Nexans Cable Catalogue QICC-Part5
Nexans Cable Catalogue QICC-Part5
LV, XLPE Insulation, STA, PVC 0.6/1 Contact
kV Nexans Qatar
[email protected]
IEC LV, XLPE INSULLATION 0.6/1 KV STA 12C
Nom. Max. DC Perm. current Current
Approx. Voltage drop,
outer Resist. Cond. rating open rating,
Nexans ref. Name weight 3 conductors
diam. 20°C air buried
[kg/km] [V/A.km]
[mm] [Ohm/km] [A] [A]
2E002BXZVTB09BD0 12x1.5 18.3 580 12.1 25 23 22.8
2E003BXZVTB09BD0 12x2.5 20.2 750 7.41 33 30 14.0
IEC LV, XLPE INSULLATION 0.6/1 KV STA 19C
Nom. Max. DC Perm. current Current
Approx. Voltage drop,
outer Resist. Cond. rating open rating,
Nexans ref. Name weight 3 conductors
diam. 20°C air buried
[kg/km] [V/A.km]
[mm] [Ohm/km] [A] [A]
2F002BXZVTB09BD0 19x1.5 20.7 770 12.1 25 23 22.8
2F003BXZVTB09BD0 19x2.5 23.0 1010 7.41 33 30 14.0
IEC LV, XLPE INSULLATION 0.6/1 KV STA 24C
Nom. Max. DC Perm. current Current
Approx. Voltage drop,
outer Resist. Cond. rating open rating,
Nexans ref. Name weight 3 conductors
diam. 20°C air buried
[kg/km] [V/A.km]
[mm] [Ohm/km] [A] [A]
2I002BXZVTB09BD0 24x1.5 23.6 990 12.1 25 23 22.8
2I003BXZVTB09BD0 24x2.5 26.3 1310 7.41 33 30 14.0
IEC LV, XLPE INSULLATION 0.6/1 KV STA 37C
Nom. Max. DC Perm. current Current
Approx. Voltage drop,
outer Resist. Cond. rating open rating,
Nexans ref. Name weight 3 conductors
diam. 20°C air buried
[kg/km] [V/A.km]
[mm] [Ohm/km] [A] [A]
2M002BXZVTB09BD0 37x1.5 26.5 1290 12.1 25 23 22.8
2M003BXZVTB09BD0 37x2.5 29.6 1720 7.41 33 30 14.0
All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Version 01 Generated 9/1/20 www.nexans.qa Page 141 / 159
IEC LV, XLPE Insulation, SWA+TCWA, Contact
PVC 0.6/1 kV KM Nexans Qatar
[email protected]
IEC 605021 & Kahramaa
Galvanized steel + Tin copper wire armoured LV cable, PVC sheathed for fixed
installations. Rated voltage 0.6/1 KV
DESCRIPTION
Application
These power cables are used for electricity supply in low voltage installation systems.
The cables are fully complying to IEC and Kahramaa EPMSP4/S3040 specification.
They are well adapted to underground use in industrial applications where chemical
and mechanical protections are needed (refinery areas, chemical plant…)
STANDARDS
Design International IEC 603321;
IEC 605021
1. Conductor
Stranded bare copper class 2 acc. to IEC 60228.
2. Insulation
Cross Linked Polyethylene "XLPE".
3. Inner Sheath or Bedding
Extruded bedding "PVC".
4. Armour
Single layer consisting of both galvanized Steel and tinned copper wires "SWA
+TCWA" / Water blocking tape above and under the armour layer.
