STULZ E2 Controller Operation Manual OZU0037M
STULZ E2 Controller Operation Manual OZU0037M
2
Operation Manual
Microprocessor Controller for STULZ Branded
Precision Air Conditioners and Air Handlers
QUICK START INSTRUCTIONS
FOR INITIAL START-UP,
SEE SECTION 3.3
Starting the A/C System
Notice
This document contains information protected by copyright. All rights are reserved. The owner of the
equipment for which this manual is written may photocopy the contents of this manual for internal
use only. No part of this document may be photocopied, reproduced, or translated into another
language for use by anyone other than the owner of the equipment for which this manual is written
without the prior written consent of STULZ Air Technology Systems, Inc. (STULZ).
This document contains confidential and proprietary information of STULZ Air Technology Systems,
Inc. Distributing or photocopying this document for external distribution is in direct violation of
United States copyright laws and is strictly prohibited without the express written consent of STULZ.
Unpublished rights reserved under the copyright laws of the United States and of other countries.
Other brands and trade names are trademarks of their respective owners.
2.3.6 Navigating Menu Screens ......................................... 6 4.3.2 Proportional/Integral (P/I) Control .....................14
2.3.7 Graphs Menu ................................................................ 6 Temperature/Humidity Control ...........................14
4.4
2.4 Controller Models ........................................................ 6
4.4.1 Dewpoint Control ..................................................... 14
2.4.1 GEN 1 Controller Layout ........................................... 6
4.5 Operating Configurations ......................................15
2.4.2 GEN 2 Controller Layout ........................................... 7
2.4.3 Expansion I/O Modules ............................................. 7 4.5.1 Cooling.........................................................................15
2.4.4 Constant Contact UPS Module ............................... 7 4.5.1.1 Chilled Water/AWS/FC ..........................................15
2.4.5 EVD Module .................................................................. 7
4.5.1.2 Compressor Based Direct Expansion (DX) .......15
3.0 Startup....................................................... 8 4.5.1.2.1 Electronic Expansion Valve .................................... 15
3.1 Navigating Controller Screens................................ 8 4.5.2 Energy Savings Configurations ........................... 15
3.1.1 Menu Selection............................................................ 8 4..5.2.1 Economizer...................................................................16
3.1.2 Menus............................................................................. 8
4.5.2.2 Alternate Water Source Cooling (AWS) .............16
3.1.3 Display Variables ......................................................... 9
4.5.2.3 Free Cooling (FC) ..................................................... 17
3.1.4 Cursor Position in Screens....................................... 9
iii
E2 Series Controller Operation Manual
vi
E2 Series Controller Operation Manual
Figures
Figure 1. Large Bezel Terminal ............................................ 5
7.1.2 Standby........................................................................54
7.1.3 Unit Rotation ..............................................................55 Figure 2. E2 Touch Screen Display Panel ........................ 5
7.1.3.1 No Rotation ................................................................55 Figure 3. GEN 1 Controller .................................................... 5
7.1.4 Out of Service ............................................................55
Figure 4. GEN 2 Controller .................................................... 5
7.2 Setting Up a Work Group ........................................55
Figure 5. Dewpoint Control ................................................... 5
7.2.1 Configure the Terminal Address ...........................55
7.2.2 Configure the I/O Board pLAN Address ............55 Figure 6. Cooling On/Off Cycle......................................... 16
7.2.3 Assign the Terminal to the Controller ..................56 Figure 7. AWS/FC/DX Operation ..................................... 16
7.2.4 Fault messages .........................................................57
Figure 8. Service Menu Selections ................................... 37
7.2.5 Displaying the Network Status and Firmware
Version .........................................................................57 Figure 9. Economizer Operation ....................................... 49
7.2.6 Configure Work Groups ..........................................57 Figure 10. Default Economizer Zone ................................. 50
7.2.6.1 Group Sensor Values ...............................................65 Figure 11. Example Economizer Zone............................... 51
7.2.6.2 Group Alarms .............................................................65 Figure 12. Configuring Multiple A/C Units ....................... 52
7.2.6.3 Lead Controller Group Sensors ............................65 Figure 13. BMS Connection Types .......................................... 66
7.2.6.4 Group Sensor Status ...............................................65
7.3 BMS Communication ...............................................66 Tables
7.3.1 Direct BMS Control ..................................................66 Table 1. BMS Interface Ports ................................................... 3
Glossary ........................................................... 73
vi
E2 Series Controller Operation Manual
1
E2 Series Controller Operation Manual
2
E2 Series Controller Operation Manual
Table 1. BMS Interface Ports display to the controller. Refer to the electrical drawing supplied
with the unit for details on the interconnecting field wiring.
BACnet IP, BACnet Steps back to the previous screen in display menu
Ethernet HTTP, SNMP Changes (increases) the value of a modifiable field
and Modbus IP
Starts/Stops operation (if Auto-On Powerup isn't
enabled)
Moves the cursor into a modifiable field Accepts
current value of a modifiable field
2.1.4 User Interface Terminals Steps to the next screen in display menu
Several user interface terminals are available with STULZ E2 Series Changes (decreases) the value of a modifiable field
controllers. The A/C unit may be equipped with a large bezel terminal
typically mounted on the door of the unit or a small bezel terminal
(termed graphic terminal) which may be door mounted or remotely 2.1.7 Alarms
mounted to a wall or control panel. See the following sections for an Alarm conditions activate a red LED indicator that backlights
overview of the user interface display panels available. the alarm function key. As an option, an alarm condition may
also be enunciated by an audible alarm signal. An alarm is
2.1.5 Graphic Terminal acknowledged by pressing the alarm key. This calls up alarm
The STULZ graphic terminal features an easy to read, backlit display screen(s) that provide a text message detailing the
liquid-crystal alphanumeric display equipped with LED alarm condition(s). After an alarm condition is corrected, the
illuminated function keys. The screens that appear on the display alarm can be cleared by pressing the alarm key.
present data that originates from the controller. The controller is
operated via 6-key menu-driven loop structure and offers an alarm 2.1.8 Contrast Adjustment
log plus four different interface menu levels to the operator: Press and hold the ( ) and (Prg) keys; then use the Up ) and
Information, Control, Service, and Factory. These menus permit the Down ) keys to adjust the contrast.
user to easily view, control and configure operating parameters for
the A/C unit .
As an option, the graphic terminal may be shipped loose for
remote mounting. It may be located directly on a wall or control
panel using the mounting kit provided. Install the terminal in a
secure area where it cannot be tampered with. A 30-foot long RJ11
telephone type cable harness is provided for interconnecting the
3
E2 Series Controller Operation Manual
2.1.10 Alarms
If the color of the Status region on the display panel changes to
red, it indicates an alarm condition has been detected. Press the
alarm symbol on display to view active alarm messages. Then
use the Up or Down arrows to scroll for any additional active
alarms.
4
E2 Series Controller Operation Manual
Press the Up and Down arrows on the screen to scroll through the
Icon Description available graph screens. The following graphs are available to view.
Alarm key Control Temperature Graph ― The first graph to appear is the
Control Temperature Graph. The current control temperature
Access Main Menu, return to
always appears at the top of the screen.
previous menu level
The date and time appearing at the bottom of the graph coincide
Step to next screen in menu loop, with the point-in-time displayed. You may use the navigating keys
increase a modifiable value described below, to scroll back and forth through time or move the
temperature scale (y-axis) up and down.
