Rayan Carte
Rayan Carte
ENPHASE IQ8PLUS-72-2-US
MICROINVERTERS
PV MODULES
TO UTILITY GRID
L1 L1
L2 L2
20A/2P N
L1
DESCRIPTION
G
L2
20A/2P
L1
L2
EXISTING GROUNDING
G
N G
AC RATING OF SYSTEM
15.95 KW
AC OUTPUT CURRENT
66.55 A
NO. OF MODULES
(55) FBM400MFG-BB(400W) URECO SOLAR MODULES
Sarasota, FL 34241
POINT OF CONNECTION LINE SIDE TAP IN MSP
155'-9"
RYAN CARTER
ARRAY STRINGING (5) BRANCHES OF 11 MODULES 18" SETBACK
37'
RISK CATEGORY II
DATE
GOVERNING CODES
FLORIDA RESIDENTIAL CODE, 7TH EDITION 2020 (FRC)
REVISIONS
DESCRIPTION
FLORIDA FIRE PREVENTION CODE, 7TH EDITION 2020 (FFPC) ROOF 2
UM
27'-4"
7'-2"
ROOF 1
(E) UTILITY METER (E) MAIN SERVICE PANEL PV ARRAY
SHEET INDEX WIND FLOW MAP
REV ENGG.
147'-11"
SHEET NO. SHEET NAME
E - 03 SYSTEM LABELING
SHEET NAME
DS - 01 MODULE DATASHEET
DS - 02
SITE MAP &
INVERTER DATASHEET
DS - 03
VICINITY MAP
COMBINER BOX DATASHEET
DS - 05 RACKING DATASHEET
ROOF ACCESS POINT
A-00
18" SETBACK
MODULE TYPE, DIMENSIONS & WEIGHT GENERAL INSTALLATION PLAN NOTES:
DATE
VIEW AREA AND IS WITHIN THE 33% REQUIREMENT.
REVISIONS
DESCRIPTION
REV ENGG.
LEGENDS
ROOF 2 UM - UTILITY METER
JB
UM ACD
JB - JUNCTION BOX
CP
67.83"
(FUSIBLE) CP - COMBINER PANEL
REVIEWER
- FIRE SETBACK
SHEET NAME
- ROOF ACCESS POINT
- MICROINVERTER ROOF PLAN
- VENT, ATTIC FAN & MODULES
FBM400MFG-BB(400W) (ROOF OBSTRUCTION)
URECO SOLAR SHEET NUMBER
- CONDUIT
MODULES
S-01
WIND LOAD INFORMATION:
ROOF DESCRIPTION: THIS SYSTEM HAS BEEN DESIGN TO MEET
(ROOF #1) (ROOF #2) THE REQUIREMENTS OF THE 7TH EDITION OF
MODULES - 49 THE FLORIDA BUILDING CODE AND USED
MODULES - 6 THE FOLLOWING DESIGN PARAMETERS:
ROOF TILT - 30° ROOF TILT - 30°
ROOF AZIMUTH - 180° ROOF AZIMUTH - 90°
ULTIMATE WIND SPEED: 150 MPH
TRUSSES SIZE - 2"X4" @ 24" O.C. TRUSSES SIZE - 2"X4" @ 24" O.C. EXPOSURE CATEGORY: B Signature with Seal
RISK CATEGORY: ll
MEAN ROOF HEIGHT: 15FT
ROOF SLOPE: 7°-20°°
NOTE:-
MAX CANTILEVER : 1'6" MAX.
1'-6"
18" SETBACK
10'
46
'-8
JUNCTION BOX
"
LEGENDS
1"
'-
19
- FIRE SETBACK
DATE
ROOF #1
- RAILS
- RAFTERS / TRUSSES
REVISIONS
- METAL SEAM
DESCRIPTION
WIND ZONE 1
- WIND ZONE 1
REV ENGG.
