ArmorStart® LT Distributed Motor Controller Manual
ArmorStart® LT Distributed Motor Controller Manual
The illustrations, charts, sample programs and layout examples shown in this guide are intended solely for purposes of
example. Since there are many variables and requirements associated with any particular installation, Rockwell Automation
does not assume responsibility or liability (to include intellectual property liability) for actual use based upon the examples
shown in this publication.
Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety
Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1 available from your
local Rockwell Automation sales office or online at http://www.rockwellautomation.com/literature/) describes some
important differences between solid-state equipment and hard-wired electromechanical devices. Because of this difference,
and also because of the wide variety of uses for solid-state equipment, all persons responsible for applying this equipment
must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the
use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or
liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or
software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation,
Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment,
which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property
damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous
voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may
reach dangerous temperatures.
IMPORTANT Identifies information that is critical for successful application and understanding of the product.
General Precautions
In addition to the precautions listed throughout this manual, the following statements, which are general to the system,
must be read and understood.
ATTENTION: This manual is intended for qualified service personnel responsible for setting up and servicing these devices. The
user must have previous experience with and a basic understanding of electrical terminology, configuration procedures,
required equipment, and safety precautions.
WARNING: The National Electrical Code (NEC), NFPA79, and any other governing regional or local code will overrule the
information in this manual. Rockwell Automation cannot assume responsibility for the compliance or proper installation of the
ArmorStart LT or associated equipment. A hazard of personal injury and/or equipment damage exists if codes are ignored
during installation.
ATTENTION: The controller contains ESD (electrostatic discharge) sensitive parts and assemblies. Static control precautions are
required when installing, testing, servicing, or repairing the assembly. Component damage may result if ESD control
procedures are not followed. If you are not familiar with static control procedures, refer to Publication 8000-4.5.2, Guarding
against Electrostatic Discharge, or any other applicable ESD protection handbooks.
ATTENTION: Only personnel familiar with the controller and associated machinery should plan or implement the installation,
startup, and subsequent maintenance of the system. Failure to do this may result in personal injury and/or equipment
damage.
Software Version
RSLinx Classic 2.56 or later
RSLogix 5000 17.01 or later
Download the most current version of the Add-On Profile from
http://www.rockwellautomation.com/support/downloads.html.
BOOTP/DHCP Version 2.3 or later
Additional Resources
These documents and websites contain additional information concerning related Rockwell Automation products.
Resource Description
http://ab.rockwellautomation.com/Networks-and-Communications Rockwell Automation networks and communication website
http://ab.rockwellautomation.com/Networks-and-Communications/Ethernet-IP- Rockwell Automation EtherNet/IP website
Network
http://www.rockwellautomation.com/services/networks/ Rockwell Automation network and security services websites
http://www.rockwellautomation.com/services/security/
http://www.ab.com/networks/architectures.html Education series webcasts for IT and controls professionals
EtherNet/IP Embedded Switch Technology Application Guide, Publication ENET-AP005 Describes how to install, configure, and maintain linear and device-level Ring (DLR)
networks using Rockwell Automation EtherNet/IP devices with embedded switch
technology.
EtherNet/IP Network Configuration User Manual, Publication ENET-UM001 Describes how to configure and use EtherNet/IP communication modules with a
Logix5000 controller and communicate with various devices on the Ethernet network.
EtherNet Design Consideration, Publication ENET-RM002A-EN-P Provides details on ethernet design and infrastructure.
EtherNet/IP Modules in Logix5000 Control Systems User Manual, Publication ENET-UM001 Provides details about how to configure your module.
EtherNet/IP Embedded Switch Technology Application Guide, Publication ENET-AP005 Provides information about using products with embedded switch technology to
construct networks with linear and ring topologies.
EtherNet/IP Industrial Protocol White Paper, Publication ENET-WP001 Describes how to implement services and data objects on a TCP/UDP/IP based Ethernet
network.
Industrial Automation Wiring and Grounding Guidelines, Publication 1770-4.1 Provides general guidelines for installing a Rockwell Automation industrial system.
Wiring and Grounding Guidelines, (PWM) AC Drives, Publication DRIVES-IN001 Describes wiring and grounding guidelines for Pulse Width Modulated (PWM) AC Drives
Product Certifications website, Provides declarations of conformity, certificates, and other certification details.
http://www.rockwellautomation.com/products/certification/
Resource Description
Industrial Controls catalog website, Industrial Controls catalog website
http://www.ab.com/catalogs/
ArmorStart LT Distributed Motor Controller Selection Guide, Publication 290-SG001 Product selection guide
Installation Assistance
If you experience a problem within the first 24 hours of installation, contact Customer Support.
United States Contact your distributor. You must provide a Customer Support case number (call the
phone number above to obtain one) to your distributor to complete the return process.
Outside United States Please contact your local Rockwell Automation representative for the return
procedure.
New and Updated This table contains the changes made to this revision.
Information Topic Page
Added source brake and IPS specifications Various
Notes:
European Communities (EC) If this product has the CE mark it is approved for installation within the
European Union and European Economic Area (EEA). It has been designed and
Directive Compliance tested to meet the following directives.
Low Voltage and EMC This product is tested to meet the European Union (EU) Council 2006/95/EC
Low Voltage Directive and the EU Council 2004/108/EC Electromagnetic
Directives Compatibility (EMC) Directive by applying the following standard(s):
Summary of Changes
New and Updated Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Preface
European Communities (EC) Directive Compliance. . . . . . . . . . . . . . . . . . 9
Low Voltage and EMC Directives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Chapter 1
Product Overview Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Feature Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Standard Features Across Product Family . . . . . . . . . . . . . . . . . . . . . . 19
Network Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Factory-Installed Options. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
ArmorStart LT Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Catalog Number Explanation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
ArmorStart LT Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Catalog Number Explanation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Basic Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Group Motor Installations for USA and Canada Markets. . . . . . . . 27
Control Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Motor Circuit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Local I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Overload Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Mode of Operation Bulletin 290E/291E . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Full-Voltage Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Mode of Operation Bulletin 294E . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Sensorless Vector Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Status LEDs and Reset. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Electronic Data Sheet (EDS) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Fault Diagnostics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Protection Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Optional HOA Selector Keypad. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Keypad Local Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Optional HOA Keypad Configuration (Bulletin 290E/291E only). . . 35
Chapter 2
Installation and Wiring Receiving . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Unpacking. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Inspecting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Storing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Installation Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Precautions for Bulletin 290E/291E Applications . . . . . . . . . . . . . . . . . . . 40
Precautions for Bulletin 294E Applications . . . . . . . . . . . . . . . . . . . . . . . . . 40
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Connection Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Wiring Terminal Detail. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Branch Circuit Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Typical System Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
ArmorConnect Media . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
ArmorConnect Cable Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Branch Circuit Protection Requirements for ArmorConnect
Three-Phase Power Media. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Fusing:. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Electrical Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Group Motor Installations for USA and Canada Markets. . . . . . . . . . . . 55
Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Cable Workmanship Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Service Space . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Hand Operation (HOA) Considerations . . . . . . . . . . . . . . . . . . . . . . . 56
General Wiring Considerations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Grounding. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Grounding Safety Grounds . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Grounding PE or Ground . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Grounding Motors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Power Distribution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Delta/Wye with Grounded Wye Neutral . . . . . . . . . . . . . . . . . . . . . . . 58
AC Line Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Line Reactor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Bulletin 294 Motor Cable Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Unshielded Cable. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Shielded Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Recommended Cable Connectors/Glands . . . . . . . . . . . . . . . . . . . . . . 60
Recommended Cord Grips . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Shield Terminating Connectors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Electromagnetic Compatibility (EMC) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
General Notes (Bulletin 294E only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Ethernet, DeviceNet, and I/O Connections . . . . . . . . . . . . . . . . . . . . . . . . 63
Chapter 3
Product Commissioning IP Address. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Gateway Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Subnet Mask . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Configuring EtherNet/IP Address. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Manually Configure the Network Address Switches . . . . . . . . . . . . . 68
Static Address Alternative. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Using the Rockwell Automation BootP/DHCP Utility . . . . . . . . . . . . . 70
Save the Relation List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Embedded Web Server . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Network Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Parameter Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
E-mail Notification Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
How to Add a New Module Using the Add-On Profile. . . . . . . . . . . . . . 78
Electronic Keying . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Configured by. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
HOA Keypad Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Source Brake, Electro-Mechanical Brake Option . . . . . . . . . . . . . . . . 82
User Configurable I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
RSLogix 5000 Add-On Profile . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Auto-Generated Tags . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Chapter 4
Bulletin 290E/291E/294E Electronic Data Sheet (EDS) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Programmable Parameters Basic Setup Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Parameter Groups . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
ArmorStart LT EtherNet/IP Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . 102
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
Parameter Programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
Bulletin 290E/291E . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
Basic Status Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
Trip Status Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
Basic Configuration Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
Starter Protection Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
User I/O Configuration Group. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
Miscellaneous Configuration Group . . . . . . . . . . . . . . . . . . . . . . . . . . 119
Advanced Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
Bulletin 294E . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
Basic Status Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
Trip Status Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
Motor and Control Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133
Chapter 5
Diagnostics Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 157
Status LEDs and Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 157
Fault Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 158
Protection Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 158
Quick Reference Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 160
Fault LED Indications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 161
Bulletin 290E/291E Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 161
Bulletin 294E Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 163
Chapter 6
Specifications Bulletin 290E/291E . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 165
Motor Overload Trip Curves. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 170
Bulletin 100-K/104-K Life-Load Curves . . . . . . . . . . . . . . . . . . . . . . 171
Bulletin 294E . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 172
Motor Overload Trip Curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 178
Appendix A
Applying More Than One ArmorStart Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 179
LT Motor Controller in a Single Branch ArmorStart LT Product Family. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 180
Multiple-Motor Branch Circuits and Motor Controllers Listed for Group
Circuit on Industrial Machinery
Installation – General. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 181
Maximum Fuse Ampere Rating According to 7.2.10.4(1)
and 7.2.10.4(2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 183
Complete Text - . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 183
Explanatory Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 185
Input and Output Conductors of Bulletin 290E and 291E
Controllers (a) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 191
Input and Output Conductors of Bulletin 294E Controllers (b). . . . . 191
Combined Load Conductors (c) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 191
Appendix B
CIP Information High Level Product Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 193
Product Codes and Name Strings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 193
CIP Explicit Connection Behavior. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 194
EDS Files . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 194
CIP Object Requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 194
Identity Object. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 195
CLASS CODE 0x0001 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 195
Appendix C
Using DeviceLogix Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 229
DeviceLogix Programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 230
DeviceLogix Programming Example. . . . . . . . . . . . . . . . . . . . . . . . . . . 230
ArmorStart LT Bulletin 294E Example Configuration. . . . . . . . . . 236
Download the AOP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 237
Use of the AOP in RSLogix 5000 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 242
Product Overview
Description ArmorStart LT is available with Full Voltage, Full Voltage Reversing, or Variable
Speed motor control performance. It comes equipped with a UL Listed At-motor
disconnect that supports a lock-out tag-out (LOTO) provision. ArmorStart LT
is listed as suitable for group installations per UL and can be applied with either
branch circuit breaker protection or fuse protection. It provides a robust IP66/
UL Type 4/12➊ enclosure suitable for water washdown environments in a single
box construction that will minimize inventory needs. All external connections
are made from the bottom of the unit minimizing accidental contact by moving
equipment. ArmorStart LT as a standard will come with quick disconnect
receptacles for the I/O and network connections. And finally, ArmorStart LT
will include DeviceLogix, a high-performing local logic engine when a fast I/O
response is critical to the application.
The ArmorStart LT is available with options that can further reduce installation
and commissioning time and cost, such as:
• Internal power supply (IPS) eliminating the need to run additional control
power to each unit
Features The ArmorStart LT provides many features and benefits that are unsurpassed in
the market place:
• DeviceLogix
IMPORTANT Not all options are available for Bulletin 290E/291E/294E. Refer to the catalog
configurator for details.
IMPORTANT AOP support for EtherNet/IP network only and requires RSLogix 5000
revision 17.01 or later. There is a known compatibility issue with revision 20.0.
Update RSLogix 5000 to 20.1 or greater.
LEDs found on the electronic control module (ECM). If a fault occurs a local
fault reset button allows the user to quickly get the process started after corrective
action is taken. The user can also configure the embedded webserver to send an e-
mail when a fault or warning occurs.
In this example the fault is precisely identified by the link status message and the supervisor opens the blocked port to
allow network traffic to continue normally.
Factory-Installed Options Internal power supply (IPS) — ArmorStart LT offers the user an optional
24V DC internal power supply. The internal power supply provides all control
and I/O power needs and is sourced from the incoming 3-phase power. This
eliminates the need to run separate control power to each unit, reducing
installation time and cost. The local at-motor disconnect will remove power
from the motor terminals and outputs when in the OFF condition.
Quick disconnect gland — ArmorStart LT offers a plug -n- play solution that
simplifies wiring and installation. These factory installed quick disconnect
receptacles provide connectivity to ArmorConnect® media for three-phase,
control, and motor connections. The cables are ordered separately.
ArmorStart LT Characteristics
Figure 4 - Bulletin 290E/291E ArmorStart LT
0
Off
1
HOA Keypad (optional)
On
Reset
ECM (Electronic
Control Module)
6 Configurable I/Os
Wiring Access
Catalog Number Explanation Examples given in this section are for reference purposes. This basic explanation
should not be used for product selection; not all combinations will produce a
valid catalog number.
a e
Bulletin Number Control Voltage
Code Description Code Description
290 Full-Voltage Starter Z External 24V DC control power
291 Reversing Starter P Internal power supply
b f
Communications Gland Plate Options
Code Description (Power and Motor)
c
Enclosure Type
Code Description g
➊ IP66/UL Type 4 is available with all gland options. UL Type 4/12 is available with G1 and G3 gland option.
➋ See selection guide 290-SG001_-EN-P Accessories section for gland configurations and ordering.
➌ Leave blank unless there is a customer-specific option defined by the factory.
ArmorStart LT Characteristics
Figure 5 - Bulletin 294E ArmorStart LT
0
Off
1
On
On/Off Switch
Wiring Access
LockOut/TagOut Provision
Hand-Off-Auto
Keypad (optional)
Reset
Catalog Number Explanation Examples given in this section are for reference purposes. This basic explanation
should not be used for product selection; not all combinations will produce a
valid catalog number.
a e
Bulletin Number Control Voltage
Code Description Code Description
294 VFD Starter Z External 24V DC control power
P Internal power supply
b
Communications f
Code Description Gland Plate Options
E EtherNet/IP (Power and Motor)
c
Enclosure Type
Code Description
F UL Type 4/12 ➊ g
Option 1
Code Description
3 Hand/Off/Auto selector keypad with Jog
function
d
Output Current
Code Description
D1P5 1.5 A (0.4 kW), 0.5 Hp
D2P5 2.5 A (0.75 kW), 1.0Hp
h
D4P2 3.6 A (1.5 kW), 2.0Hp
Option 2
Code Description
SB Source Brake
blank No option
➌
➊ IP66/UL Type 4 is available with all gland options. UL Type 4/12 is available with G1 and G3 gland option.
➋ See selection guide 290-SG001_-EN-P Accessories section for gland configurations and ordering.
➌ Leave blank unless there is a customer-specific option defined by the factory.
Basic Operation Group Motor Installations for USA and Canada Markets
The ArmorStart LT Distributed Motor controllers are listed for use with each
other in group installations per NFPA 79, Electrical Standard for Industrial
Machinery and NFPA 70, the National Electrical Code. When applied according
to the group motor installation requirements, two or more motors are permitted
on a single branch circuit. Group Motor Installation has been successfully used
for many years in the USA and Canada.
Note: For additional information regarding group motor installations with the
ArmorStart LT Distributed Motor Controller, see Appendix A.
Control Circuit
ArmorStart LT
L1 L2 L3
Switched Control Power
Off
Unswitched Control Power
*
Disconnect
L +
24VDC
N -
Class 2
External
24VDC Power
Supply
ArmorStart LT
L1 L2 L3
Switched Control Power
Off
Unswitched Control Power
*
Disconnect
T1 T2 T3
Class 2 L +
External Switched
24VDC
24VDC Power Supply
N -
Class 2
L +
External Unswitched 24VDC
24VDC Power Supply N -
ArmorStart LT
Internal Power
L1 L2 L3 Supply
Off
Disconnect
*
*
T1 T2 T3
Motor Circuit
Bulletin 290E/291E:
0.5 Hp (0.37 kW) to 5 Hp (3 kW) @ 480/277V AC
Bulletin 294E:
0.5 Hp (0.37 kW) to 2 Hp (1.5 kW) @ 480/277V AC
Local I/O
The ArmorStart LT provides as standard, 6 user configurable I/O points. By
default, all points are configured as an Input. When not using the AOP, the
user will need to refer to parameter 49 [IOPointConfiguration], to define an
output point.
When using the AOP, the I/O point is configured from the General screen
in the Module Definition section by clicking the “Change” button, see Figure 9.
This allows user to view and configure the I/O mix, refer to Figure 10.
Overload Protection
The Bulletin 290E/291E includes programmable overload Class 10, 15, and 20
protection. The Bulletin 294E provides overload protection: 150% for 60s and
200% for 3s.
100%
Percent
Voltage
Time (seconds)
Open Loop Speed Regulation with Slip Compensation allows the VFD to
automatically adjust the output frequency to compensate for speed changes due
to motor loading. This feature utilizes an open loop, current feedback, slip
compensation circuit. Slip Compensation works as an open loop speed regulator
that increases the output frequency of the drive as the load is increased, or
decreases the frequency as the load drops. This feature is used where the motor
must run at a relatively constant speed regardless of torque output.
% of speed
100 With Slip
Compensation
99
98
97 Without Slip
Compensation
96
95
0 10 20 30 40 50 60 70 80 90 100
% of load
Status LEDs and Reset Figure 12 - Status, Diagnostic LEDs, and Reset
EDS files for all ArmorStart LT EtherNet/IP devices can be uploaded directly
from the device via the web server interface. Rockwell Automation product EDS
files are also available on the internet at: http://www.ab.com/networks/eds.
