CES522 A 04 - Topic 2b - 2. RC Beam Design - Examples234 PDF
CES522 A 04 - Topic 2b - 2. RC Beam Design - Examples234 PDF
3500
Design specification:
7000
3500
Building exposure class XC3 2400
structural class S4
fire resistance 2 hrs
5000
fyk = 500 N/mm2; fck = 25 N/mm2 2800 2800 2800
6000
• brick wall = 2.6 kN/m2 (for 120 mm thick)
Variable actions, qk: refer to Table 6.1 & 6.2 of
BS EN 1991-1-1: 2002
Floor height, H = 3000 mm Full height brickwall sitting on beams:
A/5-8; 5/A-B; 8/A-B; C/5a-7a and BM5
Most of the beam loadings are transferred from the supported slabs.
It is important to obtain all permanent action and variable action acting on the slabs.
For these examples, we assumed all the slabs have been analysed and designed.
To start the beam design process, we are going to estimate thicknesses for the slabs supported by
the beams in this examples here:
Slab S5 and S5A: continuous one-way (one end span and one interior span)
end span: use 30 → l/h = 30 → h = 110 mm
interior span: use 35 → l/h = 35 → h = 100 mm
Cover:
Durability – XC3; S4 → cmin = 25 mm
Bonding – separated (assumed bar diameter 16 mm – 25 mm) → cmin = 20 mm (assumed mostly H20)
Fire (2 hrs) – bmin = 200 & a = 45 (Table 5.6 EC2 Pt1-2)
→ cmin,fire = 45 – 10 – 20/2 = 25 mm (assume link = 10 mm)
➔ Cmin to be used = 25 mm
➔ Cnom = 25 + 10 = 35 mm (cdev = 10 mm)
Loading on beam:
• SW of beam
gk = 0.2 x 0.5 x 25 = 2.5 kN/m
• Slab S5 and S5A on one side of beam (both are one-way slabs: ly/lx > 2.0):
gk = 5.325 x 3.5/2 = 9.32 kN/m
qk = 2.5 x 3.5/2 = 4.375 kN/m
• Brick wall with 3 m height
gk = 2.6 x 3 = 7.8 kN/m
The coefficients from Table 3.5 (BS8110) can be applied to this continuous beam analysis if all the
provisions stated are fulfilled:
1. qk ≤ gk : 4.375 < 19.62 (OK)
2.Loads should be uniformly distributed over 3 or more spans: 3 spans (OK)
3.Variation in span length should not exceed 15% of the longest: 7.2 > 0.85(8.4) (OK)
→ Table 3.5 from BS8110 can be used in the analysis.
Design load acting on beam BM2, w = 1.35gk + 1.5qk = 1.35(19.62) + 1.5(4.375) = 33.04 kN/m
BMD & SFD
w = 33.04 kN/m
F1 = 237.89 kN F2 = 277.54 kN F3 = 237.89 kN
166.52kN 142.73kN
107.05kN
B D
256.45kNm 256.45kNm
A C E
0.26𝑓𝑐𝑡𝑚 𝑏𝑑 0.26(2.6)(200)(445)
𝐴𝑠,𝑚𝑖𝑛 = 𝑚𝑎𝑥 ; 0.0013𝑏𝑑 = ; 0.0013(200)(445) = 120 mm2
𝑓𝑦𝑘 500
𝐴𝑠,𝑚𝑎𝑥 = 0.04𝐴𝑐 = 0.04 200 500 = 4000 mm2
ℎ𝑓 125
𝑀𝑓 = 0.567𝑓𝑐𝑘 𝑏ℎ𝑓 𝑑 − = 0.567 25 1140 125 445 − = 772 kNm
2 2
Compare Mf with the design moment, MEd: MEd =154.15 kNm < Mf = 772 kNm
→ compressive stress block lies in flange →Design the beam like a rectangular section.