5. Outer Sheath
Polyvinyl Chloride "PVC" ST2, Flame retardant to IEC 603321 or equivalent
Installation Conditions:
1. Air Temperature : 30 Deg.
2. Ground Temperature: 20 Deg.
3. Soil Thermal Resistivity : 2.5 k.m/w
4. Depth of lay : 0.7 m
All dimensions have tolerance + 7 %
Marking
All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Version 01 Generated 9/1/20 www.nexans.qa Page 142 / 159
IEC LV, XLPE Insulation, SWA+TCWA, Contact
PVC 0.6/1 kV KM Nexans Qatar
[email protected]
no. of cores x conductor sizes mm2 KAHRA MAA EPMSP4/S3040 600/1000 V
XLPE MADE IN QATAR QICCNexans Year Meters
CHARACTERISTICS
Construction characteristics
Conductor material Copper
Insulation XLPE (Crosslinked Polyethylene)
Inner sheath PVC
Armour type Galvanized steel wire + tin copper wire
Outer sheath PVC
Colour Black
Halogen free No
Electrical characteristics
Rated Voltage Uo/U (Um) 0.6/1 kV
Usage characteristics
Max. conductor temperature in service 90 °C
Shortcircuit max. conductor temperature 250 °C
Flame retardant Yes
Bending factor when laying 15 (xD)
Bending factor when installed 8 (xD)
KAHRAMAA LV, XLPE INSULATION 0.6/1KV GALVANISED STEEL + TINNED
COPPER WIRE ARMOUR
Nom. Max. DC Perm. current Current
Approx. Voltage drop,
outer Resist. Cond. rating open rating,
Nexans ref. Name weight 3 conductors
diam. 20°C air buried
[kg/km] [V/A.km]
[mm] [Ohm/km] [A] [A]
24016EXZVDB09BA0 4x16 24.0 1610 1.15 99 84 2.2
24025EXZVDB09BA0 4x25 26.5 2235 0.727 131 107 1.65
24035EXZVDB09BA0 4x35 29.0 2790 0.524 162 129 1.15
24050EXZVDB09BA0 4x50 33.0 3560 0.387 197 153 0.89
24070EXZVDB09BA0 4x70 38.0 4390 0.268 251 188 0.6
24095EXZVDB09BA0 4x95 42.0 5580 0.193 304 226 0.45
All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Version 01 Generated 9/1/20 www.nexans.qa Page 143 / 159
IEC LV, XLPE Insulation, SWA+TCWA, Contact
PVC 0.6/1 kV KM Nexans Qatar
[email protected]
All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Version 01 Generated 9/1/20 www.nexans.qa Page 144 / 159
IEC LV, XLPE Insulation, SWA, PVC Contact
0.6/1 kV QP Nexans Qatar
[email protected]
IEC 605021 & QP
Galvanized steel wire armoured LV cable, PVC sheathed for fixed installations. Rated
voltage 0.6/1 KV
DESCRIPTION
Application
These power cables are used for electricity supply in low voltage installation systems.
They are well adapted to underground use in industrial applications where chemical
and mechanical protections are needed (refinery areas, chemical plant…)
This family is fully compling with Qatar Petroleum specification
STANDARDS
Design International IEC 603321;
IEC 605021
1. Conductor
Stranded bare copper class 2 acc. to IEC 60228
2. Insulation
Cross Linked Polyethylene "XLPE"
3. Inner Sheath or Bedding
Lapped bedding or extruded PVC
4. Armour
Galvanized Steel Wire Armour "SWA"
5. Outer Sheath
Polyvinyl Chloride "PVC", Flame retardant CAT A to IEC 603323 or equivalent,
Oil resistant, Anti termite
Installation Conditions:
