6 Sizing Example #3
6 Sizing Example #3
4-DOOR APARTMENT
Type of Service – 230 Volts;
2-wire Line to Ground Current System
Floor Area per unit = 80 square meter
Refer to tables.
for a 12.52 amperes load, a 2𝑚𝑚2 or No.
14 TW copper wire having ampacity of
15amperes >12.52 amperes. But the
National Code limits the size of
convenience outlet wire to a minimum of
3.5 𝑚𝑚2 or No. 12 AWG copper wire. The
code must prevail.
Therefore use No. 12 AWG wire rather
than the No. 14 as computed.
5. Size of the Conduit Pipe