LS4 Circuit Breaker Control: Manual
LS4 Circuit Breaker Control: Manual
LS 4
Circuit Breaker Control
Manual
Software Version 3.2xxx
Manual 37105C
Manual 37105C LS 4 - Circuit Breaker Control
WARNING
Read this entire manual and all other publications pertaining to the work to be performed before instal-
ling, operating, or servicing this equipment. Practice all plant and safety instructions and precautions.
Failure to follow instructions can cause personal injury and/or property damage.
The engine, turbine, or other type of prime mover should be equipped with an overspeed (overtempera-
ture, or overpressure, where applicable) shutdown device(s), that operates totally independently of the
prime mover control device(s) to protect against runaway or damage to the engine, turbine, or other
type of prime mover with possible personal injury or loss of life should the mechanical-hydraulic gov-
ernor(s) or electric control(s), the actuator(s), fuel control(s), the driving mechanism(s), the linkage(s),
or the controlled device(s) fail.
Any unauthorized modifications to or use of this equipment outside its specified mechanical, electrical,
or other operating limits may cause personal injury and/or property damage, including damage to the
equipment. Any such unauthorized modifications: (i) constitute "misuse" and/or "negligence" within
the meaning of the product warranty thereby excluding warranty coverage for any resulting damage,
and (ii) invalidate product certifications or listings.
CAUTION
To prevent damage to a control system that uses an alternator or battery-charging device, make sure
the charging device is turned off before disconnecting the battery from the system.
Electronic controls contain static-sensitive parts. Observe the following precautions to prevent dam-
age to these parts.
• Discharge body static before handling the control (with power to the control turned off, contact a
grounded surface and maintain contact while handling the control).
• Avoid all plastic, vinyl, and Styrofoam (except antistatic versions) around printed circuit boards.
• Do not touch the components or conductors on a printed circuit board with your hands or with
conductive devices.
OUT-OF-DATE PUBLICATION
This publication may have been revised or updated since this copy was produced. To verify that you
have the latest revision, be sure to check the Woodward website:
http://www.woodward.com/pubs/current.pdf
The revision level is shown at the bottom of the front cover after the publication number. The latest
version of most publications is available at:
http://www.woodward.com/publications
If your publication is not there, please contact your customer service representative to get the latest
copy.
Important definitions
WARNING
Indicates a potentially hazardous situation that, if not avoided, could result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation that, if not avoided, could result in damage to equipment.
NOTE
Provides other helpful information that does not fall under the warning or caution categories.
Woodward reserves the right to update any portion of this publication at any time. Information provided by Woodward is believed to be
correct and reliable. However, Woodward assumes no responsibility unless otherwise expressly undertaken.
© Woodward
All Rights Reserved.
Revision History
Contents
CHAPTER 5. DISPLAY AND OPERATION COMPONENTS .............................................................. 25
Short Description of LED and Push Buttons ......................................................................................... 25
LEDs ............................................................................................................................................ 25
Push Buttons ............................................................................................................................... 25
Miscellaneous .............................................................................................................................. 25
LEDs ...................................................................................................................................................... 26
Push Buttons ......................................................................................................................................... 27
Display ................................................................................................................................................... 28
Automatic Mode (Upper Line of the Display: Measured Values) ................................................ 28
Automatic Mode (Bottom Line of the Display: Measured Values) .............................................. 28
Automatic Mode (Bottom Line of the Display: Alarm Messages) ................................................ 29
Interfaces ............................................................................................................................................... 29
Direct Configuration (DPC) ......................................................................................................... 29
CHAPTER 6. CONFIGURATION................................................................................................... 30
Basic Data ............................................................................................................................................. 31
Entering the Configuration ..................................................................................................................... 32
Password ..................................................................................................................................... 32
Basic Settings ........................................................................................................................................ 33
Direct Configuration..................................................................................................................... 33
Voltage Measuring ...................................................................................................................... 34
Potential Transformer Configuration ........................................................................................... 34
Current Transformer .................................................................................................................... 35
LS 4 Functions ....................................................................................................................................... 36
Function ....................................................................................................................................... 36
Segment Number ........................................................................................................................ 36
CAN Bus Number (Control Number) ........................................................................................... 37
Data Communication via the CAN Bus ....................................................................................... 37
Priority During Breaker Closure .................................................................................................. 37
Preparation .................................................................................................................................. 38
Configuration Screens in the LS 4 .............................................................................................. 38
Configuration Screens in the GCP Control Unit .......................................................................... 41
Examples for Configuration ......................................................................................................... 43
Control Functions .................................................................................................................................. 49
Synchronizing Functions ............................................................................................................. 49
Phase Angle Deviation (Phase Shift) .......................................................................................... 51
Blocking of Synchronization at Alarms ........................................................................................ 52
Synchronous Networks ............................................................................................................... 53
Dead Bus Start Functions ........................................................................................................... 54
Switching Time Monitoring .......................................................................................................... 55
Monitoring Functions ............................................................................................................................. 56
Monitoring Type Configuration .................................................................................................... 56
Overvoltage Monitoring ............................................................................................................... 57
Undervoltage Monitoring ............................................................................................................. 58
Voltage Asymmetry Monitoring ................................................................................................... 59
Overfrequency Monitoring ........................................................................................................... 60
Underfrequency Monitoring ......................................................................................................... 61
Phase/Vector Shift Monitoring ..................................................................................................... 62
df/dt (ROCOF) Monitoring ........................................................................................................... 63
Relay Configuration ............................................................................................................................... 64
Auto Acknowledgement of the Relays ........................................................................................ 64
Auto Acknowledgement of Messages ......................................................................................... 65
Changing the Relay Assignment ................................................................................................. 66
Interface ................................................................................................................................................. 69
General Parameters .................................................................................................................... 69
CAN Bus Parameter .................................................................................................................... 70
Change Passwords ............................................................................................................................... 71
CHAPTER 7. COMMISSIONING ................................................................................................... 72
APPENDIX A. DIMENSIONS ........................................................................................................ 74
APPENDIX B. TECHNICAL DATA ................................................................................................ 75
APPENDIX C. MEASURED QUANTITIES AND ACCURACY ............................................................. 77
APPENDIX D. INTERFACE .......................................................................................................... 78
Transmission Telegram ......................................................................................................................... 78
Receiving Telegram ............................................................................................................................... 82
Format .......................................................................................................................................... 82
Example ....................................................................................................................................... 82
CAN Ids on the Bus................................................................................................................................ 83
APPENDIX E. LIST OF PARAMETERS.......................................................................................... 84
APPENDIX F. SERVICE OPTIONS ............................................................................................... 87
Product Service Options ........................................................................................................................ 87
Returning Equipment For Repair ........................................................................................................... 87
Packing a Control ........................................................................................................................ 88
Return Authorization Number RAN ............................................................................................. 88
Replacement Parts................................................................................................................................. 88
How To Contact Woodward ................................................................................................................... 89
Engineering Services ............................................................................................................................. 90
Technical Assistance ............................................................................................................................. 91
Illustrations
Figure 3-1: Wiring diagram ...................................................................................................................................................... 10
Figure 3-2: Power supply .......................................................................................................................................................... 11
Figure 3-3: Measuring inputs - voltage - system [A] ................................................................................................................ 11
Figure 3-4: Measuring inputs - voltage - system [B] ................................................................................................................ 12
Figure 3-5: Measuring inputs - current - system [A]................................................................................................................. 13
Figure 3-6: Discrete inputs - positive logic ............................................................................................................................... 14
Figure 3-7: Discrete input - negative logic ............................................................................................................................... 14
Figure 3-8: Relay outputs ......................................................................................................................................................... 15
Figure 3-9: Interface - terminals ............................................................................................................................................... 16
Figure 3-10: Interface - CAN bus shielding .............................................................................................................................. 16
Figure 3-11: Interfaces - CAN bus topology............................................................................................................................. 17
Figure 4-1: Direction of power ................................................................................................................................................. 21
Figure 5-1: Front panel ............................................................................................................................................................. 25
Figure 6-1: LS 4 principle ......................................................................................................................................................... 37
Figure 6-2: Example A - H-Connection with two gensets per bus bar...................................................................................... 43
Figure 6-3: Example B - Double-H-connection with two gensets per bus bar .......................................................................... 44
Figure 6-4: Example C - Emergency power application with 1× generator and 1× feeder bus bar .......................................... 45
Figure 6-5: Example D - Emergency power application with 1× generator and 2× feeder bus bars......................................... 46
Figure 6-6: Example E - Multiple mains incomings to one common bus bar (no emergency power) ...................................... 47
Figure 6-7: Example F - Multiple mains/generator application ................................................................................................ 48
Figure 7-1: Dimensions............................................................................................................................................................. 74
Tables
Table 1-1: Reading LS 4 part numbers ....................................................................................................................................... 7
Table 3-1: Conversion chart - wire size ...................................................................................................................................... 9
Table 3-2: Maximum CAN bus length...................................................................................................................................... 17
Table 4-1: Permissible range for synchronization..................................................................................................................... 23
Table 5-1: Messages and alarms in the LC display ................................................................................................................... 29
Table 6-1: Power reduction....................................................................................................................................................... 40
Table 6-2: Example A - H-Connection with two gensets per bus bar ....................................................................................... 43
Table 6-3: Example B - Double-H-connection with two gensets per bus bar ........................................................................... 44
Table 6-4: Example C - Emergency power application with 1× generator and 1× feeder bus bar............................................ 45
Table 6-5: Example D - Emergency power application with 1× generator and 2× feeder bus bars .......................................... 46
Table 6-6: Example E - Multiple mains incomings to one common bus bar (no emergency power) ....................................... 47
Table 6-7: Example F - Multiple mains/generator application ................................................................................................. 48
Table 6-8: Calculation of the phase angle deviation ................................................................................................................. 51
Table 6-9: Auto-acknowledgment of the relay messages ......................................................................................................... 65
Table 6-10: Relay manager ....................................................................................................................................................... 67
Chapter 1.
General Information
The LS 4 is an intelligent synchronizer and protection device capable of measuring voltage and current though
integrated measuring inputs. It can calculate set point values using internal software routines (i.e. for synchroni-
zation) and can transfer these set point values to a lower level GCP control unit using the integrated CAN bus
(Guidance Level). The LS 4 is also capable of closing the connected breaker at the synchronous point. Addition-
ally the measured/calculated values may be monitored for exceeding/falling below a predefined set point result-
ing in an automatic opening of the connected circuit breaker.
LS415 B
Mounting
[B]=Flush-mounting
Current transformer, secondary
[1] = ../1 A
[5] = ../5 A
Voltage transformer, secondary
[1] = 100 Vac
[4] = 400 Vac
Type
Table 1-1: Reading LS 4 part numbers
Example:
LS 415B (flush mounted, standard unit with 100 Vac PT and ../5 A CT inputs)
Intended Use: This control must only be operated for the uses described in this manual. The prerequisite for a
proper and safe operation of the product is correct transportation, storage, and installation as well as careful op-
eration and maintenance.
NOTE
This manual has been developed for an item fitted with all available options. Inputs/outputs, functions,
configuration screens and other details described which do not exist on your item may be ignored.
The present manual has been prepared to enable the installation and commissioning of the item. Due
to the large variety of parameter settings it is not possible to cover every possible combination. This
manual is therefore only a guide. In case of incorrect entries or a total loss of functions, the default set-
tings can be taken from the enclosed list of parameters.
Chapter 2.
Electrostatic Discharge Awareness
All electronic equipment is static-sensitive, some components more than others. To protect these components
from static damage, you must take special precautions to minimize or eliminate electrostatic discharges.
1.) Before doing maintenance on the electronic control, discharge the static electricity on your body to
ground by touching and holding a grounded metal object (pipes, cabinets, equipment, etc.).
2.) Avoid the build-up of static electricity on your body by not wearing clothing made of synthetic materials.
Wear cotton or cotton-blend materials as much as possible because these do not store static electric
charges as easily as synthetics.