Fault Diagnostics Fault diagnostics capabilities built in the ArmorStart LT Distributed Motor
Controller are designed to help you pinpoint a problem for easy troubleshooting
and quick re-starting.
Protection Faults
➊ Cannot be disabled.
The Auto key allows for Start/Stop control via the communications
AUTO network
OFF If the starter is running, pressing the OFF key will cause the starter to stop.
DIR Arrow The Dir arrow selects the direction of the motor, either forward or reverse.
When pressed, JOG will be initiated if no other control devices are sending
JOG a stop command. Releasing the key will cause the drive to stop, using
selected stop mode.
Optional HOA Keypad The ArmorStart LT offers optional factory-installed Hand/OFF/Auto (HOA)
configurations: Standard (Bulletin 290E) and Forward/Reverse (Bulletin 291E).
Configuration
(Bulletin 290E/291E only) Figure 13 - Bulletin 290E Standard HOA
Bulletin 290E
Bulletin 291E
Optional HOA Selector The HOA Selector Keypad with Jog function allows for local start/stop control
with capabilities to jog in forward/reverse motor directions.
Keypad with Jog Function
(Bulletin 294E only) Figure 15 - Bulletin 294E Jog/Forward/Reverse HOA
IMPORTANT If multiple buttons are pressed at the same time, the software interprets this as
a “no button pressed” condition. The only exception to this rule is if multiple
buttons are pressed and one of them is the OFF button. If the OFF button is
pressed in combination with any combination of other buttons, the processor
will behave as if the OFF button were pressed by itself.
“Keypad Disable”, parameter 67, only inhibits the “HAND”, “FWD”, “REV” and
“JOG” buttons on the HOA keypad. The “OFF” and “AUTO” buttons are
always enabled, even if parameter 67 is set to “1=Disable”. The keypad OFF
button can not be disabled.
Source Brake Contactor An internal contactor is used to switch the electromechanical motor brake
On/Off. The motor brake contactor is actuated via the internal power which
and Connector supplies L1 and L2 voltage to the mechanical brake in the motor. The source
(Bulletin 294E only) brake can be configured for independent control via parameter configuration.
WARNING: If the branch circuit protective device trips, the user must ensure
that the Source Brake function is still operational prior to putting the
equipment back in service. If the source brake function is not working properly,
loss of brake function or motor damage can occur.
Receiving It is the responsibility of the user to thoroughly inspect the equipment before
accepting the shipment from the freight company. Check the item(s) received
against the purchase order. If any items are damaged, it is the responsibility of the
user not to accept delivery until the freight agent has noted the damage on the
freight bill. Should any concealed damage be found during unpacking, it is also
the responsibility of the user to notify the freight agent. The shipping container
must be left intact and the freight agent should be requested to make a visual
inspection of the equipment.
Unpacking Remove all packing material, wedges, or braces from within and around the
ArmorStart LT distributed motor controller and other device(s). Check the
contents of the package to see if all contents are included. Contact your local
Allen-Bradley representative if any items are missing.
IMPORTANT Before the installation and start-up of the drive, a general inspection
of mechanical integrity (i.e. loose parts, wires, connections, packing
materials, etc.) must be made.
Inspecting After unpacking, check nameplate catalog number(s) of the item(s) against the
purchase order. See Chapter 1 for an explanation of the catalog numbering system
which will aid in nameplate interpretation.
Storing The controller should remain in the shipping container prior to installation.
If the equipment is not to be used for a period of time, it must be stored according
to the following instructions in order to maintain warranty coverage.
Precautions for
SHOCK HAZARD: To prevent electrical shock, open appropriate machine
Bulletin 290E/291E disconnect switch prior to connecting and disconnecting cables. Risk of shock —
Applications environment rating may not be maintained with open receptacles.
Precautions for
SHOCK HAZARD: The drive contains high voltage capacitors which take time
Bulletin 294E Applications to discharge after removal of mains supply. Before working on drive, ensure
isolation of mains supply from line inputs (L1, L2, L3). Wait three minutes
for capacitors to discharge to safe voltage levels. Failure to do so may result
in personal injury or death.
Dimensions Dimensions are shown in millimeters (inches). Dimensions are not intended
to be used for manufacturing purposes. All dimensions are subject to change.
260
130 (10.2) 166,5
(5.1) (6.6)
217,83
(8.6)
202,05
(8.0) 170
(6.7)
152,65
65 (6.0)
(2.6) Front View Right Side View
Line Control
Motor
37
37 (1.5)
(1.5)
57,13
57,13 (2.3)
(2.3)
38,49
38.49 1 in. conduit opening (1.5)
(1.5) 24,25 48,5
24,25 0.75 in. conduit opening
(1.0) (1.9)
(1.0) 48,5
Conduit Gland Entrance ArmorConnect Media
(1.9)
Gland Entrance (optional)
Line
Line
Motor Motor Control
37 37 Source Brake
(1.5) (1.5)
57,13 57,13
(2.3) (2.3)
38,61 38,49 48,5
(1.5) 24,25
(1.0) (1.5) (1.9)
ArmorConnect Internal Power ArmorConnect Source Brake
Supply Gland Plate (optional) Gland Plate (optional)
IMPORTANT For proper heat dissipation and product operation, mount the ArmorStart LT in the
vertical orientation as shown.
219,32
206,43 (8.6)
(8.1)
170
(6.7)
120
(4.7)
Front View
202,27
(8.0)
37
(1.5)
92,9
(3.7)
38.49
(1.5) 1 in. conduit opening
24,25 48,5 0.75 in. conduit opening
(1.0) (1.9)
Conduit Gland Entrance - Bottom View Right Side View
Line Line
Control
Line
Motor Control
Motor Motor
37 37 37 Source Brake
(1.5) (1.5) (1.5)
38,55
38,61 (1.5) 24,25 38,55 48,5
(1.5) 24,25 (1.0) 48,5 (1.5) (1.9)
(1.0) (1.9)
ArmorConnect Internal Power ArmorConnect Media Gland ArmorConnect Gland Entrance
Supply Gland Plate (optional) Entrance (optional) with Source Brake (optional)
IMPORTANT For proper heat dissipation and product operation, mount the ArmorStart LT in the
vertical orientation as shown.
Dia. 25.5 mm
1.00 in. Dia. 20.5 mm 290-G3-A4
Internal Power Supply (25.4 mm)
No Source Brake 0.75 in.
(19.05 mm)
Dia. 25.5 mm
Dia. 20.5 mm
1.00 in. 290-G3-A5
Internal Power Supply (25.4 mm)
and Source Brake 0.75 in.
(19.05 mm)
45°
290-G3-A1
Gland Plate Clearances
Modifications are not permitted in the keepout region. Fitting(s) should be oriented 66.1 mm 80.7 mm
User Modified
so that they do not interfere with the enclosure when the gland plate is installed.
Torque the gland mounting screws to 12…14 in•lb (1.3…1.6 N•m).
10.1 mm 91.3 mm 11.8 mm
Wiring Terminal Detail The power, control, and ground wire capacity and the tightening torque
requirements are shown in Table 8. The maximum number of connections
per terminal are shown in Table 7. As shown in Figure 21 all the terminals are
found in the wiring area. Access can be gained by removing the terminal access
cover plate.
L1 A1
L2 L3 A2 A3
T1
T2 T3
PE
B1 B2
Table 8 - Power, Control, and Ground Wire Capacity and the Tightening Torque Requirements
Wire Size (2) #18…#10 AWG (0.8…5.2 mm2) per terminal
Power Terminals
Tightening Torque 10.6 +/– 2 lb•in (1.2 +/– 0.2 N•m)
Wire Size #18…#10 AWG (0.8…5.2 mm2) per terminal
Motor Terminals
Tightening Torque 10.6 +/– 2 lb•in (1.2 +/– 0.2 N•m)
Wire Size (2) #18…#10 AWG (0.8…5.2 mm2) per terminal
Control Terminals
Tightening Torque 10.6 +/– 2 lb•in (1.2 +/– 0.2 N•m)
Wire Size (2) #16…#10 AWG (1.3…5.2 mm2) per terminal
PE/Ground
Tightening Torque 18 +/– 2 lb•in (2 +/– 0.2 N•m)
Wire Size #16 …#10 AWG (1.0…4.0 mm2) per terminal
Source Brake (Bulletin 294)
Tightening Torque 4.8 ± 2 lb•in (0.5 ± 0.2 N•m )
IMPORTANT ArmorStart LT is UL Listed for use with 14 AWG wire or preassemble power
cable. Refer to your local electrical code(s) when applying 16 AWG wire or cable
in a motor circuit.
Typical System Example The primary function of ArmorStart LT is to control and protect a three-phase
squirrel cage induction motor. Three-phase power enters through terminals that
are connected to a manually operated disconnect switch. The three-phase power
may also connect internally to an optional three-phase to 24V DC power supply
(IPS). Wired in series with the disconnect is an electrically operated contactor or
a variable frequency drive. For Bulletin 294E an optional source brake contactor
may also be connected to the disconnect output terminals. The source brake
contactor is used to control an electromechanical brake physically attached to the
motor. The microcontroller and interface circuits are contained in the ECM.
The ECM also houses 6 user configurable I/O points. These six I/O points are
used for system level control and are accessible via by the communication
network or DeviceLogix.
The user has the flexibility to coordinate the appropriate safety function for their
application. ArmorStart LT does not provide a safe torque-off input. Therefore,
the safety function is configured externally from the controller and based upon
the risk assessment.
For example, the risk assessment may require a safety circuit with a high level
of performance. In this example, a safety relay with redundant safety contactors
and emergency stop function can be integrated into the machine controls.
Figure 22 below is an example of this configuration. Contact your local
Rockwell Automation supplier for additional support regarding the safety
circuit or for a risk assessment of your machinery.
Figure 22 -
ArmorConnect Media For greater flexibility and faster installations the user may also use
ArmorConnect media for a complete plug-n-play solution. This solution
provides plug-in style stop stations, as shown in Figure 23. The ArmorConnect
power media offers both three-phase and control power cable cord set systems.
These include patchcords, receptacles, tees, reducers and accessories to be utilized
with the ArmorStart LT Distributed Motor Controller. This cable system allows
quick connections and reduced installation time by utilizing pre-manufactured
cable assemblies for more reliable connection of the three phase and
control power.
IMPORTANT When specifying power media for use with the ArmorStart LT Distributed
Motor Controllers (Bulletin 290E/291E and Bulletin 294E) use only
ArmorConnect power media. The use of any other power media
will void the UL Listing of the motor controller.
IMPORTANT Refer to your local electrical code for proper application and protection of long
length power cable to minimize physical damage and appropriate short-circuit
and ground-fault protection for the assembly.
6. The E-stop Out tee (Cat. No.: 898N-653ES-NKF) is used with cordset or patchcord to connect to the ArmorStart Distributed Motor Controller.
7. Control Power Receptacles – Female receptacles are a panel mount connector with flying leads (Cat. No.: 888N-D65AF1-*)
8. Three-Phase Power Trunk – Patchcord cable with integral female or male connector on each end (Example Cat. No.:280-PWRM35A-M*)
9. Three-Phase Drop Cable – PatchCord cable with integral female or male connector on each end (Example Cat. No.:280-PWRM22A-M*)
10. Three-Phase Power Tees and Reducer – Tee connects to a single drop line to trunk with quick change connectors (Cat. No.: 280-T35)
Reducing Tee connects to a single drop line (Mini) to trunk (Quick change) connector (Cat. No.: 280-RT35)
Reducer connects from quick change male connector to mini female connector (Cat. No.: 280-RA35)
11. Three-Phase Power Receptacles – Female receptacles are a panel mount connector with flying leads (Cat. No.: 280-M35F-M1)
ArmorConnect Cable Ratings The ArmorConnect Power Media cables are rated per UL Type TC 600V 90°C
Dry 75°C Wet, Exposed Run (ER) or MTW 600V 90°C or STOOW 105°C
600V - Canadian Standards Association (CSA) STOOW 600V FT2.
For additional information regarding ArmorConnect Power Media refer
to ArmorStart LT selection guide, publication 290-SG001_-EN-P.
Circuit Breaker:
WARNING: The total circuit impedance including each cable assembly's own
impedance, must be low enough to ensure any short-circuit or ground fault
current that can flow through any assembly, will be large enough to operate the
magnetic trip of the Cat. No. 140U-D63-C* circuit breaker. Refer to NFPA 70 and
NFPA 79 or your local electrical code for guidance in coordinating over current
protective devices and the circuit being protected.
Fusing:
Electrical Wiring ArmorStart LT EtherNet/IP utilizes 24V DC control power for communications
and I/O. The control power terminal connections are labeled A1, A2, and A3.
Switched power (A1) will supply outputs and motor control. Unswitched
power (A3) will supply logic power, communications, and sensor inputs.
Disconnect
State,
Voltage
Monitoring Micro Internal Internal
and Power Loss Outputs Inputs
PE Power EtherNet/IP
Conditioning Logic
Board
Power
Switched A1 Loss
(SW)
A2 External External
Common Outputs Inputs
A3
Un-
Switched Sensor Voltage
(USW) Sinking
Input or 1 2
Sourcing
output 5
4 3
Common
6-User Configurable I/O Points
Disconnect
State,
Voltage
Monitoring Micro Internal Internal
and Power Loss Outputs Inputs
PE Power EtherNet/IP
Conditioning Logic
Board
Power
Switched A1 Loss
(SW)
A2 External External
Common) Outputs Inputs
A3
Un-
Switched Sensor Voltage
(USW) Sinking
Input or
Sourcing 1 2
output 5
4 3
Common
6-User Configurable I/O Points
Disconnect
State,
Voltage
Monitoring Micro Internal Fan Internal
and Power Loss Outputs Inputs
PE Power EtherNet/IP
Conditioning Logic
Board
Power
Switched A1 Loss
(SW)
A2 External External
Common) Outputs Inputs
A3
Un-
Switched Sinking
(USW) Input or Sensor Voltage
Sourcing
output
1 2
5
4 3
Common
6-User Configurable I/O pOINTS
Disconnect
State,
Voltage
Monitoring Micro Fan Internal Internal
and Power Loss Outputs Inputs
PE Power EtherNet/IP
Conditioning Logic
Board
Power
Switched A1 Loss
(SW)
A2 External External
Common Outputs Inputs
A3
Un-
Switched Sinking
(USW) Input or Sensor Voltage
Sourcing
output 1 2
5
4 3
Common
6-User Configurable I/O Points
Disconnect
State,
1 Voltage
Monitoring Micro Internal Internal
and Power Loss Outputs Inputs
PE EtherNet/IP
Logic
Power
Loss 4
1 External External
2 Outputs Inputs
3
Sensor Voltage
Sinking
Input or 1 2
Sourcing
output 5
4 3
Common
6-User Configurable I/O Points
Disconnect
State,
Voltage
Monitoring Micro Internal Internal
and Power Loss Outputs Inputs
PE EtherNet/IP
Logic
Power
Loss 4
1 External External
2 Outputs Inputs
3
Sinking Sensor Voltage
Input or
Sourcing 1 2
output 5
4 3
Common
6-User Configurable I/O Points
At Motor
Disconnect
L1 T1
L1 T1
L2 T2
L2 T2 Motor
L3 T3
L3 T3
TB2
1
Drive J3
Enable 11
Disconnect Status
Disconnect
State,
Voltage
Monitoring Micro Internal Fan Internal
and Power Loss Outputs Inputs
PE EtherNet/IP
Logic
Power
Loss 4
1
External External
2 Outputs Inputs
3
Sinking
Input or Sensor Voltage
Sourcing
output 1 2
5
4 3
Common
6-User Configurable I/O Points
Disconnect
State,
Voltage
Monitoring Fan Internal Internal
and Power Loss Micro Outputs Inputs
PE EtherNet/IP
Logic
Power
Loss 4
1
External External
2 Outputs Inputs
3
Sinking
Input or Sensor Voltage
Sourcing
output 1 2
5
4 3
Common
Group Motor Installations for When ArmorStart LT is applied according to group motor installation
requirements, two or more motors of any rating or controller type, are permitted
USA and Canada Markets on a single branch circuit. Group Motor Installation has been successfully used
for many years in the USA and Canada.
IMPORTANT For additional information regarding group motor installations with the
ArmorStart LT Distributed Motor Controller, see Appendix A
➊ Historically cable meeting these crush and impact requirements was designated and marked “Open Wiring.” Cable so marked is
equivalent to the present Type TC-ER and can be used.
Service Space
1. Install not less than 2 ft (0.6 m) above the servicing level and within easy
reach of the operator, who is in a normal working position.
2. Install where the operator is not placed in a hazardous situation when
operating the equipment.
3. Install where the possibility of inadvertent operation is minimized.
Where inadvertent operation may cause adverse effects the HOA can be disabled
via parameter 67.
General Wiring Wire in an industrial control application can be divided into three groups: power,
control, and signal. The following recommendations for physical separation
Considerations between these groups is provided to reduce the coupling effect:
• Minimum spacing between different wire groups in the same tray should
be 6 in. (16 cm).
The object of safety grounding is to ensure that all metalwork is at the same
ground (or Earth) potential at power frequencies. Impedance between the drive
and the building scheme ground must conform to the requirements of national
and local industrial safety regulations or electrical codes. These will vary based
on country, type of distribution system and other factors. Periodically check the
integrity of all ground connections.
General safety dictates that all metal parts are connected to earth with separate
copper wire or wires of the appropriate gauge. Most equipment has specific
provisions to connect a safety ground or PE (protective earth) directly to it.
Grounding PE or Ground
The safety ground - PE must be connected to earth ground. This point must
be connected to an adjacent building steel (girder, joist), a floor ground rod, a bus
bar or a building ground grid. Grounding points must comply with national and
local industrial safety regulations or electrical codes. Some codes may require
redundant ground paths and periodic examination of connection integrity.
