Clean Agent Comparison Chart
Clean Agent Comparison Chart
7 EXTINGUISHING ABILITY WITH Affected Affected Affected but not as the gases
DOOR/ WINDOW OPEN – more dense
8 EFFECT WITH HIGH CEILING Max. = 7.3m No Max = 8m
9 ENVIRONMENT EFFECT YES NO NO
See EU Directives on HFC ban Green Labeled
10 GLOBAL WARMING POTENTIAL 3500 0 0
(GWP) – IPCC 2001
11 OZONE DEPLETION POTENTIAL 0 0 0
(ODP)
ATMOSPHERIC LIFETIME 36.5 year negligible
12 RISK TO OCCUPANTS DUE TO YES YES NO
ACCIDENTAL DISCHARGE
13 SYSTEM APPLICATION Total Flooding In Enclosure Total Flooding In Total Flooding In Enclosure
Enclosure
14 ELECTRICAL NON-DISCHARGE YES YES YES
15 DISCHARGE DISRUPTION NO NO NO
16 SYSTEM INSTALLATION Complicated Difficult Easy
17 VISIBILITY WHILE DISCHARGE Not Clear Clear Not Clear
18 DISCHARGE TIME 10 Sec. Within 1 Min. 10 – 20 Sec.
19 OCCUPIED AREA YES YES YES
20 PRESSURE AT CYLINDER 360 PSI (24.82 BAR) 200-300 BAR Non-Pressurized
21 PIPING INSTALLATION - SCH 40 Seam - SCH 40 & 80 Seamless None
- Fitting Class 300 - Fitting Class 3000 Not Required
22 STANDARD OF SYSTEM UL, FM, LPCB, BS, EPA Vds, JIS NFPA, ISO, CEN, IMO, BRL, UL
23 LISTINGS OF SYSTEM UL, VdS ULC, KIWA, ANPI, BSI,EPA
24 MANUFACTURING (AGENT GREAT LAKES-CHEMTURA / - FIREPRO SYSTEMS LTD
ONLY) DUPONT
25 REFILL PRICE, THB/ ROOM 1,200 THB/ M³ (200 Bar) 175 THB / M³ NOT APPLICABLE – 15 YEAR
VOLUME CERTIFIED LIFETIME
As per IPCC Third Assessment Report (TAR) of 2001 the GWP of FM200 is 3500 and not 2900 (that was in the 2nd Assessment
Report - SAR) IPCC Third Assessment Report - Climate Change 2001 - Complete online versions | UNEP/GRID-Arendal -
Publications - Other