244ENG AC2speed UML51R Set PDF

1. The document appears to be a wiring diagram showing electrical connections for a motor control system. 2. It shows power connections from a 220/240VAC source to contactors, terminals, and fuses that control the operation of two motors labeled M1 and M2. 3. It also includes options for a soft start, motor cooling fan, and thermistor that can be added to the basic motor control configuration.

Uploaded by

Sinuhe Lopez
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
102 views6 pages

244ENG AC2speed UML51R Set PDF

1. The document appears to be a wiring diagram showing electrical connections for a motor control system. 2. It shows power connections from a 220/240VAC source to contactors, terminals, and fuses that control the operation of two motors labeled M1 and M2. 3. It also includes options for a soft start, motor cooling fan, and thermistor that can be added to the basic motor control configuration.

Uploaded by

Sinuhe Lopez
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 6

5 4 3 2 1

U
OL L1 1 2 U
R L2
F
V M2
3x380 / 5 6 1 2

~
415VAC S
L3

3
T U 3 4 W
F High Speed
D
D 1 2 X D

F1/F2/F3 Soft Start Option


N S
C3x2A 5 6 1 2 Y M1

~
L1/R U
Z

3
D 3 4
PE L2/S V
T2
T 15
S2
Motor Fan Option
S Slow Speed
G R2
S NV L3/T W
R 18 G
- 220 /
F1 L1 240VAC N
Thermistor Option 21 22
S
BG2 53 54 F10 /2A
220 R2 A1 T1 T1 F5-B6A
/240VAC A2
TPR
T2
F1
N T2 + 1 2
.
95

96

18V

6
F1
24V 4 3
L
C
F4-C4A F1 C
5 6

5
380V * AC1 (110vac)
22/18

/415V
VE3 VE2 VE1
Supply Only to J9 9VAC
TR 120
. .

U F
the Master 9VAC - + 110VdC 4 3 5 6
Card. 9VAC 0 BG1 B1
D S
4 3 5 6
BR
F7/8/9 Motor Brake
3x1.5A
G * WHEN THERE IS RETIRING CAM, F4 SOULD BE 6A B2
3x380 /415V Doors
O
OLD 1 2 dm1
L1
dm2 DM
B B
L2 3 4
L3
5 6 dm3
O
Door Motor

F6 / C6A
LS LO C
G
4 1 1 2
P L
CAR LIGHT Car Fan
N Sw 3
C
4
Inspection Light Sw.
220/240VAC 5
C
6

C=0.33mF/600V
Inspection Light Automatic Car Light. Car R=470R/1W
Fan
OZ
A A

TR - TRANSFORMER
TPR - THERMISTOR APP. NAME : Benci
OL - MAIN SWITCH AND OVERLOAD Title
OLD - DOOR OPERATOR SWITCH AND OVERLOAD APP. DATE : POWER AC-2 SPEED FOR UML-51r 110VAC
BG1 - CONTROL BRIDGE
BG2 - SIGNALIZATION BRIDGE
NV - PHASE FAILURE DETECTOR
CARD TERMINAL . Size Document Number Rev
TERMINAL
A4 Eng-UML51r-POWER-AC2 SPEED-110VAC 308006 01
Date: Wednesday, October 04, 2006 Sheet 1 of 9
5 4 3 2 1
5 4 3 2 1

Manual Door Contacts Gate Contact. Interlock Contacts

MDC GC ICS
C6A C7 P7 HI8
.
HI5 C19 C32
.
2 C

R6
Top Car Inspection Box
R
D D
10
CIPB For Manual Doors Circuit Only.
PERMANENT SAFETIES SOS EMERG. G
FLS-3 FLS-2 FLS-1
F3A /2A NV C1 C3 STOP Gate Contact. Interlocks Contacts
AC-1 110VAC 15 18 GC ICS
C19 C32 C7
3 Phase and
Sequence
C2 ITS .
HI5

BSDS
(C21)
Detector
Bottom Slow Down . HI3 Normal
RSN I1. NSR
SW. G
R6 ISS
TSDS Inspection
Option For 1 3 (C22)
Manual Doors Top Slow Down
SW.
. HI4 BUP-UP Inspection Direction

Door
PHC (PHC)
. IND. 1 (C61)
UIPB-Up Inspection Direction
2C
.
3C . I11
Photocell I6 Up Slow Down . HI2
I10 1C . P7