Program key
Control Temperature Graph ― The first graph to appear is the
Control Temperature Graph. The current control temperature
Step back to previous screen in always appears at the top of the screen.
menu loop, decrease a modifiable
value Control Temperature vs. Humidity Graph
In the Control Temperature vs. Humidity graph, the humidity scale
Figure 3 – Icons and Descriptions and graph line are superimposed in blue over the temperature
graph. This enables you to view both temperature and relative
2.1.12 Navigating Menu Screens humidity history for various times.
From the Main screen, press Prg to access the Main Control Temperature vs. Dewpoint Graph ― In the Control
menu. The Main menu displays icons that when Temperature vs. Dewpoint graph, the dewpoint scale and graph line
touched, take you to the menu loops indicated. The are superimposed in blue over the temperature graph. This enables
menu loops are described in detail in section 5.0 of the you to view both temperature and dewpoint history together for
E² Controller Operation Manual. various points in time.
The touch screen user interface display panel presents 1. Fan Speed Graph ― In the Fan Speed graph, the fan speed
menu screens that appear in the same sequential order. graph line is shown in white. The fan speed is defined as a
It shows the same information as described in the percentage of the fan’s full rated speed.
manual. 2. CW Valve Graph ― If your unit is configured for CW operation,
this graph appears.
2.1.13 Graphs Menu 3. In the CW Valve graph, the valve position graph line is shown.
The valve position is defined as a percentage of the valve’s
In addition to the menu loops described in the E² fully open position.
Controller Operation Manual, a graphs menu loop is 4. CW Valve vs. Fan Speed Graph― If your unit is configured for
available with the E2 touch screen display panel. Press CW operation, this graph appears. In the CW Valve vs. Fan
the GRAPH icon in the Main menu screen to enter a Speed graph, the fan speed scale and graph line are
menu loop to view the history of the following graphs superimposed over the CW Valve graph. The fan speed is
are recorded by the E2 Controller. defined as a percentage of the fan’s full rated speed.
Temperature
Humidity 2.1.14 Graph Navigating Icons
Dewpoint conditions. Navigating icons are arranged along the bottom- and right-hand
Fan operating history side of the graph screens. These icons enable you to:
Scroll the X and Y axis
Enlarge or shrink the screen view
Select a point in time to display the recorded temperature and
humidity
5
E2 Series Controller Operation Manual
Pan to latest
Zoom y-axis in
8 4 3
7 6
Reset x-axis default
(beginning of time scale)
Figure 2. GEN2 Controller
6
E2 Series Controller Operation Manual
CAUTION
When the power supply to the equipment has been shut off to
service the unit, be aware that the Constant Contact UPS
module in the electric box still contains stored electric power
up to 32 VDC. This voltage will also be present in circuits that
are electrically common to the constant contact module.
7
E2 Series Controller Operation Manual
3.0 STARTUP
When the desired menu is centered in the screen with bold
capital letters and an arrow symbol pointing towards the Enter ( )
3.1 Navigating Controller Screens key, press the Enter key to access that menu. Menu screens
3.1.1 Menu Selection located within the designated menu selection may be
The STULZ E2 Series controller provides five user selectable accessed using the Up and Down arrow keys. Access to some
menus needed to view operating data and enter setpoints for menus are protected by a built-in security protocol and
the system (see Figure 4). These menus may be accessed from a requires the use of a password to gain access.
scrolling Main menu screen by pressing the Program key.
Scroll between adjacent menu selections within the Main menu
by use of the Up and Down arrow keys.
3.1.2 Menus
From the Main screen press the Program key to select from among the five menus shown in Figure 4.
8
E2 Series Controller Operation Manual
3.1.7 Password Protected Screens Enter Password field. A requested menu is displayed any time a
valid password is entered and the Enter key is pressed.
Upon first attempting to select a secure menu in a given
3.1.9 Starting the A/C System
session, the Enter Password screen will be displayed. This
screen displays the current security level authorized in the 3.1.10 Setting the Passwords
lower field.
The initial passwords are set by the factory to 1 for the Control menu
A session is defined as from the time access is gained to a secure and to 2 for the Service menu. In the Service>Save Cfg menu, the
menu until 300 seconds (five minutes) elapses with no key activity.
operator is allowed to change the passwords. Ensure all system
Security access will be terminated at this point and the password hookups to the air conditioner(s) are the Control and Service menus.
will have to be re-entered to gain access. The menus that may
If changed, from that point on, access may only be gained to that
be password protected by the user are the Control and menu by personnel who know the new password completed and
Service menus. The Factory level menu screens are also that power is available.
password protected however the password is set at the
factory to limit access. Turn the main power disconnect switch for the A/C unit to ON. Upon
applying control power, the controller display function keys
illuminate and the controller begins con- ducting internal diagnostics
to confirm functionality. The controller monitors the alarm inputs and
alarm logic to determine if it's safe to start the unit. After about 30
seconds the Main screen is displayed. The Main Screen is a status
screen displaying the current date, time, temperature, relative humidity
and dewpoint conditions. It also indicates the current system
operating status.
It is intended that access to the Factory menu screens only be
granted while the user is working with the guidance of STULZ 1. If the controller is configured for Automatic On
Product Support (see Section 9.0) because incorrect settings operation (standard), a status message Unit On then
made at that level could unintentionally damage the appears in the display and the controller begins the startup
equipment. The level of authority is established by entering the sequence.
proper password for a given security level. The controller is Note: The A/C unit may be turned off at any time by
shipped from the factory with preset passwords for all of the pressing and holding the Enter key for 3 seconds.
security levels. 01/01/09 00:00:00
00.0°F
Operators who are allowed access to the Service menu (level
2) for example, must know the password to enter that level. If 00%rh
the entered password equals or exceeds the level requested dp 00.0°F
during a given session, the operator is allowed to access the Unit On
requested menu. For example, if the entered password allows
access to level 2 and the Control menu (level 1) is requested, Main Screen
access will be allowed. If the entered password authority level 2. If the status message OFF - Manual Restart Req
is lower than the level requested, the words WRONG appears instead of Unit On, turn the air conditioner on by
PASSWORD will appear for several seconds at the bottom of pressing the Enter ( ) key. In this case the Automatic On
the screen. feature may not be enabled in the Service>Options menu
(see Section 5.5.7.1).
3.1.8 Wrong Password
The WRONG Other status messages that may appear at the bottom of
PASSWORD message the screen are:
is displayed any time an Off by Remote Shutdown - Indicates the Remote
incorrect password is Start/Stop feature is enabled and requires a remote start
entered and the Enter switch to be turned On.
key is pressed. If the Off by Clock - Unit is off by time clock schedule.
“Wrong Password” Off by Network - Indicates the unit is part of a group
message appears, use and is off due to a grouping priority command such as a
of the Enter key will compressor alarm or loss of air flow, or,
return the operator to the the BMS communication feature is enabled and the unit
received a network signal to pause operation.
