EasyPower Data Collection For Arc Flash Studies - 1a
EasyPower Data Collection For Arc Flash Studies - 1a
CHAPTER
Data Collection for an
Arc Flash Hazard Study
Introduction
Like any other project, data collection requires prior planning and should take into
consideration the following concerns.
• What existing documents are available and how accurate are these documents?
• What is the scope of the study and how much of the system is included?
• Where are the interfaces between the system to be evaluated and the local
utility or other entities?
• How much field data collection will be required and how will it be done?
• What are the responsibilities of the facility team versus the study team?
Based on the answers to these questions, the arc-flash risk assessment may need
to be broken up into different phases. It might be better to collect data and build
the one-line model from the medium and high voltage distribution downstream to
the individual low voltage substations, collecting data for each feeder serving a
switchboard, MCC and panelboard. Typically, arc-flash incident energies are higher
at these locations than in other low voltage equipment further downstream in the
system. After the intermediate study has been completed, then additional data
may be collected and added to the EasyPower model to perform the arc-flash risk
assessment. The scope of the study and the best approach to sequencing the work
should be discussed with the facility staff and well-documented.
The scheduling and sequencing of data collection will depend on who will be doing
the on-site work: a member of plant staff, a contracted individual who is normally
on-site, or a consultant or contracted individual who has traveled to the site. If site
personnel will be responsible for data collection, it will be important to communicate
clearly regarding what data is required.
Obviously, the amount of time required for data collection depends on many factors,
including:
The following steps can serve as rough mileposts for the data collection process,
recognizing that every facility and situation will have unique aspects.
76
Practical Solution Guide to Arc Flash Hazards
77
CHAPTER 7 | Data Collection for an Arc Flash Hazard Study
the equipment data, you can obtain help from experienced people using the
picture.
8. Most equipment has nameplates that show the equipment ratings. Note the
details from the nameplates and take a photo if possible.
9. For equipment with adjustable settings, note the range of available settings
and the current setting. The status of switching devices should also be noted
(open or closed).
10. Create a one-line diagram showing all the equipment such as utility
connections, transformers, cables, switches, circuit breakers, fuses, loads,
switchgear, etc. Make sure that their interconnection is correctly represented
in the drawing. Mark each equipment item with the ID names and enter the
relevant data. Commercial power system software like EasyPower can create
one-line diagrams, store all the necessary equipment data, and perform arc-
flash risk assessment. ID names are also important for placing arc-flash labels
in the appropriate locations after the equipment incident energy has been
determined.
11. The more knowledge the electrician (plant personnel) has of the facility, the
better the final model will be. You may need to consult with several plant
individuals before you understand or gather data you need.
12. If you have information from previous studies with recommended settings or
drawings, be sure to verify the data. The facility may not have been updated
after the previous study, fuses may have been changed, or the instantaneous
trip functions may have been adjusted due to nuisance tripping.
13. Before beginning data collection, understand the purpose and scope of the
data collection. What kind of study are you performing and what areas of the
facility must be modeled?
14. Strive to collect all necessary data while in a particular area to minimize the
need for additional site visits or data requests. Take photographs of equipment
whenever possible.
15. The electrical safety of the data collection team is the first priority and needs
to be included in a comprehensive Job Safety Plan document for the data
collection project.
This book is focused on performing arc-flash hazard assessment studies, but if other
studies could be performed in the future using the one-line model developed for the
arc-flash study, you may want to consider collecting additional information while
performing this study. The data to be collected as described in this chapter will allow
for short circuit analysis, protective device coordination, and arc-flash studies
78
Practical Solution Guide to Arc Flash Hazards
• Facility drawings.
• A non-conductive flashlight.
• A non-conductive mirror and handle, so that you can view difficult locations
and avoid blind reaching.
• Remain behind the Restricted Approach Boundary at all times while collecting
data.
• Some data may not be safely obtainable through field inspection. If the
equipment is energized and all the necessary information cannot be obtained,
perform data collection during a scheduled shutdown, or obtain data from shop
drawings, test reports, or other documentation. In some cases, reasonable
assumptions must be made. Any assumptions should be noted in the report. Do
not take unnecessary risks when collecting data.
• Electrical hazards such as shock and arc flash are not the only hazards that
79
CHAPTER 7 | Data Collection for an Arc Flash Hazard Study
exist during data collection. Follow all site safety policies regarding the use of
ladders and lifts for work above the floor and use fall protection as required. If
necessary, shutdown and lockout conveyors or other moving equipment.
• Do not touch any equipment unless necessary and avoid leaning or sitting on
equipment.
• Keep track of all tools, cameras, phones, and backpacks, and avoid leaving
things behind. All equipment should be left in the same condition as found.
Be sure to document all assumptions in the report in case any questions or issues
should arise in the future.
• For MCCs and panelboards, it may not be necessary to collect data and model
every feeder completely. If no arc-flash label is needed at the downstream
80
Practical Solution Guide to Arc Flash Hazards
• For long runs of bus duct with numerous taps, it may be time consuming to
collect data for all the equipment served from the bus taps. If time or access
to the bus plugs are an issue, consider collecting feeder data for an assortment
of bus plug sizes along the length of the bus duct. For example, if a bus plug
is 200 feet in length, you might consider collecting data at the beginning (0
feet), middle (100 feet) and end (200 feet), for different bus plug sizes (30 A, 100
A, 200 A). Then in the EasyPower software, model a bus at each of the three
bus duct locations and add the generic feeder data for each of the bus plug
sizes at each bus. An example is shown in the following figure. As long as the
conductor length is similar, using the generic arc-flash incident energy should
be sufficient. If the length is much longer, then these cases should be modeled
individually. Also, it is recommended that any bus plugs 400A or larger should
be modeled individually. Since an EasyPower bus is required to show taps from
the bus duct, it is reasonable to group the taps at buses instead of creating a
bus for each tap. It is important to get an approximation of the total length of
the bus duct and model the bus duct system such that the modeled length is
roughly equal to the actual length.
kV
kV
kV
BD B BD M BD E
48
48
48
800A-(Generic) 800A-(Generic)
0.