3.) Keep plastic, vinyl, and Styrofoam materials (such as plastic or Styrofoam cups, cigarette packages, cello-
phane wrappers, vinyl books or folders, plastic bottles, etc.) away from the control, modules, and work
area as much as possible.
4.) Opening the control cover may void the unit warranty.
Do not remove the printed circuit board (PCB) from the control cabinet unless absolutely necessary. If
you must remove the PCB from the control cabinet, follow these precautions:
• Ensure that the device is completely voltage-free (all connectors have to be disconnected).
• Do not touch the electrical conductors, connectors, or components with conductive devices or with
bare hands.
• When replacing a PCB, keep the new PCB in the plastic antistatic protective bag it comes in until you
are ready to install it. Immediately after removing the old PCB from the control cabinet, place it in the
antistatic protective bag.
CAUTION
To prevent damage to electronic components caused by improper handling, read and observe the pre-
cautions in Woodward manual 82715, Guide for Handling and Protection of Electronic Controls, Printed
Circuit Boards, and Modules.
Chapter 3.
Installation
CAUTION
A circuit breaker must be located near to the unit and in a position easily accessible to the operator.
This must also bear a sign identifying it as an isolating switch for the unit.
NOTE
Inductive devices connected to the system (such as operating current coils, undervoltage tripping
units, or auxiliary/power contacts) must be connected to a suitable interference suppressor.
The following chart may be used to convert square millimeters [mm²] to AWG and vice versa:
AWG mm² AWG mm² AWG mm² AWG mm² AWG mm² AWG mm²
30 0.05 21 0.38 14 2.5 4 25 3/0 95 600MCM 300
28 0.08 20 0.5 12 4 2 35 4/0 120 750MCM 400
26 0.14 18 0.75 10 6 1 50 300MCM 150 1000MCM 500
24 0.25 17 1.0 8 10 1/0 55 350MCM 185
22 0.34 16 1.5 6 16 2/0 70 500MCM 240
Table 3-1: Conversion chart - wire size
Wiring Diagram
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
X1 X2 X3 X4 X5
The socket for the PC configuration is located CAN-L
on the side of the unit. This is where the direct
configuration cable DPC must be plugged in. CAN-H
Interface
CAN bus GND
(Guidance Level)
CAN-L
System
[A]
CAN-H
CAN-L R R CAN-L
LS 4.17
GCP-31.x
CAN-H CAN-H
GND GND
3/(4)
CAN-L CAN-L
CAN-L CAN-L
Measuring
LS 4.18
GCP-31.2
3/(4) Voltage - System [A] - L2
2
CAN-H CAN-H
voltage GND GND
CAN-L CAN-L
(Voltage - System [A] - N)
LS 4.19
GCP-31.1
45 44 43 42 41 40 4
CAN-H CAN-H
GND GND
LS 4.x
GW 4
CAN-H CAN-H
GND GND
9 10 11 12 13 14 15 16 19 20 21 22 23 24 25 26 27 28 29
S1/X1 (K) s1/x1 (k)
s1/x1 (k)
L3 Current - System [A] - L3 Relay 8
S2/X2 (L) s2/x2 (l)
s2/x2 (l) Synchronization
(impulse relay)
75 74 73 72 71 70 32 31 30
Common
Relay 7
Enable CB
Reply: CB is open
CB
Relay 6
Voltage - System [B] - L1
3
Voltage - System [B] - L2
3/(4)
Relay 5
Voltage - System [B] - L3
LS 4 (Circuit Breaker Control)
Common
Disconnector
Relay 4
Reply: Isolation switch is open
Command: open CB
Relay 3
System
3/(4)
Relay 2
5
0 Vdc
7
Relay 1
#
24 Vdc
8
Power Supply
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
18 to 30 Vdc
18 to 30 Vdc
8
Power supply
0V
7
Figure 3-2: Power supply
Measuring Inputs
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
Voltage - System [A]
Isolation
CB switch
System [A]
System [B]
L1
L2
L3
N
4
L3 Voltage
3
L2 - System [A]
2
L1
1
Figure 3-3: Measuring inputs - voltage - system [A]
System [A]
System [B]
L1
L2
L3
N
70 71 72
L3
L2
Voltage
- System [B]
L1
CAUTION
Before disconnecting the secondary current transformer connections or the connections of the current
transformer at the device, ensure that the current transformer is short-circuited.
NOTE
Grounding of the secondary of a current transformer must always be single-sided.
Isolation
CB switch
System [B]
L1
L2
L3
N
Detail:
Connection of the transducers
S1/X1 S2/X2
s1/x1 s2/x2
40 41 42 43 44 45
s2/x2 (l)
System [A] System [B] L3 Current
s1/x1 (k)
- System [A]
s2/x2 (l)
L2
s2/x2 (l) s1/x1 (k) ../1 A
..
s1/x1 (k)
Discrete Inputs
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
CAUTION
Please note that the maximum voltages, which may be applied at the discrete inputs, are defined as fol-
lows. Voltages higher than those specified will destroy the hardware!
• Maximum input range: +/-18 to 250 Vac.
The discrete inputs may be either connected in a positive or a negative logic circuit:
• positive logic The discrete input is connected with +/-18 to 250 Vac.
• negative logic The discrete input is connected with GND.
Positive Logic
+/-18-250 Vac/dc
Signal device
B A
Discrete input
Negative Logic
+/-18-250 Vac/dc
B A
Discrete input
Signal device
Figure 3-7: Discrete input - negative logic
Relay Outputs
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
CAUTION
The function "Command: open CB" must be assigned to one of the freely configurable relays using the
relay manager (see Parameter 98).
B A
Relay output
external device
external device
E D C
Relay output
external device
Description Amax
Make contact
Root Switched
A B [NO]
9 10 Relay 1 (ready for operation; NC) 2.5 mm²
19 20 Relay 4 2.5 mm²
21 22 Relay 5 2.5 mm²
23 24 Relay 6 2.5 mm²
25 26 Relay 7 2.5 mm²
Change-over contact
Swtchd Root Opened
C [NO] D E [NC]
11 12 13 Relay 2 2.5 mm²
14 15 16 Relay 3 2.5 mm²
27 28 29 Synchronization (pulse relays) 2.5 mm²
Interface
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
Interface Connection
A B C D E
CAN-H
GND
CAN-H
CAN-L
CAN-L
CAN bus
Interface
Figure 3-9: Interface - terminals
Terminal Description
A (X1) B (X2) C (X3) D (X4) E (X5)
[1] [1] GND CAN-H CAN-L CAN bus
[1] may be used to loop CAN bus and/or to connect termination resistance.
0.01 µF
1 MOhm
400 Vac
NOTE
Please note that the CAN bus must be terminated with an impedance which corresponds to the wave
impedance of the cable (e.g. 120 Ω). The CAN bus is terminated between CAN-H and CAN-L.
Termination Termination
resistor resistor
CAN-H
CAN-H
CAN-H
CAN-H
GND
GND
GND
CAN-L
CAN-L
CAN-L
CAN-L
Termination
Termination
Note:
The termination has to be
performed with a resisitance,
which corresponds to the
impedance of the used cable
(e.g 120 Ohms)
If no data is transmitted on the CAN bus, check the following for common CAN bus communication problems:
- T structure bus is utilized (stub-end feeders or branch lines are not recommended)
- CAN-L and CAN-H are interchanged
- Not all devices on the bus are using identical Baud rates
- Terminating resistor(s) is/are missing
- Incorrect baud rate (too high) for length of CAN bus
The maximum length of the communication bus wiring is dependent on the configured Baud rate. Refer to Table
3-2 for the maximum bus length (Source: CANopen; Holger Zeltwanger (Hrsg.); 2001 VDE VERLAG GMBH,
Berlin und Offenbach; ISBN 3-8007-2448-0).
The maximum specified length for the communication bus wiring might not be achieved if poor quality wire is
utilized, there is high contact resistance, or other conditions exist. Reducing the baud rate may overcome these is-
sues.
NOTE
To configure via the configuration interface (direct configuration), you need the configuration cable
(part number 5417-557), the program LeoPC1 (delivered with the cable), and the corresponding confi-
guration files. Please consult the online help installed when the program is installed for a description
of the LeoPC1 program and its setup.
If Parameter 5 "Direct para" is enabled on the control, communication via the CAN bus interface on
terminals X1/X5 is disabled.
Chapter 4.
Functional Description
Introduction
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
Measuring Values
• Voltage
Three-phase measurement of the rms values of the phase-to-neutral and phase-to-phase voltages of two sys-
tems (system [A] and [B]; system [B] only phase-to-phase). This unit can be delivered with the following
measuring voltage ranges (rated values). Selection of type during ordering (see page 75 "Technical Data"):
- 66/115 Vac
- 230/400 Vac
• Frequency
Time measurement from the digitally filtered measuring voltages. The measurement of the frequency is three-
phased if all voltages are greater than 15 % of the rated value (100 Vac or 400 Vac). This guarantees a fast
and precise measurement of the frequency. However the frequency is still measured correctly even if voltage
is only applied to one phase.
• Current
Three-phase rms values.
• Real power
Single-phase measuring calculated from apparent power and power factor cosphi (power factor).
• Re-active power
Single-phase measurement calculated from apparent power and power factor sinphi.
• Power factor cosphi
Time measurement between the filtered measuring values of the voltage VL12 and the conductor current IL1.
General Functions
• 1 freely configurable relay output (NO) as ready for operation relay
• 4 freely configurable relay outputs (NO)
• 2 freely configurable relay outputs (change-over)
• 1 relay output (change-over) for synchronization (pulse relay)
• Discrete input for alarm blocking or acknowledgment
• Password system
• CAN bus interface
• 4 discrete control inputs
Protection Functions
CAUTION
The function "Command: open CB" must be assigned to one of the freely configurable relays using the
relay manager (see Parameter 98).
Control/Synchronization Functions
• Transmission of set point values via CAN bus to a lower level control unit (i.e. GCP-31) for synchronization
of one circuit breaker with voltage and frequency adjustment
• Transmission of actual values via the CAN bus to a control unit (i.e. GCP-31) for real power control
• Closing of the CB onto a dead (de-energized) bus bar
Direction of Power
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
If the unit’s current transformers are wired according to the pin diagram shown below, the following values are
indicated:
System [B]
LS 4
CB
circuit breaker
40 Q
s1/x1 (k) S1/X1 (K) ind
System [A]
Figure 4-1: Direction of power
Power Factor is defined as a ratio of the real power to apparent power. In a purely resistive circuit, the voltage
and current waveforms are instep resulting in a ratio or power factor of 1.00 (often referred to as unity). In an in-
ductive circuit the current lags behind the voltage waveform resulting in usable power (real power) and unusable
power (reactive power). This results in a positive ratio or lagging power factor (i.e. 0.85lagging). In a capacitive
circuit the current waveform leads the voltage waveform resulting in usable power (real power) and unusable
power (reactive power). This results in a negative ratio or a leading power factor (i.e. 0.85leading).
Inductive: Electrical load whose current waveform lags Capacitive: Electrical load whose current waveform
the voltage waveform thus having a lagging power fac- leads the voltage waveform thus having a leading pow-
tor. Some inductive loads such as electric motors have er factor. Some capacitive loads such as capacitor
a large startup current requirement resulting in lagging banks or buried cable result in leading power factors.
power factors.
+ (positive) - (negative)
lagging leading
The generator is
A voltage lower "-" signal is output as long as the A voltage raise "+" signal is output as long as the
measured value is "more inductive" than the reference measured value is "more capacitive" than the reference
set point set point
Example: measured = i0.91; set point = i0.95 Example: measured = c0.91; set point = c0.95
Phasor diagram:
inductive capacitive
Function
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
Synchronizing
The variable system is synchronized to the fixed system (variable and fixed system can be configured) for vol-
tage and frequency. This is done by sending set point values through the CAN bus to the lower level GCP control
that are electrically connected with the configured variable system. The LS 4 calculates the correct synchronous
point to issue a CB close command using the switching time of the CB (Parameter 37). Synchronizing/closing of
the CB is done if the following conditions are fulfilled simultaneously:
In conditions 1 and 2 the frequency of systems [A] or [B] must be within the configured range.