10
E2 Series Controller Operation Manual
11
E2 Series Controller Operation Manual
Change the 0 7. Press the Escape (Esc) key twice to exit the
to 1 (or to the current Control menu password if it was Control>Setpoints screens and return to the Main menu
changed in the Service menu) with the Up arrow key and screen.
then press the Enter key to accept the password. Press 8. Observe the indicator symbols in the Main screen to
the Enter key again to access the Control menu screens. determine if the unit is operating in the required mode(s).
4. From the Control menu, select Setpoints by scrolling 9. One to six hours may be required to see the desired
through the menu selections with the Up and Down arrow temperature/humidity level in the conditioned space.
keys and pressing the Enter key when SET appears in Once room conditions have been programmed or set, a
bold capital letters in the center of the screen. repeat visit to the conditioned site may be required to
ensure the air conditioner is meeting the room's
requirements.
13
E2 Series Controller Operation Manual
14
E2 Series Controller Operation Manual
Actual
Temp/RH
Setpoint
Cool Only- No
Humidificatio
n Needed
Psychrometric
15
E2 Series Controller Operation Manual
10
Minimum
Run Stop 2 Start
2
Stop 1 Start
1
CW Valve
Dehum Cut-out Cut-out Cut-in Cut-in
Min Temp
Se
are adjustable in the Factory>Cool>Energy Savings menus 4.5.4.1 Humidifying With Proportional Control
above the Cut-Out value or continues to rise. The Valve Start, Start If this option is selected, proportional control of humidification
DX delay and CW Valve End. may be provided as an option for even more precise control of
These may be set to AWS/FC Primary, DX Primary and the relative humidity. With this option the controller transmits
DX only in the Factory>Cool>Energy Savings menus. There an analog output signal to the humidifier that is proportional to
are three ways the AWS and DX circuits interact the demand for humidification.
17
E2 Series Controller Operation Manual
18
E2 Series Controller Operation Manual
20
E2 Series Controller Operation Manual
21
E2 Series Controller Operation Manual
The Main menu is accessed from the Main screen by pressing the Prg key. The Main menu screen provides a listing of the menus
that are available. Scroll through the menu categories using the Up and Down arrow keys. From the Main menu screen select from
among the following standard menus:
Info- Displays basic read-only status information. Allows the monitoring of system operational parameters. No password is
needed at this level.
Alarm Log- Displays all alarms and power-ups in sequential order with a time and date stamp. No password is needed at this
level.
Control- Allows modification of basic control parameters such as setpoints and clock. Level 1 password is needed to enter this
menu.
Service- Allows modification of advanced control parameters such as offsets, blower speed, BMS set-up and permits the user to
save customer parameters and reset the controller to the customer or factory default values. Level 2 password is needed to enter this
menu.
Factory- Allows modification of more advanced control parameters such as sensor scaling, start-up delays, grouping parameters
and night setback schedules. Level 3 password is needed to enter this menu. Entry to the Factory menu is intended for qualified
technicians working under the guidance of STULZ Product Support during start-up and commissioning of the A/C system. The
password to enter this menu may be obtained by contacting Product Support. (See section 9.0 of this manual).
22
E2 Series Controller Operation Manual
Shadow unit alarm messages appear in the controller display of the main unit when
an alarm occurs to a unit in the shadow group assigned to the main unit. The top
line of the first menu screen is the display number assigned to the shadow group.
The next line is the unit number of the first shadow unit in the shadow group. The
remaining messages shown are alarm conditions which appear only if the particular
ALARM ON UNIT 10 alarm has occurred on the first shadow unit.
SMOKE SHUTDOWN The top line is the unit number of the second shadow unit in the shadow group. The
AIR DX Heat Hu remaining messages shown are alarm conditions which appear only if the particular
Flow T/H Sensor
alarm has occurred on the second shadow unit.
5.2.3 Return Sensor
Return Sensor
00.0°F This screen displays Temperature and Relative Humidity as measured by the
00%rh return temperature and RH sensor inputs. The return dewpoint is calculated by the
return dewpoint controller based on the return sensor inputs and shown at the bottom of the
display screen.
5.2.4 Compressor Status- (DX based systems)
This screen displays the On or Off status icon for the A/C system compressor(s)
and shows the status of the Low Pressure and High Pressures witches (Open or
Closed). The field beneath the status icon indicates if the compressor is in the
“minimum time on” or “minimum time off” delay period. The field at the bottom of
the screen shows the number of compressor starts since power was applied and
the total compressor run-time during the period since the last reset was
performed in the Service>Run Hours menu. If the system has more than one
compressor, similar compressor status display screens are provided for each
compressor.
The controller will also display the current discharge pressure value (Disch). A value
in the field (High Press) indicates how many times the controller has attempted to
restart the compressor after a high pressure shutdown.
23
E2 Series Controller Operation Manual
24
E2 Series Controller Operation Manual
Underfloor Static
5.2.10 Under Floor Pressure
195miwg If the unit is equipped with an under floor pressure sensor, the function of the
sensor is displayed on the first line. This configurable to be Underfloor Static Pr,
Setpoint 200 Underfloor Diff Pr, Cold Aisle Static Pr, or Cold Aisle Diff Pr. The next line shows
Fan out(PID) 67.6
the measured value displayed in milli-inches water gauge (1 miwg = 0.001
iwg). The under floor pressure setpoint and the commanded fan speed are
displayed as well.
Pressure Sensor
(Monitor Only) 5.2.11 Differential Air Pressure Sensor
640miwg If the unit is equipped with a differential air pressure sensor, the difference between
the entering and leaving air pressure is displayed in milli-inches water gauge (1
miwg = 0.001 iwg).
Dewpoint Sensor
5.2.12 Dewpoint Sensor
34.2°F If the unit is equipped with a dewpoint sensor, it is used in place of the dewpoint
calculated from the return air temperature and humidity sensors. The value of the
dewpoint sensor is displayed.
23
E2 Series Controller Operation Manual
ATMOSPHERIC PRESSURE
5.2.19 Atmospheric Pressure
16.7 IWG If the special sensors are enabled and Airflow Rate (No GPM) is selected in
Source:
From Elevation Factory>Options>Enb Special Sensors, this screen appears displaying the source
00000Ft selected in Factory>Options>BAROMETRIC PRESSURE (From Elevation, Manual,
Barometer, or Network) which is shown on the next to last line. The value of the
source is displayed on the second line and the unit of measure is either mbar or iwg.
If the source is elevation, the bottom line shows the altitude.
24
E2 Series Controller Operation Manual
25
E2 Series Controller Operation Manual
Network
Underfloor Static Pr
43.6 miwg
All units off
SP Sensor Value Lead
Unit 1 of 3 Lead:2
Group
All Units Off
Avg 43.6 miwg
Min 40.4 miwg
Max 45.5 miwg
Min Static Unit 2
Max Static Unit 7
26
E2 Series Controller Operation Manual
27
E2 Series Controller Operation Manual
28
E2 Series Controller Operation Manual
29
E2 Series Controller Operation Manual
Ebmpapst Fan#_- Motor Superheating The indicated overheat alarm has been received from the fan.
Ebmpapst Fan#_- Intern. Circ.
Superheat The indicated overheat alarm has been received from the fan.
Ebmpapst Fan#_- Output Stage
Superheat The indicated overheat alarm has been received from the fan.
Ebmpapst Fan#_- Hall Sensor Error The indicated alarm has been received from the fan.
