Özgüney: Test Transformer

1) This document is a transformer test report conducted on June 29, 2011 for a 630 KVA, 3 phase transformer with Dyn11 vector group. 2) Tests were conducted to measure turns ratio, insulation resistance, applied voltages, impedance, no load and load losses, regulation, and efficiency. 3) Results showed turns ratio errors were within 0.5%, insulation resistances met specifications, and performance met or exceeded guaranteed values for no load loss, load loss, regulation, and efficiency.

Uploaded by

mominzadah
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
100 views

Özgüney: Test Transformer

1) This document is a transformer test report conducted on June 29, 2011 for a 630 KVA, 3 phase transformer with Dyn11 vector group. 2) Tests were conducted to measure turns ratio, insulation resistance, applied voltages, impedance, no load and load losses, regulation, and efficiency. 3) Results showed turns ratio errors were within 0.5%, insulation resistances met specifications, and performance met or exceeded guaranteed values for no load loss, load loss, regulation, and efficiency.

Uploaded by

mominzadah
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

F 8.2.

4-03
Date 29.06.2011

ÖZGÜNEY TRANSFORMER
TEST
Serial No:
Brand
11-5848
BESE

REPORT Vector Group Dyn11


CUSTOMER TYPE Normal Project 11-01200
POWER 630 KVA 3 PHASE FREQUENCY 50 Hz Cooling Sys ONAN

Tab. HV (V) LV(V) HV(A) LV(A) D.C. RESISTANCE 24,5

1 19000 H.V. (Ω) L.V.(mΩ)


2 19500 1U1V= 5,71 2U2V= 2,22
3 20000 400/231 18,187 909,353 1V1W= 5,79 2V2W= 2,21
4 20500 1W1U= 5,85 2W2U= 2,23
5 21000 RORT= 5,783 Rort= 2,22

NOMINAL TURNS-RATIO TESTING % ERROR(± 0.5)


TAB.
TURN RATIO 1U1V 1V1W 1W1U 1U1V 1V1W 1W1U

1 82,27 82,28 82,25 82,31 0,009 0,027 0,046


2 84,44 84,45 84,51 84,48 0,015 0,086 0,050
3 86,60 86,57 86,65 86,65 0,038 0,055 0,055
4 88,77 88,79 88,83 88,82 0,025 0,070 0,059
5 90,93 90,94 91,00 91,00 0,008 0,074 0,074

IZOLATION RESISTANCE(Giga ohm) 20 °C ISOLATION TESTING


TIME (s) 15 30 45 60 30 60 TEST NAME KV Hz. S.
H.V.-TANK (5 KV) _ 17 _ 24 17,0 24,0 Applied V oltage H.V. 50 50 60
H.V.-L.V(5 KV) _ 20 _ 22 20,0 22,0 Applied V oltage l..V. 3 50 60
L.V.-TANK (3 KV) _ 10 _ 18 10,0 18,0 Enduced Overvoltage 0,8 120 60

MEASUREMENT OF IMPEDANCE AND LOAD LOSS MEASUREMENT OF NO-LOAD AND CURRENCY

NOMINAL VOLTAGE Wattmeter Multiplier Currents (A) Wattmeter


20000 W. 1 1 2093 W. 1 2U 5,2 1 328
Cur. (A) 18,187 V.T. 1 2 2062 V.T. 1 2V 4,73 2 507
Uk (V) 866 C.T. 1 3 1771 C.T. 1 2W 4,36 3 290

CALCULATION NO LOAD NO LOAD LOAD SHORT CIRCUIT Regulation Efficiency


VALUES LOSS CURRENT ( % ) LOSS VOLTAGE at 4/4 Fuil Load at 4/4 Fuil Load

(W) (% ) (W) +%10 CosΦ=1 CosΦ=1


GUARANTIED 1300 1,5 8700 4 (%) (%)
VALUES 1125 0,52 6971 4,37 1,20 98,73

OIL USED WEIGHT OF OIL (kg) WEIGHT OF ACTIVE PART (kg) TOTAL WEIGHT(kg)
SHELL DIALA BX 400 1165 1990

CUSTUMER TEST MANAGER