1) LV Switchgear 5

The document summarizes the results of calculations for carbon dioxide flow in a fire suppression system protecting a room measuring 14.6m x 8.4m x 6.0m high. It details that 1080kg of CO2 will be discharged from 24 cylinders storing 45kg each. Pressure and flow rates are calculated over 18 sections of the pipe network, with 375kg discharged in the first two minutes. Nozzle discharge times are provided for the six nozzles used.

Uploaded by

ChowKC03
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
72 views

1) LV Switchgear 5

The document summarizes the results of calculations for carbon dioxide flow in a fire suppression system protecting a room measuring 14.6m x 8.4m x 6.0m high. It details that 1080kg of CO2 will be discharged from 24 cylinders storing 45kg each. Pressure and flow rates are calculated over 18 sections of the pipe network, with 375kg discharged in the first two minutes. Nozzle discharge times are provided for the six nozzles used.

Uploaded by

ChowKC03
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

HP CO2 FLOW CALCULATIONS

Version 1. 0. 3

Data input file name: Y:\LJY\DILA\CADENCE\PAN ENGINEERING\FIRST SOLAR\1) LV ROOM 5.hp2


FIRST SOLAR

REMARKS: 1) LV ROOM 5 (14.6m x 8.4m x 6.0m(h)


SI units (meters, kilograms, kiloPascals) are specified
Total flooding system for Deep Seated hazard
Nozzle Codes are specified

Agent Storage Conditions

Nominal Storage Pressure is 5171 kPa at 21 degrees Celsius


45 kgs of carbon dioxide is stored in each of 24 cylinders.
Total carbon dioxide discharged is 1080 kgs
375 kgs discharged during first two minutes of flow

Pressure Drop Results

Sec Sec Nominal Length Equiv Elev Tee/ Start Term Flow
Start End Pipe Size (m) Length(m) (m) Mfld kPa kPa (kgs/min)

1 2 1/2 80 T 1.8 20.1 1.8 Cyl 5171 5143 7.92


2 3 1 1/4 80 T 3.6 20.5 0.0 23 cyl 5143 5012 182.23
3 4 1 1/4 80 T 4.2 5.2 4.2 5012 4950 190.15
4 5 1 1/4 80 T 1.5 2.5 0.0 4950 4930 190.15
5 6 1 1/4 80 T 0.7 1.7 0.0 4930 4923 190.15

6 7 1 1/4 80 T 1.7 2.7 0.0 4923 4909 190.15


7 8 1 1/4 80 T 4.0 5.0 0.0 4909 4881 190.15
8 9 3/4 40 T 3.7 5.0 0.0 BHT 4881 4709 120.99
9 10 1/2 40 T 2.2 3.1 0.0 BHT 4709 4599 60.49

10 11 1/2 40 T 2.4 3.3 0.0 BHT 4599 4564 30.25


10 12 1/2 40 T 2.4 3.3 0.0 BHT 4599 4564 30.25
9 13 1/2 40 T 2.2 3.1 0.0 BHT 4709 4599 60.49
13 14 1/2 40 T 2.4 3.3 0.0 BHT 4599 4564 30.25

13 15 1/2 40 T 2.4 3.3 0.0 BHT 4599 4564 30.25


8 16 3/4 40 T 3.7 5.0 0.0 BHT 4881 4840 69.16
16 17 1/2 40 T 2.2 3.1 0.0 BHT 4840 4806 34.58
16 18 1/2 40 T 2.2 3.1 0.0 BHT 4840 4806 34.58

11 301 1/2 40 T 0.2 0.7 -0.2 4564 4564 30.25


12 302 1/2 40 T 0.2 0.7 -0.2 4564 4564 30.25
14 303 1/2 40 T 0.2 0.7 -0.2 4564 4564 30.25
15 304 1/2 40 T 0.2 0.7 -0.2 4564 4564 30.25

17 305 1/2 40 T 0.2 0.7 -0.2 4806 4792 34.58


18 306 1/2 40 T 0.2 0.7 -0.2 4806 4792 34.58

1 (Continued)
HP CO2 FLOW CALCULATIONS
Version 1. 0. 3

Data input file name: Y:\LJY\DILA\CADENCE\PAN ENGINEERING\FIRST SOLAR\1) LV ROOM 5.hp2

Calculation based on 25 degree Celsius pre-discharge Pipeline Temperature

Nozzle Performance Summary

Nozzle Nominal Nozzle Weight (kgs) Initial Vapor Liquid End of Discharge
Number Pipe Size Code Discharged Time (sec) Time (sec) Time (sec)
301 1/2 40 T 5.50 171.8 3.7 241.6 245.2
302 1/2 40 T 5.50 171.8 3.7 241.6 245.2
303 1/2 40 T 5.50 171.8 3.7 241.6 245.2
304 1/2 40 T 5.50 171.8 3.7 241.6 245.2
305 1/2 40 T 5.50 196.4 3.6 241.7 245.2

306 1/2 40 T 5.50 196.4 3.6 241.7 245.2


Total carbon dioxide discharged is 1080 kgs

Messages

Hydraulic calculation was successful.


Nozzle codes are fixed. Convergance of the iteration of nozzle flow rate and pressure is 2.5%
The system is calculated using nozzle codes rounded and fixed at nearest 1/2 code. Convergence of
nozzle flow rate and pressure to ±2.5%
Calculation performed on 17/1/2020 8:37:00 AM
Calculation by Unique Fire Industry Sdn Bhd
No 9, Jalan Anggerik Mokara 31/55, Seksyen 31, Kota Kemuning,
Shah Alam Selangor 40460 Malaysia
Telephone: 03-5131-1226
Fax: 03-5131-3826
17/1/2020 Time: 8:37:21 AM

2 End of Printout