30
E2 Series Controller Operation Manual
Ebmpapst Fan#_- Communication Error The indicated alarm has been received from the fan.
Ebmpapst Fan#_- Generic Error The indicated alarm has been received from the fan.
Ebmpapst Fan#_- Out Stage High Temp. The indicated warning has been received from the fan.
Ebmpapst Fan#_- Intern. Circ. High Temp. The indicated warning has been received from the fan.
Ebmpapst Fan#_- Motor High Temperature The indicated warning has been received from the fan.
Ebmpapst Fan#_- DC Link Voltage Low The indicated warning has been received from the fan.
Ebmpapst Fan#_- Limited Mains Power The indicated warning has been received from the fan.
Ebmpapst Fan#_- Limited Mains Current The indicated warning has been received from the fan.
Ebmpapst Fan#_- Brake mode The indicated warning has been received from the fan.
31
E2 Series Controller Operation Manual
The Alarm Setpoints (ALARM SET) screens allow the operator to enable
and adjust the high and low temperature and humidity alarm setpoints and
offsets and compare them to the control setpoints and to the system level
operating data derived from the Sensor/Transmitter inputs. See Section
5.4.2.
The Clock screens allow the operator to view and adjust the current time,
date and day and set-up operating schedule(s) and setpoints for the A/C
system. See Section 5.4.3
Two Version screens are provided for information only. They show controller
hardware and software details that are useful to STULZ Product Support if
technical assistance is needed.
32
E2 Series Controller Operation Manual
The Setpoints (SET) screens below may be accessed from the If the customer sensor(s) are set for Calculate GPM in
Control menu. Factory>Options>Enb Special Sensors, then the GPM menus
for CW circuit 1 and 2 (if appropriate) are enabled. The maximum
Temperature GPM is used to limit the CW valve opening. The current GPM is
the calculated GPM. Del T1 Flow ON is the number of degrees
Set Point 72.0°F
below the leaving water temperature that the entering water
STATUS temperature must be to enable GPM calculations. Del T1 Flow
Temp: 72.6°F Set:72.0°F OFF is the number of degrees below the leaving water
Dew: 50.1°F temperature that the entering water temperature must be to
disable GPM calculations. The bottom field in the screen (Valve)
is the current position of the valve as a percentage of fully
open.
5.4.2 Alarm Setpoint Screens
Humidity
Set Point 45.0%
STATUS
Hum: 45.5°F Set:45%
Dew: 50.1°F
The Temperature and Humidity setpoint screens allow the The Alarm Setpoints screens are accessed from the Control menu.
operator view and adjust the control setpoints and compare They allow the operator to enable the High and Low temperature
them to system level operating data derived from the various and humidity alarms, adjust their setpoints and compare them to the
Sensor/Transmitter inputs. control operating setpoints and to the system level operating data
derived from the Sensor/ Transmitter inputs.
5.4.1.1 High Pressure Auto Reset (Optional)
Temperature Alarm
Low alarm Enable:Yes
Set Point 60.0°F
STATUS
Temp: 72.6°F Set:72.0°F
Dew: 50.1°F
33
E2 Series Controller Operation Manual
34
E2 Series Controller Operation Manual
Humidity Alarm
Humidity Alarm Offset: 5.0%
Low alarm Enable:Yes
Set Point 30.0%
STATUS
STATUS
Temp: 72.6°F Set:72.0°F
EWT1 Temp: 54.0°F Dew: 50.1°F
EWT2 Temp: 59.0°F
Following the temperature and humidity alarm enable screens If the offset for the water temperature alarm is set at 5 °F
are the alarm offset screens. From these screens the operator (default), the high water temperature alarm will cancel when the
may adjust offsets for the high and low alarm setpoints at actual temperature drops to the High Water Temperature Alarm
which the alarm will be cancelled. The entered offset applies setpoint (60.0 °F) - the Offset (5.0 °F), or, 60.0 °F - 5.0 °F =
to both the upper and lower values entered in the Alarm 55.0 °F. The high water temperature Alarm will cancel at 55
Setpoints Screens. The offset is subtracted when its applied °F.
to the high alarm setpoint and it is added when its applied to
the low alarm setpoint.
Temperature Alarm
EXAMPLE 1: Temperature Alarm Offset: 5.0°F
Offset
STATUS
If the offset for the temperature alarm is set at 5.0 °F (default), Temp: 72.6°F Set:72.0°F
Dew: 50.1°F
the high temperature alarm will cancel when the actual
temperature drops to the High Temperature Alarm setpoint
(80.0 °F) - the Offset (5.0 °F) or, 80.0 °F - 5.0 °F = 75.0 °F
35
E2 Series Controller Operation Manual
5.5.1 Cool
5.5 Service Menu The Service>Cool menu screens differ depending upon
whether the A/C unit is configured for DX operation and/or
CW/WG/AWS operation.
SERVICE
Blowers
The Service menu screens allow the user to enter cut-in and
COOL
cut-outvalues, calibrate the system control sensor(s), save Heat
and restore parameters and view the event log. The Service
menu may be entered and programmed by the user via the
password menu (requires level 2 password). Once password 5.5.1.1 DX Cooling Screens
access is granted, the user may access the service menu If the A/C unit has compressor(s), the cut-in/ cut-out
screens. offsets for each compressor stage may be adjusted from
It allows the operator to adjust the number of days for the Service>Cool menu. The offset values are added to the
switching the lead cooling circuit duty and select an hour of temperature setpoint and establish the temperatures for the
the day for this to occur. The current lead circuit may also
be changed at the display compressor to turn on (Cut-in) and off (Cut-out). This screen
Figure 8. Service Menu Selections displays the current air temperature and setpoint
temperature. The On/Off status of the compressor (Stage 1)
is shown along with the offset multiplier (M). The offset
Press Enter ( ) multipliers may be set in the Service>Options>T/H Scaling
Key
menu screen
Redundant Setup
Alarms
Number of Days 0
BMS COMM SENSORS
Group Blower
Hour of Day 0
Current Lead 1
RUN HOURS BLOWER
BMS Comm
37
E2 Series Controller Operation Manual
CW, AWS, FC
Cooling Band: 3.0°F Heat Stage 1
Min deltaT1: 2.0°F
CW Cut In/Out: Offset Multiplier Cut In Offset: -2.0°F
STATUS--------------- Cut Out Offset: -0.3°F
Temp:73.7°F Set:72.0°F See Sect. 5.5.7.3
Valve:0.0% M: 1.0 STATUS---------------
Temp:73.7°F Set:72.0°F
Ht1:Off M: 1.0
If the A/C unit is configured for CW, AWS or FC operation, the
cooling band may be adjusted in the Service>Cool menu. The The cut-in/cut-out offsets for each heating stage (up to three
Cooling Band establishes the number of degrees above stages) may be adjusted from the Service>Heat menu.
setpoint (+ the CW Cut In/Out value described below) for
the valve to reach the fully open position. 5.5.3 Humidity
The Min deltaT1 is the minimum temperature rise expected The cut-in/cut-out offsets for the Humidify, Dehumidify and
between the entering and leaving water temperature. A flow Reheat modes may be adjusted from the Service>Humid menu.
alarm is activated if the temperature difference falls below NOTE: The Humidifier screen only appears if the A/C unit is
this value while the unit is actively cooling. The CW Cut In/ equipped with a humidifier at the factory.
