Load Flow Spreadsheet
Load Flow Spreadsheet
Sr. Equipment Name Equip ID No Absorbed Rated Load Eff cosØ MCC Nature of Continous Intermittent Standby Remarks
Power Power Factor Load*
KW KVAR KW KVAR KW KVAR
1 Pump Water WP 1 11 15 0.7 0.85 0.75 Maiin C 12.94 11.41 List
2 Pump Water WP2 11 15 0.7 0.85 0.75 Main C 12.94 11.41 C
3 Pump Water WP3 11 15 0.7 0.85 0.75 Main S 12.94 11.41 I
4 Exhaust Fan FN1 3 4 0.7 0.85 0.75 Main I 3.53 3.11 S
5 Exhaust Fan FN2 3 4 0.7 0.85 0.75 Main S 3.53 3.11 150+KW
6 Fire Water Pump FP1 18 22 0.75 0.89 0.8 Emer I 20.22 15.17
7 Fire Water Pump FP2 18 22 0.75 0.89 0.8 Emer S 20.22 15.17 ###
8 Lighting Load 15 20 0.75 0.89 0.8 Emer C 16.85 12.64 ###
###
Maximum Load = 100% of continous load + 50% of Intermittent load + 10% of standby or biggest individual load (higher one)
Maximum of normal running load with 10% Growth Factor 60.075 49.068 77.567 0.7745 112 400
Peak load with 10% Growth Factor 82.322 65.753 105.36 0.7814 152 400
Reccemended Generator Size when 70% loading 117.6 93.933 150.51 0.7814 217 400