IMPORTANT To avoid electrolytic corrosion on the external earth terminal, avoid spraying
moisture directly on the terminal. When used in washdown environments
apply a sealant or other corrosion inhibitor on the external ground terminal
to minimize any negative effects of galvanic or electro-chemical corrosion.x
Ground connections should be inspected on a regular basis.
Grounding Motors
The motor frame or stator core must be connected directly to the PE connection
with a separate ground conductor. It is recommended that each motor frame be
grounded to building steel at the motor.
Power Distribution The type of transformer and the connection configuration feeding an
ArmorStart LT Bulletin 294E plays an important role in its performance
and safety.
AC Line Voltage Incoming voltage imbalances greater than 2% can cause large unequal currents
in a drive. An input line reactor may be necessary when line voltage imbalances
are greater than 2%.
Line Reactor In general, ArmorStart LT does not require line reactors. In most applications,
the ArmorStart LT is further away from the power distribution panel, therefore
the length of cable provides additional impedance as compared to an in-panel
solution.
Bulletin 294 Motor Cable The majority of recommendations regarding drive cable address issues are caused
by the nature of the drive output. A PWM drive creates AC motor current by
Considerations sending DC voltage pulses to the motor in a specific pattern. These pulses
affect the wire insulation and can be a source of electrical noise. The rise time,
amplitude, and frequency of these pulses must be considered when choosing a
wire/cable type. The choice of cable must consider:
Keep the motor cable lengths less than 45 ft from the ArmorStart LT.
Unshielded Cable
Properly designed multi-conductor cable can provide superior performance
in wet applications, significantly reduce voltage stress on wire insulation and
reduce cross coupling between drives.
R G
Single Ground
Conductor
Shielded Cable
Drain Wire
Shield
W G
R B
Knockout Sealing
Cord Grip Lock Nut
Description Gland Size Cable Diameter Range (in.2) Ring
Motor/Source Brake G1 0.75 in. 0.500…0.750 2932NM 5263 142TB
Motor/Source Brake G1 0.75 in. 0.660…0.780 2675 5263 142TB
Power G1 1.0 in. 0.660…0.780 2676 5264 143
Power G1 1.0 in. 0.770…0.895 2677 5264 143
Control Power, Motor/Source
G3 M20 0.236…0.473 CC-ISO20-G ➊ GMN-M20
Brake
3-Phase Power G3 M25 0.512…0.709 CC-ISO25-G ➊ GMN-M25
➊ Contact Thomas and Betts for product selection details
Metal locknut bonds the Drain wires pulled back in a 360° pattern
connector to the panel around the ground cone of the connector
Electromagnetic The following guidelines are provided for EMC installation compliance.
Compatibility (EMC)
General Notes (Bulletin 294E only)
• The motor cable should be kept as short as possible in order to avoid
electromagnetic emissions as well as capacitive currents. CE conformity
of ArmorStart LT with EMC directive does not guarantee the entire
machine installation complies with CE EMC requirements. Many
factors can influence total machine/installation compliance.
• The EMI filter may result in relatively high ground leakage currents.
Therefore, ArmorStart LT must only be applied in installations that are
solidly grounded (bonded) to the building power distribution ground.
I/O Connections
ArmorConnect Power ArmorStart LT utilizes a M22 male receptacle for power inputs and a M22
female receptacle for motor or motor brake output.
Media Receptacles Motor Connector (optional)
Pin 1 - T1 (black)
Pin 2 - T2 (white)
Pin 3 - T3 (red)
Pin 4 - Ground (green/yellow)
Pin 1 - L1 (black)
Pin 2 - L2 (white)
Pin 3 - L3 (red)
Pin 4 - Ground (green/yellow)
Optional Locking Clip The locking clip is an optional device that can be used, if desired. The clam shell
design clips over power quick disconnect connections to limit customer access to
disconnection.
Figure 37 -
SHOCK HAZARD: The ArmorStart LT local disconnect will only isolate the motor
power and remove switched power when turned OFF. Power inputs must be
switched OFF properly from their respective sources before connection or
disconnection of incoming power. Proper Lock-Out Tag-Out procedures should
be followed to reduced the risk of severe injury.
Notes:
Product Commissioning
IP Address The IP address identifies each node on the IP network (or system of connected
networks). Each TCP/IP node on a network must have a unique IP address.
The IP address is 32 bits long and has a net ID part and Host ID part. Networks
are classified A, B, C, (or other). The class of the network determines how an IP
address is formatted.
0 23 24 31
Class C 110 Net ID Host ID
You can distinguish the class of the IP address from the first integer in its
dotted-decimal IP address as follows:
Each node on the same physical network must have an IP address of the same
class and must have the same net ID. Each node on the same network must have
a different Host ID thus giving it a unique IP address.
Gateway Address
Subnet Mask
The subnet mask is used for splitting IP networks into a series of subgroups,
or subnets. The mask is a binary pattern that is matched up with the IP address
to turn part of the Host ID address field into a field for subnets.
Configuring EtherNet/IP Address Before using the ArmorStart LT, you may need to configure an IP address, subnet
mask, and optional Gateway address. The rotary network address switches found
on the front of the ECM, are set to 999 and DHCP is enabled as the factory
default. The network Internet Protocol (IP) address can be set one of three ways:
If the switches are set to an invalid number (for example, 000 or a value greater
than 254 excluding 888), DHCP is enabled. The DHCP server will assign the
IP address and the Transport Control Protocol (TCP) parameters.
Set the network address by adjusting the three rotary switches on the front
of the ECM. When the IP address switches are valid, the subnet mask will be
255.255.255.0 and the gateway address is set to 0.0.0.0. A power cycle is required
for any new IP address to take effect when the switches are used.
6 46 46 4
X100 X10 X1
The switch value of 888 allows the user to reset to factory default configuration
including configuration parameters. This setting is useful in situations where the
user wishes to decommission a module or when the user wishes to commission a
previously-used module that has an unknown configuration. When the switches
are set to 888, upon the next power cycle the ArmorStart LT will return to
factory default settings and cease all communications. The Module Status LED
shall transition to blinking red and the Network Status LED shall transition
to OFF.
After reset, the user will then need to change the IP address to a valid setting and
power cycle. The purpose of this is to prevent the user from resetting the module
and then never changing the switch setting from 888.
IMPORTANT Setting the IP address to “888” followed by a power cycle will reset the device
to its factory default configuration. To resume network communication the
address MUST be set to DHCP or a valid IP address and power cycled again.
Using the The Rockwell Automation BootP/DHCP utility is a stand alone program that
incorporates the functionality of standard BootP/DHCP software with a user
Rockwell Automation friendly graphical interface. It is located in the Utils directory on the
BootP/DHCP Utility RSLogix 5000 installation CD. The ArmorStart LT must have DHCP
enabled (factory default) to use the utility.
To configure your adapter using the BootP/DHCP utility, perform the following
steps:
3. Enter the IP Address you want to assign to the device, and click OK.
The device is added to the Relation List, displaying the Ethernet
Address (MAC) and corresponding IP Address, Hostname, and
Description (if applicable).
You can save the Relation List to use later. To save the Relation List perform the
following steps:
When DHCP is enabled (factory default Enabled), the unit will request its
network configuration from a DHCP/BOOTP server. Any configuration
received from a DHCP server will be stored in non-volatile memory.
The unit will try to obtain the same IP address from the DHCP server. If the
server is not present (e.g., server fails to power up), the unit will use the IP address
it previously received from the server. The DHCP timeout = 30 s.
Embedded Web Server The embedded web server is used to access configuration and status data.
IMPORTANT The user should set the password to a unique value for authorized
personnel.
If the login and password are lost you will need to reset the device
to the factory defaults, which results in losing its configuration.
To access the internal web browser, open your computer’s internet browser and
enter the IP address of the desired ArmorStart LT (for example, 192.168.1.1).
From here you are able to view parameter settings, device status, and diagnostics
from multiple tab views.
Network Configuration
The user will be prompted to enter the default User Name (Administrator).
The factory default password is blank. The user is expected to change the
password to avoid unauthorized access.
From this screen you can change the Ethernet Configuration. For example
in the above image the IP address will be changed to 10.10.10.101. Choose
“APPLY Changes” for new settings to take effect.
Parameter Configuration
ArmorStart LT embedded web server provides the user the ability to view and
modify the device configuration without having to access RSLogix 5000. To view
the device configuration from the web server, select the parameters folder.
Figure 50 -
In the figure above, the Starter Setup parameters are viewed. To modify a
parameter the user will click the “Edit” button.
The user will be prompted to enter the default User Name (Administrator).
The factory default password is blank. The user is expected to change the
Password to avoid unauthorized access.
ArmorStart LT internal web server will support the e-mailing of warning and
trip messages via Simple Mail Transfer Protocol (SMTP). The configuration
parameters for the SMTP Server’s IP address, user login, and port number are
configurable through the Administrative Settings page of the internal web server.
The user will configure the device name, device description, and device trip type.
E-mail triggers:
• when a trip occurs
• when a trip is cleared
• when a warning occurs
• when a warning is cleared
IMPORTANT “Cleared Event” e-mails will only be sent when all events have been cleared
and if a trip event e-mail has previously been sent.
Trip Info: Load has drawn excessive current based on the trip
class selected.
How to Add a New Module ArmorStart LT is provided with an Add-On Profile (AOP). An Add-on profile
streamlines the programming and installation by eliminating the task of
Using the Add-On Profile individually configuring the device tags and providing an easy to use
configuration interface. In addition, the copy and paste function allows easy
configuration of multiple ArmorStart LTs with RSLogix™ 5000 revision 17.01
or later. There is a known compatibility issue with revision 20.0. Update RSLogix
5000 to 20.1 or greater.
IMPORTANT If your version of RSLogix 5000 does not include the AOP for ArmorStart LT, it
can be installed from http://support.rockwellautomation.com/controlflash/
LogixProfiler.asp
3. From the list of modules find the ArmorStart LT using the catalog number.
The AOP will include all options therefore the list will only display the base
catalog number.
6. In the “General” page, select the “Change” button. From here, define what
options are available and what discrete point, if any, will need to be defined
as an output.
The “General” page of the ArmorStart LT AOP differs from many other product
AOPs. The Module definition allows the user to specify the following items:
• Electronic Keying: Module Compatibility
• Configured By: RSLogix 5000 or ArmorStart LT Embedded Web Page
• Connection Type: Data or Listen Only
• User I/O Configuration: Specify the Input or Output use for each I/O
point
• Keypad Option: Is product supplied with this option
• Electro-Mechanical Brake Option: Is product supplied with this option
Electronic Keying
IMPORTANT Changing electronic keying selections online may cause the I/O communication
connection to the module to be disrupted and may result in a loss of data.
Connections
Two Class 1 connections for I/O transfer will be supported and six Class 3
explicit connections will be supported. The Class 1 connections are:
• Data
• Listen Only
Configured by
The ArmorStart LT may be configured via the ArmorStart LT’s web page or
RS Logix 5000. Often times, customers utilize the web interface to configure
the unit before it is ever connected to the PLC. The AOP will require the user
to specify how the ArmorStart LT is configured, once added to RS Logix 5000.
The valid options are:
• “Web Page” — The unit is configured by the ArmorStart LT’s web pages.
The AOP will NOT display any page or content of a page that allows
configuration of the unit. In this mode Connection Type will include a
“Backup” and “Restore” feature. The Backup selection will store parameter
data in the RSLogix 5000 programming file and in the PLC. The Restore
selection will allow the user to manually re-configure a replacement unit.
• “RSLogix 5000” — The unit is configured by RSLogix 5000. The AOP
controls all parameter configurations. Any change made using the webpage
will be over written by the PLC configuration. When the user changes the
“Configured By” field from “Web Page” to “RSLogix 5000”, the values
stored by the “Backup” function will be copied to the configuration
in the PLC. The “Backup/Restore” will no longer be displayed.
ArmorStart LT units are available with or without an HOA Keypad. The user
will specify either “Installed” or “Not Installed”. When a unit is provided without
the HOA keypad this setting should be set to “Not Installed” which removes the
keypad parameters.
Using the navigation tree on the left, start configuring the ArmorStart LT with
the simplified wizard. The minimum configuration is displayed on each page.
Review each field to determine if the default setting is acceptable or modify
as appropriate for your application. Note that more advanced properties are
available using the “Advance” buttons on the screen.
Once complete the new ArmorStart LT will appear in the Ethernet tree. If there
are multiple ArmorStart LTs with similar configurations, utilize the copy-paste
function and update only those parameters that change between units.
The final step is to download your project to the controller and the ArmorStart
LT. Define the path to the PLC and then download.
RSLogix 5000 Add-On Profile The Add-On Profile (AOP) for ArmorStart LT consists of several standard pages
and multiple product specific pages for configuration within RS Logix 5000.
In addition the AOP will automatically create descriptive tag names for the input
and output assemblies.
The following table lists the available AOPs for ArmorStart LT when adding a
new module in RS Logix 5000.
Catalog Number AOP Description
290E-FAZ ArmorStart LT DOL, 0.24…3.5 A, 24V DC
290E-FBZ ArmorStart LT DOL, 1.1…7.6 A, 24V DC
291E-FAZ ArmorStart LT Reverser, 0.24…3.5 A, 24V DC
291E-FBZ ArmorStart LT Reverser, 1.1…7.6 A, 24V DC
294E-FVD1P5Z ArmorStart LT VFD, 480V AC, 0.5 Hp
294E-FVD2P5Z ArmorStart LT VFD, 480V AC, 1 Hp
294E-FVD4P2Z ArmorStart LT VFD, 480V AC, 2 Hp
290E-FAP ArmorStart LT DOL, 0.24…3.5 A, IPS
290E-FBP ArmorStart LT DOL, 1.1…7.6 A, IPS
291E-FAP ArmorStart LT Reverser, 0.24…3.5 A, IPS
291E-FBP ArmorStart LT Reverser, 1.1…7.6 A, IPS
The AOP presents an organized view of parameters within groups and specific
functional pages. All of the parameters are distributed within the AOP pages.
Each page includes basic information that must be reviewed by the user.
In addition, within each page there are capabilities that can be accessed
using the advance buttons.
The AOP page below is an example of the “Advanced” button that provides the
user additional functionality.
Auto-Generated Tags
After you install and configure the AOP, the controller tags are generated. The
tag names are descriptive and automatically generated. This greatly simplifies
programming. The figure below shows an example of the auto-generated tags
for ArmorStart LT.
The following tables provide more clarification regarding the Produce and
Consume assemblies and how they correlate with the auto-generated names.
Instance 156 “Drive Status” - Produced Assembly for Bulletin 294 Starters
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 Reserved - (name):I.ConnectionFault ➊
1 Reserved - (name):I.ConnectionFault ➊
2 Reserved - (name):I.ConnectionFault ➊
3 Reserved - (name):I.ConnectionFault ➊
4 AtReference NetRefStatus NetControlStatus Ready RunningReverse RunningForward WarningPresent TripPresent
5 BrakeStatus DisconnectClosed KeyPadJogging KeyPadHand KeyPadOff KeyPadAuto DLXEnabled
6 OutputFrequency (Low) (xxx.x Hz)
7 OutputFrequency (High) (xxx.x Hz)
8 Pt05 Pt04 Pt03 Pt02 Pt01 Pt00
9
10 Pt07DeviceOut Pt06DeviceOut Pt05DeviceOut Pt04DeviceOut Pt03DeviceOut Pt02DeviceOut Pt01DeviceOut Pt00DeviceOut
11 Pt15DeviceOut Pt14DeviceOut Pt13DeviceOut Pt12DeviceOut Pt11DeviceOut Pt10DeviceOut Pt09DeviceOut Pt08DeviceOut
12 AnalogDeviceOut (low byte)
13 AnalogDeviceOut (high byte)
14
Param3 — OutputCurrent
15
16
Param 4 — OutputVoltage
17
18
Param 5 — DCBusVoltage
19
20
Param 11 — SwitchedVolts (OutputSourceV, IPS units)
21
22
Param 12 — UnswitchedVolts (SensorSourceV, IPS units)
23
24
Param 13 — InternalFanRPM
25
26
Param 14 — ElapesedRunTime
27
28
Param 15 — DriveTemperature
29
30
Param 16 — TripStatus
31
32
Param 17 — WarningStatus
33
➊ PLC Communication Fault Only
The following table provides a brief explanation for the tag function:
Notes:
Bulletin 290E/291E/294E
Programmable Parameters
Electronic Data Sheet (EDS) When a 3rd party PLC is used, an embedded EDS file can be uploaded directly
from the ArmorStart LT. This allows device configuration through 3rd party
tools. EDS files are also available on the internet at: http://www.ab.com/
networks/eds.
Basic Setup Parameters When the RSLogix AOP is not used, Table 22 lists the minimum setup
configurations required for Bulletin 290E/291E or Bulletin 294E. Basic
parameter configuration, status, and diagnostic information can be accessed
from the embedded web browser.
➊ When using the AOP this parameter is configured during module definition on the “General” page.
IMPORTANT All I/O points are configured as inputs, by default. Identify which points
are outputs, when needed for proper operation, using parameter 49
[IOPointConfiguration].
Parameter Groups
Bulletin Common to Bulletin 290E/291E Bulletin
Bulletin 294E Units
290E/291E Units and Bulletin 294E Units 290E/291E Units
Basic Status Trip Status Basic Config
1 PhaseL1Current 1 OutputFreq 16 TripStatus 20 TripLog2 28 FLASetting
2 PhaseL2Current 2 CommandFreq 17 WarningStatus 21 TripLog3 29 OLResetLevel
3 PhaseL3Current 3 OutputCurrent 18 TripLog0 22 TripLog4 30 OverloadClass
4 AverageCurrent 4 OutputVoltage 19 TripLog1 31…40 Reserved
5%ThermalUtilized 5 DCBusVoltage
Bulletin
6 StarterStatus 6 StarterStatus Bulletin 294E Units
7 StarterCommand 7 StarterCommand 290E/291E Units
8 AuxIOStatus 8 AuxIOStatus Trip Status
9 NetworkStatus 9 NetworkStatus
10 DLXControlStatus 10 DLXControlStatus 23 SnapShotL1Amps 23 SnapShotOutFreq
11 OutputSourceV 11 OutputSourceV 24 SnapShotL2Amps 24 SnapShotOutAmps
12 SensorSourceV 12 SensorSourceV 25 SnapShotL3Amps 25 SnapShotOutVolts
13 Reserved 13 InternalFanRPM 26 SnapShotAvgAmps 26 SnapShotBusVolts
14 Reserved 14 ElapsedRunTime 27 SnapShot%Thermal 27 SnapShotDrvTemp
15 Reserved 15 DriveTemperature
Parameter Programming
Each Distributed Motor Controller type will have a common set of parameters
and a set of parameters that pertain to the individual starter type. Parameters
41…68 are common to all ArmorStart LTs.