DSE (ROD)
Inductor 1C
. I9 BDN-Down Inspection Direction
I9

C
Door Safety
Edge
. I8 Down Slow Down
IND. 2
(C4)
.
DIPB-Down Inspection Direction CIP-1=Controller Inspection Panel
C

DOB
Inductor HI6
(C6A In Case Of Manual Hall Doors) HI8
.
(OD)
Door Open
PB.
. I7
Door Zone
Inductor.
IND. 3
(C6)
. HI7
C1 C19 C7A

CFM (C93)
Car Fireman . I2
CIPB - COMMON INSPECTION PUSH BUTTON
SDO - SWITCH DOOR OPEN
DOL DCL
Key L - CAR LIGHT RELAY FDLS FULS

HFM (C94)
O - DOOR OPEN CONTACTOR HI1 .
Hall Fireman
Key
. I3 * For Uk Please jumper
C - DOOR CLOSE CONTACTOR
S - SLOW SPEED CONTACTOR C18 C14 C8 61
F
62 C9
I2 with I3 Inputs. F - FAST SPEED CONTACTOR
FLS (FL) D - DOWN DIRECTION CONTACTOR CIP-1
Car Full
Load
. I5 U - UP DIRECTION CONTACTOR SDO
ROL - OVERLOAD RELAY
TPR TH U S F ROL FDLS - FAST DOWN LIMIT SW.
Droped D 2,2KW
Contacts Check 96 21 22 21 22 21 1 4 .(RC) FULS - FAST UP LIMIT SW.
DOL - DOOR OPEN LIMIT SW.
2 C A1
2,2KW
C A1 C A1 C A1 C A1 C A1 C

I4
B B
L O C S F D U
1

Motor 60o DCL - DOOR CLOSE LIMIT SW. R R R R R R R

Contact ROL FLS-1 FLS-2= LIMIT SWITCHES 10 A2 A2 A2 A2 A2 A2

22
22

62
FLS-3 = PIT SWITCH Mechanical
Jumper Option Interlock
P7 - RELEASE P.B AFTER INSPECTION
3

C O S

OLS OVERLOAD

21
21

61
HI7
. BUZZER
10

R=470r/1w (LC) (O) (C) (S) (F) (D) (U)


2

G ROL
C=0.33uF/600V OL
SOL BZ SG OG H07 H05 H06 H04 H03 H02 H01
18V G
R

Car Light Door Open Door Close Slow Speed Fast Speed Down Up
CAR OVERLOAD RELAY AND BUZZER ELV- 5
OPTION : WHEN THE UML-52-EX/SP ABSENT

A A

APP. NAME : Benci


Title
APP. DATE : UML-51r_ 110AC SAFETIES AC2 SPEED
CARD TERMINAL-
. Size Document Number Rev
A4 ENG-UML-51r CONTROL-AC-2 SPEED 310806 01
CONTROLLER TERMINAL-
Date: Wednesday, October 04, 2006 Sheet 2 of 9
5 4 3 2 1
5 4 3 2 1

09 010 011 G SRI SRO SRX STX G 24V 9V 9V G COM I1-I8 G COM I1-I8 G COM I1-I8 G COM I1 - I8 G COM I1-I8 G COM I1 -I8
J4B J4B
AD AU Ng/ Digital Display J4B SW4 SW4
Group Com. SW4 SW4 SW4 01-08 SW4 01-08
Buzy Com. 0 01-08 0 0 0 0
0 J4B J4B
1 J4B 1 0 1 0
0
D
1
1 B SP
1
D SP
0
1 F
0
1
H SP1 1
0 J 1
0
L SP2 D
1

UML-52EX UML-52EX UML-52EX UML- 52EX UML-52EX UML- 52EX


ELV-5 M
SW3 SW3 SW3 SW3 SW3 SW3
SW2 SW1 1 1
1
1 A
1
0 C
1
1 E 0 G 1 I
1
0 K
1 1 0 0 1 1
1 1 1 1 0 0
Car Calls 1-8 Down Calls 1-8
I9 - I16 G COM I17 - I24 G COM I1-I8 G COM I1-I8 G COM I1-I8 G COM I1-I8 G COM I1-I8 G COM I1-I8

0010
Car Calls (Outputs 17-24 / SP) Special Port / SP1

0001
H Special Port / SP2

0011
Car Calls 1-8 ELV-5 M SW4 D UML-52EX/SP1
SW4 SW4 L
UML-52EX/SP UML-52EX/SP2
I/O I/O1 I/O2 I/O3 I/O4 I/O5 I/O6 I/O7 I/O8 I/O I/O1 I/O2 I/O3 I/O4 I/O5 I/O6 I/O7 I/O8
I/O I9 I10 I11 I12 I13 I14 I15 I16 O O1 O2 O3 O4 O5 O6 O7 O8 Floors Floors
C Floors Floors C