- WIND ZONE 1'
WIND ZONE 2
"
'-8
46
- WIND ZONE (2) PERMIT DEVELOPER
'-
46
DESIGNER OVL
- WIND ZONE (2e)
REVIEWER
- WIND ZONE (2n)
SHEET NAME
WIND ZONE 3
65'-5"
ARRAY
- WIND ZONE (3)
LAYOUT
ROOF #2
- WIND ZONE (3r)
SHEET NUMBER
- WIND ZONE (3e)
S-02
PHOTOVOLTAIC MODULE GENERAL NOTES:
1. APPLICABLE CODE: 2020 FLORIDA BUILDING CODE 7th ED. & ASCE 7-16
MINIMUM DESIGN LOADS FOR BUILDING AND OTHER STRUCTURES
2. BOLT DIAMETER AND EMBEDMENT LENGTHS ARE DESIGNED PER NDS(2012)
REQUIREMENTS. ALL BOLT CAPACITIES ARE BASED ON A Signature with Seal
RYAN CARTER
MANUFACTURER'S INSTRUCTIONS. SHINGLE FLASHING
9. I CERTIFY THAT THE INSTALLATION OF THE MODULES IS IN COMPLIANCE WOOD SHEATHING
WITH FBC:BUILDING CHAPTER 16 AND FBC:RESIDENTIAL CHAPTER 3.
BUILDING STRUCTURE WILL SAFELY ACCOMMODATE CALCULATED 5/16"x4" STAINLESS
WIND LATERAL AND UPLIFT FORCES AND EQUIPMENT DEAD LOADS.
RAFTERS STEEL LAG SCREW
CROSSRAIL 44-X
DATE
K2 (SPLICE FOOT XL)
REVISIONS
DESCRIPTION
SOLAR MODULE
REV ENGG.
WOOD SHEATHING
SHINGLE FLASHING
PERMIT DEVELOPER
DATE 05/08/2023
DESIGNER OVL
REVIEWER
S-03
NOTE:
Q CABLES
1. SUBJECT PV SYSTEMS HAS BEEN DESIGNED TO MEET THE
REQUIREMENTS OF THE NEC 2017, NFPA 70 AND THOSE SET FORTH BY
THE FLORIDA SOLAR ENERGY CENTER CERTIFICATION, INCLUDING
MAXIMUM NUMBER OF MODULE STRINGS, MAXIMUM NUMBER OF
MODULES PER STRING, MAXIMUM OUTPUT, MODULE MANUFACTURER
AND MODEL NUMBER, INVERTER MANUFACTURER AND MODEL
NUMBER, AS APPLICABLE.
2. PROVIDE TAP BOX IN COMPLIANCE WITH 312.8 IF PANEL GUTTER Signature with Seal
SPACE IS INADEQUATE.
PV MODULES
TO UTILITY GRID
JUNCTION BOX 2
600 V, NEMA 3R
LINE TAP USING INSULATION L1 L2 N
UL LISTED PIERCING 705.12(A)
BI-DIRECTIONAL
(2) 10/2 ROMEX RUN IN ATTIC OR
UTILITY METER
(2) #10 AWG THWN-2 - RED
1-PHASE, 240V
DATE
(2) #10 AWG THWN-2 - BLACK (N) AC DISCONNECT:
(2) #10 AWG THWN-2 GND 240V, 100AMP, FUSED L1 L2 N
IN 1" IMC, RMC, FMC, LFMC, (N) 125A EATON COMBINER PANEL WITH 90 A FUSES
PVC, HDPE, NUCC, RTRC, NEMA 3R, UL LISTED
LFNC, FMT, ENT OR EMT
CONDUIT RUN L1 L2 N
MAIN SERVICE
L1 L1 L1
(3) 10/2 ROMEX RUN IN ATTIC OR PANEL, 200A RATED, 240V.
NEMA 3 RATED 15A
REVISIONS
(3) #10 AWG THWN-2 - RED L2 L2 L2
DESCRIPTION
(3) #10 AWG THWN-2 - BLACK WATERPROOF MAIN BREAKER
N N N
(3) #10 AWG THWN-2 GND BOX 200A/2P, 240V
IN 1" IMC, RMC, FMC, LFMC, G G G
PVC, HDPE, NUCC, RTRC, 200A/2P
LFNC, FMT, ENT OR EMT
CONDUIT RUN
(3) #2/0 AWG THWN-2 (3) #2/0 AWG THWN-2
(1) #4 AWG THWN-2 GND IN 3/4" IMC, RMC, FMC, LFMC,
IN 3/4" IMC, RMC, FMC, LFMC, PVC, HDPE, NUCC, RTRC,
L1 L1
REV ENGG.