IMPORTANT Parameter setting changes take effect immediately unless otherwise noted
in the parameter listing. These changes maybe immediate even during the
"running" status.
Bit
Function
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
— — — — — — — — — — — — — — — X TripPresent
— — — — — — — — — — — — — — X — WarningPresent
— — — — — — — — — — — — — X — — RunningForward
— — — — — — — — — — — — X — — — RunningReverse
— — — — — — — — — — — X — — — — Ready
— — — — — — — — — — X — — — — — NetControlStatus
— — — — — — — — — X — — — — — — Reserved
— — — — — — — — X — — — — — — — CurrentFlowing
— — — — — — — X — — — — — — — — DLXEnabled
— — — — — — X — — — — — — — — — KeyPadAuto
— — — — — X — — — — — — — — — — KeyPadOff
— — — — X — — — — — — — — — — — KeyPadHand
— — X X — — — — — — — — — — — — Reserved
— X — — — — — — — — — — — — — — DisconnectClosed
X — — — — — — — — — — — — — — — Reserved
Bit
Function
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
— — — — — — — — — — — — — — — X RunForward
— — — — — — — — — — — — — — X — RunReverse
— — — — — — — — — — — — — X — — ResetFault
— — — — — — — — X X X X X — — — Reserved
— — — — — — — X — — — — — — — — Out00
— — — — — — X — — — — — — — — — Out01
— — — — — X — — — — — — — — — — Out02
— — — — X — — — — — — — — — — — Out03
— — — X — — — — — — — — — — — — Out04
— — X — — — — — — — — — — — — — Out05
X X — — — — — — — — — — — — — — Reserved
Bit
Function
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
— — — — — — — — — — — — — — — X Pt00
— — — — — — — — — — — — — — X — Pt01
— — — — — — — — — — — — — X — — Pt02
— — — — — — — — — — — — X — — — Pt03
— — — — — — — — — — — X — — — — Pt04
— — — — — — — — — — X — — — — — Pt05
X X X X X X X X X X — — — — — — Reserved
Bit
Function:
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
— — — — — — — — — — — — — — — X ExplicitCnxn
— — — — — — — — — — — — — — X — I/OConnection
— — — — — — — — — — — — — X — — ExplicitCnxnFlt
— — — — — — — — — — — — X — — — IOCnxnFault
— — — — — — — — — — — X — — — — IOCnxnIdle
— — — — — — — — — — X — — — — — Reserve
— — — — — — — — — X — — — — — — DLREnabled
— — — — — — — — X — — — — — — — DLRFault
X X X X X X X X — — — — — — — — Reserved
Bit
Function:
7 6 5 4 3 2 1 0
— — — — — — — X RunForward
— — — — — — X — RunReverse
— — — — — X — — Out00
— — — — X — — — Out01
— — — X — — — — Out02
— — X — — — — — Out03
— X — — — — — — Out04
X — — — — — — — Out05
Bit
Function
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
— — — — — — — — — — — — — — — X OverloadTrip
— — — — — — — — — — — — — — X — PhaseLossTrip
— — — — — — — — — — — — — X — — UnderPowerTrip
— — — — — — — — — — — — X — — — SensorShortTrip
— — — — — — — — — — — X — — — — PhaseImbalanceTrip
— — — — — — — — — — X — — — — — NonVolMemoryTrip
— — — — — — — — — X — — — — — — Reserved
— — — — — — — — X — — — — — — — JamTrip
— — — — — — — X — — — — — — — — StallTrip
— — — — — — X — — — — — — — — — UnderloadTrip
— — — X X X — — — — — — — — — — Reserved
— — X — — — — — — — — — — — — — OutputShortTrip
— X — — — — — — — — — — — — — — UserDefinedTrip
X — — — — — — — — — — — — — — — HardwareFltTrip
Bit
Function
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
— — — — — — — — — — — — — — — X OverloadWarning
— — — — — — — — — — — — — — X — Reserved
— — — — — — — — — — — — — X — — UnderPowerWarn
— — — — — — — — — — — — X — — — Reserved
— — — — — — — — — — — X — — — — PhaseImbalanceWarn
— — — — — — — — — X X — — — — — Reserved
— — — — — — — — X — — — — — — — JamWarning
— — — — — — — X — — — — — — — — Reserved
— — — — — — X — — — — — — — — — UnderloadWarning
— — X X X X — — — — — — — — — — Reserved
— X — — — — — — — — — — — — — — UnswitchedPwrWarn
X — — — — — — — — — — — — — — ConfigWarning
Table 23 - FLA Setting Ranges and Default Values (with indicated setting precision)
FLA Current Range (A)
Default Value
CatNo 460V AC Minimum Value Maximum Value
290E/1_-FA_* 3 Hp 0.24 3.5 0.24
290E/1_-FB_* 5 Hp 1.1 7.6 1.1
Bit
Function
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
— — — — — — — — — — — — — — — X OverloadTrip
— — — — — — — — — — — — — — X — PhaseLossTrip
— — — — — — — — — — — — — X — — UnderPowerTrip
— — — — — — — — — — — — X — — — SensorShortTrip
— — — — — — — — — — — X — — — — PhaseImbalanceTrip
— — — — — — — — — — X — — — — — NonVolMemoryTrip
— — — — — — — — — X — — — — — — Reserved
— — — — — — — — X — — — — — — — JamTrip
— — — — — — — X — — — — — — — — StallTrip
— — — — — — X — — — — — — — — — UnderloadTrip
— — — X X X — — — — — — — — — — Reserved
— — X — — — — — — — — — — — — — OutputShortTrip
— X — — — — — — — — — — — — — — UserDefinedTrip
X — — — — — — — — — — — — — — — HardwareFltTrip
The highlighted functions are enabled by default.
Bit
Function
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
— — — — — — — — — — — — — — — X OverloadWarning
— — — — — — — — — — — — — — X — Reserved
— — — — — — — — — — — — — X — — UnderPowerWarn
— — — — — — — — — — — — X — — — Reserved
— — — — — — — — — — — X — — — — PhasImbalanceWarn
— — — — — — — — — X X — — — — — Reserved
— — — — — — — — X — — — — — — — JamWarning
— — — — — — — X — — — — — — — — Reserved
— — — — — — X — — — — — — — — — UnderloadWarning
— — X X X X — — — — — — — — — — Reserved
— X — — — — — — — — — — — — — — UnswitchedPwrWarn
X — — — — — — — — — — — — — — — ConfigWarning
Bit
Function
5 4 3 2 1 0
— — — — — X Pt00
— — — — X — Pt01
— — — X — — Pt02
— — X — — — Pt03
— X — — — — Pt04
X — — — — — Pt05
Advanced Configuration
OLWarningLevel Parameter Number 69
Access Rule GET
This parameter determines the Overload
Warning Level in % Thermal Capacity Used Data Type USINT
(%TCU).
Group Advanced Config.
Units %TCU
Minimum Value 0
Maximum Value 100
Default Value 85
Bit
Function
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
— — — — — — — — — — — — — — — X TripPresent
— — — — — — — — — — — — — — X — WarningPresent
— — — — — — — — — — — — — X — — RunningForward
— — — — — — — — — — — — X — — — RunningReverse
— — — — — — — — — — — X — — — — Ready
— — — — — — — — — — X — — — — — NetControlStatus
— — — — — — — — — X — — — — — — NetRefStatus
— — — — — — — — X — — — — — — — AtReference
— — — — — — — X — — — — — — — — DLXEnabled
— — — — — — X — — — — — — — — — KeyPadAuto
— — — — — X — — — — — — — — — — KeyPadOff
— — — — X — — — — — — — — — — — KeyPadHand
— — — X — — — — — — — — — — — — KeyPadJogging
— — X — — — — — — — — — — — — — Reserved
— X — — — — — — — — — — — — — — DisconnectClosed
X — — — — — — — — — — — — — — — BrakeStatus
Bit
Function
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
— — — — — — — — — — — — — — — X RunningForward
— — — — — — — — — — — — — — X — RunningReverse
— — — — — — — — — — — — — X — — ResetFault
— — — — — — — — — — — — X — — — JogForward
— — — — — — — — — — — X — — — — JogReverse
— — — — — — — — X X X — — — — — Reserved
— — — — — — — X — — — — — — — — Out00
— — — — — — X — — — — — — — — — Out01
— — — — — X — — — — — — — — — — Out02
— — — — X — — — — — — — — — — — Out03
— — — X — — — — — — — — — — — — Out04
— — X — — — — — — — — — — — — — Out05
— X — — — — — — — — — — — — — — Accel2
X — — — — — — — — — — — — — — — Decel2
Bit
Function:
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
— — — — — — — — — — — — — — — X Pt00
— — — — — — — — — — — — — — X — Pt01
— — — — — — — — — — — — — X — — Pt02
— — — — — — — — — — — — X — — — Pt03
— — — — — — — — — — — X — — — — Pt04
— — — — — — — — — — X — — — — — Pt05
X X X X X X X X X X — — — — — — Reserved
Bit
Function:
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
— — — — — — — — — — — — — — — X ExplicitCnxn
— — — — — — — — — — — — — — X — IOConnection
— — — — — — — — — — — — — X — — ExplicitCnxnFlt
— — — — — — — — — — — — X — — — IOCnxnFault
— — — — — — — — — — — X — — — — IOCnxnIdle
— — — — — — — — — — X — — — — — Reserve
— — — — — — — — — X — — — — — — DLREnabled
— — — — — — — X — — — — — — — DLRFlt
X X X X X X X X — — — — — — — — Reserved
Bit
Function:
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
— — — — — — — — — — — — — — — X RunForward
— — — — — — — — — — — — — — X — RunReverse
— — — — — — — — — — — — — X — — Out00
— — — — — — — — — — — — X — — — Out01
— — — — — — — — — — — X — — — — Out02
— — — — — — — — — — X — — — — — Out03
— — — — — — — — — X — — — — — — Out04
— — — — — — — — X — — — — — — — Out05
— — — — — — — X — — — — — — — JogForward
— — — — — — X — — — — — — — — — JogReverse
— — — — — X — — — — — — — — — — Accel2
— — — — X — — — — — — — — — — — Decel2
— — — X — — — — — — — — — — — — Command Freq
X X X — — — — — — — — — — — — — Reserved
Bit
Function
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
— — — — — — — — — — — — — — — X OverloadTrip
— — — — — — — — — — — — — — X — PhaseShortTrip
— — — — — — — — — — — — — X — — UnderPowerTrip
— — — — — — — — — — — — X — — — SensorShortTrip
— — — — — — — — — — — X — — — — OverCurrentTrip
— — — — — — — — — — X — — — — — NonVolMemoryTrip
— — — — — — — — — X — — — — — — ParamSyncTrip
DCBusTrip/
— — — — — — — — X — — — — — — — OpenDisconnect
— — — — — — — X — — — — — — — — StallTrip
— — — — — — X — — — — — — — — — OverTemperature
— — — — — X — — — — — — — — — — GroundFault
— — — — X — — — — — — — — — — — RestartRetries
— — — X — — — — — — — — — — — — DriveHdwFault
— — X — — — — — — — — — — — — — OutputShortTrip
— X — — — — — — — — — — — — — — UserDefinedTrip
X — — — — — — — — — — — — — — — HardwareFltTrip
Bit
Function
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
— — — — — — — — — — — — — — X X Reserved
— — — — — — — — — — — — — X — — UnderPowerWarn
— — — — — — — — — — X X X — — — Reserved
— — — — — — — — — X — — — — — — DriveParamInit
— — X X X X X X X — — — — — — — Reserved
— X — — — — — — — — — — — — — — UnswitchedPwrWarn
X — — — — — — — — — — — — — — — ConfigWarning
Set to the motor nameplate rated voltage. Group Motor and Control
Units V AC
Minimum Value 35
Maximum Value 460
Default Value 460
Valid Stop Mode for the Bulletin 294E ArmorStart LT are the following: Related Parameters
0 = RampToStop, “Stop” command clears active fault Access Rule GET/SET
1 = Coast to Stop, “Stop” command clears active fault
2 = DCBrake, DC Injection Braking Stop, “Stop” command clears active fault Data Type UINT
3 = DCBrakeAuto, DC Injection Stop with Auto Shutoff
Standard DC Injection Braking for value set in Parameter 75 (DC Brake Time) Group Motor and Control
or Units —
Drive shuts off if current limit is exceeded.
Minimum Value 0
Maximum Value 3
Default Value 0
Sets the highest frequency the drive will Data Type UINT
output. Group Speed Control
Units Hz
Minimum Value 0.0
Maximum Value 400
Default Value 60
D ec
n
atio
eler
Minimum Value 0.0
eler
Speed
atio
Acc
n
Maximum Value 600.0
0
Accel Time Decel
0 Time 1 Time 1
Default Value 10.0
eler
Speed
atio
Acc
Figure 53 - S Curve
Bit
Function
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
— — — — — — — — — — — — — — — X OverloadTrip
— — — — — — — — — — — — — — X — PhaseShortTrip
— — — — — — — — — — — — — X — — UnderPowerTrip
— — — — — — — — — — — — X — — — SensorShortTrip
— — — — — — — — — — — X — — — — OverCurrentTrip
— — — — — — — — — — X — — — — — NonVolMemoryTrip
— — — — — — — — — X — — — — — — ParamSyncTrip
DCBusTrip/
— — — — — — — — X — — — — — — — OpenDisconnect
— — — — — — — X — — — — — — — — StallTrip
— — — — — — X — — — — — — — — — OverTemperature
— — — — — X — — — — — — — — — — GroundFault
— — — — X — — — — — — — — — — — RestartRetries
— — — X — — — — — — — — — — — — DriveHdwFault
— — X — — — — — — — — — — — — — OutputShortTrip
— X — — — — — — — — — — — — — — UserDefinedTrip
X — — — — — — — — — — — — — — — HardwareFltTrip
Bit
Function
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
— — — — — — — — — — — — — — X X Reserved
— — — — — — — — — — — — — X — — UnderPowerWarn
— — — — — — — — — — X X X — — — Reserved
— — — — — — — — — X — — — — — — DriveParamInit
— — X X X X X X X — — — — — — — Reserved
— X — — — — — — — — — — — — — — UnswitchedPwrWarn
X — — — — — — — — — — — — — — — ConfigWarning
Bit
Function
5 4 3 2 1 0
— — — — — X Pt00
— — — — X — Pt01
— — — X — — Pt02
— — X — — — Pt03
— X — — — — Pt04
X — — — — — Pt05
Advanced Configuration
AccelTime2 Parameter Number 69
When active, sets the rate of acceleration for all speed increases except for jog. Related Parameters 36
Maximum Freq- = Accel Rate
-------------------------------------
Accel Time Access Rule GET/SET
Speed
atio
Acc
eler
Speed
atio
Acc
Frequency Command
Frequency
Drive Output
Frequency
2x Skip
Skip Frequency Frequency Band
Time
ATTENTION:
Volts Speed
Speed
Volts Speed
}
[DC Brake Time]
}
Spee
}
d
Time Time
Stop Command Stop Command
Compensation
Parameter Number 79
Enables/disables correction options
that may improve problems with Access Rule GET/SET
motor instability,
0 = Disabled Data Type UINT
1 = Electrical (Default)
Some drive/motor combinations have
inherent instabilities which are exhibited Group Advanced Config.
as non-sinusoidal motor currents. This
setting attempts to correct this condition
Units —
2 = Mechanical
Some motor/load combinations have
mechanical resonances which can be Minimum Value 0
excited by the drive current regulator. This
setting slows down the current regulator
response and attempts to correct this Maximum Value 3
condition.
3 = Both Default Value 1
Clear an Overvoltage, Undervoltage, or Heatsink OvrTmp Fault without Restarting the Drive
[Motor NP Hertz]
1/2
Settings
5-14
0 50 100
%P29 [Motor NP Hertz]
IMPORTANT For parameter 90 and 91 the value of the threshold can be set beyond the
operational maximum limit of the product, or at a level which may cause
multiple transitions during operation. Threshold values near the operational
levels should be avoided.
Notes:
Diagnostics
Overview This chapter describes the fault diagnostics of the ArmorStart LT Distributed
Motor Controller and the conditions that cause various faults to occur.
Status LEDs and Reset Figure 57 - Status and Diagnostic LEDs and Reset
Fault Diagnostics Fault diagnostics capabilities built in the ArmorStart LT Distributed Motor
Controller are designed to help you pinpoint a problem for easy troubleshooting
and quick restarting.
Protection Faults
LED Flash Bit Enumeration Bulletin 290E/291E Trip Status Bits Bulletin 294E Trip Status Bits
1 0 OverloadTrip ➊ OverloadTrip ➊
2 1 PhaseLossTrip PhaseLShortTrip
3 2 UnderPowerTrip ➊ UnderPowerTrip ➊
4 3 SensorShortTrip ➊ SensorShortTrip ➊
5 4 PhaseImbalTrip OverCurrentTrip
6 5 NonVolMemoryTrip ➊ NonVolMemoryTrip ➊
7 6 reserved ParamSyncTrip ➊
8 7 JamTrip DCBusOrOpenDiscnnct ➊
9 8 StallTrip StallTrip ➊
10 9 UnderloadTrip OverTemperature ➊
11 10 reserved GroundFault ➊
12 11 reserved RestartRetries
13 12 reserved DriveHdwFault ➊
LED Flash Bit Enumeration Bulletin 290E/291E Trip Status Bits Bulletin 294E Trip Status Bits
14 13 OutputShortTrip ➊ OutputShortTrip ➊
15 14 UserDefinedTrip UserDefinedTrip
16 15 HardwareFltTrip ➊ HardwareFltTrip ➊
There are two Protection Fault Reset modes: manual and automatic. When
parameter 41 “ProtFltResetMode” is set to the value 0=Manual mode, a manual
fault reset must occur before the fault is reset. When manual reset mode faults are
latched until a fault reset command has been detected either locally or remotely.
