Step 2 : Identify the Seismic Zone Factor Using NSCP 2015
According to Page 2-188, Section 208.4.4.1, Figure 201.1, the location of the building is at Davao
City, Philippines and it is on the Zone 4.
According to Page 2-189, Section 208.4.4.1 table 208.3 Seismic Zone Factor, the Zone is 4 therefore
0.40
VOLCANIC HAZARDS ASSESSMENT
All hazard assessments are based on the available susceptibility maps and the coordinates of
the user’s selected location.
Depending on the basemaps used and methods employed during mapping, discrepancies
may be observed between location of hazards or exposure information and actual ground
observations.
According to Page 2-185, Section 208.4.2, Table 208.1, the seismic factor under.
-Special Occupancy.
According to Page 2-188, Section 208.4.4.2 Seismic Source Type, Table 209-4, it is
Type A because it can generate a 7 to 9 magnitude earthquake.
Step 7 : Solve for Near – Source Factor Na and Nv
According to Page 2-207, Section 208.4.4.3, Table 208.5 the seismic sources type is A and the
distance from the nearest fault line is 8.4 km (Central Davao Fault System: New Carmen Fault)
therefore the Na is 1.0.
According to Page 2-207, Section 208.4.4.3, Table 208.5 the seismic sources type is A and the
distance from the nearest fault line is 8.4 km (Central Davao Fault System: New Carmen Fault)
therefore the Nv is 1.2.
Step8 : Solve for the Seismic Response Coefficients Ca and Cv
According to Page 2-207, Section 208.4.4., Table 208.7, the soil profile type is SD and it is on
Zone 4, therefore we will use Ca = 0.44Na.
According to Page 2-207, Section 208.4.4., Table 208.8, the soil profile type is SD and it is on
Zone 4, therefore we will use Cv = 0.64Na.
STRUCTURAL DESIGN
According to Page 2-224, Table 208-11B, the structural system is Building Frame Systems
Ct: Ct = 0.0731