HILTI Ferro/Rebar Scanning Report of HSIA Domestic Terminal.

NDT, Ferro/Rebar Scanning Report for Detail Engineering Assessment (DEA) of Hazrat Shahjalal International Airport (Domestic Terminal) by HILTI PS 200 S ferro scanner.

Uploaded by

Biprojit Hore
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
101 views45 pages

HILTI Ferro/Rebar Scanning Report of HSIA Domestic Terminal.

NDT, Ferro/Rebar Scanning Report for Detail Engineering Assessment (DEA) of Hazrat Shahjalal International Airport (Domestic Terminal) by HILTI PS 200 S ferro scanner.

Uploaded by

Biprojit Hore
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 45

Report On

Reinforcement Scanning Work Of


Hazrat Shahjalal International Airport
(Domestic Terminal)

This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Dear Sir,
We are enclosing the NDT reports for the scanning work that has been performed at your site. The scans have been done by using HILTI PS
200 S. Details are mentioned below:

PS 200 S Scanner:
1. Please note that the dimensions per scan is maximum 600mm X 600mm (1 scan)
2. The scan will give an estimate of the following parameters:
 Rebar Layout
 Rebar Diameter
 Rebar Spacing
 Rebar Covering Depth
 Others
3. The scanning surface should be as smooth as possible for optimal results.
4. There should not be any ferrous material/pipes nearby at a distance of at least 30mm which can cause a deviation in the magnetic waves.
5. Results are mentioned; however, scans were not clear for accurate estimation of diameter.

Depends on scan mode, rebar spacing and diameter.


Operating range Position/diameter: To resolve single bars min. spacing 36mm or spacing: coverage (s:c) = min. 2:1 whichever is greater.
Depth: Min. depth 10 mm for depth reading.
Depth: Depends on scan mode, rebar spacing and diameter.
Typical accuracy Bar diameter: ±1 standard diameter (s:c ≥ 2:1) (Up to 60mm depth)
Bar location: bar center ±3mm / ±1in (s:c ≥ 1.5:1).

This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Project Name:
Hazrat Shahjalal International Airport

Building Name:
Domestic Terminal

Project Address:
Kurmitola, Dhaka Maymansingh Hwy, Dhaka-1229, Bangladesh.

Scanning & Report Generated By:


Engr. Biprojit Hore (Shouvo)
(B.Sc in Civil)
Structure Diagnosis Consultant
RETECH Associates

Contact:
+8801714545272
+8801738246511

This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
LETTER OF DECLARATION

We do hereby declare that this report is prepared based on the scanning data from different location in the structure
as suggested by the engineer/consultant using Hilti PS 200 S under the guidance and supervision of us. We will be
responsible for rationality and verification of any data presented in this report based on scanning only. While scanning
and analyzing, civil engineering knowledge and judgment was applied where necessary.

This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Image of Used Apparatus

This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Member Details: Finding & Remarks:
 Member Type: Column  Main Reinforcement:
 Member Grid: B-1 03-16Ømm
 Member Size: 13” Stirrup: Ø10 mm @ 8.89” C/C
 Floor: Ground Floor  Remarks:
 Ferro scanning no.- 01 Visible phase

This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Member Details: Finding & Remarks:
 Member Type: Column  Main Reinforcement:
 Member Grid: B-2 08-16Ømm
 Member Size: 13” X 13” Stirrup: Ø10 mm @ 8.48” C/C
 Floor: Ground Floor  Remarks:
 Ferro scanning no.- 02 Image not clear due to excess covering.

This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Member Details: Finding & Remarks:
 Member Type: Column
 Main Reinforcement:
 Member Grid: A’-2
08-16Ømm
 Member Size: 13” X 13”
 Stirrup:
 Floor: Ground Floor
Ø10 mm @ 8.12” C/C
 Ferro scanning no.- 03

This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Member Details: Finding & Remarks:
 Member Type: Column  Main Reinforcement:
 Member Grid: A’-4 08-16Ømm
 Member Size: 13” X 13” Stirrup: Ø10 mm @ 9.25” C/C
 Floor: Ground Floor  Remarks:
 Ferro scanning no.- 04 Image not clear due to excess covering by plywood.

