Vacon NXN Nfe User Manual Dpd01172c Uk
Vacon NXN Nfe User Manual Dpd01172c Uk
ac drives
2. Before taking any commissioning actions, read carefully the safety instructions
in Chapter 1.2
3. Before the mechanical installation, check the minimum clearances around the
unit and check the ambient conditions in Chapter 5
4. Check the size of the supply cable/bus bar, DC output cable/bus bar, and mains
fuses, DC fuses and check the cable connections.
5. Follow the installation instructions, see Chapter 5.
Vacon Ltd is not responsible for the use of the Non-Regenerative Front End against
the instructions.
vacon 2
CONTENTS
INDEX
1 SAFETY
2 EU DIRECTIVE
3 RECEIPT OF DELIVERY
4 Non-REGENERATIVE FRONT END UNIT (NFE)
5 INSTALLATION
6 CONTROL KEYPAD
7 APPENDICES
The User's Manual will provide you with the necessary information about the installation, commissioning
and operation of VACON® NX Non-Regenerative Front End. We recommend that you carefully study these
instructions before powering up the Non-Regenerative Front End for the first time.
In the Non-Regenerative Front End Application Manual you will find information about the Non-
regenerative Front End application. Should that application not meet the requirements of your process,
please contact the manufacturer for information on special application.
This manual is available in both paper and electronic editions. We recommend you to use the electronic
version if possible. If you have the electronic version at your disposal, you will be able to benefit from the
following features:
The manual contains several links and cross-references to other locations in the manual, which makes it
easier to move around in the manual. The reader can thus easily find and check things.
The manual also contains hyperlinks to web pages. To visit these web pages through the links, you must
have an internet browser installed on your computer.
This manual is applicable only for Non-Regenerative Front End unit, AC choke and optional components
that are introduced in this manual.
Table of contents
Document code: DPD01172C
Date edited: 30.01.2019
1. Safety ............................................................................................................................ 6
1.1 Warnings ........................................................................................................................................ 6
1.2 Safety Instructions ........................................................................................................................ 6
1.3 Grounding ...................................................................................................................................... 6
1.4 Warning symbols ........................................................................................................................... 7
2. EU directive ................................................................................................................... 8
2.1 CE marking .................................................................................................................................... 8
2.2 EMC directive ................................................................................................................................. 8
2.2.1 Introduction...........................................................................................................................8
2.2.2 Technical criteria..................................................................................................................8
2.2.3 VACON® Non-Regenerative Front End EMC classification ...............................................8
2.2.4 ..........................................................................8
3. Receipt of delivery ....................................................................................................... 10
3.1 Type designation code for the NFE unit ..................................................................................... 10
3.2 Type designation code for the AC choke .................................................................................... 12
3.3 Storage ......................................................................................................................................... 12
3.4 Maintenance ................................................................................................................................ 12
3.5 Lifting the modules ..................................................................................................................... 13
3.6 Lifting the AC choke .................................................................................................................... 14
3.7 Warranty ...................................................................................................................................... 14
4. Non-Regenerative Front End (NFE) .............................................................................. 15
4.1 Introduction ................................................................................................................................. 15
4.2 Non-Regenerative Front End enclosure sizes .......................................................................... 17
4.3 Non-Regenerative Front End unit technical data ..................................................................... 18
4.4 Application ................................................................................................................................... 19
4.5 Diagrams...................................................................................................................................... 19
4.5.1 Connection between control unit and power unit ............................................................19
4.6 Non-Regenerative Front End power ratings ............................................................................. 20
4.6.1 VACON® NXN; DC voltage 460 800V .................................................................................20
4.6.2 VACON® NXN; DC voltage 640 1100V ...............................................................................20
4.7 Non-Regenerative Front End unit Dimensions ...................................................................... 20
4.8 AC choke Dimensions .............................................................................................................. 20
4.9 Non-Regenerative Front End Fuse selection ......................................................................... 21
4.9.1 Introduction.........................................................................................................................21
4.9.2 Fuses; mains voltage 380 690V ........................................................................................21
4.9.2.1 AC fuses........................................................................................................................21
4.9.2.2 DC fuses .......................................................................................................................21
4.10 Non-Regenerative Front End unit Circuit breaker selection ................................................ 21
4.11 Non-Regenerative Front End unit Main contactor ................................................................. 22
4.12 Pre-Charging and start up.......................................................................................................... 22
1. SAFETY
1.1 Warnings
1 The components of the power unit circuit are live when the Non-
Regenerative Front End is connected to AC supply. Coming into contact
with this voltage is extremely dangerous and may cause death or severe
injury. The control unit is isolated from mains potential.
