Determining The Relative Effectiveness of Islanding Detection Methods Using Phase Criteria and Nondetection Zone - 00875495
Determining The Relative Effectiveness of Islanding Detection Methods Using Phase Criteria and Nondetection Zone - 00875495
3, SEPTEMBER 2000
Fig. 3. Block diagram representation of PV system and load after the switch
is opened.
TABLE I
PHASE CRITERIA FOR SEVERAL ISLANDING PREVENTION METHODS
(FROM [6], [7])
Fig. 4. Mapping of the NDZ of the AFD (frequency bias) method of islanding
prevention in a load parameter space, for three different values of load
resistance. The NDZ of the SMS method for R = 14:4
is also shown.
PJD, the worst case loads (that is, those that lead to the longest
run-on times) are predicted to be loads with a relatively low real
power consumption (small ), a small value of , and a large
Fig. 6. Mapping of the NDZ of the PJD method of islanding prevention in a
load parameter space, obtained using phase criteria. In these calculations, = value of . This may be expressed in terms of the quality factor,
2 [3]. or -factor, of the circuit. (This is not the same as the
reactive power consumption of the load, denoted or .)
The -factor is given by
(2)
and is the ratio of the amount of energy stored in the load’s re-
active elements to the amount of energy dissipated in the load’s
resistance. (For example, for , there is twice as much en-
ergy stored in the and of the load as is being dissipated in
.) Loads that are near resonance at and have a high -factor
are the ones that cause difficulty in islanding detection.
It is clear from the phase criteria and the NDZ mappings that
the steady-state frequency of depends on the load pa-
Fig. 7. Mapping of the NDZ of the SFS method (AFDPF in the figure). For rameters. Unfortunately, the level of real or reactive power mis-
comparison, the NDZ of AFD is also shown, as are the NDZ’s of SMS and the match is not uniquely determined by load parameters. Specifi-
OFR/UFR.
cally, the reactive power consumption of the load is given by
TABLE II
PARAMETER VALUES FOR NDZ MAPPING EXPERIMENT
Fig. 12. Results of islanding testing on the same PCS used in the tests in
Fig. 11, but now with varying L(C = C ).
when the load has a unity power factor but is not purely resis-
tive. In these tests, . Notice that, as the -factor which is the phase criterion given in Table II, with
of the RLC load increases (that is, decreases and increases, .
maintaining near resonance at the line frequency), the run-on
time of the PCS also increases. The scatter in run-on times is REFERENCES
primarily due to experimental variability, as discussed previ- [1] A. Kitamura, M. Okamoto, F. Yamamoto, K. Nakaji, J. Matsuda, and K.
ously. The observed results are consistent with the predictions Hotta, “Islanding phenomenon elimination study at Rokko Test Center,”
suggested by the results in Fig. 4. in Proceedings of the 1st IEEE World Conference on Photovoltaic En-
ergy Conversion, 1994, pp. 759–762.
[2] IEEE-P929: Recommended Practice for Utility Interface of Photo-
V. CONCLUSION voltaic (PV) Systems, Draft 9 of IEEE Prestandard P929, December
1998.
This work demonstrates that phase criteria (expressions de- [3] R. A. Jones and T. R. Sims, “Investigation of potential islanding of
rived from the conditions at which the PLL of the PV PCS de- dispersed photovoltaic systems,” Sandia National Laboratories, Albu-
querque, NM, Sandia National Laboratories Report SAND87-7027,
tects a zero phase error between the PV output current and ter- 1988.
minal voltage) are highly useful in determining the relative merit [4] H. Kobayashi, K. Takigawa, and E. Hashimoto, “Method for preventing
of islanding prevention methods that rely on a frequency change mismatch islanding phenomenon on utility grid with a number of small
scale PV systems,” in Proceedings of the 21st IEEE Photovoltaic Spe-
for islanding detection. In spite of their simplicity, the phase cri- cialists Conference, 1991, pp. 695–700.