Configuration Methods
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
Following configuration methods may be utilized . Configuration may be performed via:
• CAN bus using a CAN bus card in the PC and the PC program LeoPC1,
• The configuration plug using the direct configuration cable DPC and the PC program LeoPC1, or
• Via front touch pad-buttons and the LC display.
Chapter 5.
Display and Operation Components
The pressure-sensitive membrane of the front panel consists of a plastic coating. All keys have been designed as
touch-sensitive membrane switch elements. The display is a LC-display, consisting of 2 rows of 16 characters
each, with indirect green lighting. The contrast of the display can be infinitely adjusted via a rotary potentiometer
positioned on the left side of the control. The configuration plug is located on the left side of the unit as well.
Please connect the direct configuration cable there (DPC).
29 5
30 Hz
CB on Display Menu Clear
1/2
Operating Alarm
3 4 12 13 14
Figure 5-1: Front panel
Push Buttons
No. Description Function
12 Display↓ Advance to next screen
12 Select Confirm selection
13 Menu Select menu
13 Digit↑ Increase the digit
14 Clear Acknowledgement of alarm messages
14 Cursor→ Move cursor one position to the right
Miscellaneous
No. Description Function
5 LC display Display all text messages and readings
29 DPC plug Configuration plug
30 Potentiometer Adjust LCD contrast
LEDs
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
NOTE
If the "Delta" LED not illuminated and an "A" is visible in the field "[ ]" of the LC display, the conductor
currents may be read in the first line of the LC display.
1 CB on CB is closed
Color: Yellow
If this LED is illuminated the connected CB is closed.
3 Operation Operation
Color: Green
This LED is illuminated constantly when the LS 4 is in the Automatic mode.
If this LED is flashing, the LS 4 is in the configuration mode.
4 Alarm Alarm
Color: Red
This LED flashes as long as a set point limit is exceeded. When all measur-
ing values are below the configured set point limit again and "Auto clearing
display" is configured "OFF", this LED will change to steady illumination.
Push Buttons
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
In order to facilitate the setting of the parameters the buttons are equipped with an "AUTOSCROLL" function
while the controller is in the configuration mode. It permits the user to rapidly advance to the next setting and
configuration screens, the digits, or the cursor position. The "AUTOSCROLL" function will only be enabled
when the user presses and holds the corresponding buttons.
Display
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
5 LC display LC display
NOTE
The user can scroll through the upper display line with the "Display ↓" button.
"Delta" = off Upper line of display when in automatic mode: measured values System [A]
Æ Phase-neutral voltages
230 230 230 V The following measured values of system [A] are displayed (depending if the "Del-
---------------- ta" LED is or is not illuminated):
• The "Delta" LED is not illuminated (Delta=off) and the letter "V" is displayed to
"Delta" = on
Æ Phase-phase voltages the right of the numerical values.
The line-neutral voltages of system [A] (VL1-N, VL2-N, and VL3-N) of the wye or
400 400 400 V
----------------
four-conductor system will be displayed. If the available system is a Delta or
three-conductor system, the Parameter 6 "Volt. measuring" must be set to "Phase-
"Delta" = off to-phase". As a result the line-neutral display does not appear.
Æ Conductor currents
• The "Delta" LED is illuminated (Delta=on) and the "V" is displayed to the right
314 314 314 A of the numerical values.
----------------
The line-to-line voltages of system [A] (VL1-L2, VL2-L3, and VL3-L1) of the
three/four conductor system are displayed.
• The "Delta" LED is not illuminated (Delta=off) and the letter "A" is displayed to
the right of the numerical values. The conductor currents (IL1, IL2, and IL3) of sys-
tem [A] are visible.
NOTE
The "Menu" button may be used to scroll through the messages shown on the bottom line of the dis-
play.
NOTE
The user may scroll through the alarm messages that have occurred with the "Menu" button.
Interfaces
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
The LS 4 is equipped with two interfaces that work at the following baud rates:
Chapter 6.
Configuration
Configuration may be performed by manually inputting the desired set points utilizing the touch pad buttons and
the LC display. Alternately, the unit may also be configured using a PC/laptop computer and the program
LeoPC1 via the serial interface or through the CAN bus. The following baud rates are usable if the unit is confi-
gured through Leo PC1:
CAUTION
Please note that configuration only should be done while the system is not in operation.
NOTE
A list of all parameters may be found in Appendix B of this manual.
You can advance through the individual parameter screens if you are in configuration mode (simultaneously
pressing of "Digit↑" and "Cursor→" push buttons permits access to the configuration mode) by using the "Se-
lect" button. If you press and hold the "Select" push button, the scroll function will be activated, allowing for the
parameter screens to be advanced through more rapidly. The control unit will permit the operator to reverse up to
four previous screens (exception: it is not possible to reverse from the first parameter to the last parameter or to
backup through the service screens). To perform the reverse function through the parameter screens, the "Select"
and "Cursor→" push buttons must be pressed and released simultaneously. The control unit will revert to auto-
matic mode if an entry isn’t performed, a change made, or any other action performed for 120 seconds.
NOTE
There are two different hardware versions described in this operating manual: A 100 V-version [1] and
a 400 V-version [4]. The versions vary as far as the configuration screens and the parameter input
ranges are concerned. The two types are differentiated by indicating the voltage: ([1] ... or [4] ...).
Basic Data
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
Parameter 1
Software version
Software version
X.xxxx This screen displays the software version loaded into the control (the last two xx
are for software revisions which do not affect the function of the unit).
Parameter 2
Language selection Deutsch/English
SPRACHE/LANGUAGE
---------------- The desired language for the controller to operate in is set by this parameter. The
screens (configuration and display screens) can be displayed either in German or
English.
Code level CS1 (Basic Service Level) Factory password = "0 0 0 1"
This code level entitles the user to change selected parameters, like setting Bar/PSI, °C/°F, and clock adjustment.
Changing a password is not permitted at this level. This password expires two hours after entering the password
and the user is returned to the CS0 level.
NOTE
Once the code level is entered, access to the configuration menus will be allowed for two hours or until
another password is entered into the control. If a user needs to exit a code level, then code level CS0
should be entered. This will block any configuration of the control. A user may return to CS0 by allow-
ing the entered password to expire after two hours or by changing any one digit on the random num-
ber generated on the password screen and entering it into the unit.
NOTE
The following configuration screen "Enter code number" only appears if the parameter "Password Pro-
tection" is configured "ON" (see below).
Parameter 3
Enter code number 0000 to 9999
Enter code
number 0000 Upon enabling the configuration mode, the user is required to enter an access code
number, which identifies the various users. The displayed number XXXX is a ran-
domly generated number. If the random number is confirmed by pressing the "Se-
lect" button without being changed, the current level of access maintained. Upon
entering either a level 1 or level 2 access code, the corresponding level of access is
granted. If an incorrect access code is entered the control unit changes to code level
0 and all access is blocked until a code level 1 or 2 access code is entered.
Parameter 4
Password protection ON/OFF
Password
Protection ON ON ................Password protection is enabled. Configuration access is enabled by
entering the appropriate password (Code level 1/2). If an incorrect
code number has been entered, configuration is blocked.
OFF ..............Password protection is disabled. Access to configuration screens is
permanently set to code level 2 and the code number is not queried.
This parameter can only be changed if the code number of code lev-
el 2 has been entered.
Basic Settings
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
WARNING
The incorrect configuration of the unit may lead to faulty measurement of the system and cause dam-
age to the generator or switchgear systems!
Direct Configuration
NOTE
For configuration via the direct configuration plug, a direct configuration cable DPC (P/N 5417-557), the
program LeoPC1 (supplied with the cable), and the corresponding configuration files are required. Af-
ter installing LeoPC1 consult the online help feature for a description of the program and its setup.
CAUTION
If the subsequent parameter "Direct Config." (Parameter 5) is configured to "YES", the communication
with the terminals X1 to X5 via the interface is blocked. This setting can lead to malfunctions during
operation because there is no connection to the other LS 4/GCP. If the communication via the interface
X1 to X5 is to be re-established after the configuration of the unit ( i.e. CAN bus link to a GCP or via a
Gateway GW 4), the parameter must be set to "NO" (Parameter 5).
NOTE
The following conditions must be fulfilled to enable configuration via DPC:
• Parameter 5 "Direct parametr." is configured to "YES"
• A reply is present that signals that the circuit breaker is open (LED "CB ON" is off, DI at terminal 32
is energized)
• A reply is present that signals that the disconnector is open (only if Parameter 17 "Segement num-
ber Disconnector" ≠ "0", DI at terminal 74 is energized)
Parameter 5
Direct configuration YES/NO
Direct parametr.
YES YES .............. Configuration via the direct configuration port is possible if the CAN
bus link that may be established via the terminals X1 to X5 is dis-
abled . The following conditions must exist for direct configuration:
- a connection must be established between the unit and the PC via
the direct configuration cable DPC
- the Baud rate of the program LeoPC1 must be set to 9,600 Baud
- the correct configuration file must be used (file name: "xxxx-xxxx-
yyy-zz.asm").
NO................ Configuration via the direct configuration port is not possible. The
CAN bus link which may be established via the terminals X1 to X5 is
activated.
Voltage Measuring
Parameter 6
Voltage measuring Phase to phase/Phase-neutral
Volt. measuring
---------------- This parameter is used to distinguish how the voltage is to be measured. If this pa-
This parameter only affects the rameter is set to "Phase to phase", the configuration screen "Volt.-
display. The monitoring screens monitoring" (Parameter 56) does not appear.
are defined further below.
Example: If a voltage of 400 V is measured without a potential transformer, the secondary transformer voltage
must be configured to 400V and the primary transformer voltage must be configured to 00.400V.
Current Transformer
Parameter 11
Current transformer, system [A] 1 to 9,990/{X} A
Current transf.
0000/x The input of the current transformer ratio is necessary for the indication and control
of the actual monitored value. The current transformers ratio should be selected so
at least 60% of the secondary current rating can be measured when the monitored
system is at 100% of operating capacity (i.e. at 100% of system capacity a 5A CT
should output 3A). If the current transformers are sized so that the percentage of
the output is lower, the loss of resolution may cause inaccuracies in the monitoring
and control functions and may affect the functionality of the control.
The control may be ordered with either ../1 A or ../5 A current transformer inputs.
The CT inputs will dictate how this parameter is displayed on the control. Informa-
tion about the current transformers inputs may be found on the unit data plate.
CAUTION
The settings of the rated voltage in the system must to be equal to the settings in the lower level con-
trol unit GCP since the LS 4 only transmits a percentage [%] value via the CAN bus.
Parameter 12
Rated voltage [1] 50 to 120 V; [4] 50 to 480 V
Rated voltage
000V Using this parameter the rated value for voltage is defined (percentage parameters
of protective functions relate to this value only).
Parameter 13
Rated frequency 40.0 to 70.0 Hz
Rated frequency
00.0Hz Rated frequency in the system (of the generator or public grid).
NOTE
With a positive real power, a positive real current flows in the "k-l" direction in the current transformer.
Positive re-active power means that with a positive effective direction, inductive re-active (lagging) cur-
rent flow in the effective direction. If the circuit of the current transformer facing the system [A] are
connected to "k", the unit shows a positive real power when system [A] supplies real power. This is
explained in the section "Direction of Power" on page 21.
CAUTION
The settings of the rated power in the system (Parameter 14) must be equal to the settings in the lower
level GCP control unit because the LS 4 only transmits a percentage [%] value via the CAN bus. If the
lower level GCP control unit is connected to more than one incoming mains no control of the mains in-
terchange power is possible. The total power evaluated in all LS 4 is displayed in the GCP.
Parameter 14
Rated power 5 to 16,000 kW
Rated power
00000kW The rated power is configured here. The exact value of the rated power is absolute-
ly vital. Many measurement, control, and monitoring functions refer to this value.
