Micro-ohmmeter
MJÖLNER 600
Micro-ohmmeter
DESCRIPTION APPLICATIONS
The MJÖLNER™600 is designed to measure the resistance of circuit MJÖLNER 600 test system is designed to serve a number of applica-
breaker contacts, bus-bar joints, contact elements in bus-bars and tions. The most common are contact resistance measurements of
other high-current links. The product has been designed with safety, low-, medium- and high-voltage breakers and also at bus-bar joints,
ease of use and versatility in mind. and other high current links.
The micro-ohmmeter conducts true DC ripple free current and can The contact resistance measurements concerning breaker testing are
be used anywhere to measure a low resistance value with high particularly called for in the following standards:
accuracy. With MJÖLNER 600 it is possible to make measurements IEEE C37.09-1999 and IEC 62271-1 (2011).
according to the DualGround™ method. This means that the test
If the contact resistance is too high this will lead to power loss and
object will be grounded on both sides throughout the test giving a
temperature rise, which often leads to serious trouble. To avoid such
safer, faster and easier workflow.
problems, it is necessary to check the resistance at regular intervals.
Choose the MJÖLNER 600 with excessive power resources for
The following table demonstrates how important low resistance is at
demanding applications, superior measurement accuracy and when
high currents:
300 Amp continuous is required.
The lightweight and rugged suitcase design makes MJÖLNER 600 Current Contact resistance Power loss
an excellent choice when you need a portable solution in the field. 10 kA 1 mΩ 100 kW
When the case is closed, the product can withstand the impact of 10 kA 0.1 mΩ 10 kW
water, dust or sand – it even floats.
1 kA 1 mΩ 1 kW
Optional accessories are a remote control and the PC software 1 kA 0.1 mΩ 100 W
MJÖLNER Win with export functions for tables to Microsoft® Excel®
At 10 kA a contact with the resistance 0.1 mΩ gives a power loss
of 10 kW. This power loss in one single point will definitely confer
a temperature rise, which may result in overheating and possibly
premature failure.
MJÖLNER 600
Micro-ohmmeter
12
2
3
13
14
4
15
5
6
16
7
8 9 10 11
2
MJÖLNER 600
Micro-ohmmeter
Transformer testing The following table indicates other test methods and Megger instru-
Winding resistance – not on all type of transformers. ments that can use the DualGround testing:
(In many transformers there is a need for higher voltage Timing TM1700/1800 with DCM module
than 5 V)
Motion TM1700/1800
Internal/external connections
Dynamic Resistance TM1700/1800 with SDRM202
Everywhere you need to test a low resistance/ Measurement (DRM)
high current connection
Switches
Equipment and methods that supports DualGround™ testing
Disconnecting devices are associated with the DualGround symbol. This symbol
Safety
certifies the use of groundbreaking technology and methods
ground connections
that enables a safe, fast and easy workflow with both sides
Welding points grounded throughout the test.
Fuses
Cables
Using the remote control you can measure the voltage drop You can make tests with both sides of the test object
(voltage) across each contact element within every section of grounded, an additional safety feature.
the bus-bar being tested.
