11 AC Voltage Control
11 AC Voltage Control
Lecture 11
1
Ac voltage control
If a thyristor switch is connected between ac supply and load, the
power flow can be controlled by varying the rms value of ac voltage
applied to the load.
wt
Practically, n+m < 100 cycles.
ig1 Gate pulse of T1
Due to zero-voltage and zero-
current switching of thyristors, wt
2 ( n m ) 0
n
vo Vs Vs k
mn
where k=n/(m+n) and is called the duty cycle. Vs is the rms phase voltage.
The input current is the same as the load current The rms supply
current Is = the rms load current Ia .
5
Q1/Sheet 3: A single-phase ac voltage controller has a resistive load
of R=10Ω and the input voltage is Vs=120V, 60Hz. The thyristors are
switched on for n=25 cycles and are switched off for m=75 cycles.
Calculate: (a) the rms output voltage, (b) the input power factor, and (c)
the average and rms current of thyristors.
Solution
R 10 , Vs 120 V , Vm 2 120 169.7V ,
and k n /( n m) 25 / 100 0.25
n 25
a- v o Vs k Vs 120 60V
mn 100
And the rms load current is Io=Vo/R=60/10=6.0A.
6
b- The load power is Po= Io2 R = 6 2 ×10 = 360W.
The volt-ampere (VA) input: VA Vs I s Vs I o 120 6 720VA
P0 360
PF k 0.25 0.5
VA 720
V0 k Vs 1 Vm 1
I
Note: 0 I s k k Im
R R 2 R 2 k Im
2 2 IR
I0 IR |T 1 I R|T 2 2 I R 2
7
Single-phase Bidirectional controllers with resistive loads
1 sin 2
Vo Vs ( ) 0 Vo Vs
2
Power Factor
It would require detecting the zero crossing of the load current to
guarantee turn-off of the conducting thyristor before firing the next
one.
Three power devices conduct at the same time and the efficiency
is also reduced.
12
Q2/Sheet 3: A single-phase full-wave ac voltage controller has a
resistive load of R=10Ω and the rms input voltage is Vs=120V (rms),
60Hz. The delay angles of thyristors are α1 =π/2 and α2 =3π/2. Determine
(a) the rms output voltage, (b) the input power factor, and (c) the
average and rms currents of thyristors.
Solution
R 10 , Vs 120 V , / 2 ,Vm 2 120 169.7V ,
sin 2
a- Vo Vs 1 sin 2 120
1
2 120
84.85V
2 2 2 2
b- The rms load current is Io=Vo /R=84.85/10=8.485A and the load
power is Po=Io2 × R = 8.4852 × 10 =719.95W. Because the input
current is the same as the load current, the input VA rating is
2Vs 120
IA (cos 1 ) 2 2.7 A
2R 2 10
Vs 1 sin 2 120
IR 6A
2R 2 2 10
14
Single-phase AC Voltage Controllers with inductive load
In practice, most loads are
inductive to a certain extent. A full-
wave controller with RL load is
shown in the figure to the left.
Let us assume that thyristor T1 is
fired during the positive half-cycle
and caries the load current.
Due to inductance in the circuit, the current of thyristor T1 would
not fall to zero at ωt=π, when the input voltage starts to be negative.
Thyristor T1 continues to conduct until its current i1 falls to zero at
ωt=β (the extinction angle).
The conduction angle of thyristor T1 is δ=β-α which depends on the
delay angle α and the power factor of the load.
The waveforms for the thyristor current, gating pulses, and input
voltage are shown in the next slide.
15
If vs 2Vs sin t is the instantaneous
input voltage and the delay angle of
thyristor T1 is α , the thyristor current
i1 can be found from:
di1
L Ri1 2Vs sin t .............1
dt
The solution of equation 1 is in the
from:
2Vs
i1 sin(t ) A1e t / .........2
Z
Where load impedance Z = [ R2 + (ωL)2 ]1/2 and the load angle
θ=tan-1(ωL/R) and the time constant of the load τ =L/R.