LS 4 Functions
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
Function
The voltage measuring of the LS 4 is connected three phase. Current measuring is connected three-phase to sys-
tem [A] if this function is required. The possible functions are:
• Measuring conversion of both systems three-phase measured voltages as well as the three-phase measured
current of system [A] (if connected).
• Protection of the measured primary values via comparison of the configured set point values with the true
RMS values for over-/under voltage, over-/under frequency, phase/vector jump, df/dt (ROCOF), and voltage
asymmetry.
• Calculation of set point values for synchronization that are transmitted via the CAN bus to the lower level
GCP control unit). Frequency/voltage are controlled according to these set point values for synchronization in
the GCP.
• Operation of the connected breaker.
Segment Number
A segment is defined as a section of the bus, feeder, or interconnection, which cannot electrically be isolated to a
smaller section and is connected to a circuit breaker or an isolation switch with is operated or supervised by an
LS 4. A transformer is not to be considered as a segment or a point of isolation. Each segment, feeder, or inter-
connection must be assigned a number that is unique to that segment. The following restrictions apply when as-
signing segment numbers:
• A busbar must be assigned a number same number as the lowest numbered generator on that bus bar segment.
• The numbers assigned to other generators on the same busbar cannot be used to identify busbar segments.
Example: A system with six generators and two bus bars with a tiebreaker must be numbered in the following
manner. Generators 1, 2, and 3 are on busbar one and generators 4, 5, and 6 are on busbar 2. Busbar one is
assigned segment number 1 and busbar 2 is assigned segment number 4. The numbers 2, 3, 5, and 6 cannot
be used to identify segments of the system.
Otherwise the segment numbers can be assigned freely (see examples A to F).
NOTE
It is not permissible to connect a load between the breaker and the isolation switch (segment no. [B]).
on/off
CB LS 4
[B]
Segment no. [B]
Disconnector
System [B]
Figure 6-1: LS 4 principle
Preparation
Please prepare the LS 4 for configuration as follows:
• Draw a one-line diagram that only contains essential equipment. The schematic should consist of a minimum:
all used GCPs, all transformers, all breaker elements (such as circuit breakers and isolation switches), all ele-
ments to be controlled, and all LS 4s. Assign numbered addresses for each component of the system in accor-
dance with the methods described below.
• Number all GCP control units from 1-14 (order is user-defined and depends on your application). DO NOT
CHANGE this number after configuration of the LS 4 has begun. If this number is changed all LS 4s must be
reconfigured.
• Number all system LS 4s from 17-24 (order is user-defined and depends on your application). DO NOT
CHANGE this number after configuration of the LS 4 has begun. If this number is changed all LS 4s must be
reconfigured.
• Number all segments, generators, and mains/feeders in the system. DO NOT CHANGE this number after
configuration of the LS 4 has begun. If this number is changed all LS 4s must be reconfigured.
• Define which GCPs are connected to a common busbar.
• Configure all GCPs.
The LS 4s are now ready to be configured via the touch pad buttons or Leo PC.
Parameter 16
Segment number of system B 1 to 28
Segment number
System [B] 00 Enter the pre-assigned segment number for system B of this LS 4.
Parameter 17
Segment number of the disconnector/isolation switch 0 to 28
Segment number
Disconnector 00 If a disconnector/isolation switch is connected to one of the two systems A or B,
enter the segment number opposite of the disconnector/isolation switch. If no dis-
connector/isolation switch is utilized enter 00.
NOTE
Do not configure the following system (A or B) as mains connection.
Parameter 18
Voltage system of the disconnector/isolation switch Voltage A / Voltage B
Disconnector at
---------------- Enter which system a disconnector/isolation switch is connected to. If you entered
"Segment number Disconnector" 00 in the prior screen this screen is irrelevant
and should be ignored.
Parameter 19
Validity of power measurement invalid / valid
Mains power meas
---------------- invalid .......... If the measured power is not to be used for control configure as
"invalid".
valid ............. If the measured power is to be used for mains interchange real power
control configure as "valid".
Parameter 20
Mains connection Voltage A / Voltage B / Disconnector / none
Mains connection
---------------- Fixed networks in the system must be defined as a mains connection. This is used
to transfer mains parallel and mains failures for Automatic Mains Failure (AMF) to
the lower level GCP.
Voltage A........ System [A] is a fixed mains incoming.
Voltage B ........ System [B] is a fixed mains incoming.
Disconnector .. On the opposite side of the disconnector a fixed mains incoming is
connected.
none ................ None of the systems is a fixed mains incoming and is not used for
mains failure detection.
Parameter 21
Select variable system Voltage A / Voltage B
Variable system
---------------- One of the systems must be defined as a variable system. A variable system is de-
fined as a system that can change in frequency and voltage due to changes in fre-
quency and voltage of the GCP control unit. In normal applications this is the fre-
quency/voltage that is situated opposite the mains voltage of the MCB. The
opposite side of the CB is therefore either constant (mains voltage) or a controlled
stable (bus coupler) system. If one of the systems is configured as mains con-
nection the other system is automatically assumed as variable.
Parameter 22
Select bus bars Y/N
Busbar generator 1-8
Busb. y 12345678 With this parameter all generators connected to the same (generator) busbar are de-
Gen. 00000000 fined (each generator controlled through one GCP) as connected to the same bus
[y = 1 to 3]
bar. In the upper line the generator (control) number of the GCP are shown
(A = 10, B = 11, ..., E = 14). Enter a Y if the generator supplies to the selected bus-
Parameter 23 bar). This parameter is necessary for a correct function ( i.e. for load/var sharing
Busbar generator 9-14 used with paralleled generators). Three [y = 1 to 3] bus bars per system are possi-
Busb. y 9ABCDE ble. Parameters for three busbars must be configured. The busbar number is
Gen. 000000 represented by “y” in the sample display screen to the left. All generators con-
nected to the same busbar are defined by this parameter. The top line of the display
[y = 1 to 3]
represents the individual generators. For generators 10 and above, hexidecimal is
used to represent the individual units (i.e. 10=A, 11=B, etc).
Parameter 24
Measuring system for closing the CB one-phase / three-phase
Measuring CB ON
---------------- one-phase ....... For synchronization of the CB only one phase of voltage VL12 for
both systems A and B is used.
three-phase .... For synchronization of the CB all three phases of voltage VL123 for
both systems A and B are used (three-phase synchronization). Ad-
ditionally the direction of field rotation for both systems is moni-
tored and an alarm is issued if the directions do not match.
Parameter 25
Command to immediately open CB YES/NO
Command open CB
not delayed YES YES ..............The command to open the CB (DI at terminal 75) is carried out im-
mediately, regardless if there is a request for power reduction, syn-
chronization, or opening of a CB by another LS 4/GCP. The follow-
ing screens of this function will not be displayed.
NO ................The command to open the CB (DI at terminal 75) is carried out fol-
lowing the verification that no other LS 4/GCP is requesting a power
reduction, synchronization, or opening of a CB. The following
screens of this function are displayed.
Parameter 26
Power reduction prior to "Command: open CB" YES/NO
Command open CB
Pow. reduct. NO YES ..............The "Command: open CB" would be issued following a power re-
Visible only if Parameter 25 has duction after reaching the following configured level (see Table ).
been configured to NO NO ................The "Command: open CB" would be issued after the comparison of
other LS 4/GCP with the discrete input "Command: open
CB"(terminal 75). A power reduction is not carried out.
Parameter 27
"Command: open CB" at 0 to 100 %
Command open CB
Open at 000% If the prior screen is configured to YES the "Command: open CB" is issued to the
Visible only if Parameter 25 has configured relay following a power reduction and reaching or falling below this
been configured to NO level.
NOTE
This section describes the configuration screens in the GCP control unit which work together with the
LS 4. Please also note the settings for the emergency power and the mains settling time.
Parameter 28
LS 4 mode ON/OFF
LS 4 modus
ON ON................ The GCP is operating in LS 4. The control unit CAN bus messages
from the LS 4 and reacts accordingly. Additionally the control unit
transmits messages to the LS 4.
OFF.............. The control unit operates without LS 4 functionality as a normal gen-
set control.
Parameter 29
Rated power in the system 0 to 16,000 kW
Rated power
system 00000kW The LS 4 transmits the actual mains real power in percent related to the rated power
in the system to the GCP control unit .
Note
This configuration is valid only if Parameter 28 is configured to ON.
ATTENTION
Due to the LS 4 only transmitting a percentage value related to the rated value it is
mandatory to configure the rated power in all units (GCPs and LS 4s) to the same
value.
Parameter 30
Mains decoupling through GCB/external
Mains decoupling
via --------- GCB ............. If a mains failure occurs (see mains protection) the GCB would be
opened. (A mains failure would be detected using the mains voltage
on terminals 50/51/52.)
external........ The GCP control unit reacts as follows to a mains failure: a mains
decoupling order is issued by closing the relay "Mains failure exter-
nal" in the GCP. This command must be evaluated externally (i.e.
open the mains circuit breaker).
Note
"Mains decouple through external" is valid only if Parameter 28 is configured to
ON.
[A] [A]
15 17 18 16 19
LS 4.18
on/off
on/off
LS 4.17 LS 4.19
on/off
[A]
[B]
[B] [B]
Load
1 3
Busbar 1 Busbar 2
Load
V~ V~ V~ V~
on/off
on/off
on/off
on/off
GCP 1 GCP 2 GCP 3 GCP 4
#1 #2 #3 #4
V~ V~ V~ V~
I~ I~ I~ I~
G V/Q
G V/Q
G V/Q
G V/Q
Figure 6-2: Example A - H-Connection with two gensets per bus bar
LS 4.18
LS 4.20
on/off
on/off
on/off
LS 4.17 LS 4.19 LS 4.21
on/off on/off
[A]
[B]
[A]
[B]
[B] [B] [B]
Load
1 5 9
Busbar 1 Busbar 2 Busbar 3
Load
V~ V~ V~ V~ V~ V~
on/off
on/off
on/off
on/off
on/off
on/off
GCP 1 GCP 4 GCP 5 GCP 8 GCP 9 GCP 12
#1 #4 #5 #8 #9 #12
V~ V~ V~ V~ V~ V~
........ ........ ........
I~ I~ I~ I~ I~ I~
G V/Q
G V/Q
G V/Q
G V/Q
G V/Q
G V/Q
Figure 6-3: Example B - Double-H-connection with two gensets per bus bar
Example C - Emergency power application with 1× generator and 1× feeder bus bar
[B]
Load
17 16
on/off
LS 4.17
15
[A]
[A] 18
on/off
LS 4.18
17
[B]
Busbar 1
(Gen. Busbar)
1
V~ V~
1 2
on/off
I~ I~
G G
V/Q V/Q
ϑ/n/Vbatt/.. ϑ/n/Vbatt/..
Start/stop Start/stop
n/f/P n/f/P
Figure 6-4: Example C - Emergency power application with 1× generator and 1× feeder bus bar
Example D - Emergency power application with 1× generator and 2× feeder bus bars
[A] [A]
15 16
17 18
on/off
on/off
LS 4.17 LS 4.18
[B] [B]
Load Load
[A] [A]
17 18
19 20
on/off
on/off
LS 4.19 LS 4.20
[B] [B]
Busbar 1
1
V~ V~
on/off
on/off
GCP 1 GCP 2
#1 #2
V~ V~
I~ I~
G V/Q
G V/Q
ϑ /n/Vbatt/.. ϑ /n/Vbatt/..
Start/stop Start/stop
n/f/P n/f/P
Figure 6-5: Example D - Emergency power application with 1× generator and 2× feeder bus bars
Example E - Multiple mains incomings to one common bus bar (no emergency power)
on/off
on/off
on/off
LS 4.17 LS 4.18 LS 4.19 LS 4.20
Load
1
Busbar 1
V~ V~
on/off
on/off
GCP 1 GCP 2
#1 #2
V~ V~
I~ I~
G V/Q
G V/Q
ϑ /n/Vbatt/.. ϑ /n/Vbatt/..