teria predict the ranges of loads that lead to detection failure with [5] S. Yuyuma, T. Ichinose, K. Kimoto, T. Itami, T. Ambo, C. Okado, K.
good accuracy. In addition, clear evidence is provided that the Nakajima, S. Hojo, H. Shinohara, S. Ioka, and M. Kuniyoshi, “A high-
speed frequency shift method as a protection for islanding phenomena of
SFS method is the most effective islanding prevention method utility interactive PV systems,” Solar Energy Materials and Solar Cells,
among those discussed here. Finally, this work also establishes vol. 35, pp. 77–486, 1994.
clearly that nondetection limited range of loads can give a mis- [6] M. Ropp, M. Begovic, and A. Rohatgi, “Prevention of islanding in grid-
connected photovoltaic systems,” Progress in Photovoltaics, Summer
leading picture of the effectiveness of an islanding prevention 1999, to be published.
method. Mappings should be made in a load parameter space [7] M. Ropp, “Design issues for grid-connected photovoltaic systems,”
such as the space used here, or several power mis- Ph.D. dissertation, Georgia Institute of Technology, Atlanta, GA,
December 1998.
match mappings should be made with different values of RLC. [8] G. Kern, “SunSine300: Utility interactive AC module anti-islanding test
Furthermore, in order to obtain an accurate test of the effec- results,” in Proceedings of the 26th IEEE Photovoltaic Specialists Con-
tiveness of an anti-islanding method that depends on frequency ference, 1997, pp. 1265–1268.
[9] G. Kern and Ascension Technology, Inc., “Status report #6: Sandia anti-
change for islanding detection, it is suggested that the PCS be islanding investigation,”, contract report to Sandia National Laborato-
tested with loads with high values of the -factor. The data pre- ries, May 27, 1998.
sented here indicate that tests should include a sweep of
over the range 0.9 to 1.1, in order to ensure that the NDZ is
accurately located. Michael E. Ropp (S’94–M’99) received the Ph.D. in EE from the Georgia In-
stitute of Technology in December, 1998. He is currently an Assistant Professor
of Electrical Engineering at South Dakota State University. His research inter-
APPENDIX ests include power electronics, renewable energy, and electric vehicles.
CURSORY DESCRIPTION OF THE DERIVATION OF THE PHASE
CRITERION FOR AFD
AFD is implemented by adding short zero or “dead” times Miroslav Begovic (S’87–M’89–SM’92) received the Ph.D. in EE from Virginia
into the PV system output current, as shown in Fig. 13. These Tech in 1989. He is presently an Associate Professor in the School of Electrical
and Computer Engineering at Georgia Institute of Technology. Dr. Begovic’s
dead times have length . The AFD waveform has neither odd research activities are in computer applications in power systems monitoring
nor even symmetry; therefore, there will be a phase shift in the and control, and PV systems.
296 IEEE TRANSACTIONS ON ENERGY CONVERSION, VOL. 15, NO. 3, SEPTEMBER 2000
Ajeet Rohatgi (M’78–SM’86–F’91) received the Ph.D. degree in metallurgy R. H. Bonn Sr. is currently the PV balance of systems Project Leader for the
and material science from Lehigh University, Bethlehem, PA, in 1977. He is a Sandia National Laboratories PV program. He is responsible for developing
Regents’ Professor and a Georgia Power Distinguished Professor in the School standardized methods for evaluating PV PCS’s and for developing a laboratory
of Electrical Engineering. He is the Founding Director of the University Center that supports PV PCS manufacturers. Dr. Bonn has over 30 years’ experience in
of Excellence for Photovoltaic Research and Education at Georgia Tech. His re- instrumentation and measurements.
search interests include design and fabrication of high-efficiency silicon solar
cells; performance and reliability of PV systems; silicon MOS devices; semi-
conductor material and device characterization; defects and recombination in
semiconductors; and MBE and MOCVD growth of compound semiconductors.