17-24 Floors 17l 18l 19l/RPS 20l/BZ 21l/OL 22l/ZFR 23l/OFR 24l/RFL INPUTS GN BM CD CHD Lc/As SOL - - INPUTS C18R RODR PHCR ODR Lc/As SOL - -
1-8 Floors 1C 2C 3C 4C 5C 6C/CD 7C/LC 8C/BM
OUTPUTS ZFR OFR RFL BZI TFR OL - - OUTPUTS NGR OFR RFL OR CR OL - -

0011
Car Calls (Inputs 17-24 / SP)
Down Calls 1-8 According To SW4 D
ELV-5 M UML-52EX/SP

1010
the Lobby floor

1001
Up Calls 17-24 Rear Car Calls 1CR-8CR
I/O I1 I2 I3 I4 I5 I6 I7 I8 SW3 G SW3 K
I/O Floors UML-52EX UML-52EX
Floors I17 I18 I19 I20 I21 I22 I23 I24
17-24 Floor 17c-18c/GN-19c/PS-20c/SS-21c/SOL-22c/CD-23c/LC-24c/BM I/O I/O
I1 I2 I3 I4 I5 I6 I7 I8 Floors I1 I2 I3 I4 I5 I6 I7 I8
7 Lobby Floor 1U 2U 3U 4U 5U 6U 7U 8U Floors
17- 24 Floors 17U 18U 19U 20U 21U 22U 23U 24U 1-8 Floors 1CR 2CR 3CR 4CR 5CR 6CR 7CR 8CR
6 Lobby Floor 1U 2U 3U 4U 5U 6U 7U 8D/2D Hall Calls 17-24

1011
SW3 C
5 Lobby Floor 1U 2U 3U 4U 5U 6U 7D/3D 8D/2D UML-52EX
Up Calls 9-16

0101
Rear Hall Calls 1UR-8DR

0110
4 Lobby Floor 1U 2U 3U 4U 5U -6D/4D-7D/3D 8D/2D I/O I1 I2 I3 I4 I5 I6 I7 I8 SW4 F J
Floors SW4
UML-52EX UML-52EX
3 Lobby Floor 1U 2U 3U 4U 5D -6D/4D-7D/3D 8D/2D 17-24 Floors 17d-18d/8U-19d/7U-20d/6U-21d/5U-22d/4U-23d/3U-24d/2U
I/O I1 I2 I3 I4 I5 I6 I7 I8 I/O I1 I2 I3 I4 I5 I6 I7 I8
2 Lobby Floor 1U 2U 3U 4D 5D -6D/4U-7D/3D 8D/2D Floors Floors
Car Calls (Outputs 9-16/SP)

0111
1 Lobby Floor 1U 2U 3D 4D 5D -6D/4U-7D/3U 8D/2D 9-16 Floors 9U 10U 11U 12U 13U 14U 15U 16U 1-8 Floors 1ur 2dr/8ur-3dr/7ur-4dr/6ur-5dr/5ur-6dr/4ur-7dr/3ur-8dr/2ur

UML-52EX/SP
SW4 B
B 0 Lobby Floor 1U 2D 3D 4D 5D -6D/4U-7D/3U 8D/2U B

1101
Hall Calls According The Lobby Rear Hall Calls 1UR-8UR

1110
O O1 O2 O3 O4 O5 O6 O7 O8
Floors
UML-52EX
SW3 E SW3 I
9-16 Floors 9L 10L 11l/RPS 12l/BZ 13l/OL 14l/ZFR 15l/OFR 16l/RFL UML-52EX
SP-1 Inputs SP-1 Outputs
I/O I17 I18 I19 I20 I21 I22 I23 I24 I/O I1 I2 I3 I4 I5 I6 I7 I8
GN - Generator ZFR - Zero Floor Run Floors Floors
Car Calls (Inputs 9-16/SP)
0111