Start/stop Start/stop
n/f/P n/f/P
Figure 6-6: Example E - Multiple mains incomings to one common bus bar (no emergency power)
Mains Mains
18
LS 4.18
[A] [A]
15 17 16 19
on/off
on/off
on/off
[A]
[B]
LS 4.17 LS 4.19
[B] [B]
[A] [A]
17 20 18 21
on/off
on/off
LS 4.20 LS 4.21
[B] [B]
19 20
22
LS 4.22
on/off
[A]
[B]
Load
1 3
Busbar 1 Busbar 2
Load
V~ V~ V~ V~
on/off
on/off
on/off
on/off
GCP 1 GCP 2 GCP 3 GCP 4
#1 #2 #3 #4
V~ V~ V~ V~
I~ I~ I~ I~
G V/Q
G V/Q
G V/Q
G V/Q
Control Functions
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
Synchronizing Functions
Function: "Synchronization"
The control unit calculates internally the electrical angle of advance to issue the circuit breaker closure command.
The corresponding lead-time remains constant due to the inherent delay of the breaker regardless of the frequen-
cy differential of the two systems. If the voltage and frequency differential of the two systems are within per-
missible limits, the breaker closure command may be issued under the following conditions:
• The momentary voltage effective values of the two systems must each be greater than 75 % and less than
112.5 % of the configured set point voltage. (With activation of the voltage protection these values apply as
valid; Parameter 57 and Parameter 63)
• The set point for the maximum permissible differential voltage between the two systems is not exceeded
(Parameter 34).
• The set point for the maximum permissible differential frequency between the two systems is not exceeded
(Parameter 32 and Parameter 33).
• The electrical angle between two equal phases must be less than the permissible phase-displacement angle
(slip-dependent) set point (Parameter 35).
Synchronizing Functions
Parameter 31
Synchronizing functions ON/OFF
Synchronizing
functions ON ON................ The synchronization functions are enabled, and the following screens
of this function are displayed.
OFF.............. The synchronization functions are disabled, and the subsequent
screens of this function are not indicated.
Parameter 32
Max. admissible positive differential frequency 0.02 to 0.49 Hz
Synchronization
df max 0.00Hz The prerequisite for the issuing of a close CB command is that the differential fre-
quency is lower than the configured positive limit. This value indicates the upper
limit frequency (positive value corresponding to positive slip Æ frequency) of the
variable system is greater than the frequency of the fixed system during synchroni-
zation of the CB.
Parameter 33
Max. admissible negative differential frequency 0.00 to -0.49 Hz
Synchronization
df min -0.00Hz The prerequisite for the issuing of a close CB command is that the differential fre-
quency has fallen below the configured negative limit. This value indicates the
lower frequency (a negative value represents negative slip) of the variable system
lower than the frequency of the fixed system during synchronization of the CB.
Parameter 34
Max. admissible differential voltage 0.1 to 15.0 %
Synchronization
dV max 00.0% The set percentage refers to the configured secondary voltage. To ensure that a
connect command will be issued, the actual value must fall below the entered diffe-
rential voltage percentage.
Parameter 35
Optimum slip +/-0.04 to +/-0.50 %
Synchronization
s opt 0.00% This value allows for adjustment of the synchronization frequency in relationship
to the system being synchronized with. It is possible to set slip in the positive and
negative directions. The LS 4 transfers this difference as a set point value to the
GCP. The GCP then controls the frequency according to the value set in this
screen.
Parameter 36
Pulse duration for switching 50 to 250 ms
Synchronization
Time pulse>000ms The duration of the breaker closure command is defined by this parameter. The
length of the pulse can be adjusted to the requirements of the individual breaker.
The configured value defines the minimum on time of the pulse.
Parameter 37
Switcher time delay circuit breaker 40 to 300 ms
Synchronization
Closing t. 000ms The inherent switching time of the power circuit breaker corresponds to the lead-
time of the close CB order. This set point is the amount of time that the close CB
command is issued prior to the generator reaching the synchronous time, irrespec-
tive of the differential frequency.
WARNING
Ensure the following parameters are configured correctly to prevent erroneous synchronization set-
tings. Incorrect wiring of the system cannot be compensated for with this parameter!
Parameter 38
Phase angle deviation -180 to 0 to +180 °
Synchronization
Phase diff.±000° This parameter compensates for phase angle deviations, which can be caused by
transformers (i.e. a delta to wye transformer) located within the electrical system.
Ensure the following parameters are configured correctly to prevent erroneous syn-
chronization settings. Incorrect wiring of the system cannot be compensated for
with this parameter!
Please act as follows: If a transformer is not located between systems [A] and [B]
or if the transformer has a vector group without a phase angle deviation, then a
phase angle deviation of 0° should be configured in this parameter.
With a phase angle deviation of 0° and the generator not running and the mains energized, close the GCB. This
will result in system [A] and system [B] being at the same voltage potential. The phase angle deviation will now
be displayed on the LS 4 screen (synchronization angle phi). Enter the displayed value into this parameter.
CAUTION
The correct setting must be validated in every control unit with a differential voltage measurement (see
chapter "Commissioning")!
The vector group of the transformer is known and states the phase angle deviation in multiplies of 30°. Out of the
vector group the phase angle deviation can be calculated as an angle from 0° to 360°. For this value the voltage
of the low voltage side is behind the voltage of the high voltage side Ö phase angle deviation α! When cal-
culating the resulting value, the low voltage side of the transformer always lags behind the high voltage
side (phase angle deviation α).
High voltage side = System [A] High voltage side = System [B]
α < 180 ° α -α
α > 180 ° -360 ° + α 360 ° - α
Table 6-8: Calculation of the phase angle deviation
Mains Example 1
System [B] is connected to the generator. The generator voltage is connected to the low
[A] voltage side of a transformer with the vector group Dyn5. The MCB is connected to the
high voltage side, which connects the transformer to the mains. System [A] is con-
on/off
LS 4
nected to the mains. Because of the transformer the phase angles at the breaker differ
MCB
[B] between the measuring voltages of system [A] and system [B]. A phase angle deviation
High voltage side
exists which can be compensated with the LS 4.
Dyn5
Δ:Y Using the vector group 5 (Dyn5) it counts α = 5 × 30 ° = 150 °. Because 150 ° < 180 °
and system [A] is connected to the high voltage side this results into α to be used as
Low voltage side
phase difference. Enter 150 ° into as parameter for the phase difference.
G
Synchronization
Phase diff. 150°
Mains Example 2
LS 4
330 ° > 180 ° and system [A] is connected to the high voltage side this results into (-
MCB
[B]
High voltage side 360 ° + α) to be used as phase difference. Enter -30 ° into as parameter for the phase
difference.
Yd11
Y:Δ Synchronization
Phase diff.-030°
Low voltage side
CAUTION
The correct setting must be validated in every control unit with a differential voltage measurement (see
chapter "Commissioning")!
Synchronous Networks
Parameter 40
Parallel mains blocked / available
Parallel mains
---------------- available ...... Closing of the CB onto synchronous networks is enabled. The fol-
lowing screens of this function are visible.
blocked ........ Closing of the CB onto synchronous networks is disabled. The fol-
lowing screens of this function are not visible.
Parameter 41
Max. admissible angle between both voltage systems 0 to 20 °
Parallel mains
phi max 00° The prerequisite for the issuing of a close CB order is that the differential angle is
below the configured limit.
Parameter 42
Min. time "Angle phi max" to issue a close CB command 0 to 99 s
Parallel mains
phi max 00s For a close CB order to be issued, the differential angle between the both voltage
systems must be lower than the "Synchr. networks phi max" (Parameter 41) conti-
nuously for the time specified with this parameter.
CAUTION
The measuring voltages are normally protected. A blown fuse may lead to the unit executing a dead
bus start. In this case the unit would, among other things, switch to an asynchronous voltage, which
can lead to substantial damage to the system. Therefore, the release of the dead bus start function
must be locked via external safety measures if a blown fuse is detected (Removal of the "Enable CB"
signal).
Parameter 43
Dead bus start of CB ON/OFF
Dead bus op. CB
ON ON ................Dead bus start function is enabled. The prerequisite for this is the de-
tection of an operating condition that corresponds to the specifica-
tions. The subsequent screens of this function are displayed.
OFF ..............No dead bus start is carried out, and the subsequent screens of this
function are not displayed.
Parameter 44
Dead bus start function 1: VA = VB = 0 ON/OFF
Dead bus op. CB
VA=O/VB=O ON Enabling dead bus start function 1: This application requires the voltage in both
systems to fall below an adjustable threshold value in order to enable the output of
a close CB order (dead system A - dead system B).
Parameter 45
Dead bus start function 2: VA = 0, VB = Vn ON/OFF
Dead bus op. CB
VA=O/VB=Vn ON Enabling dead bus start function 2; This application dictates the approximate value
of the voltage of system VA must be zero and the voltage of system VB must be
applied (dead system A - live system B).
Parameter 46
Dead bus start function 3: VA = Vn, VB = 0 ON/OFF
Dead bus op. CB
VA=Vn/VB=O ON Enabling dead bus start function 3: This application dictates the approximate value
of the voltage of system VB must be zero and the voltage of system VA must be
applied (live system A - dead system B).
Parameter 47
Min. monitoring time of the dead bus start conditions 0 to 20 s
Dead bus op. CB
Tmin > 00s Before a dead bus start may be initiated, all conditions for the closing of the circuit
breaker must be maintained for the preset time.
Parameter 48
Max. adm. zero voltage diff. for switching to the dead busbar 3 to 50 %
Dead bus op. CB
dV |V-O| < 00% To ensure that the value of a voltage is detected as "approximate zero" the maxi-
mum deviation from zero must not exceed the preset value (referring to the rated
voltage).
Parameter 49
Min. rated voltage diff. for switching to the dead busbar 1 to 20 %
Dead bus op. CB
dV |V-Vn| < 00% To ensure that a voltage is detected as "applied", the deviation from the rated vol-
tage must not exceed the preset value.
Parameter 50
Max. rated frequency diff. for switching to the dead busbar 0.05 to 5.00 Hz
Dead bus op. CB
df max 0.00Hz To ensure that a circuit breaker may be closed, the deviation of the frequency of the
voltage-carrying system from the rated frequency must not exceed the differential
frequency preset.
Parameter 51
Blocking of dead bus start at alarm ON/OFF
Dead bus op. CB
block.alarm ON ON................ The dead bus start function is not permitted if an alarm is present.
OFF.............. The dead bus start function is permitted if an alarm is present.
Monitoring Functions
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
CAUTION
The function "Command: open CB" must be assigned to one of the freely configurable relays using the
relay manager (see Parameter 98).
NOTE
Parameter 56 does not appear if a "Phase to phase" measurement (Parameter 6) has been configured
in the configuration screen "Volt. measuring".
Parameter 56
Monitoring for ... Phase to phase / Phase-neutral
Volt.-monitoring
---------------- The unit can monitor either the phase-neutral voltages (four-wire wye system) or
the phase-to-phase voltages (three-wire delta system). Typically, the phase-neutral
voltages are monitored in the low voltage system (400 Vac version; parameter text:
(Phase-N)), and the phase-to-phase voltages are monitored in the mid-tap voltage
system (100 Vac version; parameter text: (ph-ph)). A monitoring of phase-to-
phase voltage is primarily utilized if a triggering of the voltage watchdog for a
ground fault condition is not desired in an isolated or compensated system.
Parameter 6 "Volt. measuring" must be configured "Phase to phase" to obtain
this effect. The settings of this parameter have the following effect on the configu-
ration screens:
Overvoltage Monitoring
Function: "Voltage not within permissible limits"
The monitored voltage in at least one phase is not within the configured permissible limits for overvoltage. The
alarm message "Overvolt.1" or "Overvolt.2" will be displayed. This message cannot be suppressed with
the discrete input "Blocking of protective functions / remote acknowledgement".
Parameter 57
Overvoltage monitoring ON/OFF
Overvoltage
Monitoring ON ON................ Overvoltage monitoring is enabled. The subsequent screens of this
function are displayed.