1. Air Temperature : 30 Deg.
2. Ground Temperature: 20 Deg.
3. Soil Thermal Resistivity : 2.5 k.m/w
4. Depth of lay : 0.7 m
All dimensions have tolerance + 7 %
Marking
All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Version 01 Generated 9/1/20 www.nexans.qa Page 145 / 159
IEC LV, XLPE Insulation, SWA, PVC Contact
0.6/1 kV QP Nexans Qatar
[email protected]
no. of cores x conductor sizes mm2 Cu / XLPE / SWA / PVC 600/1000 V Standard
MADE IN QATAR QICCNexans Year Meters
CHARACTERISTICS
Construction characteristics
Conductor material Copper
Insulation XLPE (Crosslinked Polyethylene)
Inner sheath PVC
Armour type Galvanized steel wires
Outer sheath PVC
Colour Black
Halogen free No
Usage characteristics
Max. conductor temperature in service 90 °C
Shortcircuit max. conductor temperature 250 °C
Flame retardant Yes
Bending factor when laying 15 (xD)
Bending factor when installed 8 (xD)
QP, LV, XLPE INSULATION, SWA 0.6/1 KV 4 C
Nom. Max. DC Perm. current Current
Approx. Voltage drop,
outer Resist. Cond. rating open rating,
Nexans ref. Name weight 3 conductors
diam. 20°C air buried
[kg/km] [V/A.km]
[mm] [Ohm/km] [A] [A]
24010BXZVSB09BNS 4x10 25.0 1265 1.83 78 65 3.5
24016BXZVSB09BNS 4x16 27.0 1610 1.15 99 84 2.2
24025BXZVSB09BNS 4x25 32.0 2275 0.727 131 107 1.65
24035BXZVSB09BNS 4x35 34.0 2450 0.524 162 129 1.15
24050BXZVSB01B20 4x50 38.0 3085 0.387 197 153 0.89
24070BXZVSB01B20 4x70 44.0 4320 0.268 251 188 0.6
24095BXZVSB01B20 4x95 48.0 5480 0.193 304 226 0.45
24120BXZVSB01B20 4x120 53.0 6945 0.153 353 257 0.37
24150BXZVSB01B20 4x150 63.0 8340 0.124 406 287 0.3
All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Version 01 Generated 9/1/20 www.nexans.qa Page 146 / 159
IEC LV, XLPE Insulation, SWA, PVC Contact
0.6/1 kV QP Nexans Qatar
[email protected]
All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Version 01 Generated 9/1/20 www.nexans.qa Page 147 / 159
IEC LV, XLPE Insulation, SWA, PVC Contact
0.6/1 kV Nexans Qatar
[email protected]
IEC 605021, FEWA, SEWA
Galvanized steel wire armoured LV cable, PVC sheathed for fixed installations. Rated
voltage 0.6/1 KV
DESCRIPTION
Application
These power cables are used for electricity supply in low voltage installation systems.
They are well adapted to underground use in industrial applications where chemical
and mechanical protections are needed (refinery areas, chemical plant…)
Design STANDARDS
International IEC 603321;
1. Conductor IEC 605021
Stranded bare copper class 2 acc. to IEC 60228
2. Insulation
Cross Linked Polyethylene "XLPE"
3. Inner Sheath or Bedding
Lapped bedding or extruded PVC
4. Armour
Galvanized Steel Wire Armour "SWA"
5. Outer Sheath
Polyvinyl Chloride "PVC"
Options :
Flame retardant : "CAT A, CAT B, CAT C" to IEC60332 or equivalent.
Ozone resistant.
Oil resistant.
Anti termite.
Installation Conditions:
1. Air Temperature : 30 Deg.
2. Ground Temperature: 20 Deg.
3. Soil Thermal Resistivity : 2.5 k.m/w
4. Depth of lay : 0.7 m
All dimensions have tolerance + 7 %
All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Version 02 Generated 9/1/20 www.nexans.qa Page 148 / 159
IEC LV, XLPE Insulation, SWA, PVC Contact
0.6/1 kV Nexans Qatar
[email protected]
Marking
no. of cores x conductor sizes mm2 Cu / XLPE / SWA / PVC 600/1000 V IEC 605021
MADE IN QATAR QICCNexans Year Meters
CHARACTERISTICS
Construction characteristics
Conductor material Copper
Insulation XLPE (Crosslinked Polyethylene)
Inner sheath PVC
Armour type Galvanized steel wires
Outer sheath PVC
Colour Black
Halogen free No
Usage characteristics
Max. conductor temperature in service 90 °C
Shortcircuit max. conductor temperature 250 °C
Flame retardant Yes
Bending factor when laying 15 (xD)
Bending factor when installed 8 (xD)
IEC LV, XLPE INSULATION 0.6/1KV 2 CORES
Nom. Max. DC Perm. current Current
Approx. Voltage drop,
outer Resist. Cond. rating open rating,
Nexans ref. Name weight 3 conductors
diam. 20°C air buried
[kg/km] [V/A.km]
[mm] [Ohm/km] [A] [A]
22002BXZVSB09BD0 2x1.5 13.0 300 12.1 25 23 22.8
22003BXZVSB09BD0 2x2.5 14.0 385 7.41 33 30 14.0
22004BXZVSB09BD0 2x4 15.0 450 4.61 44 39 8.7
22006BXZVSB09BD0 2x6 16.0 540 3.08 56 49 5.9
22010BXZVSB09BD0 2x10 18.0 700 1.83 78 65 3.5
22016BXZVSB09BD0 2x16 21.0 1045 1.15 99 84 2.2
22025BXZVSB09BD0 2x25 21.0 1080 0.727 131 107 1.65
22035BXZVSB09BD0 2x35 24.0 1510 0.524 162 129 1.15
All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Version 02 Generated 9/1/20 www.nexans.qa Page 149 / 159
IEC LV, XLPE Insulation, SWA, PVC Contact
0.6/1 kV Nexans Qatar
[email protected]
IEC LV, XLPE INSULATION 0.6/1KV 3 CORES
Perm.