This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Member Details: Finding & Remarks:
 Member Type: Column  Main Reinforcement:
 Member Grid: A-4 03-16Ømm
 Member Size: 13” Stirrup: Ø10 mm @ 7.84” C/C
 Floor: Ground Floor  Remarks:
 Ferro scanning no.- 05 Visible phase with plaster.

This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Member Details: Finding & Remarks:
 Member Type: Column  Main Reinforcement:
 Member Grid: B-4 08-16Ømm
 Member Size: 13” X 13” Stirrup: Ø10 mm @ 7.88” C/C
 Floor: Ground Floor  Remarks:
 Ferro scanning no.- 06 Image not clear due to excess covering by tiles.

This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Member Details: Finding & Remarks:
 Member Type: Column  Main Reinforcement:
 Member Grid: B-5 08-16Ømm
 Member Size: 13” X 13” Stirrup: Ø10 mm @ 7.80” C/C
 Floor: Ground Floor  Remarks:
 Ferro scanning no.- 07 Image not clear due to excess covering by tiles.

This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Member Details: Finding & Remarks:
 Member Type: Column  Main Reinforcement:
 Member Grid: B-6 08-20Ømm
 Member Size: Not Mentioned Stirrup: Ø10 mm @ 12.95” C/C
 Floor: Ground Floor  Remarks:
 Ferro scanning no.- 08 Image not clear due to excess covering by tiles.

This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Member Details: Finding & Remarks:
 Member Type: Column  Main Reinforcement:
 Member Grid: B-9 08-20Ømm
 Member Size: 13” X 13” Stirrup: Ø10 mm @ 10.52” C/C
 Floor: Ground Floor  Remarks:
 Ferro scanning no.- 09 Image not clear due to excess covering by tiles.

This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Member Details: Finding & Remarks:
 Member Type: Column  Main Reinforcement:
 Member Grid: A’-9 08-16Ømm
 Member Size: 13” X 13” Stirrup: Ø10 mm @ 10.04” C/C
 Floor: Ground Floor  Remarks: Image not clear due to excess
 Ferro scanning no.- 10 covering by tiles & others surface limitation.

This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Member Details: Finding & Remarks:
 Member Type: Column  Main Reinforcement:
 Member Grid: A-10 03-16Ømm
 Member Size: 13” Stirrup: Ø10 mm @ 10.0” C/C
 Floor: Ground Floor  Remarks: Vissible phase image not clear due to
 Ferro scanning no.- 11 excess covering by plaster.

This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Member Details: Finding & Remarks:
 Member Type: Column  Main Reinforcement:
 Member Grid: A-11 03-16Ømm
 Member Size: 13” Stirrup: Ø10 mm @ 8.54” C/C
 Floor: Ground Floor  Remarks: Vissible phase image not clear due to
 Ferro scanning no.- 12 excess covering by plaster.

This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Member Details: Finding & Remarks:
 Member Type: Column  Main Reinforcement:
 Member Grid: B-14 03-16Ømm
 Member Size: 13” Stirrup: Ø10 mm @ 8.24” C/C
 Floor: Ground Floor  Remarks: Vissible phase image not clear due to
 Ferro scanning no.- 13 excess covering by plaster.

This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Member Details: Finding & Remarks:
 Member Type: Column  Main Reinforcement:
 Member Grid: B-13 03-16Ømm
 Member Size: 13” Stirrup: Ø10 mm @ 12.72” C/C
 Floor: Ground Floor  Remarks: Vissible phase image not clear due to
 Ferro scanning no.- 14 excess covering by plaster & others surface limitation.

This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Member Details: Finding & Remarks:
 Member Type: Column  Main Reinforcement:
 Member Grid: D-11 03-16Ømm
 Member Size: 13” Stirrup: Ø10 mm @ 11.80” C/C
 Floor: Ground Floor  Remarks: Vissible phase image not clear due to
 Ferro scanning no.- 15 excess covering by tiles & others surface limitation.

This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Member Details: Finding & Remarks:
 Member Type: Column  Main Reinforcement:
 Member Grid: D-10 03-16Ømm
 Member Size: 13” Stirrup: Ø10 mm @ 8.40” C/C
 Floor: Ground Floor  Remarks: Vissible phase image not clear due to
 Ferro scanning no.- 16 excess covering by tiles & others surface limitation.