BM - Lift Cancel OFR - One Floor Run 1- 8 Floors 1ur 2ur 3ur 4ur 5ur 6ur 7ur 8ur
CD - Close Door P.B RFL - Relay Failure UML-52EX/SP
SW4 B 7 Lobby Floor 1U 2D 3D 4D 5D 6D 7D 8D
CHD- Change Dirrection BZ1 - Buzzer 1 6 Lobby Floor 1U 2D 3D 4D 5D 6D 7D 8U
LC/AS - Loading Control TFR - Two Floor Run I I1 I2 I3 I4 I5 I6 I7 I8
Floors 5 Lobby Floor 1U 2D 3D 4D 5D 6D 7U 8U
SOL - Switch Overload OL - Overload Signal
RES ERVE RES ERVE 9-16 Floors 9c 10c/GN 11c/PS 12c/SS 13c/SOL 14c/CD 15c/LC 16c/BM 4 Lobby Floor 1U 2D 3D 4D 5D 6U 7U 8U
RES ERVE RES ERVE
AS - Attendant Service 3 Lobby Floor 1U 2D 3D 4D 5U 6U 7U 8U
Hall Calls 9-16
1111

SW3 A 2 Lobby Floor 1U 2D 3D 4U 5U 6U 7U 8U


UML-52EX
SP-2 Inputs SP-2 Outputs 1 Lobby Floor 1U 2D 3U 4U 5U 6U 7U 8U
I/O I1 I2 I3 I4 I5 I6 I7 I8
C18R - Open Limit Sw Rear Door NGR - Rear Door Nudging Floors
0 Lobby Floor 1U 2U 3U 4U 5U 6U 7U 8U
RODR - Safety Edge Rear Door OFR - One Floor Run 9-16 Floors 9D-10D/8U-11D/7U-12D/6U-13D/5U-14D/4U-15D/3U -16D/2U
PHCR - Photo Cell Rear Door RFL - Relay Failure
ODR- Rear Open Door P.B OR - Open Door Output
A A
LC - Loading Control CR - Close Door Output
SOL - Switch Overload OL - Overload Signal
APP. NAME : Benci
RES ERVE RES ERVE
RES ERVE RES ERVE Title
APP. DATE :
ENG-INPUT / OUTPUT MAP FOR UML-51 (Ver. 2.04 AND ON)
Size
. Document Number Rev
A4 02
ENG-INPUT / OUTPUT MAP UML-51R 310806
Date: Wednesday, October 04, 2006 Sheet 4 of 9
5 4 3 2 1
5 4 3 2 1

ELV-5 / SW-2 ELV-5 / SW1 Inductor Magnets & Shaft Switches


0=OFF 1=ON
DIP No. 0=OFF 1=ON
1 2 3 4 5 6 7 8 I3 I2 I1
FLOOR No. FINAL LIMIT SW. FSL1
0 0 0 0 0 0
1 1 0 0 0 0 1) MANUAL HALL DOORS FULL AUTOMATIC DOORS
D 2 0 1 0 0 0 D

3 1 1 0 0 0 2) PARKING WITH OPEN DOOR (NOT LOBBY) PARKING WITH CLOSE DOOR
4 0 0 1 0 0
5 1 0 1 0 0 3) SLOW SPEED INSPECTION DRIVE FAST SPEED INSPECTION DRIVE
6 0 1 1 0 0
7 1 1 1 0 0 4) WITHOUT RE LEVELING RE LEVELING FOR HYDRAULIC AND VF
8 0 0 0 1 0
9 1 0 0 1 0 5) WITHOUT PRE OPENING PRE-OPENING (VVVF CLOSE LOOP ONLY) FULS
10 0 1 0 1 0 300 mm
6 7 8 The Number Of Lift For Group Communication
11 1 1 0 1 0 Up Identification & (HI4) TSDS
12 0 0 1 1 0
Slow Down SW.
13 1 0 1 1 0 0 0 0 SIMPLEX (WITHOUT GROUP)
14 0 1 1 1 0
15 1 1 1 1 0
16 0 0 0 0 1 1 0 0 LIFT No 1
17 1 0 0 0 1
18 0 1 0 0 1
19 1 1 0 0 1 0 1 0 LIFT No 2
20 0 0 1 0 1
21 1 0 1 0 1
C 22 0 1 1 0 1 1 1 0 LIFT No 3 I3=DZ=300mm Landing C

23 1 1 1 0 1
24 0 0 0 1 1
25 1 0 0 1 1 0 0 1 LIFT No 4
26 0 1 0 1 1
27 1 1 0 1 1 Down Dirrection
28 0 0 1 1 1 1 0 1 LIFT No 5 Slow Down
29 1 0 1 1 1
Point.
30 0 1 1 1 1 Up Dirrection
31 1 1 1 1 1 0 1 1 LIFT No 6 Slow Down
AC-2 SPEED DRIVE SYSTEM 0 0
VVVF DRIVE SYSTEM 1 0 Point.
HYDRAULIC DRIVE SYSTEM 0 1 1 1 1 LIFT No 7
RES ERVE 1 1