Nom. Max. DC Current
Approx. current Voltage drop,
outer Resist. Cond. rating,
Nexans ref. Name weight rating open 3 conductors
diam. 20°C buried
[kg/km] air [V/A.km]
[mm] [Ohm/km] [A]
[A]
23002BXZVSB09BD0 3x1.5 13.0 330 12.1 25 23 22.8
23003BXZVSB09BD0 3x2.5 15.0 410 7.41 33 30 14.0
23004BXZVSB09BD0 3x4 16.0 510 4.61 44 39 8.7
23006BXZVSB09BD0 3x6 17.0 610 3.08 56 49 5.9
23010BXZVSB09BD0 3x10 20.0 930 1.83 78 65 3.5
23016BXZVSB09BD0 3x16 22.0 1240 1.15 99 84 2.2
23025BXZVSB09BD0 3x25 24.0 1640 0.727 131 107 1.65
23035BXZVSB09BD0 3x35 27.0 2030 0.524 162 129 1.15
27025BXZVSB09BD0 3x25+16 28.0 2165 0.727 131 107 1.65
27035BXZVSB09BD0 3x35+16 29.0 2330 0.524 162 129 1.15
23050BXZVSB09BD0 3x50 30.0 2520 0.387 197 153 0.89
23070BXZVSB09BD0 3x70 33.0 2860 0.268 251 188 0.6
27050BXZVSB09BD0 3x50+25 33.0 2960 0.387 197 153 0.89
27070BXZVSB09BD0 3x70+35 37.0 3530 0.268 251 188 0.6
23095BXZVSB09BD0 3x95 38.0 3940 0.193 304 226 0.45
27095BXZVSB09BD0 3x95+50 40.0 4470 0.193 304 226 0.45
23120BXZVSB09BD0 3x120 41.0 4760 0.153 353 257 0.37
27120BXZVSB09BD0 3x120+70 44.0 5508 0.153 353 257 0.37
23150BXZVSB09BD0 3x150 46.0 6070 0.124 406 287 0.3
27150BXZVSB09BD0 3x150+70 49.0 6860 0.124 406 287 0.3
23185BXZVSB09BD0 3x185 50.0 7310 0.0991 463 324 0.26
All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Version 02 Generated 9/1/20 www.nexans.qa Page 150 / 159
IEC LV, XLPE Insulation, SWA, PVC Contact
0.6/1 kV Nexans Qatar
[email protected]
Perm.