A Manual reset operation is either remotely via the network, locally via the
“Reset” button on the front keypad, or via a DeviceLogix program. A rising edge
(0 to 1 transition) of the “ResetFault” tag will attempt a reset. A rising edge of the
parameter 44 “ProtectFltReset” will attempt a reset. A press of the local blue
“Reset” button on the front keypad will attempt a reset. A rising edge of the
“ResetFault” DeviceLogix tag will attempt a reset. When “ProtFltResetMode” is
set to the value 1=Automatic, “auto-reset” faults are cleared automatically when
the fault condition goes away.
Quick Reference The LEDs on the front of the ArmorStart LT provide an indication as to the
health of the device and network. The following is a brief troubleshooting guide.
Troubleshooting
Table 26 - LED Status Indication
Status LED Description Recommended Action
PWR (Control) Status Indicator
Off The PWR LED is not illuminated at all. Verify power is connected and with proper polarity.
Green Voltage is present. No action
Flashing Yellow Power has fallen below minimum acceptable level. Verify that the control power is between 19.2 and 26V DC.
RUN/FLT Status Indicator
Off The RUN/FLT LED is not illuminated when a Run command has Verify that PLC is in Run mode. Verify that the correct run
been issued. bit is being controlled. Verify that a stop condition does
not exist.
Green Valid start command No action
Flashing Red Protection fault Count flashes and refer to Table 27 and 28.
MS – Module Status Indicator
Off The MS LED is not illuminated. Check to make sure the product is properly wired and
configured on the network.
Steady Green Device configured and operational No action
Flashing Green Device IP Address has not been configured. . Configure IP Address
Flashing Red Resettable protection fault exists. Verify fault by reviewing [TripStatus] Parameter 16 and
[TripLog0…4] Parameters 18…22. Correct and press the
blue reset button.
Solid Red Non-resettable protection fault exists. Verify fault by reviewing [TripStatus] Parameter 16 and
[TripLog0…4] Parameters 18…22. Correct and cycle
control power (switched and unswitched).
Flashes Green-Red Self-test on power up No action
NS – Network Status Indicator
Off The NS LED is not illuminated. Check to make sure the product is properly wired
and configured on the network.
Steady Green CIP connection is established. No action
Flashing Green An IP address is configured, but no CIP connections are Check to make sure the product is properly wired
established, and an Exclusive Owner connection has not timed
out. and configured on the network.
Flashing Red Connection has timed out. Check to make sure the PLC is operating correctly and that
there are no media/cabling issues. Check to see if other
network devices are in a similar state.
Solid Red Duplicate IP address detected Check for node address conflict and resolve.
Flashes The device has not completed the initialization, is not on an Remove or change the IP address of the conflicting device.
Green-Red active network, or has not finished self test at power up.
LS1 and LS2 Port Activity/Status
Off No link established. Verify network connection.
Green Link established at 100 Mbps. No action
Flashing Green Transmit or receive activity present at 100 Mbps. No action
Yellow Link established at 10 Mbps. No action
Fault LED Indications The RUN/FLT LED will blink red in a prescribed fault pattern when a
protection fault (trip) condition is present. The LED will blink in 0.5 second
intervals when indicating a fault code. Once the pattern is finished, there will be a
2 second pause after which the pattern will be repeated.
Bulletin 290E/291E faults are detected by the main control board. When the
[ProtFltResetMode] Parameter 41 is set to the value 1=Automatic, the auto
resettable faults in the table will reset automatically when the fault condition is
no longer present.
Table 27 - Fault LED Indicator for Bulletin 290E/291E
Blink Bulletin 290E/291E
Pattern Auto-Reset Disable Default Trip Status Description Action
1 Yes No On Overload Trip The load has drawn excessive current and Verify that the load is operating correctly and is
based on the trip class selected, the device properly set-up, [FLASetting] Parameter 28,
has tripped. [OLResetLevel] Parameter 29. The fault may be reset
only after the motor has sufficiently cooled.
2 Yes Yes Off Phase Loss Trip The ArmorStart LT has detected a missing This fault is generated by monitoring the relative
phase. levels of the 3-phase currents. Correct phase
imbalance or disable fault using [ProtectFltEnable]
Parameter 42.
3 Yes No On Under Power Trip The ArmorStart LT detected switched or Check control voltage, wiring, and proper polarity (A1/
unswitched power dip below 19.2 V for A2/A3 terminal).
greater than 50 ms, or 13 V for greater
than 4 ms.
4 No No On Sensor Short Trip This error indicates a shorted sensor, Correct, isolated or remove wiring error prior to
shorted input device, wiring input restarting the system.
mistakes.
5 Yes Yes Off Phase Imbalance Trip The ArmorStart LT has detected a current Check the power system for current imbalance and
imbalance in one of the phases. correct. Correct phase imbalance or disable fault using
[ProtectFltEnable] Parameter 42.
6 No No On Non-Volatile Memory This is a major fault, which renders the 1. If the fault was initiated by a transient, power
Trip ArmorStart LT inoperable. Possible causes cycling may clear the problem.
of this fault are transients induced during 2. This fault may be reset by a [SetToDefaults]
Non-Volatile Storage (NVS) routines. Parameter 68.
3. Replacement of the ArmorStart LT may be required.
7 — — — Reserved — —
Bulletin 294E Faults Bulletin 294E faults are detected by the main control board and/or the internal
drive. When there is an internal drive fault, the main control board simply polls
the drive for the existence of faults and reports the fault state. Writing a value to
[ProtFltResetMode] Parameter 41 determines auto-reset ability for some faults.
The auto-reset ability of faults that are generated on the drive are controlled by
[AutoRestartTries] Parameter 84 and [AutoRestar Delay] Parameter 85.
Auto Reset
Table 28 - Auto Reset Ability
Auto Reset Function Description
Drive Control Auto-Reset/Run When this type of fault occurs, and [AutoRestartTries] Parameter 84 is set to a value greater than “0,” a user-configurable timer,
[AutoRestartDelay] Parameter 85, begins. When the timer reaches zero, the drive attempts to automatically reset the fault. If the
condition that caused the fault is no longer present, the fault will be reset and the drive will be restarted.
No User Action Needed This type of fault requires drive or motor repair, or is caused by wiring or programing errors. The cause of the fault must be
corrected before the fault can be cleared via manual or network reset. A rising edge of the “Fault Reset” DeviceLogix bit will also
clear the fault.
Yes [ProtFltResetMode] Faults are cleared automatically when the fault condition goes away.
Parameter 41 = 1 which
is automatic
➊ In the case of a Disconnect open fault, reclosing the disconnect will cause a reset to be issued.
Specifications
Bulletin 290E/291E
Electrical Ratings
Application Three-phase
Number of Poles 3
Input Power Terminals L1, L2, L3
Motor Power Terminals T1, T2, T3
PE (Earth Ground) Terminal 4 PE terminals
Maximum Rated Operating Voltage 400Y/230…480Y/277 (-15%, +10%)
Rated Impulsed Voltage (Uimp) 4 kV
Dielectric Withstand UL: 1960V AC, IEC: 2500V AC
Operating Frequency 50/60 Hz (±10%)
Cat. No. Hp (kW) Overload Range
Power Circuit 290_-___-A-*
Maximum Rated Operating 2 (1.5) 0.24…3.5 A
291_-___-A-*
Current
290_-___-B-*
5 (3) 1.1…7.6 A
291_-___-B-*
Overload Type Solid-state I2T
[10], 15, 20 with thermal memory retention
Trip Class
(see Motor Overload Trip Curves)
Trip Rating — Full Load 120% of FLC
Current (FLC)
Reset Mode Automatic or manual
Overload Reset Level 1…100% TCU
Overvoltage Category III
Electrical Ratings
Power Supply NEC Class 2
Rated Operating Voltage 24V DC (+10%, -20%)
Overvoltage Protection Reverse-polarity protected
Voltage 19.2…26.4V DC
Nominal Current 150 mA
Power 3.6 W
Unswitched Power Supply Input Current (each) ➊ 50 mA
Requirements
Maximum Current 450 mA
Maximum Power 14.4 W
Peak Inrush ➋ <5 A for 35 ms
Voltage 19.2…26.4V DC
Nominal Current 125 mA
Control Circuit
Power 3W
(External Source)
Switched Power Supply Output Current (each) ➊ 500 mA
Requirements
Maximum Current 1.625 A
Maximum Power 42 W
Peak Inrush ➋ <5 A for 35 ms
Voltage 19.2…26.4V DC
Nominal Current 275 mA
Power 6.6 W
Environmental Ratings
Operating Temperature Range -20…+50 °C (-4…+122 °F)
Storage and Transportation Temperature Range -25...+85 °C (-13…+185 °F)
Altitude 2000 m
Humidity 5…95% (non-condensing)
Pollution Degree 3
Enclosure Ratings IP66/UL Type 4/12 ➊
Approximate Shipping Weight 4.6 kg (10 lb)
Mechanical Ratings
Operational 30 G, exceeds IEC 60947-1
Resistance to Shock
Non-Operational 50 G, exceeds IEC 60947-1
Operational 2.5 G, tested to MIL-STD-810G, exceeds IEC 60947-1
Resistance to Vibration
Non-Operational 5 G, tested to MIL-STD-810G, exceeds IEC 60947-1
Disconnect Lock Out Maximum of 3/8 in. (9.5 mm) diameter lock shackle or hasp
Disconnect LOTO Locks Up to 2 locks or hasps are supported
Disconnect Mechanical Life 200 000 operations
Contractor Utilization Category
AC-1, AC-3, AC-4 (refer to Life Load Curves)
(IEC)
Contactor Opening Delay 8…12 ms
Contactor Closing Delay 18…40 ms
Minimum Off Time 200 ms
Contactor Mechanical Life 15 million operations
Power Terminals Motor Terminals Control Terminals PE/Ground
(2) #18 …#10 AWG #18…#10 AWG (2) #18 …#10 AWG (2) #16 …#10 AWG
Wire Size➋
(0.8…5.2 mm2) per terminal (0.8…5.2 mm2) per terminal (0.8…5.2 mm2) per terminal (1.3…5.2 mm2) per terminal
Wire Type Multi-strand copper wire
Tightening Torque 10.6 ± 2 lb•in (1.2 ± 0.2 N•m) 18 ± 2 lb•in (2 ± 0.2 N•m)
Wire Strip Length 0.35 ± 0.01 in. (9 ± 2 mm)
Power Rating 600V AC/25 Amp 600 V AC/10 Amp 600 V AC/10 Amp —
Communication Ratings
Rated Insulation Voltage 250V
Operating Dielectric Withstand UL/NEMA: 1500V AC, IEC: 2000V AC
EtherNet/IP ODVA – Conformance Testing EtherNet/IP Interoperability Performance – Per A9 PF 2.1
Ethernet Communication Rate 10/100 Mbps, half or full-duplex
Ethernet Ports 2 (embedded switch)
Ethernet Network Topologies Supported Star, Tree, Linear, and Ring
Device Level Ring Support Beacon Performance, IEEE 1588 Transparent Clock
Ethernet Connector M12, D code, female, with Ethernet keying, 4 Pin
Ethernet Cable Category 5e: Shielded or unshielded
IP Configuration Static, DHCP, or BootP
EtherNet/IP DHCP Timeout 30 s
Data Transported over both TCP and UDP
500 packets-per-second (2000 μs), Tx
Packet Rate (pps)
500 packets-per-second (2000 μs), Rx
Consume Instance (Command) Default of 3 words (Instance 150)
Produce Instance (Status) Default of 14 words (Instance 152)
Message Support Unicast or Multicast
Address Conflict Detection (ACD) IP v4 Address Conflict Detection for EtherNet/IP devices
Sockets 150 maximum
Security Login and password configurable
E-mail Support Simple Mail Transfer Protocol (SMTP)
Web Server Webpage Features Status, diagnostics, configuration
Concurrent Sessions 20
Web Server HTTP 1.1
Concurrent TCP Connections Maximum of 15 encapsulated messages over both TCP and UDP
Supports up to 2 Class 1 CIP connections [Exclusive owner (data) or
Maximum I/O Connections (CIP Class 1) listen-only]. One connection per PLC. Listen only connection requires a
data connection to be established.
Network Connections Maximum Concurrent Explicit Messages (CIP Class 3) 6
Class 1 Connection API 2…3200 ms
Class 3 Connection API 100…10 000 ms
Request Packet Interval (RPI) 20 ms default (2 ms minimum)
Class 10
Class 15
Approximate Trip Time [s]
Cold
Hot
Class 20
Approximate Trip Time [s]
Cold
Hot
10
Contact Life (millions of operations)
100-K09
(Used with ArmorStart LT)
0.1
0.01
1 10 100
Rated Current Ie AC-3 [A]
0.1
0.01
0.1 1 10
Rated Current Ie AC-4 [A]
Bulletin 294E
Electrical Ratings
Application Three-phase
Number of Poles 3
Input Power Terminals L1, L2, L3
Motor Power Terminals T1, T2, T3
Power Circuit PE (Earth Ground) Terminal 4 PE terminals
Maximum Rated Operating Voltage 400Y/230…480Y/277 (-15%, +10%)
Rated Impulsed Voltage (Uimp) 4 kV
Dielectric Withstand UL: 1960V AC, IEC: 2500V AC
Operating Frequency 50/60 Hz (±10%)
Electrical Ratings
Power Supply NEC Class 2
Rated Operating Voltage 24V DC (+10%, -20%)
Overvoltage Protection Reverse-polarity protected
Voltage 19.2…26.4V DC
Nominal Current 150 mA
Power 3.6 W
Unswitched Power Supply Input Current (each) ➊ 50 mA
Requirements
Maximum Current 450 mA
Maximum Power 14.4 W
Peak Inrush ➋ <5 A for 35 ms
Voltage 19.2…26.4V DC
Nominal Current 125 mA
Control Circuit
Power 3W
(External Source)
Switched Power Supply Output Current (each) ➊ 500 mA
Requirements
Maximum Current 1.625 A
Maximum Power 42 W
Peak Inrush ➋ <5 A for 35 ms
Voltage 19.2…26.4V DC
Nominal Current 275 mA
Power 6.6 W
Environmental Ratings
-20…+40°C (-4…+104°F)
Operating Temperature Range 50 °C (122 °F) without derating, when properly rated line reactors are installed
in branch circuit.
Storage and Transportation
–25...+85 °C (–13…+185 °F)
Temperature Range
Altitude 1000 m
Humidity 5…95% (non-condensing)
Pollution Degree 3
Enclosure Ratings IP66/UL Type 4/12 ➊
Approximate Shipping Weight 7.3 kg (16 lb)
➊ IP66/UL Type 4 is available with gland options G1-3. IP66/ UL Type 4/12 available with G1 and G3 gland option.
Mechanical Ratings
Operational 30 G (exceeds IEC 61800-5-1)
Resistance to Shock
Non-Operational 50 G (exceeds IEC 61800-5-1)
Operational 2.5 G, MIL-STD-810G, (exceeds IEC 61800-5-1)
Resistance to Vibration
Non-Operational 5 G, MIL-STD-810G, (exceeds IEC 61800-5-1)
Disconnect Lock Out Maximum of 3/8 in. (9.5 mm) diameter lock shackle or hasp
Disconnect LOTO Locks Up to 2 locks or hasps are supported
Disconnect Mechanical Life 200 000 operations
Power Terminals Motor Terminals Control Terminals PE/Ground Source Brake
(2) #18 …#10 AWG #18…#10 AWG (2) #18 …#10 AWG (2) #16 …#10 AWG #16 …#10 AWG
Wire Size ➊ (0.8…5.2 mm2) per (0.8…5.2 mm2) per (0.8…5.2 mm2) per (1.3…5.2 mm2) per (1.0…4.0 mm2) per
terminal terminal terminal terminal terminal
Wire Type Multi-strand copper wire
18 ± 2 lb•in 4.8 ± 2 lb•in
Tightening Torque 10.6 ± 2 lb•in (1.2 ± 0.2 N•m) (2 ± 0.2 N•m) (0.5 ± 0.2 N•m)
Wire Strip Length 0.35 ± 0.01 in. (9 ± 2 mm)
Power Rating 600V AC/25 Amp 600V AC/10 Amp 600V AC/10 Amp — 600V AC/10 Amp
Communication Ratings
Rated Insulation Voltage 250V
Operating Dielectric Withstand UL/NEMA: 1500V AC, IEC: 2000V AC
DeviceNet Supply Voltage Rating Range 11…25V DC, 24V DC nominal
DeviceNet Input Current 50 mA @ 24V DC
DeviceNet Input Current Surge 500 mA peak inrush
Baud Rates 125, 250, 500 kbps
500 m (1630 ft) @ 125 kbps
Distance Maximum 200 m (656 ft) @ 250 kbps
100 m (328 ft) @ 500 kbps
Auto-Baud Rate Identification Yes
"Group 2 - Slave Only" Device Type Yes
DeviceNet
Polled I/O Messaging Yes
Change of State Messaging Yes
Cyclic Messaging Yes
Explicit Messaging Yes
Full Parameter Object Support Yes
Group 4 - Off-Line Node Recovery Messaging Yes
Configuring Consistency Value Yes
Unconnected Messaging Manager (UCMN) Yes
Communication Ratings
EtherNet/IP ODVA - Conformance Testing EtherNet/IP Interoperability Performance – Per A9 PF 2.1
Ethernet Communication Rate 10/100 Mbps, half or full-duplex
Ethernet Ports 2 (embedded switch)
Ethernet Network Topologies Supported Star, Tree, Linear, and Ring
Device Level Ring Support Beacon Performance, IEEE 1583 Transparent Clock
Ethernet Connector M12, D code, female, with Ethernet keying, 4 Pin
Ethernet Cable Category 5e: Shielded or unshielded
IP Configuration Static, DHCP, or BootP
EtherNet/IP DHCP Timeout 30 s
Data Transported over both TCP and UDP
500 packets-per-second (2000 μs), Tx
Packet Rate (pps)
500 packets-per-second (2000 μs), Rx
Consume Instance (Command) Default of 4 words (Instance 154)
Produce Instance (Status) Default of 16 words (Instance 156)
Message Support Unicast or Multicast
Address Conflict Detection (ACD) IP v4 Address Conflict Detection for EtherNet/IP devices
Sockets 150 maximum
Security Login and password configurable
E-mail Support Simple Mail Transfer Protocol (SMTP)
Web Server Webpage Features Status, diagnostics, configuration
Concurrent Sessions 20
Web Server HTTP 1.1
Concurrent TCP Connections Maximum of 5 encapsulated messages over both TCP and UDP
Supports up to 2 Class 1 CIP connections [Exclusive owner (data) or
Maximum I/O Connections (CIP Class 1) listen-only]. One connection per PLC. Listen-only connection
requires a data connection to be established.
