HILTI Ferro/Rebar Scanning Report of HSIA Domestic Terminal.
HILTI Ferro/Rebar Scanning Report of HSIA Domestic Terminal.
This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Dear Sir,
We are enclosing the NDT reports for the scanning work that has been performed at your site. The scans have been done by using HILTI PS
200 S. Details are mentioned below:
PS 200 S Scanner:
1. Please note that the dimensions per scan is maximum 600mm X 600mm (1 scan)
2. The scan will give an estimate of the following parameters:
Rebar Layout
Rebar Diameter
Rebar Spacing
Rebar Covering Depth
Others
3. The scanning surface should be as smooth as possible for optimal results.
4. There should not be any ferrous material/pipes nearby at a distance of at least 30mm which can cause a deviation in the magnetic waves.
5. Results are mentioned; however, scans were not clear for accurate estimation of diameter.
This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Project Name:
Hazrat Shahjalal International Airport
Building Name:
Domestic Terminal
Project Address:
Kurmitola, Dhaka Maymansingh Hwy, Dhaka-1229, Bangladesh.
Contact:
+8801714545272
+8801738246511
This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
LETTER OF DECLARATION
We do hereby declare that this report is prepared based on the scanning data from different location in the structure
as suggested by the engineer/consultant using Hilti PS 200 S under the guidance and supervision of us. We will be
responsible for rationality and verification of any data presented in this report based on scanning only. While scanning
and analyzing, civil engineering knowledge and judgment was applied where necessary.
This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Image of Used Apparatus
This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Member Details: Finding & Remarks:
Member Type: Column Main Reinforcement:
Member Grid: B-1 03-16Ømm
Member Size: 13” Stirrup: Ø10 mm @ 8.89” C/C
Floor: Ground Floor Remarks:
Ferro scanning no.- 01 Visible phase
This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Member Details: Finding & Remarks:
Member Type: Column Main Reinforcement:
Member Grid: B-2 08-16Ømm
Member Size: 13” X 13” Stirrup: Ø10 mm @ 8.48” C/C
Floor: Ground Floor Remarks:
Ferro scanning no.- 02 Image not clear due to excess covering.
This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Member Details: Finding & Remarks:
Member Type: Column
Main Reinforcement:
Member Grid: A’-2
08-16Ømm
Member Size: 13” X 13”
Stirrup:
Floor: Ground Floor
Ø10 mm @ 8.12” C/C
Ferro scanning no.- 03
This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Member Details: Finding & Remarks:
Member Type: Column Main Reinforcement:
Member Grid: A’-4 08-16Ømm
Member Size: 13” X 13” Stirrup: Ø10 mm @ 9.25” C/C
Floor: Ground Floor Remarks:
Ferro scanning no.- 04 Image not clear due to excess covering by plywood.
This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Member Details: Finding & Remarks:
Member Type: Column Main Reinforcement:
Member Grid: A-4 03-16Ømm
Member Size: 13” Stirrup: Ø10 mm @ 7.84” C/C
Floor: Ground Floor Remarks:
Ferro scanning no.- 05 Visible phase with plaster.
This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Member Details: Finding & Remarks:
Member Type: Column Main Reinforcement:
Member Grid: B-4 08-16Ømm
Member Size: 13” X 13” Stirrup: Ø10 mm @ 7.88” C/C
Floor: Ground Floor Remarks:
Ferro scanning no.- 06 Image not clear due to excess covering by tiles.
This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Member Details: Finding & Remarks:
Member Type: Column Main Reinforcement:
Member Grid: B-5 08-16Ømm
Member Size: 13” X 13” Stirrup: Ø10 mm @ 7.80” C/C
Floor: Ground Floor Remarks:
Ferro scanning no.- 07 Image not clear due to excess covering by tiles.
This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Member Details: Finding & Remarks:
Member Type: Column Main Reinforcement:
Member Grid: B-6 08-20Ømm
Member Size: Not Mentioned Stirrup: Ø10 mm @ 12.95” C/C
Floor: Ground Floor Remarks:
Ferro scanning no.- 08 Image not clear due to excess covering by tiles.
This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Member Details: Finding & Remarks:
Member Type: Column Main Reinforcement:
Member Grid: B-9 08-20Ømm
Member Size: 13” X 13” Stirrup: Ø10 mm @ 10.52” C/C
Floor: Ground Floor Remarks:
Ferro scanning no.- 09 Image not clear due to excess covering by tiles.
This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Member Details: Finding & Remarks:
Member Type: Column Main Reinforcement:
Member Grid: A’-9 08-16Ømm
Member Size: 13” X 13” Stirrup: Ø10 mm @ 10.04” C/C
Floor: Ground Floor Remarks: Image not clear due to excess
Ferro scanning no.- 10 covering by tiles & others surface limitation.
