REM611 Series Broch
REM611 Series Broch
The 611 series is part of ABB’s Relion ® protection and The IEDs that are available from the 611 series offer
control relay family and it is designed to offer simplified powerful functionality within basic protection and control
but powerful functionality intended for most applications. configurations intended for most feeder, multipurpose
Once the application-specific parameter set has been high-impedance differential busbar and motor protection and
entered, the installed IED (intelligent electronic device) control applications. The IEDs are designed for most utility
is ready to be put into service. The further addition of substations and industrial power systems including radial,
communication functionality and interoperability between looped and meshed distribution networks that may also
substation automation devices offered by the IEC 61850 involve distributed power generation.
standard adds flexibility and value to end users as well
as electrical system manufacturers.
2 Pre-configured solutions for utility distribution and industrial applications | The 611 series
Highlights of the 611 series: – The input/output signal configuration can be altered by
– The use of application-specific standard configurations local HMI, Web HMI (Web browser-based user interface) or
results in a shorter IED setup and commissioning time. the optional application functionality of the protection and
– The application-specific settings can be made via the local control IED manager PCM600.
HMI or the Web browser-based user interface. – The compact design makes it excellent for both new and
– In addition, the improved Web browser-based user retrofit installations.
interface allows modification of the IED’s signal – The IEDs incorporate native IEC 61850 implementation
configuration – internal as well as external input and that offers support for the high-performance preconfigured
output signals. binary GOOSE messaging.
– The control of one circuit breaker is possible via remote – Optional communication protocol: Modbus®
communication or via the IED’s local HMI (human-machine – Optional second Ethernet bus is also available.
interface).
The 611 series | Pre-configured solutions for utility distribution and industrial applications 3
Feeder protection and control
with powerful Web HMI
REF611 is a dedicated feeder IED designed for the The feeder protection IED REF611 can be supplied either with
protection, control, measurement and supervision of directional or non-directional earth-fault protection. Directional
utility substations and industrial power systems including earth-fault protection is mainly used in isolated neutral or
radial, looped and meshed distribution networks with or compensated networks, whereas the non-directional earth-
without distributed power generation. REF611 is available fault protection is intended for directly or low-impedance-
in two alternative standard configurations. earthed neutral networks.
4 Pre-configured solutions for utility distribution and industrial applications | The 611 series
3I 50/
3I > 51P-1 3I >> 51P-2 3I >>>
Uo 51P
Io
3θ > F 49F 3 I >BF 51BF Io >> 51N-2
1)
0➔I 79 Lockout 86
relay
1
Io >BF 51N Io > IEF 67N Io > 67N-1
BF IEF
Io
1) Optional
3I 50/
3I> 51P-1 3I >> 51P-2 3I >>>
51P
1)
Io
1) Optional
The 611 series | Pre-configured solutions for utility distribution and industrial applications 5
Motor protection and control
for a variety of drives
REM611 is a dedicated motor protection and control IED The IED offers all the functionality needed to manage motor
designed for the protection, control, measurement and starts and normal operation, including protection and fault
supervision of asynchronous motors in manufacturing and clearance in abnormal situations.
process industry. Typically, the motor IED is used with
circuit breaker or contactor-controlled medium-sized or The main features of the motor IED include thermal overload
small motors in a variety of drives, such as pumps and protection, motor startup time supervision, locked rotor
conveyors, crushers and choppers, mixers and agitators protection and protection against too frequent motor starts.
and fans and aerators. REM611 is available in one The IED also incorporates non-directional earth-fault
standard configuration. protection, negative phase sequence current unbalance
protection and backup overcurrent protection.
6 Pre-configured solutions for utility distribution and industrial applications | The 611 series
50/
3I > 51P-1 3I >> 51P-2 3I >>>
51P
1)
1
Io > BF 51N Io > 51N Io >>> 50N
Io BF (SEF)
3
Io > 51N-1 Io >> 51N-2 Lockout 86
3I relay
1) Optional
REF611 (standard conficuration B)
Motor start blocking
3I> 51P-1 3 I >>> 50 3θ > M 49M 3I> 51P-1 3 I >>> 50 3θ > M 49M
3 3
I s2 t, n< I s2 t, n<
3I I 2 >> 46R Ist> 51LR 3I I2>> 46R Ist> 51LR
49, 66, 48, 51LR 49, 66, 48, 51LR
Io
Io >> Io > BF 51N Io > Io >> Io > BF 51N
Io > 51N-1 51N-2
BF
51N-1 51N-2
BF
M M
Lockout 86 ESTART ESTART 3I< 37 Lockout 86 ESTART ESTART
relay relay
The 611 series | Pre-configured solutions for utility distribution and industrial applications 7
Busbar and ideal multipurpose
backup protection
REB611 is a dedicated busbar protection IED designed The IED offers phase-segregated (three phases) high-
for phase-segregated short circuit protection, control and impedance differential protection and non-directional earth-
supervision of single busbars. REB611 is intended for fault protection for busbars, motors and generators. REB611
use in high-impedance-based applications within utility also offers high-impedance differential-based restricted earth-
substations and industrial power systems. In addition, the fault protection for motors, generators, reactors and power
IED can be utilized in restricted earth-fault and residual transformers. REB611 is also ideally suited for backup
earth-fault applications for the protection of generators, protection.