Network Connections Maximum Concurrent Explicit Messages (CIP Class 3) 6
Class 1 Connection API 2…3200 ms
Class 3 Connection API 100…10 000 ms
Request Packet Interval (RPI) 20 ms default (2 ms minimum)
Introduction Each ArmorStart LT motor controller is listed for group installation. This
appendix explains how to use this listing to apply ArmorStart LT motor
controllers in multiple-motor branch circuits according to 7.2.10.4(1) and
7.2.10.4(2) of NFPA 79, Electrical Standard for Industrial Machinery.
From the perspective of the ArmorStart LT product family, being listed for group
installation means one set of fuses or one circuit breaker may protect a branch
circuit that has two or more of these motor controllers connected to it. This
appendix refers to this type of branch circuit as a multiple-motor branch circuit.
The circuit topology shown in Figure 58, is one configuration, but not the only
possible configuration, of a multiple-motor branch circuit. In these circuits, a
single set of fuses (or a single circuit breaker) protects multiple motors, their
controllers and the circuit conductors. The motors may be any mixture of power
ratings and the controllers may be any mixture of motor controller technologies
(magnetic motor controllers and variable-frequency AC drive controllers).
This appendix addresses only NFPA 79 applications. This is not because these
products are only suitable for industrial machinery, but because industrial
machinery is their primary market. In fact, while all versions of the ArmorStart
LT products may be applied on industrial machinery, the versions that have
the Conduit Entrance Gland Plate Option may also be used in applications
governed by NFPA 70, National Electrical Code (NEC), (see “ArmorStart LT
Product Family”).
In the 2012 Edition of NFPA 79, motor controllers that are listed for group
installation may be installed in multiple-motor branch circuits according to either
of two alternative sets of requirements. The first is found in 7.2.10.4(2), the
second in 7.2.10.4(3). The requirements of 7.2.10.4(3) are similar to those in
430.53(C) of NFPA 70, while the requirements of 7.2.10.4(2) are found only in
NFPA 79. This appendix explains the requirements of 7.2.10.4(2), rather than
those of 7.2.10.4(3), because this is the simpler method to use when applying the
ArmorStart LT family of motor controllers.
The user must determine the requirements – NFPA 79 or NFPA 70 – to use for
the application. When making this determination, it is necessary to understand
the ArmorStart LT product characteristics and useful to understand the
definition of industrial machinery. The section of this appendix, “ArmorStart LT
Product Family”, specifies whether a motor controller is suitable for installation
according to NFPA 79 or NFPA 70 (or both). The definition of industrial
These conventions are used throughout this appendix. First, although all of the
equipment is connected to a three-phase electrical supply, all of the figures are
shown as one-line diagrams. Second, although all of the ArmorStart LT motor
controllers are listed for group installation with both fuses and a specific family
of inverse time circuit breakers, this appendix considers only fuses. This is done to
avoid repetitive explanations with minor, but necessary qualifications, for circuit
breakers. Generally, the principles for selecting the fuses also apply to selecting
inverse time circuit breakers. Third, all references unless indicated otherwise, are
to NFPA 79 – 2012.
Electrical Supply
Disconnecting
Means
Final
Overcurrent Single Set of Fuses
Device
NFPA 79, 3.3.10 Branch Circuit. The Circuit
Conductors Between the Final Overcurrent Device
Protecting the Circuit and the Outlet(s). [70:100]
1/2 Hp 2 Hp 5 Hp 5 Hp 1 Hp
ArmorStart LT This section contains a brief description of the attributes of the ArmorStart LT
motor controllers that are relevant to applying them in multiple-motor
Product Family branch circuits.
The term motor controller refers to the device that stops and starts the motor.
The ArmorStart LT product family consists of two types of motor controllers.
The Bulletin 290 and 291 controllers are magnetic motor controllers that use an
electromechanical contactor to stop and start the motor. The Bulletin 294 motor
controllers use a variable-frequency AC drive to stop, start and vary the speed
of the motor. This appendix refers to the Bulletin 290, 291 and 294 products as
either motor controllers or just controllers.
Multiple-Motor Branch Multiple-motor branch circuits, like that shown in Figure 58, have this
fundamental tradeoff: protecting more than one controller with a single set
Circuits and Motor of fuses requires more electrical and mechanical robustness in each controller.
Controllers Listed for Group
Installation – General In exchange for eliminating the cost and space necessary for a dedicated set of
fuses in front of each controller, the construction of each controller itself must be
more robust. For the circuit configuration shown in Figure 58 to be practical,
the ampere rating of the fuse must be large enough to operate all of the motors,
without opening, under normal starting and running conditions. This rating
of fuse must be larger than the rating permitted to protect a circuit that supplies
only a single motor and its controller. In general, as the rating of the fuse
increases, so does the magnitude of fault currents that flow until the fuse opens.
This higher magnitude of fault current results in more damage to the controller.
Therefore, the additional controller robustness is necessary to withstand these
higher fault currents, without controller damage, that could result in a shock
or fire hazard.
Consequently, to the controller, being listed for group installation mostly means
the UL testing is performed with fuses that have this practical, and higher,
ampere rating. This testing verifies that it is safe to apply this controller in a
multiple-motor branch circuit, provided the fuse is of the same class and does
not have a rating exceeding that marked on the controller.
The example in Figure 59, illustrates this increase in the maximum ampere rating
of fuse that is permitted to protect a controller. This example compares the rating
of the fuse used in the UL testing of two variable-frequency AC drive-based
motor controllers. Both controllers have a rated power of ½ horsepower and a
rated output current of 1.5 amperes. The controller shown on the left is intended
for installation in individual-motor branch circuits. The controller shown on the
right is the ArmorStart LT Bulletin 294 controller that must be listed for group
Referring to the controller on the right, UL 508C permits the group installation
testing to be performed with the maximum rating of fuse that can be used to
protect a multiple-motor branch circuit. According to both NFPA 70
[430.53(C)) and NFPA 79 (7.2.10.4(3)], this is 250 amperes. This value, derived
from the installation requirements of 430.53(C) and 430.53(D) of NFPA 70, is
determined by the largest size of power conductor that the ArmorStart LT
controller can accept, 10 AWG. Because the UL 508C test covers all possibilities
in NFPA 70 and NFPA 79, it permits the maximum value of 250 amperes. This
covers 7.2.10.4(2), which permits only 100 amperes. However, in this case, the
manufacturer, Rockwell Automation, chose to test and mark with the lower value
of 45 amperes. This value was chosen as the tradeoff between the maximum
number and type of controllers in the branch circuit — limited by the maximum
fuse rating — and the electrical and mechanical robustness engineered into
each controller.
6A fuse max
Current 45 A fuse max
Maximum
conductor size
= 10 AWG
Motor Motor
Maximum Fuse Ampere This section uses Figure 60 to explain the requirements from 7.2.10.4(1) and
7.2.10.4(2) that are relevant to, and permit, the multiple-motor branch circuit
Rating According to of Figure 58.
7.2.10.4(1) and 7.2.10.4(2)
The following is the complete text of 7.2.10.4(1) and 7.2.10.4(2) and an
abbreviated version of Table 30 from the 2012 Edition of NFPA 79. The table
is abbreviated to cover the size of conductors that are generally relevant to the
ArmorStart LT motor controllers.
Complete Text -
“7.2.10.4 Two or more motors or one or more motor(s) and other load(s), and
their control equipment shall be permitted to be connected to a single branch
circuit where short-circuit and ground-fault protection is provided by a single
inverse time circuit breaker or a single set of fuses, provided the following
conditions under (1) and either (2) or (3) are met:
(1) Each motor controller and overload device is either listed for group
installation with specified maximum branch-circuit protection or selected such
that the ampere rating of the motor branch short-circuit and ground-fault
protective device does not exceed that permitted by 7.2.10.1 for that individual
motor controller or overload device and corresponding motor load.
“7.2.10.4 Two or more motors (a)…and their control equipment (b) shall be
permitted to be connected to a single branch circuit (c) where short-circuit and
ground-fault protection is provided by a single inverse time circuit breaker or a
single set of fuses (d), provided the following conditions under (1) and…(2)…
are met:
(1) Each motor controller and overload device is… listed for group installation
with specified maximum branch-circuit protection (e) …
(2) The rating or setting of the branch short-circuit and ground-fault protection
device does not exceed the values in Table 7.2.10.4 for the smallest conductor
in the circuit.” (f )
1/2 HP 2 HP 5 HP 5 HP 1 HP
FLC = FLC = FLC = FLC = FLC =
1.1 A** 3.4 A** 7.6 A** 7.6 A** 2.1 A**
Explanatory Example The example addresses the overcurrent protection of the conductors, controllers
and motors. Protection for three overcurrent conditions is considered: motor
running overloads, short-circuit (line-to-line) faults, and ground-faults (line-to-
ground). The short-circuit fault and ground-fault protection is governed by
7.2.10.4(1) and 7.2.10.4(2) and explained in Requirements 1,2 and 3 and
Figure 61. The overload protection, explained in Requirement 4, is governed by
7.3.1 and 7.3.1.1. Overload coordination depends on each conductor having the
minimum ampacity given by 12.5.3 and 12.5.4. The method for determining this
minimum ampacity is explained in Requirement 5 and Figure 62.
The example branch circuit is shown in Figure 61 and Figure 62. The circuit
topology consists of a set of 10 AWG conductors that supply multiple sets of 14
AWG conductors. Each set of 14 AWG conductors supply a controller and
motor. These conductor sizes are chosen to be the smallest conductors that have
sufficient ampacity, without derating, for the loads each must carry. All of the
wiring is customer-supplied, rather than the ArmorConnect Power Media,
because all controllers have the Conduit Entrance Gland Plate Option. Fuses
protect the branch circuit.
The example addresses five basic requirements that the motor controllers, fuses
and conductors must satisfy. The letters in the circles on Figure 61 and Figure 62
are referenced in the explanations as letters in parentheses. Ellipses points (…)
are used to replace NFPA 79 text that is not applicable to the multiple-motor
branch circuit shown in Figure 61 and Figure 62. Unless indicated, all text is
from NFPA 79.
Electrical Supply -
480Y/277V
Available Fault Current
Sym. Amps RMS 9 KA
Disconnecting
Means
Fuses
a
45 A Max,
Branch short-circuit
CC, J or T
and ground-fault
d protection device
Combined Load Conductors 10 AWG
Controller
ratings
further
restrict the
fuse
“Suitable for Motor Group Installation”
14 AWG
14 AWG
14 AWG
14 AWG
14 AWG
Max. Ratings
Sym. Amps RMS 5 KA 10 KA
Fuse 45A 45A*
14 AWG
14 AWG
14 AWG
14 AWG
14 AWG
Conductor
Table 7.2.10.4
Conductor c protection
Max protection -
Fuse 60 A max, “Smallest
AWG (A) any class Determine conductor”
- - fuse class
14 60 and max
12 80 rating for
10 100 1/2 HP 2 HP 5 HP 5 HP 1 HP
conductor FLC = FLC = FLC = FLC = FLC =
8 150
- - protection 1.1 A** 3.4 A** 7.6 A** 7.6 A** 2.1 A**
7.2.10.4(2) -
“smallest
conductor in
the circuit” * Each controller is suitable for group installation with the same maximum ratings of fuse.
= 14 AWG
** Table 430.250 of NFPA 70-2011
14 AWG
14 AWG
14 AWG
14 AWG
1.8 A 5.5 A 7.6 A 7.6 A 3.0 A
½ HP 2 HP 5 HP 5 HP 1 HP
Bulletin Bulletin Bulletin Bulletin Bulletin
294 294 291 290 294
14 AWG
14 AWG
14 AWG
14 AWG
Min Amp. = Min Amp. = Min Amp. = Min Amp. = Min Amp. =
125% * 1.1A 125% * 3.4 A 125% * 7.6 A a 125% * 7.6 A b 125% * 2.1 A
1/2 HP 2 HP 5 HP 5 HP 1 HP
FLC = FLC = FLC = FLC = FLC =
1.1 A** 3.4 A** 7.6 A** 7.6 A** 2.1 A**
Text: “7.2.10.4(1) Each motor controller and overload device is… listed for group
installation with specified maximum branch-circuit protection…”
Referring to Figure 62 (a) indicates the markings on the nameplate that satisfy
7.2.10.4(1). The marking “Suitable for Motor Group Installation” satisfies the
requirement to be listed for group installation. The ratings located beneath the
description “Max. Ratings” are the specified maximum branch circuit protection.
The (a) beside the fuse(s) indicates that the maximum protection specified on the
nameplate applies to these fuse(s).
Text: “7.2.10.4(2) The rating or setting of the branch short-circuit and ground-
fault protection device does not exceed the values in Table 30 for the smallest
conductor in the circuit.”
maximum rating of the fuse protecting the branch circuit must be reduced to the
lower value so that all components are applied according to their ratings. For
example, as shown in Requirement Three, a lower value may be necessary to
protect the motor controller within its ratings because its specified maximum
protection is less than the rating that Table 30 permits for the smallest circuit
conductor. Another reason to use a lower rating of fuse is to provide more
conservative conductor and controller protection. However, in all cases it is
important to ensure the ampere rating is sufficient to start and operate the motors
without nuisance opening of the fuse(s).
Supplementary Note 2: The note at (b) points to the conductor on the output
of the ½ Hp Bulletin 294E controller in order to emphasize that the smallest
conductor in the circuit includes the conductors between each controller and
motor. This includes the output of the variable-frequency AC drive-based
Bulletin 294E controllers; even though these drives have electronic short-circuit
protection. According to NFPA 79, the fuse, and not the drive’s electronic short-
circuit protection, provides the short-circuit fault and ground-fault protection
for these output conductors.
Text: “(1) Each motor controller and overload device is… listed for group
installation with specified maximum branch-circuit protection…”
Analysis: See (d) in Figure 61. The characteristics of the fuse(s) permitted to
protect the conductors (see Requirement 2) must now be compared to those in
the controller’s ratings. To comply with the listing of each motor controller and
overload relay, the fuse(s) must comply with the maximum branch-circuit
protection specified in the controller markings. Therefore, the fuse(s) must be
of a class marked on all of the controllers and the rating of the fuse(s) must not
exceed the rating marked on any of the controllers. The markings of each
controller specify that a fuse having a maximum rating of 45 A may protect the
motor controller. When connecting to an electrical supply having an available
fault current of 5000 amperes or less, the class of the fuse is not specified and may
be any class. When connecting to an electrical supply having an available fault
current between 5000 and 10000 amperes, the class of the fuse must be CC, J
or T. Since the electrical supply has an available fault current of 9000 amperes,
selecting a Class CC, J or T fuse with a rating of 45 A or less ensures each motor
controller is applied within its own ratings.
Supplementary Note 1: The rating of the fuse must not exceed the rating
permitted by 7.2.10.4(2) to protect the smallest conductor in the circuit.
Selecting a Class CC, J or T fuse with a rating of 45 amperes, being less than 60
amperes, also protects the conductors (see Requirement 2). Although the
ArmorStart LT products presently have a maximum fuse rating of 45 A, future
controllers may have maximum fuse ratings that exceed 60 A. In this case, the
maximum rating of fuse is limited by the rating to protect the 14 AWG
conductors, 60 A. The maximum rating permitted for the controller, 45 A,
is a maximum rating and can be reduced, for more conservative protection,
provided nuisance opening of the fuses do not occur.
Text:
“7.3.1 General. Overload devices shall be provided to protect each motor, motor
controller, and branch-circuit conductor against excessive heating due to motor
overloads or failure to start.”
Text:
“12.5.3 Motor circuit conductors supplying a single motor shall have an ampacity
not less than 125 percent of the motor full-load current rating.”
“12.5.4 Combined load conductors shall have an ampacity not less than … 125
percent of the full-load current rating of the highest rated motor plus the sum of
the full-load current ratings of all other connected motors…”
Analysis: Referring to Figure 62, (a), (b) and (c) explain the method for
calculating the minimum required conductor ampacity for each of these
conductors: input and output conductors of Bulletin 290E and 291E controllers
(a), input and output conductors of Bulletin 294E controllers (b) and combined
load conductors that supply Bulletin 290E, 291E and 294E controllers (c). The
currents I1 through I5 are the input currents to the controllers. For the Bulletin
290E and 291E controllers, these are the same as the output motor currents. For
the Bulletin 294E controllers, these currents are the rated input currents.
The example does not address conditions of use such as an ambient temperature
exceeding 30 °C or more than three current-carrying conductors in a cable or
raceway. In a particular application, these conditions of use may require derating
of the ampacity given in Table 12.5.1. This example assumes that, under the
conditions of use, both conductors have sufficient ampacity for the application.