SW/6 Should Be In On=1 Position From Ver:3.5 and On


For FDS Digital Displays .
FAILURES EXPLANATION
a/1 - INTERLOCKS BRIDGED INDICATION AFTER INSPECTION DIS-1
B
b/1 - TRAVELING TIMER OR OBSTRUCTION TIMER a
B
c/1 - DOOR INTERLOCK FAILURE
d/1 - CAR FIREMAN MODE TAKEN OUT NOT AT THE MAIN HALL FIREFIGHTER KEY f
g
b Bottom Identification (HI3) BSDS
e/1 - ONE OR MORE OF THE MAIN CONTACTORS DOSN'T RELEASE. & Slow Down SW.
f/1 - DOOR OPEN LIMIT SWITCH DIDN'T OPENED e c
g/1 - HALL PUSH BUTTON STACKED
dp - LIGHTING CONTINUOUSLY = POWER ON d FDLS
dp - WHEN FLASHING = PERMANENT SAFETIES OPENED
DIS-2
a/2 - INDUCTORS I1 or I2 STOPPED FUNCTIONING a
b/2 - PHOTO ELECTRIC EYE STOPPED ACTING
c/2 - DIESEL GENERATOR TERMINATION f
g
b
d/2 - 60 sec. CAR DELAYED ON FLOOR
e/2 - SLOW SPEED TRAVELING TIMER e c FINAL LIMIT SW. FLS2
f/2 -INDUCTOR i3 DID NOT CHANGED AFTER START
FLS3 - PIT. SWITCH FLS3
g/2 -THE LIFT DOESN'T STOPPED IN DOOR ZONE d
dp - LIGHTING CONTINUOUSLY = POWER ON
dp - WHEN FLASHING = GROUP COMMUNICATION FAILURE Size Of i1 & i2 Flags = Speed/ 6 Minimum = 100 mm
A A

APP. NAME : Benci


Title
APP. DATE :
ENG Shaft Flags, Switches, Failure List and Master DipSwitches
Size Document Number Rev
A4 UML-51r_SHAFT FLAGS,Master DipSwitches & FAILURES 02
Date: Wednesday, October 04, 2006 Sheet 5 of 9
5 4 3 2 1
1

G
18VT G SRX STX
18V
Lift Is Here Y1

Y2 09 010 011
18VT G SRX STX INT UC DC LIH LUC LDC FLC-Bn 18v SRX STX G 24V 9V 9V
AD AU
Y3 ***
Y4 18VD AU AD
SW-1 3 Floor
8 0
FLC-Bn=Decoder From Serial To
7 0
Binary 12v=High 0=Low ELV-5
6 0
5 0 Master
4 0 Card SW2 SW1
Vol 3 0
2 1
SSG4 Vol
FDS-24A 1 1 SSD-2A / SSD-2A
Option for
additional
Direction Arrows I9 - I16 G COM I17 - I24

Direct Wiring Car Calls G 18V Hall Calls


Lift Is Here
*** Regular Wires For Communication to the Car and for the Shaft.

18VT G SRX STX INT UC DC LIH LUC LDC

SW-1
2 Floor
8 0
7 0
6 0
5 0
4 0 SW-1/ FLOOR ADDRESS 1=ON FDS-24A For Car Digital Indicator
Vol 3 0 0=OFF
2 1
SSG4 Vol DIP No.
FDS-24A 1 0
1 2 3 4 5 6 7 8
FLOOR No.
0 0 0 0 0 0 0
1 1 0 0 0 0 0 * **
2 0 1 0 0 0 0
3 1 1 0 0 0 0
4 0 0 1 0 0 0
A Lift Is Here 5 1 0 1 0 0 0
A