Out value is the offset added to the temperature setpoint and
SERVICE
establishes the temperatures for the control valve to open (Cut-
in) and close (Cut-out) as well as the P/I dead band. Heat
38
E2 Series Controller Operation Manual
The fan runs at the low speed setting whenever there isn't call
for heating, cooling, dehumidification or humidification. The
fan speed increases directly to the run speed during heating or
ramps up to that speed during cooling or humidification based
on the air temperature (see next Section 5.5.6.2). The fan
A log of events is stored for view from the Service>Alarms speed during dehumidification can be controlled in conjunction
menu. This menu displays the last 50 events sequentially with the CW valve opening to limit the potential for over-cooling
numbered in order of occurrence. The alarm log is cleared by (see CW Valve Dehum screen in Section 5.5.3).
pressing the Alarm key while in this menu.
The lower field (Water Alarm Action) maybe used to set the
If the Alarm ) key is pressed when in any of the action of the blower(s) in response to a CWorWG flow alarm
Service>Alarms screens, all stored alarm messages will be condition. The selections are None, Off, Min(speed)or Max(speed).
permanently erased from the controller's memory.
5.5.6.2 CW Fan Set-up
5.5.5 Sensors
When calibrating sensors, an offset at one
extreme may produce an error at the other
extreme. Always verify that any offset is valid over
the entire range of the sensor.
5.5.6 Blower
From the Service>Sensors menu, multiple display screens may This screen is provided for CW based units. The max CW
be accessed to enter offsets for calibrating the unit's various temperature is the offset above the temperature setpoint
sensors.
39
E2 Series Controller Operation Manual
at which the CW valve is fully open, or 100%. The max fan and then checking the static pressure result in the
temperature is the offset at which the fan speed reaches the Service>Blower>Underfloor Static Pr screen. When the
Run Speed value (typically 100%). At the default values of 3 adjusted Low speed value produces the desired static pressure,
degrees each, the CW valve position will be 50% open at 1.5 write down both the Low Speedvalue
degrees above setpoint and the fan speed will be 85%, as in
Re-enter the Service menu and scroll to the
halfway between 70% and 100%.
Service>Blower>Underfloor
The CW to Fan ratio is to be used as a method of tuning in the
Static Pr screen. Enter the Underfloor Static Pr
interaction of the fan and CW valve after the temperature offsets
Static setpointvalue Static setpoint: 360
are determined. A positive ratio value between 0% and 25%
that appeared in the Start fan speed: 60.0%
increases the CW valve position by that amount while decreasing
Static sensor field Static sensor: 0
the fan speed by the same amount. A negative value decreases Fan out: 00.0%
and enter the Start fan
the CW valve position while increasing the fan speed.
speed value that
For the setting of above 50% CW valve and 85% fan speed, a was the final Low Speed value.
10% ratio will increase the CW valve to 55% and decrease the The A/C unit will now operate using proportional control to
fan speed to 76.5%. A -10% ratio will decrease the CW valve to maintain the static pressure at the setpoint entered.
45% while increasing the fan to 93.5%. The regular limits on the
CW valve and fan still apply. If the unit is in the dehumidification If the speed values are adjusted in the Service>Blower Setup
mode, the fan speed will be limited to the Dehum Fan Speed screen (Section 5.5.6.1), it will have no effect on the operating
parameter. fan speeds as they are now controlled by static pressure.
5.5.6.3 Static Pressure Set-up 5.5.6.4 Modbus Fan Control and Data
Monitoring
On units equipped for static pressure control, static pressure
should be set-up and enabled when commissioning the A/C Fan kW Limiting
unit. The operating static pressure can only be set correctly Limit Fan kW: No
after the A/C unit is installed and operable in its intended Fan Totl Limit: 0.0kW
Prop:200 Int: 10
location. Err db: 4 Action:Rev
Fan Total: 0.0kW
Fan Avg: 0.0kW
To set the static pressure, turn on the A/C unit and allow the PID Output: 0.0%
blower(s) to reach full speed. Then, call up the Service menu.
Enter the Service level password and scroll to the This screen appears if the controller is configured for Modbus
Blower>Underfloor Static Prg screen. This screen is only fan control with a Field bus expansion card. It allows
available when the controller is configured by the factory to adjustments to fan kW limiting parameters. Limits total kW of
all fans (sum). P/I control parameters may also be adjusted.
Fan Data - Watts #1
Make note of the #6 0
#1 0
current miwg static #2 0 #7 0
#3 0 #8 0
pressure value #4 0 #9 0
shown in the display #5 0 #10 00
Power Add:
Total Power: 0.0kW
40
E2 Series Controller Operation Manual
Startup delay - Time delay before blower(s) begin valve position ever exceeds the percentage entered since the
operating after pushing the Enter key or after turning the unit last flush cycle, the scheduled flush cycle will be skipped and a
on with a remote on command. new interval will begin. If the valve does not reach the minimum
open position entered, aflush cycle will occur when the interval
Airflow delay - Time delay for allowing the blowers to reach
since the last flush cycle expires. The interval between flushes
adequate speed before the air proving sensor actively monitors
may be varied from 1 hour to 720 hours (30 days). The
an airflow alarm condition.
duration of the flush cycle may be varied from 30 to 300
Shutdown delay - Time delay before unit stops operating seconds. The number of flushes displayed at the bottom of
after pressing the Enter key for three seconds or after turning it the screen is the total number of flush cycles since the A/C
off with a "remote off" command. unit was initialized.
Recovery time - Time period after startup that temperature 5.5.7.5 Barometric Pressure
and humidity alarms are masked from signaling nuisance high
Barometric Pressure
or low temperature and humidity alarms.
Select Method:
5.5.7.3 T/H Offset Scaling Elevation
T/H Offset Multiplier 0
Temperature Scale 2.0
The barometric pressure set-up menu is enabled when the
Humidity Scale 1.0
special sensors are selected to be “Airflow rate (no GPM)” or
Scales effect all the “Calculate GPM” in the Factory>Options>Enb Special Sensors
cut-in, cut-out values menu. Select Elevation (default), Manual, Local Sensor, or
The Service>Options>T/H Offset Multiplier screen allows Network. The elevation defaults to sea level (0). Manual selects a
the operator to enter a multiplier to apply to scale both the fixed barometric pressure in millibars. Local Sensor selects an
temperature and humidity cut-in/cut-out offsets. The multipliers analog input to provide the barometric pressure in millibars.
are factored to the system offset values set in the Service menu Network selects a BMS supplied value for the barometric
(Sections 5.5.1, 5.5.2 and 5.5.3). pressure in millibars.
programmed to manage the dual power auto transfer The identifiers A and B may be replaced with Pre and Alt as an
sequence. The ability to select primary power sources option when the controller is configured at the factory. In such
and manually switch them is available with this screen. case, power source A is termed Pre (Preferred); power source B is
termed Alt (Alternate).
5.5.7.7 Custom Alarm Setup
From the Service>Options>Custom Setup screen, press the Enter key to access
a menu to set-up the custom alarms and sensors. Any controller alarm or signal
failure will activate the summary alarm output. Upon receiving an alarm indication,
the user may press the alarm key and call up alarm screen messages. The E²
controller may also monitor a customer supplied alarm input device. One set of
Customer Alarm input terminals is standard and up to two more may be added as
an option.