PVC, HDPE, NUCC, RTRC, LFNC, FMT, ENT OR EMT
LFNC, FMT, ENT OR EMT CONDUIT RUN L2 L2
CONDUIT RUN
20A/2P
L1 L1 L1
L2 L2 L2
20A/2P
L1 L1 L1
L2 L2 L2 PERMIT DEVELOPER
N
DATE 05/08/2023
G
DESIGNER OVL
EXISTING GROUNDING
20A/2P REVIEWER
L1
L2
20A/2P SHEET NAME
L1
L2
20A/2P ELECTRICAL
L1
L2 LINE DIAGRAM
G
SHEET NUMBER
N G
E-01
ELECTRICAL CALCULATIONS: ELECTRICAL NOTES
Sarasota, FL 34241
5. DRAWINGS INDICATE THE GENERAL ARRANGEMENT OF SYSTEMS
RYAN CARTER
CONTRACTOR SHALL FURNISH ALL NECESSARY OUTLETS,
(B) AFTER IQ COMBINER PANEL SUPPORTS, FITTINGS AND ACCESSORIES TO FULFILL APPLICABLE
CODES AND STANDARDS.
TEMPERATURE DERATE FACTOR - 0.96 6. WHERE SIZES OF JUNCTION BOXES, RACEWAYS, AND CONDUITS
GROUPING FACTOR - 1 ARE NOT SPECIFIED, THE CONTRACTOR SHALL SIZE THEM
ACCORDINGLY.
7. ALL WIRE TERMINATIONS SHALL BE APPROPRIATELY LABELED
CONDUCTOR AMPACITY AND READILY VISIBLE.
8. MODULE GROUNDING CLIPS TO BE INSTALLED BETWEEN MODULE
=(TOTAL INV O/P CURRENT) x 1.25 / 0.96 / 1 ...NEC 690.8(B) FRAME AND MODULE SUPPORT RAIL, PER THE GROUNDING CLIP
=[(55x 1.21) x 1.25] /0.96 / 1 MANUFACTURER'S INSTRUCTION.
=86.65 A 9. MODULE SUPPORT RAIL TO BE BONDED TO CONTINUOUS COPPER
G.E.C. VIA WEEB LUG OR ILSCO GBL-4DBT LAY-IN LUG.
SELECTED CONDUCTOR - #6 THWN-2 ...NEC 310.15(B)(16) 10. THE POLARITY OF THE GROUNDED CONDUCTORS IS NEGATIVE.
11. UTILITY HAS 24-HR UNRESTRICTED ACCESS TO ALL
PHOTOVOLTAIC SYSTEM COMPONENTS LOCATED AT THE SERVICE
DATE
2. PV OVER CURRENT PROTECTION ..NEC 690.9(B) ENTRANCE.
=TOTAL INVERTER O/P CURRENT x 1.25 12. MODULES CONFORM TO AND ARE LISTED UNDER UL 1703.
13. RACKING CONFORMS TO AND IS LISTED UNDER UL 2703.
=(55 x 1.21) x 1.25 = 83.19 A 14. CONDUCTORS EXPOSED TO SUNLIGHT SHALL BE LISTED AS
REVISIONS
SELECTED OCPD = 90A
DESCRIPTION
SUNLIGHT RESISTANT PER NEC ARTICLE 300.6 (C) (1) AND ARTICLE
310.10 (D).
15. CONDUCTORS EXPOSED TO WET LOCATIONS SHALL BE SUITABLE
SELECTED EQUIPMENT GROUND CONDUCTOR (EGC) = #8 THWN-2 ... NEC 250.122(A) FOR USE IN WET LOCATIONS PER NEC ARTICLE 310.10 (C).
REV ENGG.
