Taihan Calculation
Taihan Calculation
for
TAIHAN KUWAIT
Prepared By:
AL AHLIA
AL AHLIA
11-05-2023
FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
hazem TAIHAN KUWAIT
heaven Page 2
General Data
Project Title: TAIHAN KUWAIT Project File Name: TAIHAN KUWAIT.fiw
Designed By: AL AHLIA Date: 11-05-2023
Code Reference: NFPA 13 / 14 Approving Agency: KFF
Client Name: TAIHAN KUWAIT Phone:
Address: BLOCK 21, MINA ABDULLA City, State Zip Code: KUWAIT
Company Name: AL AHLIA Representative: ENG. ALI BAKOOR
Company Address: City And State:
Phone:
Building Name: TAIHAN KUWAIT FIBER OPTICS
Building Owner:
CABLE FACTORY
Contact at Building: Phone at Building:
Address Of Building: MINA ABDULLA City, State Zip Code:
Project Data
Description Of Hazard: Ordinary 2 Sprinkler System Type: Wet
Design Area Of Water Application: 1500 ft² Maximum Area Per Sprinkler: 130 ft²
Default Sprinkler K-Factor: 5.60 K Default Pipe Material: SCHED 40 WET STEEL
Inside Hose Stream Allowance: 50.00 gpm Outside Hose Stream Allowance: 0.00 gpm
In Rack Sprinkler Allowance: 0.00 gpm
Sprinkler Specifications
Make: Model:
Size: Temperature Rating: 0 F
Sprinkler Summary
Sprinkler System Type: Wet
Specified Area Of Application: 1500.00 ft²
Minimum Desired Density: 0.150 gpm/ft²
Application Average Density: 0.589 gpm/ft²
Application Average Area Per Sprinkler: 107.14 ft²
Sprinkler Flow: 884.08 gpm
Average Sprinkler Flow: 63.15 gpm
100 99
90
80
70
Pressure psi
60
50
40
30
20
10
0
1 2 3 4 5 6 7 8 9 10
Flowrate(x100) gpm