This means the 14 AWG conductors have an ampacity of no less than
9.5 A and the 10 AWG conductors have an ampacity of no less than
27.4 A.
Input and Output Conductors For Bulletin 290E and 291E controllers, which use an electromechanical
contactor to control the motor, the input current, like the output current, is just
of Bulletin 290E and 291E the current to the motor. Therefore, the minimum conductor ampacity for both
Controllers (a) input and output conductors is 125 percent of the motor full-load current rating,
as specified in the text of 12.5.3 (a).
Input and Output Conductors The Bulletin 294E controllers use a variable-frequency AC drive to control the
motor. These drives use a power conversion method that generates input currents
of Bulletin 294E Controllers that are larger than the output currents. The input currents are larger because,
(b) unlike the output currents to the motor, they are not sinusoidal. Consequently,
when determining the minimum ampacity of the input conductors, the
requirement of 12.5.3 must be based on the rated input current of the controller,
rather than the full-load current rating of the motor. Therefore, the minimum
ampacity of the input conductors must be 125% of the controller rated input
current, while that of the output conductors must be 125% of the motor full-load
current rating.
Referring to Figure 62, the 1 Hp Bulletin 294E controller has a rated input
current of 3.0 amperes. Using the rated input current, the conductors from the
combined load conductors to the controllers must have an ampacity of 125%
of 3.0 A or 3.75 A. The output conductors must have an ampacity of 125% of
2.1 A or 2.6 A.
Combined Load Conductors The requirement for the minimum ampacity of the combined load conductors
is given by 12.5.4. When the combined load conductors supply one or more
(c) Bulletin 294E controllers, the minimum ampacity calculation of 12.5.4 must
be made by substituting the rated input current of the Bulletin 294E controllers
for the full-load current rating of the motors that these controllers supply.
In Figure 62, the currents I1, I2, I3, I4 and I5 are the input currents to each
controller. I3 and I4 are the full-load current ratings of the 5 Hp motors. I1, I2
and I5 are the rated input currents of the Bulletin 294E controllers. Referring to
the explanatory text (c) in Figure 62, the method for calculating the minimum
ampacity of the combined load conductors follows: first, multiply the largest
input current to any controller – Bulletin 290E, 291E or 294E - by 125%. In this
case, the input currents to the Bulletin 290E and 291E controllers, I3 and I4, are
the largest, 7.6 A. Because they are the same, either can be used. Choose I3 to
calculate 125% of the maximum. 125% of 7.6 A is 9.5 A. Second, sum the
remaining input currents (I1, I2, I4, I5) for a total of 17.9 A. Third, add the result
from the first step to the result from the second for a total of 27.4 A. Finally, the
minimum ampacity of the combined load conductors is 27.4 A.
CIP Information
The following table lists the product codes and name strings that will be added to
the ArmorStart LT product family for EtherNet/IP.
Table 32 - Product Codes and Name Strings
Product Current Integrated
Code Rating Identity Object Name String Power Supply
0x301 0.24…3.5 amps ArmorStart 290E 0.24…3.5 A No
0x302 1.1…7.6 amps ArmorStart 290E 1.1…7.6 A No
0x311 0.24…3.5 amps ArmorStart 290EP 0.24…3.5 A Yes
0x312 1.1…7.6 amps ArmorStart 290EP 1.1…7.6 A Yes
0x341 0.24…3.5 amps ArmorStart 291E 0.24…3.5 A No
0x342 1.1…7.6 amps ArmorStart 291E 1.1…7.6 A No
0x351 0.24…3.5 amps ArmorStart 291EP 0.24…3.5 A Yes
0x352 1.1…7.6 amps ArmorStart 291EP 1.1…7.6 A Yes
0x3C2 0.5…2.5 amps ArmorStart 294E 0.5 Hp No
0x3C4 1.1…5.5 amps ArmorStart 294E 1.0 Hp No
0x3C6 3.2…16 amps ArmorStart 294E 2.0 Hp No
0x3D2 0.5…2.5 amps ArmorStart 294EP 0.5 Hp Yes
0x3D4 1.1…5.5 amps ArmorStart 294EP 1.0 Hp Yes
0x3D6 3.2…16 amps ArmorStart 294EP 2.0 Hp Yes
CIP Explicit Connection The ArmorStart LT allows run, jog and user outputs to be driven by connected
explicit messages when no I/O connection exists, or when a I/O connection
Behavior exists in the idle state. a single EtherNet/IP Class 3 explicit connection will be
allowed to send “explicit control” messages via an “Active Explicit” connection.
An EtherNet/IP Class 3 explicit connection becomes the “explicit control”
connection when it becomes the first EtherNet/IP Class 3 explicit connection to
send a “set” service to one of the following:
• The “value” attribute of any Discrete Output Point (DOP) instance (Class
Code 0x09).
EDS Files
The information contained in the EDS (Electronic Data Sheet) files for
ArmorStart LT EtherNet/IP can be extracted via the network.
CIP Object Requirements The following CIP objects will be covered in the following subsections:
For convenience, all objects that are accessible via the EtherNet/IP port are
included.
Class Object
0x0001 Identity Object
0x0002 Message Router
0x0004 Assembly Object
0x0006 Connection Manager Object
0x0008 Discrete Input Point Object
0x0009 Discrete Output Point Object
0x000A Analog Input Point
0x000B Analog Output Point
0x000F Parameter Object
0x0010 Parameter Group Object
0x001D Discrete Input Group Object
0x001E Discrete Output Group Object
0x0029 Control Supervisor
0x002C Overload Object
0x0047 Device Level Ring Object
0x0097 DPI Fault Object
0x098 Alarm Object
Class Object
0x00F5 TCP/IP Interface Object
0x00F6 Ethernet Link Object
0x0376 Trip and Warning Email Object
0x032F Email Object
The following class attributes are supported for the Identity Object:
Two instances of the Identity Object will be supported for Bulletin 290E and Bulletin
291E; 3 for Bulletin 294E. The following table shows what each instance will represent.
Each instance of the Identity Object will contain the following attributes:
➊ See product code definitions in Table 32, Product Codes and Name Strings.
Value Description
0 Self-testing or unknown
1 Firmware update in progress
2 At least one faulted I/O connection
3 No I/O connections established
4 Non-volatile configuration bad
5 Major fault – either bit 10 or bit 11 is true (1)
6 At least one I/O connection in run mode
7 At least one I/O connection established, all in idle mode
The following common services will be implemented for the Identity Object:
Implemented for:
Service Code Class Instance Service Name
0x01 Yes Yes Get_Attributes_All
0x05 No Yes Reset
0x0E Yes Yes Get_Attributes_Single
No class or instance attributes will be supported. The message router object exists
only to route explicit messages to other objects.
The following static Assembly instance attributes will be supported for each
Assembly instance:
Implemented for:
Service Code Class Instance Service Name
0x0E Yes Yes Get_Attribute_Single
0x10 No Yes Set_Attribute_Single
I/O Assemblies
The following table summarizes the Assembly instances that are supported in the
ArmrorStart EtherNet/IP product:
Instance 3
Instance 52
Instance 100
Instance 100 is the Configuration Assembly for Bulletin 290E and 291E units.
Instance 101
Instance 150
Instance 150 is the default Output (Consumed) Assembly for Bulletin 290E/
291E starters.
Instance 150 "Starter Cmd" – DeviceLogix Consumed Assembly for Bulletin 290E/291E Starters
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 — — — — — ResetFault RunReverse RunForward
1 — — Out05 Out04 Out03 Out02 Out01 Out00
2 Pt07DeviceIn Pt06DeviceIn Pt05DeviceIn Pt04DeviceIn Pt03DeviceIn Pt02DeviceIn Pt01DeviceIn Pt00DeviceIn
3 Pt15DeviceIn Pt14DeviceIn Pt13DeviceIn Pt12DeviceIn Pt11DeviceIn Pt10DeviceIn Pt09DeviceIn Pt08DeviceIn
4 AnalogDeviceIn (low byte)
5 AnalogDeviceIn (high Byte)
Instance 152
Instance 152 is the Exhaustive Starter Status Assembly for Bulletin 290E/291E
starters.
Instance 152 "Starter Stat" – DeviceLogix Produced Assembly for Bulletin 290E/291E Starters
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 Reserved
1 Reserved
2 Reserved
3 Reserved
4 CurrentFlowing NetControlStatus Ready RunningReverse RunningForward WarningPresent TripPresent
5 DisconnectClosed KeyPadHand KeyPadOff KeyPadAuto DLXEnabled
6 Pt05 Pt04 Pt03 Pt02 Pt01 Pt00
7
8 Pt07DeviceOut Pt06DeviceOut Pt05DeviceOut Pt04DeviceOut Pt03DeviceOut Pt02DeviceOut Pt01DeviceOut Pt00DeviceOut
9 Pt15DeviceOut Pt14DeviceOut Pt13DeviceOut Pt12DeviceOut Pt11DeviceOut Pt10DeviceOut Pt09DeviceOut Pt08DeviceOut
10 An00DeviceOut (low byte)
11 An00DeviceOut (high byte)
12
Parameter 1 – PhaseL1Current
13
14
Parameter 2 – PhaseL2Current
15
16
Parameter 3 – PhaseL3Current
17
18
Parameter 4 – AverageCurrent
19
20
Parameter 5 – %ThermalUtilized
21
Instance 152 "Starter Stat" – DeviceLogix Produced Assembly for Bulletin 290E/291E Starters
22 Parameter 11 – SwitchedVolts
23 OutputSourceV (IPS units)
24 Parameter 12 – UnswitchedVolts
25 SensorSourceV (IPS units)
26
Parameter 16 – TripStatus
27
28
Parameter 17 – WarningStstus
29
Instance 154
Instance 154 is the default Output (Consumed) Assembly for Inverter type
(Bulletin 294E) Distributed Starters.
Instance 154 "Drive Cmd" – DeviceLogix Consumed Assembly for Bulletin 294E Starters
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 JogReverse JogForward ResetFault RunReverse RunFoward
1 Decel2 Accel2 Out05 Out04 Out03 Out02 Out01 Out00
2 CommandFreq (Low) (xxx.x Hz)
3 CommandFreq (High) (xxx.x Hz)
4 Pt07DeviceIn Pt06DeviceIn Pt05DeviceIn Pt04DeviceIn Pt03DeviceIn Pt02DeviceIn Pt01DeviceIn Pt00DeviceIn
5 Pt15DeviceIn Pt14DeviceIn Pt13DeviceIn Pt12DeviceIn Pt11DeviceIn Pt10DeviceIn Pt09DeviceIn Pt08DeviceIn
6 An00DeviceIn (lowbyte)
7 An00DeviceIn (highbyte)
Instance 156
Instance 156 "Drive Status" – Produced Assembly for Bulletin 294E Starters
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 Reserved
1 Reserved
2 Reserved
3 Reserved
4 AtReference NetRefStatus NetControlStatus Ready RunningReverse RunningForward WarningPresent TripPresent
5 BrakeStatus DisconnectClosed KeyPadJogging KeyPadHand KeyPadOff KeyPadAuto DLXEnabled
6 Output Frequency (Low) (xxx.x Hz)
7 Output Frequency (High) (xxx.x Hz)
8 Pt05 Pt04 Pt03 Pt02 Pt01 Pt00
9
10 Pt07DeviceOut Pt06DeviceOut Pt05DeviceOut Pt04DeviceOut Pt03DeviceOut Pt02DeviceOut Pt01DeviceOut Pt00DeviceOut
Instance 156 "Drive Status" – Produced Assembly for Bulletin 294E Starters
11 Pt15DeviceOut Pt14DeviceOut Pt13DeviceOut Pt12DeviceOut Pt11DeviceOut Pt10DeviceOut Pt09DeviceOut Pt08DeviceOut
12 An00DeviceOut (low byte)
13 An00DeviceOut (high byte)
14
Parameter 3 – OutputCurrent
15
16
Parameter 4 – OutputVoltage
17
18
Parameter 5 – DCBusVoltage
19
20 Parameter 11 – SwitchedVolts
21 OutputSourceV (IPS units)
22 Parameter 12 – UnswitchedVolts
23 SensorSourceV (IPS units)
24
Parameter 13 – InternalFanRPM
25
26
Parameter 14 – ElaspedRunTime
27
28
Parameter 15 – DriveTemperature
29
30
Parameter 16 – TripStatus
31
32
Parameter 17 – WarningStatus
33
One Instance of the Connection Manager Object will be supported. It has the
following attributes:
Class 1 Connections
Class 1 connections are used to transfer I/O data, and can be established to the
assembly object instances. Each Class 1 connection establishes two data
transports, one consuming and one producing. The heartbeat instances are used
for connections that shall access only inputs. Class 1 uses UDP transport.
When all supported connections are used the error code “Connection Manager
cannot support any more connections” shall be returned.
This connection type is used for controlling the outputs of the module and shall
not be dependent on any other connection. Only one exclusive owner connection
can be opened against the module.
This connection is used to read data from the module without controlling the
outputs. This connection type shall not be dependent on any other connection. It
is recommended that the originator sets the data size in the O->T direction of the
Forward_Open be zero, there are however no check that this is actually the case.
IMPORTANT If an exclusive owner connection has been opened against the module and
times out, the input only connection shall time out as well. If the exclusive
owner connection is properly closed, the input only connection shall not be
affected.
It is recommended that the originator sets the data size in the O->T direction of
the Forward_Open be zero, there are however no checks that this is actually the
case.
Class 3 Connections
Implemented for:
Service Code Class Instance Service Name
0x01 No Yes Get_Attribute_All
0x0e No Yes Get_Attribute_Single
Implemented for:
Service Code Class Instance Service Name
0x10 No Yes Set_Attribute_Single
0x4E No Yes Forward_Close
0x54 No Yes Forward_Open
Six instances of the Discrete Input Point Object are supported. All instances
contain the following attributes:
The following common services will be implemented for the Discrete Input Point
Object:
Implemented for:
Service Code Class Instance Service Name
0x0E Yes Yes Get_Attribute_Single
0x10 No Yes Set_Attribute_Single
Eight instances of the Discrete Output Point Object are supported for DOL/
Reverser (Bulletin 290E/291E) units. Ten instances are supported for Drive
(Bulletin 294E) units. The following table summarizes the DOP (Bulletin 290E/
291E) instances:
The following common services will be implemented for the Discrete Output
Point Object:
Implemented for:
Service Code Class Instance Service Name
0x0E Yes Yes Get_Attribute_Single
0x10 No Yes Set_Attribute_Single
There are many sources that can affect an output point's value: an I/O message,
an explicit message, local logic, network fault and idle conditions, and protection
fault conditions. An output point must know how to select which source of data
to use to drive its value attribute.
The following state transition diagram is used for an unbound Bulletin 290E
Non-Existent
Power off
Power up
Connection Available
Transitions to
Protection Fault
Established
DNet Fault
Idle DNet Fault
Ready Protection
Connection Transitions to Established Fault
DNet Fault
DNet
Idle
Protection Fault Reset
Ready Protection
Protection Fault Fault
Receive
Data
Protection Fault
Receive Idle Run
DNet Fault
Yes Pr Fault
Protection Action = Ignore
Fault
Yes
Yes
Ignore I/O
Message
Comm Yes
Override
DN Yes
Fault
Yes
DN Idle
Yes
Run
Use PrFault Action &
PrFault Value
Logic
Enabled Use DNFault Action
Yes
Available & DNFault Value
Yes
Apply Value
The following flow chart illustrates the behavior of Bound DOP Instances.
Protection Yes
Fault
Yes
Ignore I/O
Message
Comm Yes
Override
DN Yes
Fault
Yes
DN Idle
Y es
Run
Turn off output
Logic
Enabled Use DNFault Action
Yes
Available & DNFault Value
Yes
Apply Value
Analog Input Point Object CLASS CODE 0x000A (Implemented in Bulletin 294E units only)
The following class attributes will be supported for the Analog Input Point
Object:
One instance of the Analog Input Point Object will supported. CommandFreq
from Assembly 154 is placed in the value attribute when it is consumed.
The following common services will be implemented for the Analog Input Point
Object:
Implemented for:
Service Code Class Instance Service Name
0x0E Yes Yes Get_Attribute_Single
0x10 No Yes Set_Attribute_Single
Analog Output Point Object CLASS CODE 0x000B (Implemented in Bulletin 294E units only)
The following class attributes will be supported for the Analog Output Point
Object:
One instance of the Analog Output Point object will supported. It will represent
the Frequency command sent to the PF40 via the DSI link. CommandFreq from
Assembly 154 is placed in the Value Attribute when it is consumed. The Value
Attribute can then be overwritten by DeviceLogix.
The following common services will be implemented for the Analog Output
Point Object:
Implemented for:
Service Code Class Instance Service Name
0x0E Yes Yes Get_Attribute_Single
0x10 No Yes Set_Attribute_Single
The following class attributes will be supported for the Parameter Object:
The number of instances of the parameter object will depend upon the type of
Distributed Starter that the control board is connected to.
Implemented for:
Service Code Class Instance Service Name
0x01 No Yes Get_Attribute_All
0x0E Yes Yes Get_Attribute_Single
0x10 No Yes Set_Attribute_Single
0x4b No Yes Get_Enum_String
The following class attributes will be supported for the Parameter Group Object:
The following instance attributes will be supported for all Parameter Group
Instances.
The following common services will be implemented for the Parameter Group
Object.
Implemented for:
Service Code Class Instance Service Name
0x01 Yes Yes Get_Attribute_All
0x0E Yes Yes Get_Attribute_Single
A single instance of the Discrete Input Group Object is supported and contains
the following instance attributes:
The following common services will be implemented for the Discrete Input
Group Object:
Implemented for:
Service Code Class Instance Service Name
0x0E No Yes Get_Attribute_Single
0x10 No Yes Set_Attribute_Single
Instance 1 exists for the sole purpose of providing a place holder for the Comm
Override and Network Override parameters. Instance 1 will contain the
following attributes:
Instance 2 controls the communication fault and idle behaviors for run/jog
outputs. Instance 2 contains the following instance attributes:
Note: There are no protection fault attributes. Behavior for protection faults is
go to OFF.