6 0 1 1 0 0 0

18VT G SRX STX INT UC DC LIH LUC LDC


7
8
1
0
1
0
1
0
0
1
0
0
0
0
18VT G SRX STX INT UC DC LIH LUC LDC
9 1 0 0 1 0 0
10 0 1 0 1 0 0
11 1 1 0 1 0 0
SW-1
SW-1
1 Floor 12
13
0
1
0
0
1
1
1
1
0
0
0
0
8 0 8 1
7 0 14 0 1 1 1 0 0 7 0
15 1 1 1 1 0 0 6 0
6 0
16 0 0 0 0 1 0 5 0
5 0
4 0 17 1 0 0 0 1 0 4 0
3 0 18 0 1 0 0 1 0 3 0
Vol 19 1 1 0 0 1 0
Vol 2 0
SSG4 Vol Vol 2 0
SSG4 FDS-24A 1 1
20 0 0 1 0 1 0 FDS-24A 1 0
21 1 0 1 0 1 0
22 0 1 1 0 1 0
23 1 1 1 0 1 0 ** Address For The Car =Sw-1 No/8=ON Only.
24 0 0 0 1 1 0
25 1 0 0 1 1 0
26 0 1 0 1 1 0
Lift Is Here 27 1 1 0 1 1 0
28 0 0 1 1 1 0
29 1 0 1 1 1 0
18VT G SRX STX INT UC DC LIH LUC LDC 30 0 1 1 1 1 0
31 1 1 1 1 1 0

* SW-1/7 = ON Only for Rear Side Floor Each FDS Haze Car Calls Acceptance Buzzer including Volume Adjustment.
SW-1 0 Floor Indicators ,Gongs and Lanterns. SSG4 = Two Sound Serial Floor Gong including Volume Adjustment.
8 0
7 0
6 0
5 0
4 0
3 0
Vol
SSG4 Vol 2 0
FDS-24A 1 0

APP. NAME : Benci


Title
APP. DATE :
Shaft and Car Position Indicators For UML-51r
Size Document Number Rev
A4 02
ENG FDS Digital_Displays and Signalization UML-51r 020906
Date: Wednesday, October 04, 2006 Sheet 6 of 9
1
5 4 3 2 1

LIFT No 1 LIFT No 2 * The cable for group communication Should Be Suitable For (RS 485)
G 18V/1 G 18V/2 twisted and shilded,
. . Communication Cable For RS-485 . . The cable should be install separetly and far as possible from
all other wires.
(*) (*)
D D

O11 G SRI SRO G 24V 9V 9V G COM I1 O11 G SRI SRO G 24V 9V 9V G COM I1
J4A J4A
SW4 SW4
0 0
0 0
Lift No 1 Lift No 2
0 SP 0 SP
SW-1 SW-1
1 1
ELV-5 6 ON
7 OFF
ELV-5 6 OFF
7 ON
8 OFF 8 OFF
SW3 SW3
1 1
1 1 X
0
X 0
1 1

1C-8C 1DU-8D 2U-7U 1C-8C 1DU-8D 2U-7U


I3 I9-I16 G COM I17-I24 G COM I1-I8 I3 I9-I16 G COM I17-I24 G COM I1-I8

C C94. . C94 C

GN . . GN
HFK=Hall Fire Fighter Key
DGS HFK DGS=Diesel Generator
Contact.
5A 5A
18V/1 . 18VT . . 18VT . . 18V/2 G .
G . G . .G .G Remarks.
18VT Is The Common Power Supply For all All the lamps and the hall calls should be Referred
Hall Push Buttons to the 18VT.

18VT . REAR HALL CALLS 18V/1 REAR CAR CALLS This drawing is a sample for full collective 8
18V/1
. CAR CALLS
011
DOWN CALLS and A.P.B FOR SELECTIVE DOORS . FOR SELECTIVE DOORS floors including special port.

B .
8C .
8D
UP CALLS
.
8DR
.
8CR For the Options of the selective rear side
inputs /outputs please refer the I/O Map.
B

.
7C .
7D .
7U .
7DR
.
7CR In the same way is possible to connect more
Lifts in a group.(Set the lift number by the
SW-1 switches on the Master Card)
18V1 and NSR Terminals Regarding For LIFT
NO1 In This Sample.
.
3U
When Existing Rear Hall Calls in Bought Lifts,
Please Jumper The Hall Calls Between The
.
2C
.
2D
.
2U
.
2DR
.
2CR
Controllers
All Common Hall Calls for Bought Lifts, Sould
.
1C .
1DU
.
1DUR .
1CR
Be Jumper Between The Controllers, Do Not
Jumper a Privet Hall Call To Other
BUSY LAMPS Controller.
NSR FOR APB .
NSR
A
.G A

APP. NAME : Benci


Title
APP. DATE :
UML-51r_8 FL_FULL COLLECTIVE+SP DUPLEX .
CARD TERMINAL -
. Size Document Number Rev

CONTROLLER TERMINAL . . A4 ENG_UML-51r_Group Hall Calls 310806 02


Date: Wednesday, October 04, 2006 Sheet 7 of 9
5 4 3 2 1