
address and Subnet mask.
Enter into the system menu and set IP address to 172.16.190.11. Please see the figure
below:
After networking settings are set correctly and successfully, return to eServer, save the
file first and then run the recipe data. Please see the figure below:
Save Run
Press icon. The following dialog box will pop-up and ask the users to enter the
password.
Please enter 12345678 in the filed of the password at the first time (12345678 is the
default setting value and the users can change it freely). After the correct password is
entered, the icon will display on the tool bar at the left-bottom corner.
When eServer performs reading, the system will examine and check if the saved file name
is saved in the destination path or not. Please refer to the figure such as .
On the other hand, if incorrect or invalid password is entered, the following error
message dialog box will appear to alert the users.
Import - Variance
Setting :
a. Select Variance.
c. Set the File Name (file name of the imported file) to be the same as the register
address of HMI. (In this case $100 character input element is used)
d. Set File Name Length (number of the imported characters). (In this case the File Name
Length is set to 4. This is because the name of the imported file is Tina.csv. The
system will refer to “Tina” these four characters and convert the imported file to
Tina.rcp and then save it to the destination path.
e. Set Destination Path (destination location) where the imported file is located.
a.
b. c. d. e.
Condition :
As for the method of sampling condition, select Const (execute sampling repeatedly in
a certain span of time).
a. Select Const.
b. Choose Import.
a.
b.
c.
After completing all the settings, please make sure that the IP address numbers of subnet
masks of the PC (172.16.190.1) and HMI (172.16.190.11) are the same; otherwise, HMI
may not be displayed in the list when finding node.
Networking Settings
Setting PC Network
Power on PC and start Windows. Click Start > Programs, point to Control Panel, and then
Double-click Network Connections icon, the following windows will appear. Right-click
the Local Area Connection icon, and then select Properties from the pop-up menu.
The Local Area Connection Properties dialog box will open. Use General tab to select
Internet Protocol (TCP/IP). Then, press Properties button.
The Internet Protocol (TCP/IP) Properties dialog box will open. Choose Use the
following IP address and enter the IP address numbers of the PC into the field of IP
address and Subnet mask.
Enter into the system menu and set IP address to 172.16.190.11. Please see the figure
below:
After completing all the settings and make sure that the communication is good, use the
most updated Screen Editor program editing software to open the selected .dpb file which
just has been modified on eServer. Create a character input element and set its address to
$100.
$100
Then, compile it and download the recipe data to HMI. After recipe data is downloaded to
HMI successfully, return to eServer, save the file first and then run the recipe data. Next,
trigger the character input element on HMI, and the system will save the imported file to
the destination path. Please see the figure below:
Save Run
Press icon. The following dialog box will pop-up and ask the users to enter the
password.
Please enter 12345678 in the filed of the password at the first time (12345678 is the
default setting value and the users can change it freely). After the correct password is
entered, the icon will display on the tool bar at the left-bottom corner.
When eServer performs reading, please trigger the character input element on HMI and
enter TINA these four characters. Please refer to the figure below:
Then, the system will examine and check if the saved file name is saved in the destination
Export – Fixed
Setting :
a. Select Fixed.
d. Set Destination Path (destination location) where the imported file is located.
Please note: the value of the selected -0223.rcp file (item d.) is the downloading value
when the element is triggered on HMI.
a.
b. c. d.
Condition :
As for the method of sampling condition, select Trigger (Execute sampling when the
trigger conditions are satisfied).
a. Select Trigger.
b. Set Address to the register address of the trigger element. (In this case the trigger
element is a numeric input element and its address is set to $200)
c. Set Operator and Value to = and 4. (In this case it indicates that when 4 is entered on
HMI, the system will trigger the element and export the file)
a.
b. c.
After completing all the settings, please make sure that the IP address numbers of subnet
masks of the PC (172.16.190.1) and HMI (172.16.190.11) are the same; otherwise, HMI
may not be displayed in the list when finding node.
Networking Settings
Setting PC Network
Power on PC and start Windows. Click Start > Programs, point to Control Panel, and then
Double-click Network Connections icon, the following windows will appear. Right-click
the Local Area Connection icon, and then select Properties from the pop-up menu.
The Local Area Connection Properties dialog box will open. Use General tab to select
Internet Protocol (TCP/IP). Then, press Properties button.
The Internet Protocol (TCP/IP) Properties dialog box will open. Choose Use the
following IP address and enter the IP address numbers of the PC into the field of IP
address and Subnet mask.
Enter into the system menu and set IP address to 172.16.190.11. Please see the figure
below:
After completing all the settings and make sure that the communication is good, use the
most updated Screen Editor program editing software to open the selected .dpb file which
just has been modified on eServer. Create a numeric input element and set its address to
$200.
$200
Then, compile it and download the recipe data to HMI. After recipe data is downloaded to
HMI successfully, return to eServer, save the file first and then run the recipe data. Next,
trigger the numeric input element on HMI, and the system will save the imported file to
the destination path. Please see the figure below:
Save Run
Press icon. The following dialog box will pop-up and ask the users to enter the
password.