OFF.............. Overvoltage monitoring is disabled. The subsequent screens of this
function are not displayed.
Parameter 58
Threshold (Phase-phase) [1] 20 to 150 V; [4] 20 to 520 V
Parameter "Phase to phase":
overvoltage level 1 (Phase-neutral) [1] 10 to 87 V; [4] 10 to 300 V
Overvoltage 1
V(ph-ph) > 000V Overvoltage (level 1) is defined by this parameter. If this limit is reached or ex-
ceeded, the unit outputs the message "Overvolt.1". If a relay was assigned to
Parameter "Phase-neutral":
this function in the relay manager (Parameter 101), that relay will be energized.
Overvoltage 1
(Phase-N) >000V
Parameter 59
Delay for level 1 0.02 to 99.98 s
Overvoltage 1
Delay 00.00s In order to initiate an overvoltage (level 1) alarm, the measured voltage must ex-
ceed and remain above the configured threshold (Parameter 58) without interrup-
tion for at least the period of time specified in this screen.
Parameter 60
Threshold (Phase-phase) [1] 20 to 150 V; [4] 20 to 520 V
Parameter "Phase to phase":
overvoltage level 2 (Phase-neutral) [1] 10 to 87 V; [4] 10 to 300 V
Overvoltage 2
V(ph-ph) >000V Overvoltage (level 2) is defined by this parameter. If this limit is reached or ex-
ceeded, the unit outputs the message "Overvolt.2". If a relay was assigned to
Parameter "Phase-neutral":
this function in the relay manager (Parameter 101), that relay will be energized.
Overvoltage 2
(Phase-N) >000V
Parameter 61
Delay for level 2 0.02 to 99.98 s
Overvoltage 2
Delay 00.00s In order to initiate an overvoltage (level 1) alarm, the measured voltage must ex-
ceed and remain above the configured threshold (Parameter 60) without interrup-
tion for at least the period of time specified in this screen.
Parameter 62
Hysteresis for overvoltage monitoring 0 to 99 V
Overvoltage
Hysteresis 00V In order to prevent system fluctuations from continually initiating overvoltage
alarms (both levels; Parameter 58 and Parameter 60), a lower release point is de-
fined here. If the control monitors the voltage above the permissible limit, the vol-
tage must drop below that threshold and the voltage level defined here for the fault
condition to be recognized as no longer existing.
Example: If a 480 V system has an overvoltage limit of 510 V and a hysteresis of
10 V, the monitored voltage for an overvoltage alarm must drop below 500 V to re-
set the alarm.
Undervoltage Monitoring
Function: "Voltage not within permissible limits"
The monitored voltage in at least one phase is not within the configured permissible limits for undervoltage. The
alarm message "Und.volt.1" or "Und.volt.2" will be displayed. This message can be suppressed with the
discrete input "Blocking of protective functions / remote acknowledgement".
Parameter 63
Undervoltage monitoring ON/OFF
Undervoltage
Monitoring ON ON ................Undervoltage monitoring is enabled. The subsequent screens of this
function are displayed.
OFF ..............Undervoltage monitoring is disabled. The subsequent screens of this
function are not displayed.
Parameter 64
Threshold (Phase-phase) [1] 20 to 150 V; [4] 20 to 520 V
Parameter "Phase to phase":
undervoltage level 1 (Phase-neutral) [1] 10 to 87 V; [4] 10 to 300 V
Undervoltage 1
V(ph-ph) <000V Undervoltage (level 1) is defined by this parameter. If this limit is reached or ex-
ceeded, the unit outputs the message " Und.volt.1". If a relay was assigned to
Parameter "Phase-neutral":
this function in the relay manager (Parameter 101), that relay will be energized.
Undervoltage 1
(Phase-N) <000V
Parameter 65
Delay for level 1 0.02 to 99.98 s
Undervoltage 1
Delay 00.00s In order to initiate an undervoltage (level 1) alarm, the measured voltage must fall
below and remain below the configured threshold (Parameter 64) without interrup-
tion for at least the period of time specified in this screen.
Parameter 66
Threshold (Phase-phase) [1] 20 to 150 V; [4] 20 to 520 V
Parameter "Phase to phase":
undervoltage level 2 (Phase-neutral) [1] 10 to 87 V; [4] 10 to 300 V
Undervoltage 2
V(ph-ph) <000V Undervoltage (level 2) is defined by this parameter. If this limit is reached or ex-
ceeded, the unit outputs the message " Und.volt.2". If a relay was assigned to
Parameter "Phase-neutral":
this function in the relay manager (Parameter 101), that relay will be energized.
Undervoltage 2
(Phase-N) <000V
Parameter 67
Delay for level 2 0.02 to 99.98 s
Undervoltage 2
Delay 00.00s In order to initiate an undervoltage (level 1) alarm, the measured voltage must fall
below and remain below the configured threshold (Parameter 66) without interrup-
tion for at least the period of time specified in this screen.
Parameter 68
Hysteresis for undervoltage monitoring 0 to 99 V
Undervoltage
Hysteresis 00V In order to prevent system fluctuations from continually initiating undervoltage
alarms (both levels; Parameter 64 and Parameter 66), a higher release point is de-
fined here. If the control monitors the voltage below the permissible limit, the vol-
tage must rise above that threshold and the voltage level defined here for the fault
condition to be recognized as no longer existing.
Example: If a 480 V system has an undervoltage limit of 440 V and a hysteresis of
10 V, the monitored voltage for an undervoltage alarm must rise above 450 V to re-
set the alarm.
Overfrequency Monitoring
The frequency monitoring is performed on two levels. The frequency measuring is monitored three-phase if all
voltages are greater than 15 % of the rated value (100 V or 400 V). This ensures quick and precise measurement
of the frequency. The frequency is still monitored correctly even if voltage is only applied to one phase.
Underfrequency Monitoring
The frequency monitoring is performed on two levels. The frequency measuring is monitored three-phase if all
voltages are greater than 15 % of the rated value (100 V or 400 V). This ensures quick and precise measurement
of the frequency. The frequency is still monitored correctly even if voltage is only applied to one phase.
NOTE
If the monitoring is configured as "3 phase only", only Parameter 88 will be displayed. If the monitor-
ing is configured as "one/three-phase", both configuration screens (Parameter 87 and Parameter 88)
will be displayed.
Parameter 87
Phase angle of phase/vector shift monitoring, single phase 2 to 30 °
Phase shift
(One phase) 00° An alarm will be issued if the phase angle in any one phase exceeds the configured
This screen is visible only if phase shift phase angle limit. If the monitored voltage/frequency reaches or ex-
Parameter 86 is configured to ceeds the phase shift limit, the unit outputs the message "Ph. shift". If a relay
one/three phase.
was assigned to this function in the relay manager (Parameter 101), that relay will
be energized.
Parameter 88
Phase angle of phase/vector shift monitoring, three phase 2 to 30 °
Phase shift
(3-phase) 00° An alarm will be issued if the phase angle in any all three phases exceeds the con-
figured phase shift phase angle limit. If the monitored voltage/frequency reaches or
exceeds the phase shift limit, the unit outputs the message "Ph. shift". If a re-
lay was assigned to this function in the relay manager, that relay will be energized.
Relay Configuration
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
NOTE
Clearing of faults and fault messages from the control unit will depend on the parameters "Exter-
nal clearing", "Auto-clearing Relays", and "Auto-clearing Display". These three parameters
will influence the other depending on how each is configured. This is explained in the following text.
Parameter 92
Acknowledgement via the discrete input ON/OFF
External
Clearing ON "Auto-clearing Relays" configured "OFF" (refer to "Auto Acknowledge-
External acknowledgement of the
ment of the Relays" on page 64):
relays via the discrete input
"Blocking of protective functions OFF ..............Alarms that cannot be blocked with discrete input "Blocking of pro-
/ remote acknowledgement".
tective functions / remote acknowledgement" will not be reset when
the fault condition is no longer present. Pressing the "Clear" button
resets the relays.
ON ................All alarms are reset when the discrete input "Blocking of protective
functions / remote acknowledgement" (terminals 5/6) is energized.
Alarms which cannot be blocked with the discrete input "Blocking of
protective functions / remote acknowledgement" are only reset after
the fault condition is no longer present.
OFF ..............Pressing the "Clear" button resets the displayed fault messages.
ON ................All displayed fault messages are reset when the discrete input
"Blocking of protective functions / remote acknowledgement" (ter-
minals 5/6) is energized. Alarms which cannot be blocked with the
discrete input "Blocking of protective functions / remote acknowled-
gement" are only reset after the fault condition is no longer present.
The alarm message in the display is cleared according to how the parameter "Au-
to-clearing Display" is configured. The subsequent screens of this func-
tion are not indicated.
NOTE
The subsequent screens are only visible if the parameter "Auto-clearing Relays" and the corres-
ponding protective function are enabled and the control unit is equipped with the protective functional-
ity.
Parameter 94
Reset delay for relays 0.02 to 99.98 s
Release delay
--------- 00.00s The individual relays will reset if "Auto-clearing relays" has been enabled and the
monitored values have returned to the permissible limits plus / minus the hysteresis
(depending on monitoring) without interruption for the time specified in this para-
meter. If the monitored value exceeds / falls below the threshold limit, the delay ti-
mer re-initiates its countdown. The following protective functions may have reset
delays configured.
NOTE
The subsequent parameter “Clearing display after ” is not visible if "Auto-clearing Relays"
is configured to "OFF".
Parameter 96
Clear displayed message delay 1 to 99 s
Clearing display
after 00s Alarm messages, which have been enabled, will be acknowledged after this confi-
gured delay time expires. This delay will initiate once the measure value ex-
ceeds/falls below the threshold limit +/- the hysteresis
Funct. relay 45 E ...................The relay is configured as normally open (N.O.) contacts. The relay
(R=release) RR will energize only if the assigned monitoring function has tripped.
R ...................The relay is configured as normally closed (N.C.) contacts. The relay
Parameter 100 is always energized and will only de-energize (release) if the as-
Funct. relay 67 signed monitoring function has tripped.
(R=release) RR
NOTE ...........Relay 1 is configured as R (release/N.C.) and cannot be modified.
NOTE
The following screen(s) will only be displayed if the unit is equipped with the corresponding protective
function(s), the protective function is enabled, and the parameter "Change relay allocation" is
enabled.
Parameter 101
Assign protective function output to relays 0 to 7
----------------
to relay 0000 Each digit in this parameter is used to assign one relay to a protective function. Up
to four relay outputs may be assigned to a protective function. The control may be
configured as follows:
0.................... If the protective function is not assigned to a relay, a "0" must be
configured in the display. None of the relay outputs will energize/de-
energize when the corresponding protective function trips if all four
relay assignments are configured with a "0". A message for the pro-
tective function will still be visible in the unit display.
1-7 ................ Relays 1 through 7 are available for assignment to protective func-
tion on all units.
Example ...... An LS 4 has a protective function that is required to output a signal
to relays 2,4, and 7. That protective function relay assignment should
be configured as 2470. The sequence of the numbers has no signific-
ance in the functionality or operations.
A relay output may be assigned to more than one protective function. This will
cause to relay to issue a signal when any of the configured protective functions trip.
If a relay should only issue a signal when a specific protective function trips, then
the relay must not be assigned to any other protective function.
NOTE
The "ready for operation" function is always assigned to relay 1. However, other protective functions
may also be assigned to relay 1 additionally. Relay 1 is always configured as Normally Closed (break
contact) and will de-energize if the unit is not ready for operation.
Parameter 102
Output of the centralized alarm to the relays 0 to 7
Collect response
to relay 0000 By setting this relay, a centralized alarm is issued. This parameter permits a horn or
buzzer to be triggered from this relay. The operator may reset the relay by pressing
the "Clear" button for a short period. The relay will be reset in the event another
alarm occurs.
Interface
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
General Parameters
Parameter 104
Control via interface ON/OFF
Serial control
ON ON................ Control via the serial interface is enabled and control orders received
via the interface are processed.
OFF.............. Control via the serial interface is disabled and control orders received
via the interface are ignored.