The operator can select any mix of the 80 alarm variables as shown in the tables that follow. As an example, for a custom alarm
based only on the occurrence of water detection, condensate pan, pump, failure of the return temperature and humidity sensors
the operator would enter the following bitmask values for the applicable alarm numbers and enter 0 for the rest:
Custom Alarm number 1 - 8: Water detection (No. 7) = 64
Custom Alarm number 9 - 16: Condensate pan (No. 9) + Pump (No. 14) = 33 (1+32)
Custom Alarm number 41- 48: Return temperature (No. 41) + Return humidity (No. 42) = 3 (1+2)
The custom alarms are set up by entering the bitmask totals developed from the following tables.
43
E2 Series Controller Operation Manual
Alarms 1 to 8 Alarms 9 to 16
The default values (shown in bold italics) are factory set to generate a custom alarm output on any of the major alarms and
any sensor failure. Only the enabled sensors can generate an alarm. To enable an additional custom alarm, add the alarm
bitmask number to the factory default total and enter the new total for the applicable alarm numbers in the Custom Alarm Setup
screen. If an alarm condition appearing in the following tables is detected, it needs to be reset at the unit's display terminal or
via the BMS.
Alarms 17 to 24 Alarms 25 to 32
44
E2 Series Controller Operation Manual
Bit Bit
No. Description Default No. Description Default
mask mask
33 Loss of power 1 1 41 Return temperature 1 1
34 Fan alarm 4 2 2 42 Return humidity 2 2
35 Damper Feedback 4 0 43 Remote temperature 4 4
36 Pre Filter 8 0 44 Remote humidity 8 8
37 Pre HP C1 16 0 45 EWT1 temperature 16 16
38 Pre HP C2 32 0 46 LWT1 temperature 32 32
39 Reserved 64 0 47 EWT2 temperature 64 64
40 Reserved 128 0 48 LWT2 temperature 128 128
Factory Default Bitmask Total 3 Factory Default Bitmask Total 255
Alarms 49 to 56- (Sensor Failure Alarms) Alarms 57 to 64- (Sensor Failure Alarms)
45
E2 Series Controller Operation Manual
Description Bit
No. Default
mask
73 System off 1 0 If the Enter key is pressed, it allows the operator to enter a
74 BMS Keep alive off 2 0 sub-menu to perform a functionality test of the economizer
75 Reserved 4 0 mode and experiment with different settings of temperature
and dewpoint. Pressing the Down arrow key advances the
76 Reserved 8 0
display to the Options>Economizer Option screen which
77 Reserved 16 0
allows the Economizer mode to be enabled. See Section 6.0
78 Reserved 32 0 for a detailed description of Economizer operation and see
79 Reserved 64 0 Section 6.3 for information on setting the operating
80 Reserved 128 0 parameters available in these screens.
Digital In
Run Hours
Digital Inputs
46
E2 Series Controller Operation Manual
BMS Comm
Assist>Group Shadow>Group Menu
47
E2 Series Controller Operation Manual
The first Service>Save Cfg menu screen allows the operator The second Service>Save Cfg menu screen allows new
to save any adjustments made in Service level menu screens passwords to be set for entering the Control and Service
as the new "Customer" parameters or, restore the controller to menus.
the previously saved "Customer" parameters. The user may 5.5.13 Factory Menu
also restore the controller to original factory default parameter
values shown in Table 2.
Set Passwords
Control:
Service:
Temperature Setpoint 72 °F
Cool Stage 1 Cut-in 74 °F
Cool Stage 1 Cut-out 72.3 °F
Cool Stage 2 Cut-in 75 °F
Cool Stage 2 Cut-out 73 °F
Heat Stage 1 Cut-in 70 °F
Heat Stage 1 Cut-out 71.7 °F
Heat Stage 2 Cut-in 69 °F
Heat Stage 2 Cut-out 71 °F
Heat Stage 3 Cut-in 68 °F
Heat Stage 3 Cut-out 70 °F
Humidity Setpoint 45% RH
Humidify Cut-in 40% RH
Humidify Cut-out 43% RH
Dehumidify Cut-in 50% RH
Dehumidify Cut-out 47% RH
48
E2 Series Controller Operation Manual
49
E2 Series Controller Operation Manual
50
E2 Series Controller Operation Manual
Figure 8 depicts the expanded dewpoint where the lower The controller monitors the outdoor air and ceiling return air
dewpoint offsets of C and D have been replaced by C and conditions and adjusts the damper setting to get the mixed air
1
D1. conditions as close as possible to the desired temperature
setpoint. If the outdoor air conditions are outside of the user
adjustable setpoints, the damper remains closed at 0%.
In the simple case where both the outdoor air and ceiling
return air temperatures are above the temperature setpoint
and outdoor conditions are within the economizer operating
2.8 2.8 B 1 envelope, the colder of the two temperatures is selected which
then drives the damper to 0% (full ceiling return air) or 100%
(full outdoor air). Temperatures on either side of the setpoint
cause the damper to open to a "New Damper" position such as
C1 -3.3 20% as shown in the above screen.
-5.0 D1
51
E2 Series Controller Operation Manual
Economizer
Expand dewpoint? Yes
Econ High Temp: 80.0°F
Dehumidify DP: 52.3
Econ High +DP: 3.0
Econ High -DP: -3.0
Economizer
52
E2 Series Controller Operation Manual
53
E2 Series Controller Operation Manual
The Main screen of each unit in the work group indicates that
unit's duty assignment in the bottom field. If the controller is the
7.1.2 Standby
group Lead, it is indicated in the bottom field also. If the lead controller in the work group loses a signal
acknowledgement from an active A/C unit in the group,
that A/C unit is deemed as failed or taken out of service.
01/01/09 00:00:00
The failed unit will be replaced with the first available
00.0°F
00%rh standby unit from the work group. The standby unit is
dp 00.0°F
Unit On cycled on and designated as the new active unit in place of
ACTIVE Lead the failed unit.
Multiple Unit Display Screen
7.1.3 Unit Rotation
One controller may be designated as the work group lead and
In this mode, the Lead controller will rotate duty between
networked with the controllers from a series of up to 7
additional A/C units. If configured for multi-unit operation, the the grouped A/C units to promote equal run time and will
work group lead controller display panel allows access to the rotate the role of group lead. When set-up for unit rotation,
same data and group control sensor choices that are available the A/C units will rotate duty in order of their group
from networked system controller display panels. addresses. Active, Capacity Assist and Standby units are
all in the rotation cycle so even a standby unit will be cycled
The controller for each A/C unit in a group may be manually
called up from the Main display of the Lead unit via the PLAN into active duty on a scheduled basis. The rotation time
network. From the Main display, simultaneously press the Up period is typically 1-week; however it may be set by the
and Down arrow keys. This allows the Main display to access user via the Factory menu. Call STULZ Product Support
the controller in the adjacent A/C units in the group. From the for assistance when accessing the Factory menu.
