DRTS 64 - EN - Vers2
DRTS 64 - EN - Vers2
Automatic Relay
Test System
DRTS 64
2
Application
• Testing all relay technologies: electromechanical, DRTS 64 can test all the following relays
solid state, numerical and IEC61850
RELAY TYPE IEEE NO
• Manual control with color display
Distance relay 21
• Simultaneously available: 6 Current and 4 Synchronizing device 25
Voltage plus 1 battery simulator outputs Under/over-voltage relay 27/59
Directional Power relay 32
• High current outputs: 6 x 32 A, 3 x 64 A, 1 x 128 A Field relay 40
Reverse phase current relay 46
• High power outputs: 6 x 430 VA, 3 x 860, 1 x 1000 VA Phase sequence voltage relay 47
• High accuracy outputs: better than 0.05% Incomplete sequence relay 48
Instantaneous over-current relay 50
• IEC 61850 protocol interface Breaker Failure 50 BF
Inverse time over-current relay 51
• USB and Ethernet interface, optional wireless Voltage restrained overcurrent 50V/51V
Voltage controlled overcurrent 51/27C
• Pen drive interface
Power factor relay 55
• Internal GPS and IRIG-B interface for end-to-end tests Voltage balance relay 60
Ground detector relay 64
• Advanced testing and data management Directional over-current relay 67
software TDMS Phase angle out of step relay 78
Automatic reclosing relay 79
• Complete library of relays from the major Frequency relay and df/dt 81
manufacturers Pilot wire receiver relay 85
• Highest quality, safety and reliability Lockout relay 86
Differential protection relay 87
• Circuit breaker simulator Voltage directional relay 91
Power directional relay 92
Tripping relay 94
Local control
Manual test setup Distance relay test setup Over-current relay test result
Technical specification
Current Generator Output Power
Current Outputs Typical values
DRTS 64 DRTS 64
6 x 0 ... 32 A AC 3 x 100 VA at 125 ... 300 V
3 x 0 ... 64 A AC 4 x 85 VA at 125 ... 300 V
1 x 0 ... 128 A AC 1 x 200 VA at 125 ... 300 V
1 x 200 VA at 600 V
Output Power
Typical values • One voltage output can be selected via software to act
as an independent voltage output, or ,via software, the
DRTS 64 output can be selected to be: V0 = (V1+V2+V3)/3 or V0 =
6 x 430 VA at 32 A (V1+V2+V3)/1.73 (bolded stays for vector sum)
• Accuracy: Typical ±0.02% of the value ± 0.01% of
3 x 860 VA at 64 A the range; guaranteed ±0.04% of the value ± 0.01% of the range
1 x 1000 VA at 64 A • Distortion: 0.015% Typical; 0.03% guaranteed.
• Resolution: 0.4 mV at 12.5 V; 10 mV at 300 V
• Connections: 4 mm banana sockets
• Accuracy: typical ±0.02% of the value ±0.01% of the
range; guaranteed 0.04% of the value ± 0.01% of the range
• Distortion: 0.05% Typical; 0.15% guaranteed Other Generator Characteristics
• Resolution: 0.1 mA at 32 A Output Frequency
• Connections: 4 mm banana sockets
Currents and Voltages output frequency: 0 to 3000 Hz.
For the voltage: 3 kHz at 60 V; 2 kHz at 100 V; 700 Hz at 300 V.
Voltage Generators Transient: 0 to 5000 Hz.
Voltage Outputs Possibility to program 12 different frequencies on all outputs.
DRTS 64 Maximum frequency error: 0.5 ppM.
Resolution: < 5 µHz.
4 x 0 ... 300 V
Phase Angle
1 x 0 ... 600 V Range: - 360° ... +360°
Resolution: 0.001°
• Ranges: 12.5 V and 300 V Accuracy (voltages and currents) 50/60 Hz: 0.01° typical, 0.02°
guaranteed
DRTS 64
4
Optional accessories
The six phase current amplifier AMI 632 is an additional device to
External Amplifiers DRTS 64. The option includes six current generators at 32 A each.
In connection with the DRTS 64, the option offers the following
AMI 332 - Current Amplifier 3X32A
(Require code 87170 in the DRTS) features:
• To control 9 currents at 32 A each at the meantime, for the test
of three windings transformer differential protection relays
• To have a six phase generator at 64 A per phase
• To have three phase generator at 128 A per phase
• To have a single phase output at 256 A
The three phase current amplifier AMI 332 is an additional device Accuracy: 0.02% of the value ± 0.01% of the range, Typical; 0.04%
to DRTS 64. The option includes three current generators at of the value ± 0.01% of the range, guaranteed
32A each. In connection with the DRTS 64, the option offers the
Distortion: 0.05% Typical; 0.15% guaranteed
following features:
Resolution: 1 mA
• To control 6 currents at 32 A each at the mean time, for
the test of two-secondary transformer protection relays Connections: 4 mm banana sockets
• To have a three phase generator at 96 A per phase
• To have a single phase generator at 192 A Power Supply for AMI 332 and AMI 632
• Mains power supply: 85V to 264 V AC, sinusoidal, single phase
AMI 332 - Technical Specification • Frequency: 45 to 65 Hz
• Power consumption:
- at rest: less than 150 W
CURRENT GENERATORS POWER - maximum load, 115 V supply: 800/1600 W
3 x 0 … 32 A AC 3 x 430 VA at 32 A AC - maximum load, 230 V supply: 1300/2700 W
1 x 0 ... 96 A AC 1 x 1000 VA at 64 A AC Connection: Standard 16 A AC socket
connected to the substation network are also called GOOSE. Transit Case
GOOSE messages describe binary status signals over the substation Three options are available:
network and are also used for relays tripping. . Heavy duty plastic transport case (Discovery type)
For relay testing applications within IEC61850 substations it is . Blue composit transport case (aluminium)
necessary to access these data. This new feature is performed by . Soft carrying bag
the ISA Automatic Relay Test Set DRTS 64.
By means of a dedicated hardware and by the TDMS software, ISA
DRTS 64 can expand its testing capabilities by handling IEC61850
messages.
The IEC61850 Interface option for DRTS 64 is required for relay
testing with Ethernet-based substation communication protocol.
The IEC61850 Interface is mounted on the front panel of DRTS 64.
The option has to be specified at order.
www.altanova-group.com
The product and the information contained herein may be changed at any time without prior notification. This document nor any parts thereof may not be reproduced or transmitted in any form either
electronically or mechanically, including photocopying and recording, without the express written consent of ISA - Altanova Group Srl.