NOTE
This functionality is not possible via a Gateway GW 4!
Parameter 105
Interface monitoring ON/OFF
Serial interface
Monitoring ON ON................ The interface monitoring is enabled. The control expects to receive
bits 2 and 3 to be written to "00" in the control word by the master
control within 15 seconds after receiving the last message. If these
bits are not read within the prescribed time, and unsuccessful data
exchange is detected, and the alarm message "Interface" is is-
sued.
OFF.............. The interface monitoring is disabled.
NOTE
The communication between the LS 4 and the GCP is always monitored and an interruption of the
communication is triggered to the relay configured here.
Parameter 106
Blocking via interface ON/OFF
Inhibit via
Interface ON ON................ The protective functions messages (i.e. underfrequency) may be sup-
press via the interface. This operates in the same manner as terminals
5/6 "Blocking of protective functions / remote acknowledgement".
OFF.............. The protective functions messages (i.e. underfrequency) cannot be
suppress via the interface.
Parameter 107
Message interface alarm to relays 0 to 2
Interface fault
to relay 0000 Relays may be configured to energize when an interface fault is detected. The de-
sired relays that to energize are configured here. The relays will only energize if the
parameter "Serial interface Monitoring" (Parameter 105) is configured
as "ON".
NOTE
Please note configure IDs must not be duplicated (every ID must be unique in the system). This applies
to all CAN bus coupled units. Base ID’s must be assigned consecutive numbers when configuring unit
addresses.
How to configure transmitting IDs:
All units on the same CAN bus are configured with the same "base ID transmitting" (Parameter 110).
With this setting all types of messages are grouped. (Example: All items are configured with "base ID
transmitting" = 800. Using the different unit numbers (Parameter 108) on the CAN bus the units are
unique; unit number 17: ID = 817; unit number 18: ID = 818, etc.)
Parameter 108
Unit number CAN-Bus 17 to 24
Device number
CAN-Bus 00 The unit number must be entered here for CAN bus. The unit number affects the
calculation of transmission and control ID's.
Parameter 109
Baudrate CAN bus 125/250/500 kBaud
Baudrate
000 kBaud Configuration of the Baudrate. If the LS 4 is used with a GCP control unit the Bau-
drate is to be configured to "125 kBaud".
Parameter 110
Base ID transmission 0 to 2.015
Base-ID (send)
0000 The ID, on which the unit transmits its data is calculated from base ID transmission
+ unit number CAN bus (Parameter 108). If the LS 4 is used with a GCP control
unit, "0800" must be configured here.
Parameter 111
Base ID control 0 to 2.015
Base-ID (remote)
0000 The ID, on which the unit receives its data is calculated from base ID control + unit
number CAN bus (Parameter 108). If the LS 4 is used with a GCP control unit
"0785", must be configured here.
Parameter 112
ID for remote configuration 0 to 2.015
ID (parametriz.)
0000 The ID, on which the unit receives its configuration data is entered here. If the unit
is configured using a CAN bus card with LeoPC1, "0831" must be configured
here.
Change Passwords
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
NOTE
Once the code level is set, it will not be changed even after entering the configuration repeatedly an in-
correct code number has been entered, the code level is set to CS0, thus locking the device for external
persons.
If for 2 hours uninterruptedly supply voltage is applied, the device automatically switches to code lev-
el 0.
Parameter 113
Code level 1 (Client) 0000 to 9999
Define level 1
code 0000 This screen appears only when the level 2 password has been entered. After enter-
ing the digits into this screen, the code level for level 1 (basic service level) is
enabled. After entering this code, the user only has the access rights assigned to this
code level.
This code level (CS) is preset to CS1 = 0 0 0 1
Parameter 114
Code level 2 (Commissioner / Engineer) 0000 to 9999
Define level 2
code 0000 This screen appears only when the level 2 password has been entered. After enter-
ing the digits into this screen, the code level for level 2 (commissioning level) is
enabled. After entering the code, the user has the access rights assigned to this code
level.
This code level (CS) is preset to CS2 = 0 0 0 2
Chapter 7.
Commissioning
DANGER TO LIFE
CAUTION
Only a qualified technician may commission unit. The "EMERGENCY-OFF" function must be opera-
tional prior to commissioning of the system, and must not depend on the unit for its operation.
CAUTION
Prior to commissioning ensure that all measuring devices are connected in correct phase sequence.
The connect command for the unit circuit breaker must be disconnected at the unit circuit breaker. The
field rotation must be monitored for proper rotation. Any absence of or incorrect connection of voltage
measuring devices or other signals may lead to malfunctions and damage the unit, the engine, and/or
components connected to the unit!
Commissioning Procedure:
CAUTION
Do not proceed to the next step until all previous steps have been accomplished!
Appendix A.
Dimensions
Front view
Configuration plug
35
65
72
27
Back plate mounting
optionally
Bottom view
130 50
Configuration plug
1 16
X1 X5 40 45
96
90
130
70 75
32 17
Appendix B.
Technical Data
NOTE
Values which does not fit are have to be added to the standard values regarding the UL listing are
marked with the amendment "(UL)".
Housing ----------------------------------------------------------------------------------------------------------
- Type ........................................................................................... APRANORM DIN 43 700
- Dimensions (W × H × D) ........................................................................ 96 × 72 × 130 mm
- Front cutout (W × H) ................................................................... 91 [+0.8] × 67 [+0.7] mm
Appendix C.
Measured Quantities and Accuracy
Appendix D.
Interface
Transmission Telegram
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
The data of the following table can be handled by a Gateway GW 4 or a PLC and can be transferred to other
busses. An LS 4 is sending the data via circular CAN messages.
(The unit number is a parameter adjustable on the LS 4, which influences directly the CAN ID on which the unit
sends the visualization message).
A visualization message which is send out of an LS 4 has 8 Bytes and is constructed as follows:
In a visualization message the byte 0 is always used to show the hexadecimal value DD. This one defines the
message as a visualization message. As the complete transmission telegram of the LS 4 includes more than three
words, byte 1 sends additionally a MUX number starting with 0. Therefore it is theoretically possible to send
(256 × 3 = 768) words via the CAN ID. The whole telegram is built up as follows:
n depends on the total length of the item special telegram and cannot be larger than H’FF.
MUX
No.
0/1 1 Protocol number "1600"
0/2 2 Voltage L12, system [A] V × 10UGNEXPO
0/3 3 Voltage L23, system [A] V × 10UGNEXPO
1/1 4 Voltage L31, system [A] V × 10UGNEXPO
1/2 5 Voltage L1N, system [A] V × 10UGNEXPO
1/3 6 Voltage L2N, system [A] V × 10UGNEXPO
2/1 7 Voltage L3N, system [A] V × 10UGNEXPO
2/2 8 Frequency, system [A] Hz × 100
2/3 9 Current in L1, system [A] A × 10IGNEXPO
3/1 10 Current in L2, system [A] A × 10IGNEXPO
3/2 11 Current in L3, system [A] A × 10IGNEXPO
3/3 12 Power factor cos ϕ dimensionless Example: 0064H cos ϕ = 1.00
0063H cos ϕ = i 0.99 (inductive)
FF9EH cos ϕ = c0.98 (capacitive)
4/1 13 Real power P, system [A] W × 10PGNEXPO
4/2 14 Re-active power Q, system [A] var × 10PGNEXPO positive = inductive; negative = capacitive
4/3 15 Voltage L12, system [B] V × 10UNTEXPO
5/1 16 Voltage L23, system [B] V × 10UNTEXPO
5/2 17 Voltage L31, system [B] V × 10UNTEXPO
5/3 18 Frequency, system [B Hz × 100
HighByte: UGNEXPO Voltage system [A]
6/1 19 Exponent
LowByte: IGNEXPO Current system [A]
HighByte: PGNEXPO Power system [A]
6/2 20 Exponent
LowByte: UNTEXPO Voltage system [B]
6/3 21 Internal alarms 1 Bit 15 = 1 \
Overfrequency level 2
Bit 14 = 0 /
Bit 13 = 1 \
Underfrequency level 2
Bit 12 = 0 /
Bit 11 = 1 \
Overvoltage level 2
Bit 10 = 0 /
Bit 9 = 1 \
Undervoltage level 2
Bit 8 = 0 /
Bit 7 = 1 \
Internal
Bit 6 = 0 /
Bit 5 = 1 \
Internal
Bit 4 = 0 /
Bit 3 = 1 \
Note: Internal
Bit 2 = 0 /
0/1 = Watchdog tripped not Bit 1 = 1 \
Internal
1/0 = Watchdog tripped Bit 0 = 0 /
7/1 22 Internal alarms 2 Bit 15 = 1 \
Overfrequency level 1
Bit 14 = 0 /
Bit 13 = 1 \
Underfrequency level 1
Bit 12 = 0 /
Bit 11 = 1 \
Overvoltage level 1
Bit 10 = 0 /
Bit 9 = 1 \
Undervoltage level 1
Bit 8 = 0 /
Bit 7 = 1 \
Internal
Bit 6 = 0 /
Bit 5 = 1 \
df/dt alarm
Bit 4 = 0 /
Bit 3 = 1 \
Note: Asymmetry
Bit 2 = 0 /
0/1 = Watchdog tripped not Bit 1 = 1 \
dϕ/dt phase/vector jump
1/0 = Watchdog tripped Bit 0 = 0 /
No.
MUX
No.
8/3 27 Internal alarms 7 Bit 15 =1 \
Internal
Bit 14 =0 /
Bit 13 =1 \
Wrong rotary field
Bit 12 =0 /
Bit 11 =1 \
Internal
Bit 10 =0 /
Bit 9 =1 \
Internal
Bit 8 =0 /
Bit 7 =1 \
Internal
Bit 6 =0 /
Bit 5 =1 \
Internal
Bit 4 =0 /
Bit 3 =1 \
Note: Internal
Bit 2 =0 /
0/1 = Watchdog tripped not Bit 1 =1 \
Internal
1/0 = Watchdog tripped Bit 0 =0 /
9/1 28 Internal Diagnosis Bit 15 =1 \
Bit 14 =1
│ 1111 = terminal 32 is set
Bit 13 =1 0000 = terminal 32 is not set
│
Bit 12 =1 /
Bit 11 =1 \
Bit 10 =1
│ 1111 = terminal 31 is set
Bit 7 =1 0000 = terminal 31 is not set
│
Bit 6 =1 /
Bit 7 =1 \
Bit 6 =1
│ 1111 = terminal 74 is set
Bit 5 =1 0000 = terminal 74 is not set
│
Bit 4 =1 /
Bit 3 =1 \
Bit 2 =1 │
1111 = terminal 75 is set
Bit 1 =1
0000 = terminal 75 is not set
│
Bit 0 =1 /
Receiving Telegram
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
Content (words) Unit Note
MUX
No.
Format
Example
CAN-ID in
[hex] [decimal]
GCP sends
Distribution message to other GCPs 180 + GENNO 384 + GENNO
Control message to LS 4 (the GCP with the lowest ID) 311 785
Visualization 320 + GENNO 800 + GENNO
GCP receives
Distribution message from other GCP 180 + GENNO 384 + GENNO
Control message from an LS 4 300 + GENNO 768 + GENNO
Configuration messages from a higher control 33F 831
LS 4 sends
Logic message to other LS 4s 180 + LS4NO 384 + LS4NO
Control message to GCP (the LS 4 with the lowest ID) 300 + GENNO 768 + GENNO
LS 4 receives
Logic message from other LS4 180 + LS4NO 384 + LS4NO
Control message from a GCP 311 785
Configuration messages and
configuration messages from a higher control 33F 831
[hex] [decimal]
GENNO = 1 to E 1 to 14
LS4NO = 11 to 1E 17 to 30
Appendix E.