Main screen, press the Up arrow key to view the Software
Version/Date display screen to verify the accessed shadow 7.1.4 No Rotation
unit's PLAN address appearing in the upper left corner of the A/C units in the group may have their duty assignments
screen. locked so they do not join the rotation cycle (capacity assist
and standby no-rotation units cannot take the lead). In this
From there, scroll through the menu screens as described in
Section 3.4. Each time the Up and Down arrow keys are case the message No_Rot appears after the duty
simultaneously pressed it sequences the display to the next assignment displayed in the main screen.
grouped unit's controller. Again, access this screen to verify the
PLAN address of the unit that has been interfaced with. 01/01/09 00:00:00
00.0°F
7.1.1 Capacity Assist 00%rh
dp 00.0°F
The Capacity Assist option can be used to maximize efficiency Unit On
ACTIVE_No_Rot
for conservation of energy and to more precisely control
capacity at low demand. This feature enables Active A/C units An Active_No_Rot unit is always On. It will never be
to handle the demand up to a certain temperature/humidity capacity assist or standby. An Active_No_Rot unit may
setpoint and then enables additional units to begin operating take the role as lead controller when the rotation puts it as
gas needed. If the Active A/C units are running and unable to
the first active unit. Units designated as "Out of Service" do
satisfy the demand, Capacity Assist A/C unit(s) may be
not rotate nor can the controller take the role of lead.
programmed to turn on to assist the Active units.
Each Capacity Assist unit may set to control operation based 7.1.5 Out of Service
on its local temperature/humidity sensor values or control A unit may be removed from the group entirely by placing it
operation based on network sensor values transmitted from Out of Service. In this mode, the unit will not operate. A unit
the Lead controller. Multiple capacity assist units are typically may be placed in this mode as a safety measure to prevent
set with each unit in the group assigned incrementally it from unexpectedly starting when performing
increasing/ decreasing offsets for cooling, heating, maintenance or repairs.
humidifying and dehumidifying so they will turn on one at a
time only if the unit(s) currently operating are unable to satisfy
the demand. They should incrementally turn off as each unit
reaches its cut-out setpoint, while active A/C unit(s) continue
to maintain room conditions at the desired level.
54
E2 Series Controller Operation Manual
Assign the terminal and controller I/O board addresses for each controller to be grouped. Review Sections 7.2.1 to 7.2.3 first,
before turning power on and the assigning addresses. Do not interconnect the controllers together before assigning their terminal
and I/O board pLAN addresses.
The first step is to change the terminal address of each controller to 0 referring to Section 7.2.1. Set the terminal address to 0
before assigning the controller (I/O board) address.
Note: If the terminal remains inactive (no key is pressed) for more than 30 seconds, the group set-up procedure is exited
automatically, without saving any changes. Configure the Terminal Address.
1. To change the address of the terminal (Display address setting), press the Enter key
once. The cursor will move to the address field (nn). Display address
setting..........: nn
2. Using the Up, Down keys, select 0 and confirm by pressing Enter .
I/O Board address: xx
The Display Address Changed screen will appear indicating the display address selected
is not the same as the one saved and the new value will be saved to memory.
3. Once the terminal address is set to zero, cycle the power to the unit Off and then back On. Address Configuration
If the Display address setting field is set to 0, the terminal will communicate with the
Display address
controller using point-to-point protocol (not pLAN). The display field I/O Board address changed
will disappear as it has no meaning until the controller I/O board pLAN address is set.
Simultaneously for 10 to 15 seconds. First a display message self-test. Please wait will appear then the pLAN Address Configuration
screen shown below will appear. Don’t press the ) key, the cursor is already in the modifiable field.
Press the key to set the pLAN address (#1 – 8) for the controller (I/O Board). The pLAN PLAN ADDRESS: 1
address #1 is already assigned by default to the first (Lead) controller in the group. Address UP: INCREASE
2 is to be assigned to the first controller added to the group (address #3 is to be assigned to DOWN: DECREASE
the second controller added and so on). Then press the key to confirm the selection. A ENTER: SAVE & EXIT
message NO LINK will appear.
Controller Address Configuration
55
E2 Series Controller Operation Manual
Next, press the Up , Down and Enter keys simultaneously. Reconfigure the terminal address following the steps in Section again.
This time set the terminal address to match the corresponding controller I/O board address. If the controller is assigned address 2,
then the corresponding terminal address should be set to 31 as shown in the table on the preceding page. If the next controller
is assigned address 3, the corresponding terminal should be set to 30.
After setting the correct terminal address, press the key once to confirm the selection. A message NO LINK will appear. At this
point, the terminal has been set with the correct address for the controller and the controller has been set for the terminal, but now
they need to be assigned to each other.
7.2.3 Assign the Terminal to the Controller
1. Access the Terminal Address Configuration screen again using the Up , Down and Enter keys.
2. Press the key until the cursor moves to the field I/O board address.
3. Using the keys, enter the address (1 – 8) for the controller I/O board. P:02 Adr Priv/Shared
Trm1 31 Pr
4. Press the key twice to display the Terminal Configuration screen. Trm2 None --
Trm3 None -- Ok?No
5. Here too, the key moves the cursor from one field to the next, and the Up and Down keys
change the value of the current field. The field P:0_ depicts the pLAN address (1 – 8)
assigned to
the I/O board. In the example shown, the controller has been assigned address 2. Terminal Configuration
6. Press the key to move to the field Trm1 xx. The field represents the address of the
56
E2 Series Controller Operation Manual
terminal associated with the controller. Using the keys enter the address (25 – 32) of the terminal assigned to the
controller (I/O board). In the example shown, address 31 has been entered for the first A/C unit added to the
group.
7. The Priv/Shared column indicates the type of terminal. The workgroup is setup using private terminals.
8. Do not change the value (Pr). Press the key to move to the last field
9. Select the field Ok? No, choose Yes using the Up and Down keys and confirm by pressing to save
the data and exit the group set-up procedure.
10. Referring to the wiring diagram provided with the A/C units, interconnect the units together with the pLAN
cable(s) provided.
7.2.4 Fault messages
If the terminal detects the status of the I/O board it is associated with is off-line, the display shows the message:
I/O Board xx fault. If this appears, check the Signal LEDs on the controller (see Figure 3) for an error signal.
See Section 8.4 for guidelines on analyzing the signal LED’s.
On the other hand, if the terminal receives no signal from the network, the display shows the following message:
NO LINK. If this appears, check the pLAN cables and ensure they are connected properly. Also, check the addressing
(refer to Section 7.2).
7.2.5 Displaying the Network Status and Firmware Version
Once each A/C unit is configured with its new controller and terminal pLAN address, the entire network set up may be examined.
Press the group set up keys together as done to access the Address Configuration screen but continue holding after the Address
Configuration screen appears for at least 5 seconds until the Network Status (NetSTAT) screen appears.
The Network Status screen, shown below, provides overview of the pLAN group indicating which and how many devices are
connected and the corresponding pLAN addresses.
57
E2 Series Controller Operation Manual
pGD1 V1.7
Feb 28 2006
HW:A
Firmware Version
Press the Enter ( ) key twice and a screen will appear to enter the password for the Service level.
Once the Service level password is accepted, press Enter to call up the menu screens. From here,
press the Up ( ) ) or Down arrow keys to scroll through the Service menu selections.