3
MJÖLNER 600
Micro-ohmmeter
SPECIFICATIONS
Specifications are valid at nominal input voltage. Specifications are Outputs
subject to change without notice. DC+ / COM
Environment Range 5 – 600 A DC (steps of 1 A)
Application field The instrument is intended for use in Max. output voltage 5.25 V at 600 A
high-voltage substations and industrial Max. ripple 80 mVpp, 28.3 mVrms
environments. at 0 - 50°C (+32°F to +122°F)
Temperature Load capacity1) 300 A (max) continuous
Operating -20°C to +50°C (-4°F to +122°F) OUTPUT 100 μV/A
Storage & transport -40°C to +70°C (-40°F to +158°F) Shunt output From internal shunt 60 mV at 600 A
Humidity 5% – 95% RH, non-condensing Inaccuracy ±1%
CE-marking Inputs
LVD 2014/35/EU SENSE Max. 20 V between terminals and to
EMC 2014/30/EU protective earth(ground)
RoHS 2011/65/EU INPUT Max. 20 V between terminals and to
General DC current clamp protective earth(ground)
Mains voltage 100 - 120 / 200 - 240 AC, 50 / 60 Hz Input sensitivity Adjustable 0.1 – 20 mV/A
Input current (max) 39 A at 100 V, 18 A at 230 V (3 sec) Input impedance >1 MΩ
1) At 25°C (77°F) ambient temperature
Protection Fuses (200 mAT and 400 mAT)
Thermal fuse, Software
Shut off temperature: 70ºC (158ºF)
internal temperature
Dimensions 486 x 392 x 192 mm (19” x15” x 7.5”)
Weight 13.8 kg (30.4 lbs)
Display LCD
Available languages English, Deutsch, Français, Espagñol,
Svenska
Printer Thermal printer
Thermal paper roll Width 57 mm, diameter 32 mm
Measurement section
Range 0 – 999.9 mΩ
Resolution 0.01 μΩ below 100 μΩ
0.1 μΩ below 1.0 mΩ
1 μΩ below 10 mΩ
10 μΩ below 100 mΩ
100 μΩ below 1000 mΩ
Inaccuracy Typ. Max.
100 A, ta 25ºC,
R < 1 mΩ ±0.2 μΩ ±1 μΩ
50 – 600 A, ta 10 – 40ºC,
R < 1 mΩ ±0.3 μΩ ±2 μΩ
50 – 600 A, ta 0 – 50ºC,
R < 1 mΩ ±0.7 μΩ ±3 μΩ
50 – 600 A, ta -20 – 50ºC,
R < 1 mΩ ±1.1 μΩ ±4 μΩ
600 A, ta 10 – 40ºC,
1 mΩ < R < 8.4 mΩ ±6 μΩ ±50 μΩ
50 A, ta 10 – 40ºC,
10 mΩ < R < 100 mΩ ±80 μΩ ±500 μΩ
5 A, ta 10 – 40ºC, ±1 mΩ ±10 mΩ
100 mΩ < R < 500 mΩ
5 A, ta 10 – 40ºC, ±2 mΩ ±20 mΩ
500 mΩ < R < 1000 mΩ
Current shunt 600 A, 60 mV
Sense ranges 0-2 mV, 0-20 mV, 0-200 mV, 0-5 V
4
MJÖLNER 600
Micro-ohmmeter
BD-90010
BD-90012
MJÖLNER Win
XA-12992
DualGround kit: Current probe 200 A, max. conductor size
50 mm diameter (2”)and 2 test cables, 5 m (15 ft).
Note: Included in Ordering No. BB-59093
Calibration shunt and XLR Bluetooth dongle
5
MJÖLNER 600
Micro-ohmmeter
INCLUDED ACCESSORIES
ORDERING INFORMATION
Current cables 2 x 5 m (16 ft), 35 mm2
Item Cat. No.
MJÖLNER 600
Incl. Cable set, current cables 2 x 5 m (16 ft), 35 mm2
and sensing cables 2 x 5 m
Ground cable, 5 m (16 ft) 2.5 mm2 BB-59091
Incl. Cable set, current cables 2 x 5 m (16 ft), 35 mm2
and sensing cables 2 x 5 m
Ground cable, 5 m (16 ft) 2.5 mm2
DualGround kit, (XA-12992) BB-59093
Optional accessories
MJÖLNER Win
Windows® software
Including XLR Bluetooth dongle (BD-90011) BD-8010X
Sensing cables 2 x 5 m (16 ft) Remote control
With connection cable, 5 m (16 ft) BD-90010
XLR Bluetooth dongle BD-90011
Temperature probe BD-90012
Thermal paper roll for printer GC-00120
Extension cable set 5 m
Current cables 2 x 5 m, 35 mm2
and sensing cables 2 x 10 m GA-03209
Extension cable set 10 m
Current cables 2 x 10 m, 35 mm2
and sensing cables 2 x 15 m GA-03210
Calibration shunt
600 A / 60 mV shunt BB-90020
DualGround kit
DC Current clamp 200 A and test cables 2 x 5 m (16 ft) XA-12992