This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Member Details: Finding & Remarks:
 Member Type: Column  Main Reinforcement:
 Member Grid: D-9 03-16Ømm
 Member Size: 13” Stirrup: Ø10 mm @ 11.89” C/C
 Floor: Ground Floor  Remarks: Vissible phase image not clear due to
 Ferro scanning no.- 17 excess covering by tiles & others surface limitation.

This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Member Details: Finding & Remarks:
 Member Type: Column  Main Reinforcement:
 Member Grid: D-8 03-16Ømm
 Member Size: 13” Stirrup: Ø10 mm @ 9.64” C/C
 Floor: Ground Floor  Remarks: Vissible phase image not clear due
 Ferro scanning no.- 18 to excess covering & others surface limitation.

This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Member Details: Finding & Remarks:
 Member Type: Column  Main Reinforcement:
 Member Grid: E’-6 08-20Ømm
 Member Size: 13” X 13” Stirrup: Ø10 mm @ 8.56” C/C
 Floor: Ground Floor  Remarks:
 Ferro scanning no.- 19 Image not clear due to excess covering by tiles.

This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Member Details: Finding & Remarks:
 Member Type: Column
 Main Reinforcement:
 Member Grid: E-6
08-20Ø mm
 Member Size: 15” X 15”
 Stirrup:
 Floor: Ground Floor
Ø10 mm @ 12.5” C/C
 Ferro scanning no.- 20

This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Member Details: Finding & Remarks:
 Member Type: Column  Main Reinforcement:
 Member Grid: E’-3 03-16Ø mm
 Member Size: Not Mentioned Stirrup: Ø10 mm @ 8.02” C/C
 Floor: Ground Floor  Remarks: Vissible phase image not clear due to
 Ferro scanning no.- 21 excess covering & others surface limitation.

This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Member Details: Finding & Remarks:
 Member Type: Column  Main Reinforcement:
 Member Grid: E-3 03-16Ømm
 Member Size: Not Mentioned Stirrup: Ø10 mm @ 8.14” C/C
 Floor: Ground Floor  Remarks: Vissible phase image not clear due
 Ferro scanning no.- 22 to excess covering & others surface limitation.

This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Member Details: Finding & Remarks:
 Member Type: Column  Main Reinforcement:
 Member Grid: C-8 08-20Ømm
 Member Size: 18” X 15” Stirrup: Ø10 mm @ 11.05” C/C
 Floor: Ground Floor  Remarks:
 Ferro scanning no.- 23 Image not clear due to excess covering by tiles.

This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Member Details: Finding & Remarks:
 Member Type: Column  Main Reinforcement:
 Member Grid: C-3 03-16Ømm
 Member Size: 14” Stirrup: Ø10 mm @ 6.36” C/C
 Floor: Ground Floor  Remarks: Vissible phase image not clear
 Ferro scanning no.- 24 due to excess covering by plywood board.

This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Member Details: Finding & Remarks:
 Member Type: Column  Main Reinforcement:
 Member Grid: C-14 08-16Ø mm
 Member Size: 14” X 14” Stirrup: Ø10 mm @ 8.22” C/C
 Floor: Ground Floor  Remarks:
 Ferro scanning no.- 25 Image not clear due to excess covering by tiles.

This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Member Details: Finding & Remarks:
 Member Type: Column  Main Reinforcement:
 Member Grid: C-13 08-20Ø mm
 Member Size: 16” X 16” Stirrup: Ø10 mm @ 10.50” C/C
 Floor: Ground Floor  Remarks:
 Ferro scanning no.- 26 Image not clear due to excess covering by tiles.

This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Member Details: Finding & Remarks:
 Member Type: Column  Main Reinforcement:
 Member Grid: E’-8 08-16Ø mm
 Member Size: 14” X 14” Stirrup: Ø10 mm @ 8.19” C/C
 Floor: Ground Floor  Remarks:
 Ferro scanning no.- 27 Image not clear due to excess covering by tiles.

This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Member Details: Finding & Remarks:
 Member Type: Column  Main Reinforcement:
 Member Grid: E-7 08-20Ø mm
 Member Size: 18” X 17” Stirrup: Ø10 mm @ 11.50” C/C
 Floor: Ground Floor  Remarks:
 Ferro scanning no.- 28 Image not clear due to excess covering by tiles.