2 The control I/O-terminals are isolated from the mains potential. Howev-
er, the relay outputs and other I/O-terminals may have dangerous control
! voltage present even when the Non-Regenerative Front End is discon-
nected from the AC supply.
WARNING 3 Do not touch the components on the circuit boards. Static voltage dis-
charge may damage the components.
4 Do not perform any voltage withstand tests on any part of the Non-
Regenerative Front End. There is a certain procedure according to which
the tests must be performed. Ignoring this procedure may result in dam-
aged product.
1.3 Grounding
The Non-Regenerative Front End unit and AC choke must always be grounded with an grounding
conductor connected to the grounding terminal.
1
vacon 7 Safety
= Dangerous voltage
= General warning
WARNING
NOTE! You can download the English and French product manuals with applicable safety, warning
and caution information from https://www.danfoss.com/en/service-and-support/.
REMARQUE Vous pouvez télécharger les versions anglaise et française des manuels produit
2. EU DIRECTIVE
2.1 CE marking
The CE marking on the product guarantees the free movement of the product within the EEA (Euro-
pean Economic Area). It also guarantees that the product complies with applicable directives (for
example, the EMC directive and other possible so-called new method directives). VACON® NX Non-
Regenerative Front End carries the CE label as a proof of compliance with the Low Voltage Directive
(LVD) and the Electro Magnetic Compatibility (EMC) directive. SGS FIMKO has acted as the Notified
Body.
The compliance of VACON® NX Non-Regenerative Front End with the EMC directive is verified with
Technical Construction Files (TCF) and checked and approved by SGS FIMKO, which is a Notified
Body. The Technical Construction Files are used to authenticate the conformity of VACON® NX Non-
Regenerative Front End with the Directive because it is impossible to test such a large product fami-
ly in a laboratory environment and because the combinations of installation vary greatly.
Class T:
Class T equipment have a small earth leaking current and can be used with floating DC input.
Warning: This product is of the restricted sales distribution class according to IEC 61800-3. In resi-
dential areas, this product may cause radio interference in which case the user may be required to
take adequate measures.
2.2.4
The following page presents the photocopy of the Manufacturer's Declaration of Conformity assuring
the compliance of VACON® NX Non-Regenerative Front End with the EMC-directives.
2
vacon 9 EU directive
3. RECEIPT OF DELIVERY
VACON® NX Non-Regenerative Front End has undergone scrupulous tests and quality checks at the
factory before they are delivered to the customer. However, after unpacking the product, check that
no signs of transportation damage are to be found on the product and that the delivery is complete
(compare the type designation of the product to the codes below, see Figure 3-1 and Figure 3-2).
Should the product have been damaged during the shipping, please contact primarily the cargo in-
surance company or the carrier.
If the delivery does not correspond to your order, contact the supplier immediately.
NOTE! Delivery does NOT include any auxiliary devices which are needed for proper operation (the
AC or DC fuses, the fuses bases, the main contactor or circuit breaker etc.) The customer must take
care of them.
3
vacon 11 Receipt of delivery
Figure 3-1. Type designation code for the Non-Regenerative Front End.
3.3 Storage
If VACON® NX Non-Regenerative Front End is to be stored before use, make sure that the ambient
conditions are acceptable:
Storage temperature °C
Relative humidity <95%, no condensation
3.4 Maintenance
All technical devices, drives as well, need a certain amount of care-taking and failure preventive
maintenance. To maintain trouble-free operation of the VACON® NX Non-Regenerative Front End,
environmental conditions, as well as load, line power, process control, etc. have to be within specifi-
cations, determined by manufacturer.
If all conditions are in accordance with the manufacturer's specifications, there are no other con-
cerns, but to provide a cooling capacity high enough for the power- and control circuits. This re-
quirement can be met by making sure, that the cooling system works properly. Operation of cooling
fans and cleanness of the heat sink should be verified regularly.
Regular maintenance is recommended to ensure trouble free operation and long lifetime of VACON®
NX Non-Regenerative Front End. At least the following things should be included in the regular
maintenance.