Please enter 12345678 in the filed of the password at the first time (12345678 is the
default setting value and the users can change it freely). After the correct password is
entered, the icon will display on the tool bar at the left-bottom corner.
When eServer performs reading, please trigger the numeric input element on HMI and
enter the value of 4. Then, the system will convert the recipe data to the data of
-0223.rcp and show on HMI screen.
On the other hand, if incorrect or invalid password is entered, the following error
message dialog box will appear to alert the users.
Export - Variance
Setting :
a. Select Variance.
c. Set the File Name (file name of the imported file) to be the same as the register
address of HMI. (In this case $100 character input element is used.)
d. Set File Name Length (number of the imported characters). (In this case the File Name
Length is set to 4. This is because the name of the exported file is Tina.csv. This file
will be open in Screen Editor and save the value into .csv file.)
e. Set Source Path (destination location) where the exported file is located (Tina.csv file
is saved in C:\).
a.
b. c. d. e.
Condition :
As for the method of sampling condition, select Trigger (Execute sampling when the
trigger conditions are satisfied).
a. Select Trigger.
b. Set Address to the register address of the trigger element. (In this case the trigger
element is a numeric input element and its address is set to $200)
c. Set Operator and Value to = and 4. (In this case it indicates that when 4 is entered on
HMI, the system will trigger the element and export the file)
a.
b. c.
After completing all the settings, please make sure that the IP address numbers of subnet
masks of the PC (172.16.190.1) and HMI (172.16.190.11) are the same; otherwise, HMI
may not be displayed in the list when finding node.
Networking Settings
Setting PC Network
Power on PC and start Windows. Click Start > Programs, point to Control Panel, and then
Double-click Network Connections icon, the following windows will appear. Right-click
the Local Area Connection icon, and then select Properties from the pop-up menu.
The Local Area Connection Properties dialog box will open. Use General tab to select
Internet Protocol (TCP/IP). Then, press Properties button.
The Internet Protocol (TCP/IP) Properties dialog box will open. Choose Use the
following IP address and enter the IP address numbers of the PC into the field of IP
address and Subnet mask.
Enter into the system menu and set IP address to 172.16.190.11. Please see the figure
below:
After completing all the settings and make sure that the communication is good, use the
most updated Screen Editor program editing software to open the selected .dpb file which
just has been modified on eServer. Then, create two elements. One is a character input
element and its address is set to $100. The other is a numeric input element and its
address is set to $200. Please refer to the figure below:
$100 $200
Then, compile it and download the recipe data to HMI. After recipe data is downloaded to
HMI successfully, return to eServer, save the file first and then run the recipe data. Next,
trigger the numeric input element on HMI, and the system will save the imported file to
the destination path. Please see the figure below:
Save Run
Press icon. The following dialog box will pop-up and ask the users if it is necessary to
convert the file of Tina.csv.
Check the box before Translate All and press OK button, the following dialog box will
pop-up and ask the users to enter the password.
Please enter 12345678 in the filed of the password at the first time (12345678 is the
default setting value and the users can change it freely). After the correct password is
entered, the icon will display on the tool bar at the left-bottom corner.
When eServer performs reading, please trigger the character input element (TINA) and the
numeric input element (4) on HMI. Then, the system will convert the recipe data to the
record data of Tina.csv file.
On the other hand, if incorrect or invalid password is entered, the following error
message dialog box will appear to alert the users.
The default setting of upload and download on Screen Editor is via USB. If the users need to
use Ethernet, please activate Screen Editor and select Options > Configuration to access the
configuration options and change the upload and download setting.
In Configuration dialog box, change the default setting of upload and download to Ethernet.
Then, press OK to complete the setting.
If the users choose to use DHCP mode, it is not necessary to set Ethernet IP address in COM
Port tab.
If the users choose to use user-defined IP address, please set Ethernet IP address in COM Port
tab and ensure that the domain name is the same as the IP address of the personal computer.
After Ethernet IP address is set, the users can enter into the system menu to verify if the IP
address is written correctly or not.
Power on PC and start Windows. Click Start > Programs, point to Control Panel, and then
select Network Connections.
Double-click Network Connections icon, the following windows will appear. Right-click the
Local Area Connection icon, and then select Properties from the pop-up menu.
The Local Area Connection Properties dialog box will open. Use General tab to select
Internet Protocol (TCP/IP). Then, press Properties button.
The Internet Protocol (TCP/IP) Properties dialog box will open. Choose Use the
following IP address and enter the IP address numbers of the PC into the field of IP
address and Subnet mask.
Please note that if the IP address numbers of subnet masks of the PC and HMI are
different, HMI may not be displayed in the list when finding node.
After completing PC networking settings, compile the editing program immediately. When
compile operation is performed successfully, choose Upload Screen & Recipe or Download
Screen & Recipe next.
The users can check the box before Auto Search, and the system will detect the connecting
HMI automatically.
When the connecting HMI is found, press Start button, and the system will start to upload or
download the screen data via Ethernet immediately.