𝑀𝐸𝑑 154.15×106
𝐾= = = 0.027 < 𝐾𝑏𝑎𝑙 → compression reinforcement not required
𝑏𝑑2 𝑓𝑐𝑘 1140×4452 ×25
𝐾 0.025
𝑧 = 𝑑 0.5 + 0.25 − 1.134 = 0.5 + 0.25 − 1.134 𝑑 = 0.97𝑑 > 0.95d → use = 0.95d
𝑀 154.15×106 2 > A
𝐴𝑠,𝑟𝑒𝑞 = 0.87𝑓𝐸𝑑 𝑧
= 0.87×500×0.95×445
= 838 𝑚𝑚 s,min → use 838 mm2
𝑦𝑘
Proposed: 3H20 (As,prov = 942 mm2) < As,max (can install in one single layer? → chk c.b.s!)
Assume max aggregate size 20 mm → c.b.sallow = max{20(1); 20+5; 20} = 25 mm c.b.sactual = 27 mm (OK?)
What is the result if you design it as a rectangular section (200 x 500)?
B. Location 2: At first interior support (can only design as a rectangular section)
𝑀𝐸𝑑 256.45×106
𝐾= = = 0.26 < 𝐾𝑏𝑎𝑙 → compression reinforcement required
𝑏𝑑2 𝑓𝑐𝑘 200×4452 ×25
𝐾′
𝑧𝑏𝑎𝑙 = 𝑑 0.5 + 0.25 − 1.134 = 0.82𝑑 d’ = 35 + 10 + 20/2 = 55 mm
′ 𝐾−𝐾′ 𝑓𝑐𝑘 𝑏𝑑2 (0.26−0.167)(25)(200)(445)2
𝐴 𝑠,𝑟𝑒𝑞 = = = 543 𝑚𝑚2 → Propose 3H16 (603 mm2)
0.87𝑓𝑦𝑘 𝑑−𝑑′ 0.87(500)(445−55)
𝐾′ 𝑓𝑐𝑘 𝑏𝑑2 ′ 0.167(25)(200)(445)2
𝐴𝑠,𝑟𝑒𝑞 = + 𝐴 𝑠,𝑟𝑒𝑞 = + 543 = 1584 𝑚𝑚2 > As,min (120) → use 1584 mm2
0.87𝑓𝑦𝑘 𝑧 0.87(500)(0.82×445)
Proposed: 2H25 + 2H20 (As,prov = 1610 mm2) < As,max (can install in one single layer? → chk c.b.s!)
Assume max aggregate size 20 mm → c.b.sallow = max{25(1); 20+5; 20} = 25 mm > c.b.sactual (x OK)
→ Provide 2H25 + 2H20 (1610) – 2 layers
C. Location 3: At middle of interior spans (can be designed as flanged or rectangular section)
End span: lo = 0.7 (8400) = 5880 mm
Calculate the effective width of flange, bf
beff = beff,i + bw b; beff,i = 0.2 bi + 0.1 l0 0.2 l0
b1 = 3500 - 200)/2 = 1650 mm
beff,1 = 0.2(1650) + 0.1(5880) = 918 mm 0.2(5880) = 1176 mm (→ use 918)
𝐾 0.03
𝑧 = 𝑑 0.5 + 0.25 − 1.134 = 0.5 + 0.25 − 1.134 𝑑 = 0.97𝑑 > 0.95d → use = 0.95d
𝑀𝐸𝑑 163.19×106
𝐴𝑠,𝑟𝑒𝑞 = = = 887 𝑚𝑚2 > As,min → use 887 mm2
0.87𝑓𝑦𝑘 𝑧 0.87×500×0.95×445
Proposed: 3H20 (As,prov = 942 mm2) < As,max (can install in one single layer? → chk c.b.s!)
Assume max aggregate size 20 mm → c.b.sallow = max{20(1); 20+5; 20} = 25 mm c.b.sactual = 27 mm (OK?)