Instance 3 will drive protection fault and communication fault/idle behaviors for
user outputs. Instance 3 will have the following attributes.
The following common services are implemented for the Discrete Input Group
Object.
Implemented for:
Service Code Class Instance Service Name
0x0E No Yes Get_Attribute_Single
0x10 No Yes Set_Attribute_Single
The following common services will be implemented for the Control Supervisor
Object.
Implemented for:
Service Code Class Instance Service Name
0x0E No Yes Get_Attribute_Single
0x10 No Yes Set_Attribute_Single
The following common services are implemented for the Overload Object.
Implemented for:
Service Code Class Instance Service Name
0x01 No Yes Get_Attribute_All
0x0E No Yes Get_Attribute_Single
0x10 No Yes Set_Attribute_Single
The following common services will be implemented for the DLR Object.
Implemented for:
Service Code Class Instance Service Name
0x01 No Yes Get_Attribute_All
0x0E No Yes Get_Attribute_Single
The following common services will be implemented for the Extended Device
Object.
Implemented for:
Service Code Class Instance Service Name
0x01 No Yes Get_Attribute_All
0x0E Yes Yes Get_Attribute_Single
0x10 No Yes Set_Attribute_Single
The following class attributes will be supported for the DPI Fault Object.
The following common services will be implemented for the DPI Fault Object.
Implemented for:
Service Code Class Instance Service Name
0x0E Yes Yes Get_Attribute_Single
0x10 Yes No Set_Attribute_Single
The table below lists Fault Codes, Fault Text, and Fault Help Strings for DOL
and Reversers.
Table 33 - Fault Codes, Fault Text, and Fault Help Strings for DOL and Reversers
Fault
Code Fault Text Help Text
1 Fault 1 —
2 User Defined User defined trip has occurred.
3 Overload Trip Load has drawn excessive current based on trip class selected.
4 Fault 4 —
5 Phase Loss Trip Indicates missing supply phase. This fault can be disabled.
6 Jam Trip Motor current above jam level for more than jam trip delay time.
7 Underload Trip Motor current below UL level for more than UL trip delay time.
8 Fault 8 —
9 Fault 9 —
10 Fault 10 —
11 Fault 11 —
12 Stall Trip Motor current above stall trip level during motor starting.
13 Switched Power Indicates the loss of switched control power.
Not available in units with Integrated Power Supply.
Table 33 - Fault Codes, Fault Text, and Fault Help Strings for DOL and Reversers
Fault
Code Fault Text Help Text
14 Under Power Trip Indicates the internal power supply is below its working level.
Available in units with Integrated Power Supply only
15 Sensor Short Flags a miswired hardware input point.
16 Output Short Flags a miswired hardware output point.
17 Fault 17 —
18 Fault 18 —
19 Phase Imbalance Indicates an imbalanced phase current.
20 Fault 20 —
21 Aux Power Loss Auxiliary Power was lost or dipped below the minimum threshold.
Not available in units with Integrated Power Supply
22 Fault 22 —
23 Fault 23 —
24 Fault 24 —
25 Fault 25 —
26 Fault 26 —
27 NonVol Memory This is a major fault which renders the unit inoperable.
28 Fault 28 —
29 Fault 29 —
30 Hardware Fault This is a major fault which renders the unit inoperable.
31 Fault 31 —
32 Fault 32 —
33 Fault 33 —
34 Fault 34 —
35 Fault 35 —
36 Fault 36 —
37 Fault 37 —
38 Fault 38 —
39 Fault 39 —
40 Unknown Fault —
The table below lists Fault Codes, Fault Text, and Fault Help Strings for Drive
units.
Table 34 - Fault Codes, Fault Text, and Fault Help Strings for Drive Units
PF4M
Fault Fault
Code Fault Text Help Text Code
1 Fault 1 —
2 User Defined User defined trip has occurred.
3 Motor Overload The load has drawn excessive current. 7
4 Drive Overload 150% load for 1 min. or 200% load for 3 sec. exceeded. 64
Table 34 - Fault Codes, Fault Text, and Fault Help Strings for Drive Units
PF4M
Fault Fault
Code Fault Text Help Text Code
5 Phase U to Gnd A Phase U to Ground fault detected between drive and motor. 38
6 Phase V to Gnd A Phase V to Ground fault detected between drive and motor. 39
7 Phase W to Gnd A Phase W to Ground fault detected between drive and motor. 40
8 Phase UV Short Excessive current detected between phases U and V. 41
9 Phase UW Short Excessive current detected between phases U and W. 42
10 Phase VW Short Excessive current detected between phases V and W. 43
11 Ground Fault A current path to earth ground at one or more output terminals. 13
12 Stall Trip The drive is unable to accelerate the motor. 6
13 Switched Power Indicates the loss of switched control power.
Not available in units with Integrated Power Supply
14 Under Power Trip Indicates the internal power supply is below its working level.
Available in units with Integrated Power Supply only.
15 Sensor Short Flags a miswired hardware input point.
16 Output Short Flags a miswired hardware output point.
17 Fault 17
18 Heatsink Temp The Heatsink temperature exceeds a predefined value. 8
19 HW Over Current The drive output current has exceeded the hardware limit. 12
20 SW OverCurrent Programmed parameter 83 (SW Current Trip) has been exceeded. 63
21 Aux Power Loss Auxiliary Power was lost or dipped below the minimum threshold.
Not available in units with Integrated Power Supply.
22 Internal Comm Communication with the internal Power Flex drive has been lost. 71
23 Drive Comm Loss The RS485 port on the internal Power Flex stopped communicating. 81
24 Power Loss Drive DC Bus Voltage remained below 85% of nominal bus voltage. 3
25 Under Voltage DC Bus Voltage fell below the minimum value. 4
26 Over Voltage DC Bus Voltage exceeded the maximum value. 5
27 MCB EEPROM This is a major fault which renders the ArmorStart inoperable.
28 Param Sync The drive and Main Control Board EEPROMS are not in sync.
29 Drive EEPROM The drive EEPROM checksum checks have failed. 100
30 Hardware Fault This is a major fault which renders the unit inoperable
31 Fan RMP The internal cooling fan is not running properly.
32 Power Unit A major failure has been detected in the drive power section. 70
33 Drive I/O Brd A failure has been detected in the drive control and I/O section. 122
34 Restart Retries Automatic fault reset and run retries exceeded. 33
35 Drive Aux In Flt The drive auxiliary input interlock is open inside the ArmorStart. 2
36 Fault 36 —
37 Drv Param Reset Internal Drive Parameters (Parameters > 100) have been defaulted. 48
38 Fault 38 —
39 Fault 39 —
40 Unknown Fault —
The following common services will be implemented for the DPI Fault Object.
Implemented for:
Service Code Class Instance Service Name
0x0E Yes Yes Get_Attribute_Single
0x10 Yes No Set_Attribute_Single
The table below lists Fault Codes, Fault Text, and Fault Help Strings.
Table 35 - Fault Codes, Fault Text, and Fault Help Strings for ArmorStart LT
Warning
Code Warning Text Help Text
1 Warning 1 —
2 Warning 2 —
3 Motor Overload Overload warning level has been exceeded.
Table 35 - Fault Codes, Fault Text, and Fault Help Strings for ArmorStart LT
Warning
Code Warning Text Help Text
4 Warning 4 —
5 Warning 5 Indicates missing supply phase. This fault can be disabled.
6 Jam Warning Motor current has exceeded jam warning level.
7 Underload Warning Motor current dropped below Underload Warning level.
8 Warning 8 —
9 Warning 9 —
10 Warning 10 —
11 Warning 11 —
12 Warning 12 —
13 Switched Pwr Warn Indicates the control power has dipped below 19 Volts.
Not available in units with Integrated Power Supply.
14 Under Power Warn Indicates the internal power supply is below its optimal level.
Available in units with Integrated Power Supply only.
15 Warning 15 —
16 Warning 16 —
17 Warning 17 —
18 Warning 18 —
19 Warning 19 —
20 Warning 20 —
21 Aux Power Warn Indicates auxiliary Power was has dipped below 19 Volts.
Not available in units with Integrated Power Supply.
The following common services will be implemented for the TCP/IP Interface
Object.
Implemented for:
Service Code Class Instance Service Name
0x0E Yes Yes Get_Attribute_Single
0x10 No Yes Set_Attribute_Single
0x4C No Yes Get_And_Clear
The following common services will be implemented for the Ethernet Link
Object.
Implemented for:
Service Code Class Instance Service Name
0x0E Yes Yes Get_Attribute_Single
0x10 No Yes Set_Attribute_Single
Attribute Need in Access NV Name Data Type Description of Attribute Semantics of Values
ID Implementation Rule
2 Required Set NV To Struct of Email address of the recipient The default value of this
of Trip and Warning Emails string is the null string.
To Length UDINT Length of string in bytes
To Data Array of ASCII characters Example:
USINT [email protected]
3 Required Set NV From Struct of Email address of this device The default value of this
string is the null string.
From Length UDINT Length of string in bytes
From Data Array of ASCII characters Example:
USINT [email protected]
5 Required Set NV SMTP Server Address Struct of SMTP Server Address String The default value of this
string is the null string.
Addr Length UDINT Length of string in bytes
Addr Data Array of ASCII characters
USINT
6 Required Set NV SMTP User Name Struct of SMTP User Name String The default value of this
string is the null string.
To Length UDINT Length of string in bytes
To Data Array of ASCII characters
USINT
7 Required Set NV SMTP Password Struct of SMTP Password String The default value of this
string is the null string.
To Length UDINT Length of string in bytes
To Data Array of ASCII characters
USINT
8 Required Set NV SMTP Port UINT The SMTP Port The Default Value is 0.
9 Optional Set NV Trip Email Mask WORD Mask to enable emails for
individual trip conditions
10 Optional Set NV Warning Email Mask WORD Mask to enable emails for
individual warning conditions
11 Optional Set NV Trip Reset Email Mask WORD Mask to enable emails when
trip conditions are cleared
12 Optional Set NV Warning Reset Email Mask WORD Mask to enable emails when warning
conditions are cleared
13 Optional Get V Trip Email Count UINT Number of emails sent in Defaults to the value 0
response to a trip condition
14 Optional Get V Trip Cleared Emails UINT Number of emails sent in Defaults to the value 0
response to clearing a trip
15 Optional Get V Warning Email Count UINT Number of emails sent in Defaults to the value 0
response to a warningcondition
16 Optional Get V Warning Cleared Emails UINT Number of emails sent in Defaults to the value 0
response toclearing a trip
17 Optional Get V Email Send Features UINT Number of email failures detected Defaults to the value 0
18 Optional Get V Trip Email Count UINT Number of emails sent in
response to a trip condition
The following common services will be implemented for the TCP/IP Interface
Object.
Implemented for:
Service Code Class Instance Service Name
0x01 No Yes Get_Attribute_All
0x0E No Yes Get_Attribute_Single
0x10 No Yes Set_Attribute_Single
Notes:
Using DeviceLogix™
In local control mode, the embedded DeviceLogix logic engine drives the local
outputs and motor run/jog commands from a local DeviceLogix program. Local
Control is completely independent of the any or all CIP connections. I/O and/or
Explicit Message connections can exist in any state and they do not affect the user
outputs or the run/jog commands for the motor. Local control mode is chosen by
when the keypad “Auto LED” is on, “Network Override” is set “Communication
Override” is set, and DeviceLogix is enabled.
In I/O networked control mode, local outputs and motor run/jog commands are
received over a CIP I/O connection in the established state. I/O networked
control mode is chosen when DeviceLogix is disabled, or when DeviceLogix is
enabled and no user outputs or run commands are being driven in the
DeviceLogix program.
DeviceLogix Programming DeviceLogix has many applications and the implementation is typically only
limited to the imagination of the programmer. Keep in mind that the application
of DeviceLogix is only designed to handle simple logic routines.
There are many reasons to use the DeviceLogix functionality, but some of the
most common are listed below:
• Increased system reliability
• Fast update times (1 - 2 ms possible)
• Improved diagnostics and reduced troubleshooting
• Operation independent of PLC or Network status
• Continue to run process in the event of network interruptions
• Critical operations can be safely shutdown through local logic
The following example will show how to program a simple logic routine to
interface the ArmorStart with a remote hard-wired startstop station. In this case
the I/O is wired as shown in the table below.
Input/Output Table
Bit Description
Pt00 Start Button
Pt01 Stop Button
Out02 Run Forward
1. Refer to section “How to Add a New Module, Using the Add-On Profile”
to configure the I/O. Then select the DeviceLogix section and create a
program.
2. Click on the “DeviceLogix” tab. If you are on-line with a device, a dialog
box will appear asking you to upload or download. Click on “Upload.”
5. Left Click on the “RSL” function block. This is a reset dominate latch.
6. Move the cursor into the grid, and left click to drop the function onto the
grid.
7. From the toolbar, Click on the “Discrete Input” button and select Pt00
from the pull-down menu. This is the remote start button based on the
example I/O table.
8. Place the input to the left of the RSL function. To drop the input on the
page, left click on the desired position.
9. Place the mouse cursor over the tip of Pt00. The tip will turn green. Click
on the tip when it turns green.
10. Move the mouse cursor toward the input of the RSL function. A line will
follow the cursor. When a connection can be made, the tip of the RSL
function will also turn green. Click the on Input and the line will be drawn
from Pt00 to the Set Input of the RSL function.
Note: If this was not a valid connection, one of the pin tips would have turned
red rather than green. Left double clicking on the unused portion of the grid or
pressing the “Esc” key at any time will cancel the connection process.
11. From the toolbar, Click on the “Discrete Input” button and select Pt01
from the pull-down menu. This is the remote stop button based on the
example I/O table.
13. Connect the input to the reset input of the RSL latch.
14. From the toolbar, Click on the “Discrete Output” button and select
“RunForward” from the pull-down menu. RunForward is the relay
controlling the coil of the contactor. Click OK.
15. Move the cursor into the grid and place the Output to the right of the RSL
function block.
16. Connect the output of the “RSL” function block to Run Fwd.
17. Click on the “Verify” button located in the toolbar or select “Logic Verify”
from the “Tools” pull-down menu.
18. Click on the “Edit” button to toggle out of edit mode if online with a
device.
19. Go to the pull-down menu in the right corner of the toolbar and select
“Download”.
Note: Ensure that the PLC key switch is in the Program position. If in any other
position, the download will not occur and an error will be generated.
21. Now from the same pull-down menu select “Logic Enable On.”
➊ IPS Units
ArmorStart LT
L1 L2 L3
Switched Control Power
Off
Unswitched Control Power
*
Disconnect
L +
24VDC Single External Power Supply
N -
Class 2
External
24VDC Power
Supply
Download the AOP Download and install the AOP for RSLOGIX5000 from the Service and
Support website.
2. From the list of the Add-On I/O Modules Profiles, scroll down and select
Bulletin 290E, 291E, 294E ArmorStart LT from the list and download the
file.
4. Upon verification, the following screen will appear. Click on the link to
download the file.
6. Select the folder to save the file and click ‘Save’. The downloading will
start.
10. The RSLogix 5000 Module Profiles Setup window will be shown. Click
‘Next’ to continue.
11. Select ‘I accept the terms in the license agreement’ and click on ‘Next’
14. The profiles will be installed, upon completion, click on ‘Next’ to proceed
Use of the AOP 1. Start the RSLogix5000 from Start ➔ Rockwell Software ➔ RSLogix 5000
Enterprise Series ➔ RSLogix 5000
in RSLogix 5000
6. In the New module dialog box enter the Unit name, IP address, and slot
then click OK
Note: Please select the appropriate module. If the wrong module is selected once
RSLOGIX 5000 is in Online with the controller a yellow triangle will appear
next to the module indicating an I/O error has occurred.
9. In the New Module window, enter the Name of the Armorstart LT and the
IP address assigned to it. You can now start to configure the ArmorStart
LT. Begin with “Motor Protection & Control”
10. At the Motor Protection & Control, enter the motor information.
11. Next select “Speed Control”. By default “Speed Reference” is set to select
Logix. The speed of the motor will be control by the controller tag in the
Contrologix. Configure the Acceleration/Deceleration and Jog Frequency
here.
12. Then proceed to the “Fault Configuration” and configure the reset mode
to Automatic or Manual. Then click OK to proceed.
14. At the Who Active window select the 1756-EN2TR, then the controller,
and click on the Download button
15. The Download dialog box will appear, click on Download to proceed
16. The configuration will be downloaded and the Downloading dialog box
will show the progress
21. Expand the output tag of the ArmorStart LT, i.e.: Armorstart_LT_36:O
Note: Setting the tag value to 500 instructs the drive to run at 50.0Hz
For an additional level of technical phone support for installation, configuration, and troubleshooting, we offer
TechConnectSM support programs. For more information, contact your local distributor or Rockwell Automation
representative, or visit http://www.rockwellautomation.com/support/.
Installation Assistance
If you experience a problem within the first 24 hours of installation, review the information that is contained in this
manual. You can contact Customer Support for initial help in getting your product up and running.
United States or Canada 1.440.646.3434
Outside United States or Canada Use the Worldwide Locator at http://www.rockwellautomation.com/support/americas/phone_en.html, or contact your local Rockwell
Automation representative.
Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the
manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures.
United States Contact your distributor. You must provide a Customer Support case number (call the phone number above to obtain one) to your
distributor to complete the return process.
Outside United States Please contact your local Rockwell Automation representative for the return procedure.
Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this
document, complete this form, publication RA-DU002, available at http://www.rockwellautomation.com/literature/.
Trademark List
Allen-Bradley, ArmorConnect, ArmorStart LT, ControlLogix, CompactLogix, PowerFlex, RSLinx, StepLogic, DeviceLogix, On-Machine, RSNetWorx, and RSLogix 5000, are trademarks of
Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies
Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400
www.rockwel lautomation.com