When the word GROUP appears in the center of the screen, press the Enter key to access the
Service>Group menu screens. From here, use the Up ( ) or Down ( ) arrow keys to scroll through
the Service>Group menu selections.
Service>Group>Group Config (Screen 1) See table below.
NOTE: Standby units are added to the number appearing in the Total in Network field although
Unit ACTIVE no field id provided in this screen indicating the number of stand by units that are part of the
Total in Network group. To determine the number of standby units, subtract Min Number Active + Min Number
Min Number Assist from Total in Network. In the example shown there is one standby unit.
Active Min
Number Assist
58
E2 Series Controller Operation Manual
From the Group Rotation screen, program the controller to rotate operation of the A/C units in the group to promote equal run
times. Three methods are available for the rotation: Multi-week basis, multi day basis and multi hour basis.
Group Rotation Group Rotation Group Rotation
Force Rotation No Force Rotation No Force Rotation No
Number of Weeks 1 Number of Weeks Number of Weeks
Day of Week Monday Number of Days Number of Days Service>Group>
Hour of the Day 18 Hour of the Day Rotate every 72 Hrs Group Rotation
Cur lead 1 Cur lead 1 Cur lead 1 (Screen 2)
Next lead 0 Next lead 0 Next lead 0
1) On a multi- week basis 2) On a multi-day basis 3) On a multi-hour basis
59
E2 Series Controller Operation Manual
1) The multi week basis is selected by setting the number of weeks to a value from 1-99. This will be the number of weeks
between rotations. The next line will show “Day of Week” which may be set to Monday through Sunday. The Hour of the Day is
the hour of the day at which rotation occurs. A setting of 1/Mon/18 will rotate every week on Monday at 6 PM (18:00 hours).
2) The multi day basis is selected by setting the number of weeks to zero and the number of days to one or more. Now the
number of days becomes an elapsed number of days between rotations. The Hour of Day is the hour of the day at which
rotation occurs. A setting of 0/5/6 will rotate every 5 days at 6:00AM.
3) The multi hour basis is selected by setting the number of weeks to zero and the number of days to zero. The rotation will
occur after the number of hours has elapsed. A setting of 0/0/72 would rotate every 72 hours
4) The first two are based on the internal calendar and will survive power losses of the lead unit. If the lead unit is
powered off, the other units will assume temporary roles until the lead unit is powered back up. Upon the lead unit
powering back up, the correct role of each unit is recalculated based on the current calendar date. The hourly
basis is not based on the internal calendar and restarts at zero hours elapsed if the lead unit is powered off and
then back on.
Capacity Assist
Assist Time 300s
Cooling Cut in 1.0°F
Cut out 0.0°F Service>Group>Capacity Assist (Screen 3)
Heating Cut in -1.0°F
Cut out 0.0°F
Each A/C unit in the group may be assigned local cut-in and cut-out setpoints for its capacity assist operation. The values
entered are offsets which are applied to the control setpoints established at the lead controller. Each unit in the group
should be assigned incrementally increasing/decreasing offsets for cooling, heating, humidifying and dehumidifying so
they will turn on one at a time only if the unit(s) currently operating are unable to satisfy the demand.
60
E2 Series Controller Operation Manual
61
E2 Series Controller Operation Manual
Alarm will appear in the Main screen of the unit that detected the group alarm and switched off.
See Section 5.5.7.7 for an overview of how to select alarms using bitmask values. The Group Alarms bitmask values are shown in
the following tables. The settings may be viewed at the Info level (see Section 5.2.22). If an alarm condition appearing in the
following tables is detected, it needs to be reset at the unit's display terminal or via the BMS for the unit to return to “Active” and
resume operation.
Group Alarms 1 to 8 Group Alarms 9 to 16
Bit Default Bit
No. Description No. Description Default
mask mask
1 Heater over temperature 1 0 9 Circuit 1 low pressure 1 0
2 Humidifier 2 0 10 Circuit 1 high pressure 2 0
3 Pump 4 0 11 Circuit 2 low pressure 4 0
4 Flow alarm CW1 8 0 12 Circuit 2 high pressure 8 0
5 Flow alarm CW2 16 0 13 CW1 Valve Error 16 0
6 Customer alarm 1 32 0 14 CW2 Valve Error 32 0
7 Customer alarm 2 64 0 15 Damper End Switch 64 0
8 Customer alarm 3 128 0 16 Reserved 128 0
62
E2 Series Controller Operation Manual
63
E2 Series Controller Operation Manual
5 6 7 8 9 0 1 2
On
Group Status Indicates if multiple A/C unit grouping is enabled. On
Off
64
E2 Series Controller Operation Manual
65
E2 Series Controller Operation Manual
BMS
BMS
Unit
The Service>BMS Comm menu is used to set-up the
Unit 1 parameters to allow a BMS (BAS) interface for monitoring
Unit controller operation for the serial-based networks such as
BACnet MS/TP. Units using the BACnet over IP, BACnet over
Ethernet, or HTTP protocols do not need to change anything
Unit 2
Unit
in this menu.
BMS Communications
Unit 3 Address: 1
Baud Rate: 19200
Figure 13. BMS Connection Types
Protocol: BACnet
If multiple A/C units are grouped together, each controller BMS keep alive: 1
added to the group must be configured with a CPU address
for BMS communication. In the daisy chain configuration The BMS address and baud rate have meaning only on RS-
an RS-485 twisted-pair connection is made from the BMS 485 networks and with the serial protocols of Modem,
to the first controller and an RS-485 connection from each Modbus RTU, Commission, and Carel. The baud rate is fixed
controller to the next; the connections form a common bus for BACnet. Systems using a 10BaseT interface should use
and each E2 controller listens on the bus and has a unique the defaults of address 1, baud rate 19200, and protocol
address. The direct connection example is via TCP/IP over lBACnet.
Ethernet. Certain Integer and Digital variables that start with BMS (see
Section 10.0) require that the BMS "keep alive" parameter
For complete details on using BMS control, contact changes between 1 and 2 within a 10-minute span. The
STULZ Product Support (see Section 9.0) and refer to general procedure is to set up variables like the BMS low fan
STULZ Controller Communications Manual, OCU0147. speed and then write a 1 to the BMS keep alive address.
66
E2 Series Controller Operation Manual
WARNING
Turn off all power to the unit before conducting any
troubleshooting procedures, unless the procedure specifically
requires the system to operate. Keep hands, clothing and tools
clear of the electrical terminals.
67
E2 Series Controller Operation Manual
68
E2 Series Controller Operation Manual
70
E2 Series Controller Operation Manual
71
E2 Series Controller Operation Manual
Term Definition
AHU AWS Air Handling Unit with Alternate Water Source option
AR AWS Remote (split) Air cooled system with Alternate Water Source option
Dual Remote (split) Air cooled system with Alternate Water Source
DAR AWS
option
DAR OA Dual Remote (split) Air cooled system with Outside Air option
DW/DG FC Dual Water or Dual Glycol cooled system with Free-cooling option
DW/DG OA Dual Water or Dual Glycol cooled system with Outside Air option
W/G AWS Water or Glycol cooled system with Alternate Water Source option
72
E2 Series Controller Operation Manual
Glossary
www.stulz-usa.com
OZU0037M 2018 © STULZ Air Technology Systems, Inc. - Specifications subject to change without notice.