3
vacon 13 Receipt of delivery
It may also be necessary to check the tightening torques of terminals at certain intervals.
It is also recommended to record all actions and counter values with dates and time for follow up of
maintenance. It may also be necessary to check the tightening torques of terminals at certain inter-
vals.
The lifting equipment must be able to carry the weight of the module.
The manufacturer shall in no event and under no circumstances be held responsible for damages
and failures resulting from misuse, wrong installation, unacceptable ambient temperature, dust,
corrosive substances or operation outside the rated specifications.
The Manufacturer's warranty period is 18 months from the delivery or 12 months from the commis-
sioning whichever expires first (General delivery terms NL92/Orgalime S92).
The local distributor may grant a warranty time different from the above. This warranty time shall be
specified in the distributor's sales and warranty terms. The manufacturer assumes no responsibility
for any other warranties than that granted by the manufacturer itself.
In all matters concerning the warranty, please contact your distributor first.
3
vacon 15 Non-Regenerative Front End (NFE)
3 3
2 2 2
* alternative
Common DC bus 2 2 2 2
3 3 3 2
CLOSE
25
-RO2
26 24
4
vacon 17 Non-Regenerative Front End (NFE)
tions ture L
4
vacon 19 Non-Regenerative Front End (NFE)
4.4 Application
The VACON® NX Non-Regenerative Front End needs a special application. The unit is delivered with
that application. If application code is needed please contact please contact the manufacturer. More
information about application can be found from this manual.
4.5 Diagrams
4.5.1 Connection between control unit and power unit
The communication connections between the Non-Regenerative Front End power unit and the con-
trol unit is established using serial cable, Figure 4-4. The control unit is located under the front cov-
er of the power unit. The control unit cannot place outside of the power unit.
For dimensions of NXN units, see Table 4-4 and AC choke Table 4-5.
For dimensions of NXN unit, see Table 4-4 and AC choke Table 4-5.
4
vacon 21 Non-Regenerative Front End (NFE)
Module AC fuses
Note: All fuses are blade type. If some other type is needed please contact your nearest distributor.
4.9.2.2 DC fuses
Module DC fuses
Module DC fuses
Note: All fuses are flush-end type. If some other type is needed please contact your nearest distributor.
fuses. A circuit-breaker can be used without a main contactor. The circuit-breakers shown are suit-
able for equipment rated at 380 690 V.
4.13 Paralleling
The power of the input group can be increased by connecting several Non-Regenerative Front End
units in parallel. No communication between the units is required; they work independently.
Each Non-Regenerative Front End unit connected in parallel must have its own short-circuit protec-
tion on AC and DC sides. The fuses are selected in accordance with Section 4.9. When paralleling,
attention must be paid to the sufficient short-circuit capacity of the system.
The derating of Non-Regenerative Front End units connected in parallel is 5% of the DC power; this
should be taken into account when selecting the input unit.
If a device is to be isolated from the AC and DC voltages, and other Non-Regenerative Front End
units connected in parallel are also to be used, separate isolators are required in the AC input and
DC output. The AC input can be isolated using a compact circuit-breaker, an ordinary circuit-breaker
or a fuse switch. Contactors are not suitable for isolating the AC input because they cannot be locked
in the safe position. The DC output can be isolated using a fuse switch. A load isolation switch or
safety isolation switch can be used for this. The device can also be connected to mains even when
the other devices connected in parallel are already connected and running. After this, the device can
be connected to the intermediate circuit.
4
vacon 23 Non-Regenerative Front End (NFE)
Note: Parallel connection means that the AC supply of more than one units connected together from DC link is
coupled with the same supply transformer.
110
100
90
Loadability, %
80 Loadability %
70
60
50
0 10 20 30 40 50 60
Ambient temperature, ºC
4
vacon 25 Non-Regenerative Front End (NFE)
120
100
80
Loadability, %
60 Loadability %
40
20
0
0 500 1000 1500 2000 2500 3000 3500
Installation altitude, m
102
100
98
96
Loadability, %
94
Loadability %
92
90
88
86
84
0 500 1000 1500 2000 2500
Installation altitude, m
Note: If higher installation altitude than 3,000 m is required please contacts your nearest distributor to get
more information.