motors, transformers and reactors. REB611 is available
in one standard configuration. The IED REB611 offers bus-differential protection in a single
zone with bus-wire supervision. It also offers the possibility for
bus-differential protection over two zones using two REB611
IEDs. REB611’s high-impedance protection functions contain
a built-in blocking functionality which is provided by the bus-
wire supervision functions to restrict faulty operations in case
of faults in the measurement circuits.
8 Pre-configured solutions for utility distribution and industrial applications | The 611 series
3I 3
3 3 3
Lockout 86
relay
Protection function overview of standard configuration A in a single zone with bus-wire supervision.
3I
Hi> 87 MCS 1I MCS 1I 3I>BF 51BF
G
3 Lockout 86
relay
1 Io
The 611 series | Pre-configured solutions for utility distribution and industrial applications 9
Standard configurations
Standard configurations
Description Standard configuration
Feeder protection and control, non-directional overcurrent and directional earth-fault protection REF611 configuration A
Feeder protection and control, non-directional overcurrent and non-directional earth-fault protection REF611 configuration B
Motor protection and control, motor protection REM611 configuration A
Busbar protection and control, high-impedance differential REB611 configuration A
x = included, o = optional
Directional earth-fault protection, low stage, instance 1 DEFLPDEF1 Io> g (1) 67N-1 (1) x2) 3)
Directional earth-fault protection, low stage, instance 2 DEFLPDEF2 Io> g (2) 67N-1 (2) x2) 3)
Directional earth-fault protection, high stage DEFHPDEF1 Io>> g 67N-2 x2) 3)
Transient / intermittent earth-fault protection INTRPTEF1 Io> g IEF 67NIEF x
Non-directional (cross-country) earth fault protection,
EFHPTOC1 Io>> (1) 51N-2 (1) x4)
using calculated Io
Negative-sequence overcurrent protection, instance 1 NSPTOC1 I2> (1) 46 (1) x x x
Negative-sequence overcurrent protection, instance 2 NSPTOC2 I2> (2) 46 (2) x x x
Phase discontinuity protection PDNSPTOC1 I2/I1> 46PD x x
Residual overvoltage protection, instance 1 ROVPTOV1 Uo> (1) 59G (1) x3)
Residual overvoltage protection, instance 2 ROVPTOV2 Uo> (2) 59G (2) x 3)
Residual overvoltage protection, instance 3 ROVPTOV3 Uo> (3) 59G (2) x 3)
Three-phase thermal protection for feeders, cables and
T1PTTR1 3Ith>F 49F x x
distribution transformers
Loss of load supervision LOFLPTUC1 3I< 37 x
Motor load jam protection JAMPTOC1 Ist> 51LR x
Motor start-up supervision STTPMSU1 Is2t n< 49,66,48,51LR x
Phase reversal protection PREVPTOC1 I2>> 46R x
Thermal overload protection for motors MPTTR1 3Ith>M 49M x
Circuit breaker failure protection CCBRBRF1 3I>/Io>BF 51BF/51NBF x x x
Three-phase inrush detector INRPHAR1 3I2f> 68 x x
Master trip, instance 1 TRPPTRC1 Master Trip (1) 94/86 (1) x x x x
Master trip, instance 2 TRPPTRC2 Master Trip (2) 94/86 (2) x x x x
High-impedance differential protection, instance 1 HIPDIF1 dHi>(1) 87 (1) x
High-impedance differential protection, instance 2 HIPDIF2 dHi>(2) 87 (2) x
High-impedance differential protection, instance 3 HIPDIF3 dHi>(3) 87 (3) x
10 Pre-configured solutions for utility distribution and industrial applications | The 611 series
x = included, o = optional
The 611 series | Pre-configured solutions for utility distribution and industrial applications 11
Contact us
www.abb.com/substationautomation
1MRS757399 A 1.0