1. The document lists equipment including water pumps, exhaust fans, fire water pumps, and lighting loads with details like equipment ID, absorbed power, rated power, load factor, efficiency, nature of load as continuous, intermittent, or standby. 2. It calculates the maximum normal running load, peak load, maximum normal running load with 10% growth factor, and peak load with 10% growth factor. 3. It recommends a generator size of 117.6 KW when loading is at 70% based on the calculations.

Uploaded by

Surya Liem
Copyright
© © All Rights Reserved
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
43 views

Load Flow Spreadsheet

1. The document lists equipment including water pumps, exhaust fans, fire water pumps, and lighting loads with details like equipment ID, absorbed power, rated power, load factor, efficiency, nature of load as continuous, intermittent, or standby. 2. It calculates the maximum normal running load, peak load, maximum normal running load with 10% growth factor, and peak load with 10% growth factor. 3. It recommends a generator size of 117.6 KW when loading is at 70% based on the calculations.

Uploaded by

Surya Liem
Copyright
© © All Rights Reserved
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 1

LOAD LISTING, CALCULATIONS & GENERATOR SIZING

Sr. Equipment Name Equip ID No Absorbed Rated Load Eff cosØ MCC Nature of Continous Intermittent Standby Remarks
Power Power Factor Load*
KW KVAR KW KVAR KW KVAR
1 Pump Water WP 1 11 15 0.7 0.85 0.75 Maiin C 12.94 11.41 List
2 Pump Water WP2 11 15 0.7 0.85 0.75 Main C 12.94 11.41 C
3 Pump Water WP3 11 15 0.7 0.85 0.75 Main S 12.94 11.41 I
4 Exhaust Fan FN1 3 4 0.7 0.85 0.75 Main I 3.53 3.11 S
5 Exhaust Fan FN2 3 4 0.7 0.85 0.75 Main S 3.53 3.11 150+KW
6 Fire Water Pump FP1 18 22 0.75 0.89 0.8 Emer I 20.22 15.17
7 Fire Water Pump FP2 18 22 0.75 0.89 0.8 Emer S 20.22 15.17 ###
8 Lighting Load 15 20 0.75 0.89 0.8 Emer C 16.85 12.64 ###
###

Sum 42.74 35.47 23.75 18.28 36.70 29.69

Maximum Load = 100% of continous load + 50% of Intermittent load + 10% of standby or biggest individual load (higher one)

KW KVAR KVA cosØ Amp Volts


Maximum of normal running load 55 45 71 0.7745 102 400
Peak load 75 60 96 0.7814 138 400

Maximum of normal running load with 10% Growth Factor 60.075 49.068 77.567 0.7745 112 400
Peak load with 10% Growth Factor 82.322 65.753 105.36 0.7814 152 400

Reccemended Generator Size when 70% loading 117.6 93.933 150.51 0.7814 217 400