4
vacon 27 Installation
5. INSTALLATION
5.1 Mounting
The equipment mounting must be sturdy enough to carry the weight of the equipment. The enclo-
sure class of the equipment will depend on the mounting and solutions to be used. The equipment
mounting must provide sufficient shielding for contact of the live parts (IP2x). The installation and
mounting must comply with local laws and regulations.
5.1.1 Non-Regenerative Front End Unit
The Non-Regenerative Front End can be mounted in a vertical position on the back plane of a cubi-
cle. Enough space must be reserved around the Non-Regenerative Front End to ensure sufficient
cooling, see Figure 5-5. Follow the minimum dimensions for installation, see Table 5-1. Required
cooling air capacity and minimum air holes on the switchgear, see Table 5-2. Also make sure that
the mounting plane is relatively even. The Non-Regenerative Front End is fixed with four bolts, Fig-
ure 5-1.
5.1.2 AC choke
The AC choke can only be mounted in a vertical position on the floor of a cubicle. Enough space must
be reserved around the AC choke to ensure sufficient cooling, see Figure 5-7. Follow the minimum
dimensions for installation, see Table 5-3. Required cooling air capacity and minimum air holes on
the switchgear, see Table 5-4. Also make sure that the floor is relatively even. AC choke must be at-
tached properly so that it will not be able to move.
AC choke can be mounted so that the connectors face forward or so that they face to the side. Figure
5-2 presents a mounting where the connectors face forward. Figure 5-3 presents a mounting where
the connectors face to the side. This mounting is recommended if the Non-Regenerative Front End
units are parallel connected. In this case it must be assured that the connectors face to the same
direction and that there is enough space between the connectors and the AC choke.
5
vacon 29 Installation
5.2 Cooling
5.2.1 Non-Regenerative Front End unit
Enough free space must be left around the Non-Regenerative Front End unit to ensure sufficient air
circulation and cooling. You will find the required dimensions for free space in the table below. You
will find the required cooling air, minimum air holes and heat dissipation in the Table 5-2.
When planning the cooling for the space, take into consideration that the Non-Regenerative Front
End unit heat loss is approx. 1% of the nominal capacity. Air flow, see Figure 5-6.
5
vacon 31 Installation
5.2.2 AC choke
Enough free space must be left around the AC choke to ensure sufficient air circulation and cooling.
You will find the required dimensions for free space in the table below. You will find the required
cooling air, minimum air holes and heat dissipation in the Table 5-4.
When planning the cooling for the space, take into consideration that the AC choke heat loss is ap-
prox. 0.5% of the nominal capacity.
Air outlet gaps must be situated on top of the cabinet. The minimum effective air outlet area per unit
frame is given in Table 5-2 and Table 5-4. The cooling arrangements inside the cabinet must be such
that they prevent hot output air from mixing with the incoming fresh air (see Chapter 5.2.4).
The ventilation gaps must fulfill the requirements set by the selected IP class. The examples in this
manual apply to protection class IP21.
During operation, air is sucked in and circulated by a fan blower at the bottom of the power unit. If
the power unit is placed in the upper part of the cabinet, the fan blower will be in the mid of the cabi-
net, at the height of the upper ventilation grid. In case of the AC choke is installed below the Non-
Regenerative Front End unit air inlet 1.1 in Figure 5-8 cannot be used.
5
vacon 33 Installation
1.1
1.2
A. Install a closed air duct from the power unit to the outlet on top of the enclosure (A in
figures below).
B. Install shields in the gaps between the power unit and the cabinet walls (B in figures
below). Place the shields above the air outlet gaps at the sides of the module.
The sheet metal airflow guides (deflectors) prevents air circulation between different sections of the
equipment. The shield guides in prevent air circulation inside a section. The exhaust air holes must not
be covered, nor must anything be placed above them to stop the free exit of warm air from inside the
equipment. The cooling air intake holes must not be blocked in any way.
The materials used for preventing the circulation of air inside the equipment must be fire-restraining.
The edges must be sealed to prevent the formation of gaps. When the deflectors are made according to
the instructions, no separate cooling fan is required.
NOTE! The deflectors must be installed above the air intake holes on the top (in the front) of the unit.
NOTE! If a flat roof is used, mount a V-shaped air guide on the underside of the roof to direct the air
flow horizontally. See Figure 5-10.