This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Member Details: Finding & Remarks:
Member Type: Column Main Reinforcement:
Member Grid: A-10 03-16Ømm
Member Size: 13” Stirrup: Ø10 mm @ 10.0” C/C
Floor: Ground Floor Remarks: Vissible phase image not clear due to
Ferro scanning no.- 11 excess covering by plaster.
This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Member Details: Finding & Remarks:
Member Type: Column Main Reinforcement:
Member Grid: A-11 03-16Ømm
Member Size: 13” Stirrup: Ø10 mm @ 8.54” C/C
Floor: Ground Floor Remarks: Vissible phase image not clear due to
Ferro scanning no.- 12 excess covering by plaster.
This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Member Details: Finding & Remarks:
Member Type: Column Main Reinforcement:
Member Grid: B-14 03-16Ømm
Member Size: 13” Stirrup: Ø10 mm @ 8.24” C/C
Floor: Ground Floor Remarks: Vissible phase image not clear due to
Ferro scanning no.- 13 excess covering by plaster.
This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Member Details: Finding & Remarks:
Member Type: Column Main Reinforcement:
Member Grid: B-13 03-16Ømm
Member Size: 13” Stirrup: Ø10 mm @ 12.72” C/C
Floor: Ground Floor Remarks: Vissible phase image not clear due to
Ferro scanning no.- 14 excess covering by plaster & others surface limitation.
This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Member Details: Finding & Remarks:
Member Type: Column Main Reinforcement:
Member Grid: D-11 03-16Ømm
Member Size: 13” Stirrup: Ø10 mm @ 11.80” C/C
Floor: Ground Floor Remarks: Vissible phase image not clear due to
Ferro scanning no.- 15 excess covering by tiles & others surface limitation.
This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Member Details: Finding & Remarks:
Member Type: Column Main Reinforcement:
Member Grid: D-10 03-16Ømm
Member Size: 13” Stirrup: Ø10 mm @ 8.40” C/C
Floor: Ground Floor Remarks: Vissible phase image not clear due to
Ferro scanning no.- 16 excess covering by tiles & others surface limitation.
This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Member Details: Finding & Remarks:
Member Type: Column Main Reinforcement:
Member Grid: D-9 03-16Ømm
Member Size: 13” Stirrup: Ø10 mm @ 11.89” C/C
Floor: Ground Floor Remarks: Vissible phase image not clear due to
Ferro scanning no.- 17 excess covering by tiles & others surface limitation.
This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Member Details: Finding & Remarks:
Member Type: Column Main Reinforcement:
Member Grid: D-8 03-16Ømm
Member Size: 13” Stirrup: Ø10 mm @ 9.64” C/C
Floor: Ground Floor Remarks: Vissible phase image not clear due
Ferro scanning no.- 18 to excess covering & others surface limitation.
This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Member Details: Finding & Remarks:
Member Type: Column Main Reinforcement:
Member Grid: E’-6 08-20Ømm
Member Size: 13” X 13” Stirrup: Ø10 mm @ 8.56” C/C
Floor: Ground Floor Remarks:
Ferro scanning no.- 19 Image not clear due to excess covering by tiles.
This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Member Details: Finding & Remarks:
Member Type: Column
Main Reinforcement:
Member Grid: E-6
08-20Ø mm
Member Size: 15” X 15”
Stirrup:
Floor: Ground Floor
Ø10 mm @ 12.5” C/C
Ferro scanning no.- 20
This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Member Details: Finding & Remarks:
Member Type: Column Main Reinforcement:
Member Grid: E’-3 03-16Ø mm
Member Size: Not Mentioned Stirrup: Ø10 mm @ 8.02” C/C
Floor: Ground Floor Remarks: Vissible phase image not clear due to
Ferro scanning no.- 21 excess covering & others surface limitation.
This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Member Details: Finding & Remarks:
Member Type: Column Main Reinforcement:
Member Grid: E-3 03-16Ømm
Member Size: Not Mentioned Stirrup: Ø10 mm @ 8.14” C/C
Floor: Ground Floor Remarks: Vissible phase image not clear due
Ferro scanning no.- 22 to excess covering & others surface limitation.
This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Member Details: Finding & Remarks:
Member Type: Column Main Reinforcement:
Member Grid: C-8 08-20Ømm
Member Size: 18” X 15” Stirrup: Ø10 mm @ 11.05” C/C
Floor: Ground Floor Remarks:
Ferro scanning no.- 23 Image not clear due to excess covering by tiles.
This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Member Details: Finding & Remarks:
Member Type: Column Main Reinforcement:
Member Grid: C-3 03-16Ømm
Member Size: 14” Stirrup: Ø10 mm @ 6.36” C/C
Floor: Ground Floor Remarks: Vissible phase image not clear
Ferro scanning no.- 24 due to excess covering by plywood board.
This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Member Details: Finding & Remarks:
Member Type: Column Main Reinforcement:
Member Grid: C-14 08-16Ø mm
Member Size: 14” X 14” Stirrup: Ø10 mm @ 8.22” C/C
Floor: Ground Floor Remarks:
Ferro scanning no.- 25 Image not clear due to excess covering by tiles.