Nom. Max. DC Current
Approx. current Voltage drop,
outer Resist. Cond. rating,
Nexans ref. Name weight rating open 3 conductors
diam. 20°C buried
[kg/km] air [V/A.km]
[mm] [Ohm/km] [A]
[A]
27185BXZVSB09BD0 3x185+95 54.0 8350 0.0991 463 324 0.26
23240BXZVSB09BD0 3x240 55.0 9135 0.0754 546 375 0.21
27240BXZVSB09BD0 3x240+120 59.0 10440 0.0754 546 375 0.21
23300BXZVSB09BD0 3x300 60.0 11015 0.0601 628 419 0.18
27300BXZVSB09BD0 3x300+150 64.0 12630 0.0601 628 419 0.18
23400BXZVSB09BD0 3x400 67.0 13760 0.047 731 439 0.17
27400BXZVSB09BD0 3x400+185 73.0 16330 0.047 731 439 0.17
IEC LV, XLPE INSULATION 0.6/1KV 4 CORES
Nom. Max. DC Perm. current Current
Approx. Voltage drop,
outer Resist. Cond. rating open rating,
Nexans ref. Name weight 3 conductors
diam. 20°C air buried
[kg/km] [V/A.km]
[mm] [Ohm/km] [A] [A]
24002BXZVSB09BD0 4x1.5 14.0 370 12.1 25 23 22.8
24003BXZVSB09BD0 4x2.5 16.0 470 7.41 33 30 14.0
24004BXZVSB09BD0 4x4 17.0 580 4.61 44 39 8.7
24006BXZVSB09BD0 4x6 19.0 825 3.08 56 49 5.9
24010BXZVSB09BD0 4x10 21.0 1100 1.83 78 65 3.5
24016BXZVSB09BD0 4x16 24.0 1430 1.15 99 84 2.2
24025BXZVSB09BD0 4x25 27.0 1970 0.727 131 107 1.65
24035BXZVSB09BD0 4x35 29.0 2470 0.524 162 129 1.15
24050BXZVSB09BD0 4x50 33.0 3150 0.387 197 153 0.89
24070BXZVSB09BD0 4x70 38.0 3890 0.268 251 188 0.6
24095BXZVSB09BD0 4x95 42.0 4930 0.193 304 226 0.45
24120BXZVSB09BD0 4x120 47.0 6450 0.153 353 257 0.37
24150BXZVSB09BD0 4x150 51.0 7645 0.124 406 287 0.3
24185BXZVSB09BD0 4x185 56.0 9250 0.0991 463 324 0.26
24240BXZVSB09BD0 4x240 62.0 11680 0.0754 546 375 0.21
24300BXZVSB09BD0 4x300 67.0 14140 0.0601 628 419 0.18
24400BXZVSB09BD0 4x400 77.0 18510 0.047 731 439 0.17
All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Version 02 Generated 9/1/20 www.nexans.qa Page 151 / 159
IEC LV, XLPE Insulation, SWA, PVC Contact
0.6/1 kV Nexans Qatar
[email protected]
IEC LV, XLPE INSULATION 0.6/1KV 5 CORES
Nom. Max. DC Perm. current Current
Approx. Voltage drop,
outer Resist. Cond. rating open rating,
Nexans ref. Name weight 3 conductors
diam. 20°C air buried
[kg/km] [V/A.km]
[mm] [Ohm/km] [A] [A]
25002BXZVSB09BD0 5x1.5 15.0 430 12.1 25 23 22.8
25003BXZVSB09BD0 5x2.5 17.0 530 7.41 33 30 14.0
25004BXZVSB09BD0 5x4 18.0 680 4.61 44 39 8.7
25006BXZVSB09BD0 5x6 20.0 950 3.08 56 49 5.9
25010BXZVSB09BD0 5x10 23.0 1270 1.83 78 65 3.5
25016BXZVSB09BD0 5x16 27.0 1900 1.15 99 84 2.2
25025BXZVSB09BD0 5x25 31.0 2550 0.727 131 107 1.65
25035BXZVSB09BD0 5x35 34.0 3170 0.524 162 129 1.15
25050BXZVSB09BD0 5x50 39.0 4390 0.387 197 153 0.89
25070BXZVSB09BD0 5x70 44.0 4980 0.268 251 188 0.6
IEC LV, XLPE INSULATION 0.6/1KV 7 CORES
Nom. Max. DC Perm. current Current
Approx. Voltage drop,
outer Resist. Cond. rating open rating,
Nexans ref. Name weight 3 conductors
diam. 20°C air buried