5
vacon 35 Installation
Terminal s for
supp ly ca bles
5.3.2 DC connection
The DC connection of the Non-Regenerative Front End unit is connected to the terminals at the top,
see Figure 5-13. The terminals are marked as B+ for connection to DC+ and B- for connection to DC-
. The DC connection must be protected using DC fuses, see Section 4.9. The terminal dimensions are
shown in Appendix 7-6.
The units are suitable for use on a circuit capable of delivering not more than 100,000 rms
symmetrical amperes, 600 V maximum, or equivalent when protected by class J, T or
Semiconductor fuses.
The tightening torques of the terminals are given below in Table 5-1.
5
vacon 37 Installation
Control cable
tightening
torque: 0.4 Nm
5
vacon 39 Installation
6. CONTROL KEYPAD
The control keypad is the link between VACON® NX Non-Regenerative Front End and the user. The
control keypad features an alphanumeric display and indicators for the status (READY, RUN, STOP,
ALARM, FAULT) and four indicators for the active menu (REF, MON, PAR, FLT). There are also three
Status Indica green red).
The control information, i.e. the menu number, description of the menu or the displayed value and
the numeric information are presented on three text lines.
The navigation wheel is used for navigating on the panel display. The wheel has two separate func-
tions;
- rotating the wheel e.g. for changing parameter value (12 steps / round)
- pressing the wheel e.g. for accepting the new value.
6
vacon 41 Control keypad
6.1 Navigation
READY RUN STOP ALARM FAULT READY RUN STOP ALARM FAULT
REFERENCE
MENU REF REF
Displays the MON MON
keypad reference
value PAR PAR
regardless of PUSH
the selected FLT Hz FLT Hz
control place. FWD REV I/O KEYPAD BUS
FWD REV I/O KEYPAD BUS
ROTATE
READY RUN STOP ALARM FAULT READY RUN STOP ALARM FAULT
MONITORING REF REF
MENU MON MON
In this menu
you can PAR PAR
browse the
monitoring FLT PUSH FLT
values.
FWD REV I/O KEYPAD BUS FWD REV I/O KEYPAD BUS
ROTATE
READY RUN STOP ALARM FAULT READY RUN STOP ALARM FAULT
PARAMETER REF
MENU REF
In this menu MON MON
you can
browse and PAR PAR
edit the
parameters. FLT PUSH FLT
FWD REV I/O KEYPAD BUS FWD REV I/O KEYPAD BUS
ROTATE
READY RUN STOP ALARM FAULT READY RUN STOP ALARM FAULT
Alternates
in the display
Browse
M1.1 - M1.20
Figure 6-2. Monitoring menu
Code Parameter Scale Unit Description
6
vacon 43 Control keypad
Alternates
in the display
Digital outputs
Code Parameter Min Max Default Unit Description
Analog outputs
Code Parameter Min Max Default Unit Description
NFE parameters
Code Parameter Min Max Default Unit Description
6
vacon 45 Control keypad
READY RUN STOP ALARM FAULT READY RUN STOP ALARM FAULT
REF REF
MON MON
PAR PAR
FLT FLT
FWD REV I/O KEYPAD BUS Push FWD REV I/O KEYPAD BUS
Browse
faults 1-9
READY RUN STOP ALARM FAULT READY RUN STOP ALARM FAULT
REF REF
MON MON
PAR PAR
FLT FLT
Push
FWD REV I/O KEYPAD BUS FWD REV I/O KEYPAD
Browse
for hours (H),
minutes (M)
and seconds (S)
Figure 6-4. Fault history menu
Note! The whole fault history can be cleared by pressing STOP button for 5 sec time
when the drive is stopped and fault history menu is selected in the display.
Note! If STOP button is pressed for 5 sec and no any menu is selected in the display fac-
tory reset is done. Factory reset set all parameters to default values!
S1.1 API SW ID
S1.3 Power SW ID
S1.5 Application SW ID
6
vacon 47 Appendices
7. APPENDICES
7
vacon 49 Appendices
Appendix 7-3. Circuit diagram for 12- pulse solution with NFE.
7
vacon 51 Appendices
IL
Enclosure Type DC terminal AC Terminal
[A]
6 x 40
40
13
13
16 17
35 38
PE: M8×25
Document ID:
Vacon Ltd
Member of the Danfoss Group DPD01172C
Runsorintie 7 Rev. C
65380 Vaasa
Finland Sales code: DOC-USERNXNNFE+DLUK