0.
0.
1-1/C-3/0 AWG
1-1/C-3/0 AWG
1-1/C-10 AWG
1-1/C-10 AWG
1-1/C-10 AWG
1-1/C-2 AWG
1-1/C-2 AWG
1-1/C-2 AWG
kV
kV
kV
kV
kV
kV
kV
kV
kV
48
48
48
48
48
48
48
48
48
81
CHAPTER 7 | Data Collection for an Arc Flash Hazard Study
• There are books and papers from manufacturers available that provide typical
data for equipment. A book that has quality data that can be used as estimations
is A Practical Guide to Short-Circuit Calculations by Conrad St. Pierre. The book
can be purchased by contacting EasyPower.
The third template is for data collection of low voltage power circuit breakers with
associated trip units. The template includes all the different device types and settings
that are required to properly model the breaker and trip units in the EasyPower
software. For other types of protective devices, data collection templates may be
created based on the software requirements.
82
Practical Solution Guide to Arc Flash Hazards
PRIMARY
PRIM BKR
PRIMARY FEEDER:
Cond/Phase:
Cond Size:
Cond Matl:
Length:
Rcwy Size:
Rcwy Type:
FUSED SWITCH:
TRANS PRI
Fuse Type:
Fuse Size: FS-1
Switch Amps:
Short Ckt:
C&L:
TRANSFORMER DATA
kVA:
Voltages:
Taps:
XFMR
Impedance:
SUB-MAIN
kV
SUBSTATION
48
0.
SECONDARY FEEDER:
SUB-1 SUB-2 SUB-3
Cond/Phase:
Cond Size:
Cond Matl: Feeder Breaker Data
Length:
Breaker Mfg: =
Rcwy Size Breaker Type: =
Rcwy Type Trip Type: =
kV
LTPU: =
48
LTD: =
0.
PANEL
PNL-1 STPU:=
STD: =
0 kVA
83
CHAPTER 7 | Data Collection for an Arc Flash Hazard Study
Substation:
FEEDER DATA:
Cond/Phase:
SUB-1 Cond Size:
MCC LOAD DATA:
Cond Matl:
Constant-Speed Motors:
Length:
Total Motor > 50 hp:
Total Motor < 50 hp:
Rcwy Size:
Rcwy Type:
Total AFD Load:
Meter Data:
LARGEST FEEDER:
LARGEST MOTOR:
Name:
(Constant-Speed)
Smallest Breaker Data: Load:
(Lowest I.C.) Bkr Type:
Name:
Frame:
HP:
Manuf: Trip:
Bkr Type:
Type: Short Circuit:
Frame:
Frame: Inst. Trip:
Trip:
Amp Rating:
Short Circuit:
Inst Setting:
Inst. Trip:
Interrupting Rating:
84
Breaker Breaker Frame Size Trip Unit Plug Long Long Short Short
Time Time I2 T Inst. Ground Ground
Time Interupting
ID Mfr/Type Rating Comments
Sensor Mfr/Type Rating Pickup Delay Pickup Delay Pickup Pickup Delay
Form for Low Voltage Breaker with Trip Units
85
Practical Solution Guide to Arc Flash Hazards
CHAPTER 7 | Data Collection for an Arc Flash Hazard Study
86
Practical Solution Guide to Arc Flash Hazards
From
Breaker Style
87
CHAPTER 7 | Data Collection for an Arc Flash Hazard Study
E38773
P93083
Wire range :
MERLIN GERIN 14AWG - 350MCM Cu
compact 10AWG - 350MCM Al
60/75°C - 15 to 125A only
NSF 250 N
Circuit breaker OFF Torque value
14AWG - 1/0
: lb.in (N.m)
: 150 (17)
600V 50/60Hz 2/0 - 4/0 : 200 (23)
250 - 350MCM : 275 (32)
UL interrupting ratings
UL/CSA
240V 65kA
480V 35kA
600Y/347V 18kA
IEC947-2 Icu
220/240V 85kA Accessory terminals
behind this cover.
380/415V 36kA Caution: Open circuit
-breaker
l power
and disconnect contro
cover.
before removing this
UNE NEMA
UTE VDE BS CEI
made in France
250A
push
to
trip
TM 250 DP
Im 250A / 40°C
10
Ir 5
250A 9
6
8
1 0,9 0,8 7
x 250 A
Ir Im
88
Practical Solution Guide to Arc Flash Hazards
89
CHAPTER 7 | Data Collection for an Arc Flash Hazard Study
90
Practical Solution Guide to Arc Flash Hazards
Generator (Example A)
Model S4
Power Factor 0.8
kVA 512
kW 410
RPM 1800
91
CHAPTER 7 | Data Collection for an Arc Flash Hazard Study
Generator (Example B)
Transformer (Example A)
92
Practical Solution Guide to Arc Flash Hazards
Transformer (Example B)
Press
Calculate for
all SC values
93