[kg/km] [V/A.km]
[mm] [Ohm/km] [A] [A]
2C002BXZVSB09BD0 7x1.5 16.0 440 12.1 25 23 22.8
2C003BXZVSB09BD0 7x2.5 19.0 650 7.41 33 30 14.0
IEC LV, XLPE INSULATION 0.6/1KV 9 CORES
Nom. Max. DC Perm. current Current
Approx. Voltage drop,
outer Resist. Cond. rating open rating,
Nexans ref. Name weight 3 conductors
diam. 20°C air buried
[kg/km] [V/A.km]
[mm] [Ohm/km] [A] [A]
2K002BXZVSB09BD0 9x1.5 18.0 630 12.1 25 23 22.8
2K003BXZVSB09BD0 9x2.5 20.0 770 7.41 33 30 14.0
All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Version 02 Generated 9/1/20 www.nexans.qa Page 152 / 159
IEC LV, XLPE Insulation, SWA, PVC Contact
0.6/1 kV Nexans Qatar
[email protected]
IEC LV, XLPE INSULATION 0.6/1KV 12 CORES
Nom. Max. DC Perm. current Current
Approx. Voltage drop,
outer Resist. Cond. rating open rating,
Nexans ref. Name weight 3 conductors
diam. 20°C air buried
[kg/km] [V/A.km]
[mm] [Ohm/km] [A] [A]
2E002BXZVSB09BD0 12x1.5 19.0 710 12.1 25 23 22.8
2E003BXZVSB09BD0 12x2.5 21.0 890 7.41 33 30 14.0
IEC LV, XLPE INSULATION 0.6/1KV 19 CORES
Nom. Max. DC Perm. current Current
Approx. Voltage drop,
outer Resist. Cond. rating open rating,
Nexans ref. Name weight 3 conductors
diam. 20°C air buried
[kg/km] [V/A.km]
[mm] [Ohm/km] [A] [A]
2F002BXZVSB09BD0 19x1.5 22.0 930 12.1 25 23 22.8
2F003BXZVSB09BD0 19x2.5 25.0 1300 7.41 33 30 14.0
IEC LV, XLPE INSULATION 0.6/1KV 24 CORES
Nom. Max. DC Perm. current Current
Approx. Voltage drop,
outer Resist. Cond. rating open rating,
Nexans ref. Name weight 3 conductors
diam. 20°C air buried
[kg/km] [V/A.km]
[mm] [Ohm/km] [A] [A]
2I002BXZVSB09BD0 24x1.5 25.0 1250 12.1 25 23 22.8
2I003BXZVSB09BD0 24x2.5 28.0 1590 7.41 33 30 14.0
IEC LV, XLPE INSULATION 0.6/1KV 37 CORES
Nom. Max. DC Perm. current Current
Approx. Voltage drop,
outer Resist. Cond. rating open rating,
Nexans ref. Name weight 3 conductors
diam. 20°C air buried
[kg/km] [V/A.km]
[mm] [Ohm/km] [A] [A]
2M002BXZVSB09BD0 37x1.5 28.0 1610 12.1 25 23 22.8
2M003BXZVSB09BD0 37x2.5 32.0 2555 7.41 33 30 14.0
All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Version 02 Generated 9/1/20 www.nexans.qa Page 153 / 159
Pilot Cable 1kV Contact
Nexans Qatar
[email protected]
IEC 605021 & KAHRAMAA
Galvanized steel wire armoured LV cable, PVC sheathed for fixed installations. Rated
voltage 0.6/1 KV
DESCRIPTION
Application
This pilot cable is used on Standard Pilot Wire Protection Schemes and
Telecommunication Purposes.
The cable is fully complying to IEC and Kahramaa EPMSP4/
S3050 specification.
STANDARDS
1. Conductor
Stranded bare copper class 2 acc. to IEC 60228 International IEC 603321;
IEC 605021
2. Conductor of Pairs
Stranded bare copper class 2 acc. to IEC 60228
3. Insulation
Cross Linked Polyethylene "XLPE"
4. Inner Sheath or Bedding
Extruded bedding "PVC".
