Navodila Za Termostat TLK48
Navodila Za Termostat TLK48
TLK 48 1
1.1
1.2
2
2.1
INSTRUMENT DESCRIPTION
GENERAL DESCRIPTION
FRONT PANEL DESCRIPTION
PROGRAMMING
FAST PROGRAMMING OF THE SET POINT
2.2 SELECTION OF THE CONTROL STATE AND
PARAMETERS PROGRAMMING
MICROPROCESSOR-BASED 2.3 PARAMETERS PROGRAMMING LEVELS
2.4 CONTROL STATE
DIGITAL 2.5 ACTIVE SET POINT SELECTION
3 INSTALLATION AND USE WARNING
2 - PROGRAMMING
Example 2: It’s required that the instrument visualises 10° whilst the
value effectively measured is 0°, but, at 500° it has to visualise a
value higher of 50° (550°).
Therefore : M1=0 ; D1=10 ; M2=500 ; D2=550
“rot” = (550 - 10) / (500 - 0) = 1,08
“OFSt” = 550 - (1,08 x 500) = 10
4.4 – NEUTRAL ZONE ON/OFF CONTROLLER (1rEG - 2rEG) In order to obtain a good stability of the process variable, in case of
All the parameters referred to the Neutral Zone ON/OFF control are fast processes, the cycle time “tcr1” has to have a low value with a
contained into the group “]rEG”. very frequent intervention of the control output.
This type of control is obtainable when 2 outputs are programmed In this case it’s recommended to use a solid state relay (SSR) to
respectively as 1rEG and 2rEG and the par. “Cont” = nr . drive the actuator.
The Neutral Zone control is used to control plants where there is an The Single Action PID control algorithm needs the programming of
element which causes a positive increment (ex. Heater, humidifier, the following parameters :
etc.) and an element which causes a negative increment (ex. "Pb" – Proportional Band
Cooler, de-humidifier, etc). "tcr1" – Cycle time of the output 1rEG
The control functioning works on the programmed outputs "Int" – Integral Time
depending on the measure, on the active Set Point “SP” and on the "rS" – Manual Reset (if “Int” =0 only)
hysteresis "HSEt". "dEr" – Derivative Time
The controller works in the following way : it deactivates the outputs “FuOC” - Fuzzy Overshoot Control
when the process value reaches the Set Point and it activates the This last parameter permits to avoid the variable overshoots at the
output 1rEG when the process value goes below value [SP - HSEt], start up of the process or at the changing of the Set Point.
or it activates the output 2rEG when the process value goes above It’s worth to remember that a low value on this parameter reduces
[SP + HSEt]. the overshoot while a high value increase it.
For the band alarms, the example of the low alarm is applicable to
the low threshold ("AL1L") while the example of the high alarm is
applicable to the high threshold ("AL1H").
7 - TECHNICAL DATA
TLK48 a b c d ee
a : POWER SUPPLY
A = 24 VAC
C = 115 VAC
D = 230 VAC
b : INPUT
C = thermocouples (J, K, S, I.R), mV, thermoresistances (Pt100)
E = thermocouples (J, K, S, I.R.), mV, thermistors (PTC, NTC)
I = thermocouples (J, K, S, I.R.), mV, normalized signals 0/4..20 mA
V = termocoppie (J, K, S, I.R.), mV, normalized signals 0/1..5V,
0/2..10V.
c : OUTPUT OUT1
R = Relay
O = 20 mA/14 VDC for SSR
d : OUTPUT OUT2
R = Relay
O = 20 mA/14 VDC for SSR