The constant A1 can be determined from the initial condition: at ωt=α,
i1=0. From equation 2, A1 is found as,
2Vs
A1 sin( )e( / ) ..........................................................3
Z
16
Substitution of A1 from 3 in 2 yields,
i1
2Vs
Z
sin(t ) sin( )e( t ) / ...........................4
The angle β, when the current i1 falls to zero and thyristor T1 is turned
off, can be found from the condition i1(ωt=β)=0 in Eq 4 and is given by
the relation,
sin( ) sin( )e( ) / .......................................................5
2 2 2 1 sin 2 sin 2
Vo
2
2Vs sin t d (t ) Vs
2
2
17
The rms thyristor current can be found from eq 4 as
1 2
IR
2 i 1 d (t )
Vs 1
2
( t ) /
IR
Z sin(t ) sin( ) e d (t ) .................7
And the rms output current can then be determined by combining the
rms current of each thyristor as
Io I I
2
R
2
R 1
2
2 I R .........................................................................8
Po I o2 R I R
The input supply power factor = o
VA Vs I o Vs
The average value of thyristor current can also be found from Eq. 4 as
1
IA
2 i 1 d (t )
IA
2 Vs
2 Z
sin(t ) sin( )e ( t ) /
d (t ) ......9
18
The gating signals of thyristors could be short pulses for a controller
with resistive loads.
However, such short pulses are not suitable for inductive loads. This is
because the current of the inductive load takes time to build from zero
the duration of the short pulse might be insufficient for the thyristor
current to exceed its holding value Thyristor is not turned-on.
This difficulty can be resolved by using continuous gate signals with a
duration of (π-α).
2- Because the conduction angle δ can not exceed π and the load
current must pass through zero, the delay angle α may not be less than
θ and the control range of delay angle is
θ≤α≤π
3- If α ≤ θ and the gate pulse of thyristors are of long duration, the load
current would not change with α , but both thyristors would conduct for
π. Thyristor T1 would turn on at ωt= θ and thyristor T2 would turn on at ωt
= π+ θ normal RL circuit (uncontrolled).
21
Short Pulse, α > θ Long Pulse, α > θ
i1
2Vs
Z
sin(t ) sin( )e( t ) /
6.18 sin(t 0.756) 23.8e t / 0.943 for t 23
The extinction angle β is determined from the numerical solution of
i1(β)=0 , yielding: β = 3.83 rad = 220°.
(b) I 1 2
o i1 d (t ) 2.71A
Vo Vs 1 sin 2 sin 2
Note: I o Why?
Z Z 2 2
(c) I R I o / 2 1.92 A
1
(d) I A
2
i1 d (t )
1 t / 0.943
2
[ 6.18 sin(t 0.756) 23.8e ]d (t ) 1.04 A
25
2) STATIC VAR CONTROL (SVC)
Capacitors are routinely placed in parallel with inductive loads for power
factor improvement. If a load has a constant reactive voltampere (VAR)
requirement, a fixed capacitor can be selected to correct the power factor to
unity. However, if a load has a varying VAR requirement, the fixed-capacitor
arrangement results in a changing power factor.
The circuit shown represents an application of an ac voltage controller to
maintain a unity power factor for varying load VAR requirements.
The power factor correction capacitance supplies a fixed amount of reactive
power, generally greater than required by the load. The parallel inductance
absorbs a variable amount of reactive power, depending on the delay angle
of the thyristors.
The net reactive power supplied by the
inductor-capacitor combination is
controlled to match that absorbed by the
load. This type of power factor correction
is known as static VAR control.
26
2) STATIC VAR CONTROL
The thyristors are placed in the inductor branch rather than in the capacitor
branch because very high currents could result from switching a capacitor.
Static VAR control has the advantage of being able to adjust to changing
load requirements very quickly. Reactive power is continuously adjustable
with static VAR control, rather than having discrete levels as with capacitor
banks which are switched in and out with circuit breakers.
27