5. Armour
Single layer of Galvanized Steel wires "SWA" / Water blocking tape above and
under the armour layer.
6. Outer Sheath
Polyvinyl Chloride "PVC" ST2, Flame retardant to IEC 603321 or equivalent
Installation Conditions:
1. Air Temperature : 30 Deg.
2. Ground Temperature: 20 Deg.
3. Soil Thermal Resistivity : 2.5 k.m/w
4. Depth of lay : 0.7 m
All dimensions have tolerance + 7 %
Marking
All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Version 01 Generated 9/1/20 www.nexans.qa Page 154 / 159
Pilot Cable 1kV Contact
Nexans Qatar
[email protected]
no. of cores x conductor sizes mm2 KAHRA MAA EPMSP4/S3050 600/1000 V
XLPE MADE IN QATAR QICCNexans Year Meters
CHARACTERISTICS
Construction characteristics
Conductor material Copper
Insulation XLPE (Crosslinked Polyethylene)
Inner sheath PVC
Armour type Galvanized steel wires
Outer sheath PVC
Colour Black
Halogen free No
Electrical characteristics
Rated Voltage Uo/U (Um) 0.6/1 kV
Usage characteristics
Max. conductor temperature in service 90 °C
Shortcircuit max. conductor temperature 250 °C
Flame retardant Yes
Bending factor when laying 8 (xD)
Bending factor when installed 15 (xD)
PILOT CABLE 0.6/1 KV
Nom. Max. DC Perm. current Current
Approx. Voltage drop,
outer Resist. Cond. rating open rating,
Nexans ref. Name weight 3 conductors
diam. 20°C air buried
[kg/km] [V/A.km]
[mm] [Ohm/km] [A] [A]
4x4 +
2P004BXZDSB09BA0 31.0 1500 4.61 44 39 8.7
4x2x1.5
All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Version 01 Generated 9/1/20 www.nexans.qa Page 155 / 159
Copper conductors Contact
Nexans Qatar
[email protected]
The diversity and the applications of copper conductors are numerous.
From a single wire to a complex cable, from the lowest section to the highest,
copper is available, annealed, hard, bare or plated.
A lot of applications use the properties of copper :
• Energy
• Telecommunication
• Welding…
The copper qualities generally used for the production of conductors are :
• ETP copper, or Cua1, with oxygen content between 200 and 300 ppm.
• OF copper, oxygenfree or Cuc1, with very small content in oxygen (20 ppm
max.) able to resist to hydrogen brittleness during a heating.
All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Generated 9/1/20 www.nexans.qa Page 156 / 159
Copper Lead Contact
Nexans Qatar
[email protected]
IEC 60228 & Kahramaa
Singlecore Copper / Lead
DESCRIPTION
Application
Singlecore Copper / Lead cable using as an earthing, This group is complying with
IEC 60228 and Kahramaa .
Design
1. Conductor
Stranded bare copper class 2 acc. to IEC 60228 or equivalent
STANDARDS
2. Metalic Sheath
International IEC 60228
Lead sheath layer to IEC 605021.
Installation Conditions:
1.Air Temperature : 30 Deg.
2.Ground Temperature : 20 Deg
3.Soil Thermal Resistivity : 1.5 km/w
4.Depth of lay : 0.8 m
All dimensions have tolerance +7 %
All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Version 01 Generated 9/1/20 www.nexans.qa Page 157 / 159
Copper Lead Contact
Nexans Qatar
[email protected]
CHARACTERISTICS
Construction characteristics
Conductor material Bare copper stranded
Conductor shape Circular
Conductor exibility Stranded class 2
Armour type Unarmoured
Dimensional characteristics
Number of cores 1
Usage characteristics
Bending factor when laying 15 (xD)
Bending factor when installed 8 (xD)
All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Version 01 Generated 9/1/20 www.nexans.qa Page 158 / 159
Distributed by
Nexans Qatar
Qatar
[email protected]