List of Parameters
Version ___________________________________________________________________________
Project ___________________________________________________________________________
Standard
Option Parameter Setting range Customer settings
setting
BASIC DATA
Software version - -
Enter code number 0000 to 9999
SPRACHE/LANGUAGE German/English English GE GE
Password protection ON/OFF OFF on off on off
BASIC SETTINGS
Direct parametr. YES/NO YES YN YN
Volt. measuring Phase to phase / Phase-neutral P-N
Volt.transformer sec.[A] 50 to 120/50 to 480 V 120/400 V
Volt.transformer prim[A] 0.100 to 65.000 kV 0.400 V
Volt.transformer sec.[B] 50 to 120/50 to 480 V 120/400 V
Volt.transformer prim[B] 0.100 to 65.000 kV 0.400 V
Current transf. 1 to 9,999/x A 1,000/x A
Rated voltage 50 to 120/50 to 480 V 120/400 V
Rated frequency 40.0 to 70.0 Hz 50.0 Hz
Rated power 5 to 16,000 kW 500 kW
LS 4 FUNCTIONS
Segment number System [A] 1 to 28 1
Segment number System [B] 1 to 28 2
Segment number Disconnector 0 to 28 0
Disconnector at Voltage A / Voltage B Voltage A AB AB
Mains power meas valid/invalid invalid vi vi
Voltage A / Voltage B
Mains connection none
Disconnector / none
Variable system Voltage A / Voltage B Voltage A AB AB
Busb. 1 12345678 Gen. Y/N NNNNNNNN
Busb. 1 9ABCDE Gen. Y/N NNNNNN
Busb. 2 12345678 Gen. Y/N NNNNNNNN
Busb. 2 9ABCDE Gen. Y/N NNNNNN
Busb. 3 12345678 Gen. Y/N NNNNNNNN
Busb. 3 9ABCDE Gen. Y/N NNNNNN
Measuring CB ON one-/three-phase one-phase 13 13
Command open CB not delayed YES/NO NO YN YN
Command open CB Pow.reduct. YES/NO NO YN YN
Command open CB Open at 0 to 100 % 10 %
SYNCHRONIZATION
Synchronizing functions ON/OFF ON on off on off
Synchronization df max 0.02 to 0.49 Hz 0.18 Hz
Synchronization df min 0.00 to -0.49 Hz -0.10 Hz
Synchronization dV max 0.1 to 15.0 % 6.0 %
Synchronization s opt +/-0.04 to +/-0.50 % -0.04 %
Synchronization Time pulse> 50 to 250 ms 200 ms
Synchronization Closing t. 40 to 300 ms 80 ms
Synchronization Phase diff. -180 to 0 to +180 ° 0°
Synchronization block.alarm ON/OFF OFF on off on off
Standard
Option Parameter Setting range Customer settings
setting
SYNCHRONOUS NETWORKS
Parallel mains blocked / available blocked ed ed
Parallel mains phi max 0 to 20 ° 20 °
Parallel mains phi max 0 to 99 s 1s
DEAD BUS START
Dead bus op. CB ON/OFF OFF on off on off
Dead bus op. CB VA=0/VB=0 ON/OFF OFF on off on off
Dead bus op. CB VA=0/VB=Vn ON/OFF OFF on off on off
Dead bus op. CB VA=Vn/VB=0 ON/OFF OFF on off on off
Dead bus op. CB Tmin> 0 to 20 s 5s
Dead bus op. CB dV|V-0| < 3 to 50 % 10 %
Dead bus op. CB dV|V-Vn| < 1 to 20 % 5%
Dead bus op. CB df max 0.05 to 5.00 Hz 0.25 Hz
Dead bus op. CB block.alarm ON/OFF OFF on off on off
TIME MONITORING
CB timeout ON/OFF OFF on off on off
CB timeout Delay 0 to 999 s 120 s
CB timeout Release del. 0 to 999 s 120 s
CB syn.ti. fault to relay 0 to 7 0002
MONITORING FUNCTIONS
Volt.-monitoring Phase to phase / Phase-neutral P-P 34 34
Overvoltage Monitoring ON/OFF OFF on off on off
Overvoltage 1 V(ph-ph) > 20 to 130/20 to 520 V 110/440 V
(Phase-N) > 10 to 75/10 to 300 V 64/254 V
Overvoltage 1 Delay 0.02 to 99.98 s 0.10 s
Overvoltage 2 V(ph-ph) > 20 to 130/20 to 520 V 120/480 V
(Phase-N) > 10 to 75/10 to 300 V 69/277 V
Overvoltage 2 Delay 0.02 to 99.98 s 0.04 s
Overvoltage Hysteresis 0 to 99 V 8V
Undervoltage Monitoring ON/OFF OFF on off on off
Undervoltage 1 V(ph-ph) < 20 to 130/20 to 520 V 90/360 V
(Phase-N) < 10 to 75/10 to 300 V 51/207 V
Undervoltage 1 Delay 0.02 to 99.98 s 0.10 s
Undervoltage 2 V(ph-ph) < 20 to 130/20 to 520 V 80/320 V
(Phase-N) < 10 to 75/10 to 300 V 46/184 V
Undervoltage 2 Delay 0.02 to 99.98 s 0.04 s
Undervoltage Hysteresis 0 to 99 V 8V
Asymmetry Monitoring ON/OFF OFF on off on off
Asymmetry Response v. 0 to 99 V 10/40 V
Asymmetry Delay 0.02 to 99.98 s 2.00 s
Asymmetry Hysteresis 0 to 99 V 4V
Overfrequency Monitoring ON/OFF OFF on off on off
Overfrequency 1 f > 40.00 to 80.00 Hz 50.20 Hz
Overfrequency 1 Delay 0.02 to 99.98 s 0.10 s
Overfrequency 2 f > 40.00 to 80.00 Hz 51.00 Hz
Overfrequency 2 Delay 0.02 to 99.98 s 0.04 s
Overfrequency Hysteres. 0.01 to 9.99 Hz 0.05 Hz
Underfrequency Monitoring ON/OFF OFF on off on off
Underfrequency 1 f < 40.00 to 80.00 Hz 49.80 Hz
Underfrequency 1 Delay 0.02 to 99.98 s 0.10 s
Underfrequency 2 f < 40.00 to 80.00 Hz 49.00 Hz
Underfrequency 2 Delay 0.02 to 99.98 s 0.04 s
Underfrequency Hysteres. 0.01 to 9.99 Hz 0.05 Hz
Phase shift Monitoring ON/OFF OFF on off on off
Phase shift mon. one/three phase / 3 phase only 3-phase only 1-3 3 1-3 3
Phase shift (One phase) 2 to 30 ° 30 °
Phase shift (3-phase) 2 to 30 ° 8°
df/dt- Monitoring ON/OFF OFF on off on off
df/dt Response> 1.0 to 9.9 Hz/s 2.5 Hz/s
df/dt Delay T= 0.1 to 9.9 s 0.1 s
Standard
Option Parameter Setting range Customer settings
setting
RELAY OUTPUTS
External Clearing ON/OFF ON on off on off
Auto-clearing Relays ON/OFF ON on off on off
Release delay Overvolt. 0.02 to 99.98 s 0.10 s
Release delay Und.volt. 0.02 to 99.98 s 0.10 s
Release delay Asymmetry 0.02 to 99.98 s 0.10 s
Release delay Overfreq. 0.02 to 99.98 s 0.10 s
Release delay Underfrq. 0.02 to 99.98 s 0.10 s
Release delay Ph. shift 0.02 to 99.98 s 0.10 s
Release delay df/dt 0.02 to 99.98 s 0.10 s
Auto-clearing Display ON/OFF ON on off on off
Clearing display after 1 to 99 s 1s
Change relay- allocation? YES/NO YES YN YN
Funct. relay 123 (R=release) R/E RRR
Funct. relay 45 (R=release) R/E RR
Funct. relay 67 (R=release) R/E RR
Overvoltage 1 to relay 0 to 7 0002
Overvoltage 2 to relay 0 to 7 0002
Undervoltage 1 to relay 0 to 7 0002
Undervoltage 2 to relay 0 to 7 0002
Asymmetry to relay 0 to 7 0002
Overfrequency 1 to relay 0 to 7 0003
Overfrequency 2 to relay 0 to 7 0003
Underfrequency 1 to relay 0 to 7 0003
Underfrequency 2 to relay 0 to 7 0003
Phase shift to relay 0 to 7 0003
df/dt to relay 0 to 7 0003
Collect response to relay 0 to 7 0000
Command open CB to relay 0 to 7 0000
rot. field fault to relay 0 to 7 0000
INTERFACE
Serial control ON/OFF ON on off on off
Serial interface Monitoring ON/OFF ON on off on off
Inhibit via Interface ON/OFF ON on off on off
Interface fault to relay 0 to 7 0003
Device number CAN-Bus 17 to 24 17
Baudrate 125/250/500 kBaud 125 kBaud
Base-ID (send) 0 to 2,015 0800
Base-ID (remote) 0 to 2,015 0785
ID (parameterize.) 0 to 2,015 0831
PASSWORDS
Define level 1 code 0000 to 9999 0001
Define level 2 code 0000 to 9999 0002
Appendix F.
Service Options
CAUTION
To prevent damage to electronic components caused by improper handling, read and observe the pre-
cautions in Woodward manual 82715, Guide for Handling and Protection of Electronic Controls, Printed
Circuit Boards, and Modules.
Packing a Control
Use the following materials when returning a complete control:
NOTE
We highly recommend that you make arrangement in advance for return shipments. Contact a
Woodward customer service representative at +49 (711) 789 54-0 for instructions and for a Re-
turn Authorization Number.
Replacement Parts
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
When ordering replacement parts for controls, include the following information:
• The part numbers P/N (XXXX-XXX) that is on the enclosure nameplate
• The unit serial number S/N, which is also on the nameplate
Woodward GmbH
Handwerkstrasse 29
70565 Stuttgart - Germany
For assistance outside Germany, call one of the following international Woodward facilities to obtain the address
and phone number of the facility nearest your location where you will be able to get information and service.
You can also contact the Woodward Customer Service Department or consult our worldwide directory on
Woodward’s website (www.woodward.com) for the name of your nearest Woodward distributor or service fa-
cility. [For worldwide directory information, go to www.woodward.com/ic/locations.]
Engineering Services
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
Woodward Industrial Controls Engineering Services offers the following after-sales support for Woodward
products. For these services, you can contact us by telephone, by e-mail, or through the Woodward website.
• Technical support
• Product training
• Field service during commissioning
Technical Support is available through our many worldwide locations, through our authorized distributors, or
through GE Global Controls Services, depending on the product. This service can assist you with technical ques-
tions or problem solving during normal business hours. Emergency assistance is also available during non-
business hours by phoning our toll-free number and stating the urgency of your problem. For technical engineer-
ing support, please contact us via our toll-free or local phone numbers, e-mail us, or use our website and refer-
ence technical support.
Product Training is available on-site from several of our worldwide facilities, at your location, or from GE
Global Controls Services, depending on the product. This training, conducted by experienced personnel, will as-
sure that you will be able to maintain system reliability and availability. For information concerning training,
please contact us via our toll-free or local phone numbers, e-mail us, or use our website and reference customer
training.
Field Service engineering on-site support is available, depending on the product and location, from our facility
in Colorado, or from one of many worldwide Woodward offices or authorized distributors. Field engineers are
experienced on both Woodward products as well as on much of the non-Woodward equipment with which our
products interface. For field service engineering assistance, please contact us via our toll-free or local phone
numbers, e-mail us, or use our website and reference field service.
Technical Assistance
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
If you need to telephone for technical assistance, you will need to provide the following information. Please write
it down here before phoning:
Contact
Your company ___________________________________________________
_______________________________________________________________
_______________________________________________________________
_______________________________________________________________
_______________________________________________________________
_______________________________________________________________
Please be sure you have a list of all parameters available. You can print this using LeoPC1. Additionally you can
save the complete set of parameters (standard values) and send them to our Service department via e-mail.
Woodward GmbH
Handwerkstrasse 29 - 70565 Stuttgart - Germany
Phone +49 (711) 789 54-0 • Fax +49 (711) 789 54-100
[email protected]
Homepage
http://www.woodward.com/power
2008/11/Stuttgart