This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Member Details: Finding & Remarks:
Member Type: Column Main Reinforcement:
Member Grid: C-13 08-20Ø mm
Member Size: 16” X 16” Stirrup: Ø10 mm @ 10.50” C/C
Floor: Ground Floor Remarks:
Ferro scanning no.- 26 Image not clear due to excess covering by tiles.
This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Member Details: Finding & Remarks:
Member Type: Column Main Reinforcement:
Member Grid: E’-8 08-16Ø mm
Member Size: 14” X 14” Stirrup: Ø10 mm @ 8.19” C/C
Floor: Ground Floor Remarks:
Ferro scanning no.- 27 Image not clear due to excess covering by tiles.
This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Member Details: Finding & Remarks:
Member Type: Column Main Reinforcement:
Member Grid: E-7 08-20Ø mm
Member Size: 18” X 17” Stirrup: Ø10 mm @ 11.50” C/C
Floor: Ground Floor Remarks:
Ferro scanning no.- 28 Image not clear due to excess covering by tiles.
This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Member Details: Finding & Remarks:
Member Type: Column Main Reinforcement:
Member Grid: G-3 03-16Ø mm
Member Size: 13” Stirrup: Ø10 mm @ 6.25” C/C
Floor: Ground Floor Remarks:
Ferro scanning no.- 29 Visivle phase
This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Member Details: Finding & Remarks:
Member Type: Column Main Reinforcement:
Member Grid: G-10 03-16Ø mm
Member Size: 13” Stirrup: Ø10 mm @ 8.40” C/C
Floor: Ground Floor Remarks:
Ferro scanning no.- 30 Visivle phase
This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Member Details: Finding & Remarks:
Member Type: Column Main Reinforcement:
Member Grid: G-6 03-16Ømm
Member Size: 13” Stirrup: Ø10 mm @ 7.89” C/C
Floor: Ground Floor Remarks: Image not clear due to excess
Ferro scanning no.- 31 clear cover by plaster.
This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Member Details: Finding & Remarks:
Member Type: Slab Main Reinforcement:
Member Grid: G11:H11-G10:H10 X direction: Ø10 mm @ 7.0” C/C (average)
Member Size: N/A Y direction: Ø12 mm @ 8.0” C/C
Floor: Ground Floor
Ferro scanning no.- 32
This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Member Details: Finding & Remarks:
Member Type: Beam
Main Reinforcement:
Member Grid: G:H-10
Bottom: 2-16Ø mm & 2-20Ø mm
Member Size: Bottom 13” X Side 18”
Stirrup:
Floor: Ground Floor
Ø10 mm @ 8.04” C/C
Ferro scanning no.- 33
This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Member Details: Finding & Remarks:
Member Type: Beam Main Reinforcement:
Member Grid: E’-1:2 Bottom: 2-20Ø mm & 1-16Ø mm
Member Size: Side 19” X Bottom 11” Stirrup: Ø10 mm @ 7.25” C/C
Floor: Ground Floor Remarks:
Ferro scanning no.- 34 Image not clear due to surface limitation
This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Member Details: Finding & Remarks:
Member Type: Slab Main Reinforcement:
Member Grid: G:E’-1:2 X direction: Ø10 mm @ 6.97” C/C
Member Size: N/A Y direction: Ø12 mm @ 7.91” C/C
Floor: Ground Floor
Ferro scanning no.- 35
This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Member Details: Finding & Remarks:
Member Type: Column Main Reinforcement:
Member Grid: C-17 08-16Ø mm
Member Size: 15” X 15” Stirrup: Ø10 mm @ 8.20” C/C
Floor: Ground Floor Remarks:
Ferro scanning no.- 36 Image not clear due to excess covering by tiles.
This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Member Details: Finding & Remarks:
Member Type: Column Main Reinforcement:
Member Grid: B-16 08-16Ø mm
Member Size: 15” X 15” Stirrup: Ø10 mm @ 8.48” C/C
Floor: Ground Floor Remarks:
Ferro scanning no.- 37 Image not clear due to excess covering by plaster.
This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Member Details: Finding & Remarks:
Member Type: Column Main Reinforcement:
Member Grid: A’-16 03-16Ø mm
Member Size: 15” Stirrup: Ø10 mm @ 7.0” C/C
Floor: Ground Floor Remarks:
Ferro scanning no.- 38 Visible phase
This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Member Details: Finding & Remarks:
Member Type: Beam (Side) Main Reinforcement:
Member Grid: G-9:10 Side: 2-25Ø mm & 2-20Ø mm
Member Size: Side 24” Stirrup: Ø10 mm @ 6.67” C/C (average)
Floor: Ground Floor Remarks:
Ferro scanning no.- 39 Vissible phase
This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Pictorial Evidence:
This report is prepared based on images can and quick scan only.
Date of reporting: April 2023