MODULE SPECIFICATION
FBM400MFG-BB(400W)
MODEL NO. URECO SOLAR
PERMIT DEVELOPER
MODULESMODULES
PEAK POWER 400 W DATE 05/08/2023
RATED VOLTAGE (Vmpp) 31.17 V
RATED CURRENT (Impp) 12.84 A DESIGNER OVL
RYAN CARTER
ELECTRIC SHOCK HAZARD
DO NOT TOUCH TERMINALS
LABEL LOCATION:
AC DISCONNECT, INVERTER
PHOTOVOLTAIC SYSTEM ! WARNING
TERMINALS ON BOTH LINE AND (PER CODE: NEC 690.54) EQUIPPED WITH RAPID
LOAD SIDES MAY BE ENERGIZED DEDICATED SOLAR PANELS DO
IN THE OPEN POSITION SHUTDOWN NOT CONNECT ANY OTHER LOADS
LABEL LOCATION:
AC DISCONNECT, POINT OF INTERCONNECTION, LABEL LOCATION:
COMBINER PANEL WARNING AC DISCONNECT, DC DISCONNECT, POINT OF
(PER CODE: NEC 690.13(B)) INTERCONNECTION
INVERTER OUTPUT CONNECTION DO NOT (PER CODE: NEC 690.56(C)(3))
RELOCATE THIS OVERCURRENT DEVICE
WARNING PHOTOVOLTAIC LABEL LOCATION:
POWER SOURCE POINT OF INTERCONNECTION, MAIN SERVICE DISCONNECT
(PER CODE: NEC 705.12 (B)(2)(c))
EMERGENCY RESPONDER THIS
LABEL LOCATION:
CONDUIT RUNWAY
[Not required if panelboard is rated not less than sum of ampere ratings
of all overcurrent devices supplying it] ! WARNING SOLAR PV SYSTEM IS EQUIPPED
(PER CODE: NEC690.31(G)(3)(4))
WITH RAPID SHUTDOWN
DATE
INVERTER OUTPUT CONNECTION
DO NOT RELOCATE THIS
DATA PER PANEL OVERCURRENT DEVICE
! WARNING DUAL POWER SOURCE NOMINAL OPERATING AC VOLTAGE - 240 V TURN RAPID SHUTDOWN
REVISIONS
SOLAR ELECTRIC
DESCRIPTION
SECOND SOURCE IS PHOTOVOLTAIC SYSTEM SWITCH TO THE PV PANELS
REV ENGG.
ADHESIVE FASTENED SIGNS: NEC690.56(C)(1) AND NFPA 111.12.2.1.1.1.1, 11.12.2.1.4
·ANSI Z535.4-2011 PRODUCT SAFETY SIGNS AND LABELS, PROVIDES MAXIMUM OVERCURRENT DEVICE RATING 20 A
GUIDELINES FOR SUITABLE FONT SIZES, WORDS, COLORS, SYMBOLS, AND FOR AC MODULE PROTECTION PER CIRCUIT-
LOCATION REQUIREMENTS FOR LABELS. NEC 110.21(B)(1)
·THE LABEL SHALL BE OF SUFFICIENT DURABILITY TO WITHSTAND THE
ENVIRONMENT INVOLVED. NEC 110.21(B)(3) PERMIT DEVELOPER
·ADHESIVE FASTENED SIGNS MAY BE ACCEPTABLE IF PROPERLY
ADHERED. VINYL SIGNS SHALL BE WEATHER RESISTANT. IFC 605.11.1.3 LABEL LOCATION:
DATE 05/08/2023
COMBINER PANEL, AC DISCONNECT
(PER CODE: NEC 690.52)
DESIGNER OVL
REVIEWER
SHEET NAME
SYSTEM
LABELING
SHEET NUMBER
E-03
Signature with Seal
DESCRIPTION
REV ENGG.
PERMIT DEVELOPER
DATE 05/08/2023
DESIGNER OVL
REVIEWER
SHEET NAME
MODULE
DATASHEET
SHEET NUMBER
DS-01
Signature with Seal
DESCRIPTION
REV ENGG.
PERMIT DEVELOPER
DATE 05/08/2023
DESIGNER OVL
REVIEWER
SHEET NAME
INVERTER
DATASHEET
SHEET NUMBER
DS-02
Signature with Seal
DESCRIPTION
REV ENGG.
PERMIT DEVELOPER
DATE 05/08/2023
DESIGNER OVL
REVIEWER
SHEET NAME
COMBINER BOX
DATASHEET
SHEET NUMBER
DS-03
Signature with Seal
DESCRIPTION
REV ENGG.
PERMIT DEVELOPER
DATE 05/08/2023
DESIGNER OVL
REVIEWER
SHEET NAME
ATTACHMENT
DATASHEET
SHEET NUMBER
DS-04
Signature with Seal
DESCRIPTION
REV ENGG.
PERMIT DEVELOPER
DATE 05/08/2023
DESIGNER OVL
REVIEWER
SHEET NAME
RACKING
DATASHEET
SHEET NUMBER
DS-05