What is the result if you design it as a rectangular section (200 x 500)?
Design the shear reinforcement (common practice: to carry out design for 3 locations for each span –
approximately one-third of the span)
(Asw/s)min = 0.08bw/fyk x fck1/2 = 0.16 (provide H8 – 200) for locations where VEd < VRdc
Continue shear design for other critical locations: Span 1 – location 3; internal span – location 2, 3 →
student homework.
Check beam’s capacity against deflection.
Check only at mid section (sagging moment) of each span. Support not required!
Location 1: middle of end span
= As,req/bwd = 838/(200x445) = 0.0094 > 0 = (25)1/2x10-3 = 5.0x10-3 → use eq. 7.16b:
From table 7.4N, K = 1.3 (end span of continuous beam)
𝑙 𝜌 1 𝜌′
𝑑𝑏𝑎𝑠𝑖𝑐
0
= 𝐾 11 + 1.5 𝑓𝑐𝑘 𝜌−𝜌 ′ + 12 𝑓𝑐𝑘 𝜌0
= 19.49
modification factor - reinforcement:
310/s = (500/500) x (942/838) = 1.12 < 1.5
modification factor - section shape:
the section was designed as a flanged section. bf/bw = 1140/200 = 5.7 > 3
What is the result if you
→ need to multiply 0.8
design it as a rectangular
modification factor - span length: section (200 x 500)?
span length = 7.2 m > 7 m → length MF = 7/7.2 = 0.97
(l/d)allowable = 19.49 x 1.12 x 0.8 x 0.97 = 16.93 > (l/d)actual = 7200/445 = 16.18 (OK)
Location 2: middle of interior span
= As,req/bwd = 887/(200x445) = 0.01 > 0 = (25)1/2x10-3 = 5.0x10-3 → use eq. 7.16b:
From table 7.4N, K = 1.5 (end span of continuous beam)
𝑙 𝜌0 1 𝜌′
𝑑𝑏𝑎𝑠𝑖𝑐
= 𝐾 11 + 1.5 𝑓𝑐𝑘 𝜌−𝜌 ′ + 12
𝑓𝑐𝑘 𝜌0
= 22.12
modification factor - reinforcement:
310/s = (500/500) x (942/887) = 1.06 < 1.5
modification factor - section shape:
the section was designed as a flanged section. bf/bw = 1100/200 = 5.5 > 3
→ need to multiply 0.8 What is the result if you
design it as a rectangular
modification factor - span length: section (200 x 500)?
span length = 8.4 m > 7 m → length MF = 7/8.4 = 0.83
(l/d)allowable = 22.12 x 1.06 x 0.8 x 0.83 = 15.57 < (l/d)actual = 8400/445 = 18.88 ( not OK)
Propose two layers of reinf’t 3H20 + 2H12 (1168) – 2H12 to be curtailed at supports
310/s = (500/500) x (1168/887) = 1.32 < 1.5
(l/d)allowable = 22.12 x 1.32x 0.8 x 0.83 = 19.38 < (l/d)actual = 8400/445 = 18.88 (OK)
Check the beam for cracking.
Check at all tension zones.
Location 1: mid span of end span (left) s for location 1 (3H20) = 45 mm
Location 2: interior supports s for location 2 (2H25+2H20) = 85
Location 3: mid span of end span (right) s for location 3 (3H20+2H12) = 45 mm
fs = fyk/1.15 x (Gk + 0.3Qk)/(1.35Gk + 1.5Qk)
= 500/1.15 x (19.62 + 0.3x4.375)/(1.35x19.62 + 1.5x4.375)
= 275 MPa
Taking wk = 0.3 mm → maximum allowable bar spacing 150 mm > s for all locations → Passed
Detailing
3H16
Example 3: Design of beam BM3
Beam BM3: continuous 3 spans (7.2 m , 8.4 m, 7.2 m)
Use uniform beam height, h for all spans, variable loading heavier than BM2 → h should be larger.
