Applications of Line and Load Reactors With Variable Frequency Drives PDF
Applications of Line and Load Reactors With Variable Frequency Drives PDF
Reactors can protect motors, variable frequency drives (VFDs) and other sensitive electrical equipment and
increase their reliability and life span by absorbing the disturbances from the power line, preventing
overvoltage trips, improving total power factor, and reducing nuisance tripping. Reactors can also help
reduce the harmonics distortion of the power line by adding impedance to the utility grid.
AC to DC DC Bus Filter DC to AC
Inverter Capacitor Inverter
Figure 1: VFD and Motor System with Line and Load Reactors
1
2. Where harmonic distortion is a concern. parameters. The typical overvoltage magnitude is
Refer to IEEE-519 [1] Harmonic Control in between 1.2-1.6 p.u. with a ringing frequency of
Power Systems. 400-600 Hz. During the transient overvoltage
3. Where the supply line power capacity is event, the DC bus capacitor in the VFD attempts
much higher (10 times greater kVA rating) charging to the peak of the incoming transient
than the connected VFD system. line voltage, resulting in the VFD tripping off-
line – showing an overvoltage fault code or in
No line reactor
some cases even damaging the input diode front-
With 3% line reactor
end.
With 5% line reactor
200
175
154
150 138 137 141
115
90 95
100
67 73
57
50 41
24
13 6
0 RMS Current Total Power Input (kVA) 5th Harmonic 7th Harmonic 11th 13th THD (%)
(A) Factor (A) (A) Harmonic (A) Harmonic (A)
(kW/kVA, %)
2
current waveshape in each half cycle. Each pulse supply voltage causes high current on one of the
is related to the charging of the DC bus capacitor phases on the line side of the VFD. For VFDs that
to the peak incoming voltage. The result is a non- are connected close to a transformer allowing a
sinusoidal current flow with a total harmonic high available short-circuit current, the peak
distortion (THD) of typically 90-150% with a current may reach 200% to 250% of the rated line
harmonic content that is predominantly 5th, 7th, current, causing strip of the line-side overload
11th, and 13th harmonics as shown in Figure 3. protector (fuse, circuit breaker, etc.) during the
The application of a line reactor causes the sag. Application of line reactors reduces the
discontinuous current to become continuous. The available fault current at the drive terminals and
main reason is that with line reactors, the voltage minimizes the chance of overload protector
at the VFD terminals becomes flat-topped, and operation during un-symmetrical voltage sags.
the charging time for the DC bus capacitor
III. Benefits of Load Reactors
increases, thereby increasing the current pulse
width while decreasing its peak amplitude. The Load reactors (also called an output reactors) are
use of 5% impedance line reactors can eliminate installed after the VFD to protect the motor. They
about 65% of the current THD, which will help to can increase load inductance and reduce the effect
comply with the IEEE 519 Standard and reduce of reflected waves. If a load reactor is used at the
motor operating temperature and noise. output, it should be located as close to the VFD
as possible.
Improving VFD Power Factor and Reducing
Line Losses Reducing the Effect of Reflected Wave
VFDs typically have a poor power factor (0.6- Load reactors are used to protect the motor when
0.65). However, this does not mean that VFDs long wires between the VFD and motor are
have a high reactive power demand. VFDs do not required. The VFD generates a high frequency
have any reactive power demand as the reactive (such as 16 kHz) PWM output by turning on and
power is supplied from the DC bus capacitor. The off the switching components like MOSFETs and
high kVA demand from VFDs, which related to IGBTs. The output voltage rise time is short, and
poor factor is due to the harmonic content in the usually less than a few microseconds. These short
current waveshape. Reducing the harmonics rise times combined with long wires between the
either by a reactor or by an appropriate harmonic drive and motor can produce voltage reflections,
filter leads to an improvement of the power also called reflected waves [3], that have high
factor. As explained in the previous section, use peak voltages as shown in Figure 4. The resulting
of line reactors reduces the harmonic currents, voltage can exceed the motor’s peak voltage
which causes a reduction of total rms current and rating where insulation breakdown occurs.
the kVA demand of the drive. Since the line Generally, a load reactor should be used if the
reactor does not change the fundamental motor wiring extends over 100 ft., but this value
component of the current, the kW input required can vary depending on the motor. If a motor
remains the same, dictated by load requirements. meets the NEMA MG-1 Part 31 standard [4], it is
This means that the ratio of kW/kVA defined as possible to have as much as 300 ft of cabling
“power factor” will be improved. without a load reactor. If it does not meet the
standard, the maximum cable length should be
Minimizing Line-Side Overload Protector
100 ft. For any motor, if the distance is between
Trips During Unsymmetrical Voltage Sags
300 to 500 ft., a load reactor should be used. If
A large majority of faults in utility power systems the distance is over 500 ft. then a special type of
are single line-to-ground faults. During such filter called a dV/dt filter (low-pass filter) should
faults, the voltage at the drive terminals is highly be used.
unbalanced. This momentary unbalance in the
3
IV. Reactors Percent Impedance: 3% or
5%