This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Member Details: Finding & Remarks:
 Member Type: Column  Main Reinforcement:
 Member Grid: G-3 03-16Ø mm
 Member Size: 13” Stirrup: Ø10 mm @ 6.25” C/C
 Floor: Ground Floor  Remarks:
 Ferro scanning no.- 29 Visivle phase

This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Member Details: Finding & Remarks:
 Member Type: Column  Main Reinforcement:
 Member Grid: G-10 03-16Ø mm
 Member Size: 13” Stirrup: Ø10 mm @ 8.40” C/C
 Floor: Ground Floor  Remarks:
 Ferro scanning no.- 30 Visivle phase

This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Member Details: Finding & Remarks:
 Member Type: Column  Main Reinforcement:
 Member Grid: G-6 03-16Ømm
 Member Size: 13” Stirrup: Ø10 mm @ 7.89” C/C
 Floor: Ground Floor  Remarks: Image not clear due to excess
 Ferro scanning no.- 31 clear cover by plaster.

This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Member Details: Finding & Remarks:
 Member Type: Slab  Main Reinforcement:
 Member Grid: G11:H11-G10:H10 X direction: Ø10 mm @ 7.0” C/C (average)
 Member Size: N/A Y direction: Ø12 mm @ 8.0” C/C
 Floor: Ground Floor
 Ferro scanning no.- 32

This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Member Details: Finding & Remarks:
 Member Type: Beam
 Main Reinforcement:
 Member Grid: G:H-10
Bottom: 2-16Ø mm & 2-20Ø mm
 Member Size: Bottom 13” X Side 18”
 Stirrup:
 Floor: Ground Floor
Ø10 mm @ 8.04” C/C
 Ferro scanning no.- 33

This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Member Details: Finding & Remarks:
 Member Type: Beam  Main Reinforcement:
 Member Grid: E’-1:2 Bottom: 2-20Ø mm & 1-16Ø mm
 Member Size: Side 19” X Bottom 11” Stirrup: Ø10 mm @ 7.25” C/C
 Floor: Ground Floor  Remarks:
 Ferro scanning no.- 34 Image not clear due to surface limitation

This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Member Details: Finding & Remarks:
 Member Type: Slab  Main Reinforcement:
 Member Grid: G:E’-1:2 X direction: Ø10 mm @ 6.97” C/C
 Member Size: N/A Y direction: Ø12 mm @ 7.91” C/C
 Floor: Ground Floor
 Ferro scanning no.- 35

This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Member Details: Finding & Remarks:
 Member Type: Column  Main Reinforcement:
 Member Grid: C-17 08-16Ø mm
 Member Size: 15” X 15” Stirrup: Ø10 mm @ 8.20” C/C
 Floor: Ground Floor  Remarks:
 Ferro scanning no.- 36 Image not clear due to excess covering by tiles.

This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Member Details: Finding & Remarks:
 Member Type: Column  Main Reinforcement:
 Member Grid: B-16 08-16Ø mm
 Member Size: 15” X 15” Stirrup: Ø10 mm @ 8.48” C/C
 Floor: Ground Floor  Remarks:
 Ferro scanning no.- 37 Image not clear due to excess covering by plaster.

This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Member Details: Finding & Remarks:
 Member Type: Column  Main Reinforcement:
 Member Grid: A’-16 03-16Ø mm
 Member Size: 15” Stirrup: Ø10 mm @ 7.0” C/C
 Floor: Ground Floor  Remarks:
 Ferro scanning no.- 38 Visible phase

This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Member Details: Finding & Remarks:
 Member Type: Beam (Side)  Main Reinforcement:
 Member Grid: G-9:10 Side: 2-25Ø mm & 2-20Ø mm
 Member Size: Side 24” Stirrup: Ø10 mm @ 6.67” C/C (average)
 Floor: Ground Floor  Remarks:
 Ferro scanning no.- 39 Vissible phase

This report is prepared based on images can and quick scan only.
Date of reporting: April 2023
Pictorial Evidence:

This report is prepared based on images can and quick scan only.
Date of reporting: April 2023