Try l/h = 14 (end span); l/h = 18 (interior span) → h = 7200/14 = 514; h = 8400/18 = 466
→ Propose h = 600 mm; b = 200
➔ Beam size = 200 x 600
Loading on beam:
• SW of beam
gk = 0.2 x 0.6 x 25 = 3.0 kN/m
• Slab S5 and S5A on one side of beam (both are one-way slabs: ly/lx > 2.0):
gk = 5.325 x 3.5/2 x 2 = 18.6375 kN/m
qk = 2.5 x 3.5/2 x 2 = 8.75 kN/m
• Brick wall → none
The coefficients from Table 3.5 (BS8110) can be applied to this continuous beam analysis if all the
provisions stated are fulfilled:
1. qk ≤ gk : 8.75 < 21.6375 (OK)
2.Loads should be uniformly distributed over 3 or more spans: 3 spans (OK)
3.Variation in span length should not exceed 15% of the longest: 7.2 > 0.85(8.4) (OK)
→ Table 3.5 from BS8110 can be used in the analysis.
Design load acting on beam BM2, w = 1.35gk + 1.5qk = 1.35(21.6375) + 1.5(8.75) = 42.33 kN/m
BMD & SFD
w = 42.33 kN/m
F1 = 304.77 kN F2 = 355.57 kN F3 = 304.77 kN
B D
328.54kNm 328.54kNm
A C E
beff = beff,1 + beff,2 + bw = (942 + 942) + 200 = 2084 mm < b = 1650 + 1650 + 200 = 3500
(→ use 2080)
Design the main reinforcement
0.26𝑓𝑐𝑡𝑚 𝑏𝑑 0.26(2.6)(200)(545)
𝐴𝑠,𝑚𝑖𝑛 = 𝑚𝑎𝑥 ; 0.0013𝑏𝑑 = ; 0.0013(200)(545) = 147 mm2
𝑓𝑦𝑘 500
𝐴𝑠,𝑚𝑎𝑥 = 0.04𝐴𝑐 = 0.04 200 600 = 4800 mm2
ℎ𝑓 125
𝑀𝑓 = 0.567𝑓𝑐𝑘 𝑏ℎ𝑓 𝑑 − = 0.567 25 2080 125 545 − = 1409 kNm
2 2
Compare Mf with the design moment, MEd: MEd =197.49 kNm < Mf = 1778 kNm
→ compressive stress block lies in flange →Design the beam like a rectangular section.
𝑀𝐸𝑑 197.49×106
𝐾= = = 0.0128 < 𝐾𝑏𝑎𝑙 → compression reinforcement not required
𝑏𝑑2 𝑓𝑐𝑘 2080×5452 ×25
𝐾 0.011
𝑧 = 𝑑 0.5 + 0.25 − 1.134 = 0.5 + 0.25 − 1.134 𝑑 = 0.99𝑑 > 0.95d → use = 0.95d
𝑀 197.49×106 2 > A
𝐴𝑠,𝑟𝑒𝑞 = 0.87𝑓𝐸𝑑 𝑧
= 0.87×500×0.95×545
= 876 𝑚𝑚 s,min → use 876 mm2
𝑦𝑘
Proposed: 3H20 (As,prov = 942 mm2) < As,max (can install in one single layer? → chk c.b.s!)
Assume max aggregate size 20 mm → c.b.sallow = max{20(1); 20+5; 20} = 25 mm c.b.sactual = 27 mm (OK?)
What is the result if you design it as a rectangular section (200 x 600)?
B. Location 2: At first interior support (can only design as a rectangular section)
𝑀𝐸𝑑 328.54×106
𝐾= = = 0.22 < 𝐾𝑏𝑎𝑙 → compression reinforcement not required
𝑏𝑑2 𝑓𝑐𝑘 200×5452 ×25
𝐾′
𝑧𝑏𝑎𝑙 = 𝑑 0.5 + 0.25 − 1.134 = 0.82𝑑 d’ = 35 + 10 + 20/2 = 55 mm
′ 𝐾−𝐾′ 𝑓𝑐𝑘 𝑏𝑑2 (0.22−0.167)(25)(200)(545)2
𝐴 𝑠,𝑟𝑒𝑞 = = = 369 𝑚𝑚2 > As,min → Propose 2H16 (402 mm2)
0.87𝑓𝑦𝑘 𝑑−𝑑′ 0.87(500)(545−55)
𝐾′ 𝑓𝑐𝑘 𝑏𝑑2 ′ 0.167(25)(200)(545)2
𝐴𝑠,𝑟𝑒𝑞 = + 𝐴 𝑠,𝑟𝑒𝑞 = + 369 = 1644 𝑚𝑚2 > As,min (147) → use 1644 mm2
0.87𝑓𝑦𝑘 𝑧 0.87(500)(0.82×545)
Proposed: 4H25 (As,prov = 1963 mm2) < As,max (can install in one single layer? → chk c.b.s!)
Assume max aggregate size 20 mm → c.b.sallow = max{25(1); 20+5; 20} = 25 mm > c.b.sactual (x OK)
→ Provide 2H25 + 2H25 (1963) – 2 layers
C. Location 3: At middle of interior spans (can be designed as flanged or rectangular section)
End span: lo = 0.7 (8400) = 5880 mm
Calculate the effective width of flange, bf
beff = beff,i + bw b; beff,i = 0.2 bi + 0.1 l0 0.2 l0
b1 = b2 = (3500 - 200)/2 = 1650 mm
beff,1 = beff,2 = 0.2(1650) + 0.1(5880) = 918 mm 0.2(5880) = 1176 mm (→ use 918)
beff = beff,1 + beff,2 + bw = (918 + 918) + 200 = 2036 mm < b = 1650 + 1650 + 200 = 3500
(→ use 2000)
𝐾 0.012
𝑧 = 𝑑 0.5 + 0.25 − 1.134 = 0.5 + 0.25 − 1.134 𝑑 = 0.98𝑑 > 0.95d → use = 0.95d
𝑀𝐸𝑑 209.07×106
𝐴𝑠,𝑟𝑒𝑞 = = = 928 > As,min → use 928 mm2
0.87𝑓𝑦𝑘 𝑧 0.87×500×0.95×545
Proposed: 3H20 (As,prov = 942 mm2) < As,max (can install in one single layer? → chk c.b.s!)
Assume max aggregate size 20 mm → c.b.sallow = max{20(1); 20+5; 20} = 25 mm c.b.sactual = 27 mm (OK?)
What is the result if you design it as a rectangular section (200 x 500)?
Design the shear reinforcement (common practice: to carry out design for 3 locations for each span –
approximately one-third of the span)
(Asw/s)min = 0.08bw/fyk x fck1/2 = 0.16 (provide H8 – 200) for locations where VEd < VRdc
Continue shear design for other critical locations: Span 1 – location 3; internal span – location 2, 3 →
student homework.
Check beam’s capacity against deflection.
Check only at mid section (sagging moment) of each span.
Location 1: middle of end span
= As,req/bwd = 876/(200x545) = 0.008 > 0 = (25)1/2x10-3 = 5.0x10-3 → use eq. 7.16b:
From table 7.4N, K = 1.3 (end span of continuous beam)
𝑙 𝜌 1 𝜌′
𝑑𝑏𝑎𝑠𝑖𝑐
0
= 𝐾 11 + 1.5 𝑓𝑐𝑘 𝜌−𝜌 ′ + 12 𝑓𝑐𝑘 𝜌0
= 20.39
modification factor - reinforcement:
310/s = (500/500) x (942/876) = 1.08 < 1.5
modification factor - section shape:
the section was designed as a flanged section. bf/bw = 2080/200 = 10.4 > 3
What is the result if you
→ need to multiply 0.8
design it as a rectangular
modification factor - span length: section (200 x 600)?
span length = 7.2 m > 7 m → length MF = 7/7.2 = 0.97
(l/d)allowable = 20.39 x 1.08 x 0.8 x 0.97 = 17.09 > (l/d)actual = 7200/545 = 13.21 (OK)
Location 2: middle of interior span
= As,req/bwd = 928/(200x545) = 0.0085 > 0 = (25)1/2x10-3 = 5.0x10-3 → use eq. 7.16b:
From table 7.4N, K = 1.5 (end span of continuous beam)
𝑙 𝜌0 1 𝜌′
𝑑𝑏𝑎𝑠𝑖𝑐
= 𝐾 11 + 1.5 𝑓𝑐𝑘 𝜌−𝜌 ′ + 12
𝑓𝑐𝑘 𝜌0
= 23.11
modification factor - reinforcement:
310/s = (500/500) x (942/928) = 1.02 < 1.5
modification factor - section shape:
the section was designed as a flanged section. bf/bw = 2000/200 = 10 > 3
→ need to multiply 0.8 What is the result if you
design it as a rectangular
modification factor - span length: section (200 x 600)?
span length = 8.4 m > 7 m → length MF = 7/8.4 = 0.83
(l/d)allowable = 23.11 x 1.02 x 0.8 x 0.83 = 15.65 < (l/d)actual = 8400/545 = 15.41 (OK)
Check the beam for cracking.
Check at all tension zones.
Location 1: mid span of end span (left) s for location 1 (3H20) = 45 mm
Location 2: interior supports s for location 2 (2H25+2H25) = 85
Location 3: mid span of end span (right) s for location 3 (3H20) = 45 mm
fs = fyk/1.15 x (Gk + 0.3Qk)/(1.35Gk + 1.5Qk)
= 500/1.15 x (21.6375 + 0.3x8.75)/(1.35x21.6375 + 1.5x8.75)
= 249 MPa
Taking wk = 0.3 mm → maximum allowable bar spacing 190 mm > s for all locations → Passed
Detailing
25
16
Example 4: Design of beam 5/B-A (200 x 750)
P = 137.16 kN
• Beam 5/B-A is supporting secondary beam BM3 B
Gk = 70.1 kN
A
where loading from BM3 are transferred as point Qk = 28.35 kN
loads to this beam.
• No loading of slab is being directly transferred to gk = 11.55 kN/m w = 15.59 kN/m
this beam.
• UDL on this beam are beam self weight + brick wall 7m
123.145 kN
Characteristic loadings:
SW of beam = 0.2 x 0.75 x 25 = 3.75 kN/m 68.58 kN
B/W = 2.6 x 3 = 7.8 kN/m (3m height)
gk = 3.75 + 78 = 11.55 kN/m qk = 0
68.58 kN
Design loading:
w = 11.55 x 1.35 = 15.59 kN/m
P = 1.35(70.1) + 1.5(28.35) = 137.16kN 335.52 kNm
Assume link diameter = 10 mm and bar diameter = 20 mm.
d = 750 – 35 – 10 – 20/2 = 695 mm
Zone 2:
VEd,2 = 77.93 kN
Proposed reinforcements 2H25+2H20 → Asl = 1610 mm2
k = 1 + (200/695)1/2 = 1.54 2.0; l = Asl/bwd = 1610/(200x695) = 0.011 < 0.02
VRd,c 2 = max{77.53; 46.48} = 77.53 kN < VEd,2 (77.93) → shear reinforcement is required
Try = 22: VRd,max(22) = 391.05 kN > VEd,1 → (concrete strut is safe - use = 22)
(Asw/s)req = 0.12 mm2/mm → Propose H8-200 (Asw/s = 0.5 mm2/mm)
smax = min{0.75d = 521.25 mm; min dimension = 200 mm} ≥ proposed s = 200 mm (OK)
Detailing