NFPA 2023-04-14 0015 - CUARTO IT - PVE23001102 - Computo de 46 m2
NFPA 2023-04-14 0015 - CUARTO IT - PVE23001102 - Computo de 46 m2
In compliance with NFPA 2001 (2012 Edition) Annex C Enclosure Integrity Procedure
Fitflow Peru
Page 1 of 12 4/15/2023
C:\Users\user\Desktop\NFPA 2023-04-14 0015 [2023-04-14 0243] BBVA TRUJILLO CEDE PRINCIPAL.docx
Summary – CUARTO IT
version: 5.12.35
FanTestic Integrity licensed to: Fitflow Peru
Test date: 2023-04-14 By: HENRY FULLEDA Certification: 3
Location: TRUJILLO Building: BANCO BBVA
Witness: GV PROYECTOS
Enclosure conditions prior to discharge Extinguishing agent details
Net protected volume, V [m³] 110.5 Agent Novec 1230 [FK-5-1-12]
Max flooded height, Ho [m] 2.42 Quantity [kg] 76.6
Required protected height, Hp [m] 2.1 Type Halocarbon
Design temp, T [C] 20.0 Discharge time, [s] 10
Enclosure pressure limit, [Pa] 500 Mixing during hold time No
Specified Hold Time, [min] 10 Initial concentration, ci 4.7962%
Elevation, [m] 90 Design concentration, c 4.5%
Minimum design humidity 56% Bias during Hold, Pbh [Pa] -0.7
Maximum design humidity 100%
Test equipment Hold time results
Fan make/model Retrotec 3000SR
Fan serial # PH001019 Leakage exponent, n 0.887
Fan calibration date Leakage constant, k1 [CFM/Paⁿ] 11.75
Gauge make/model DM32 Total Leakage Area, [cm²] 172
Gauge serial # 416306
Gauge calibration date 2023-01-24 Predicted Hold Time, t [min] 18.9
Calculations predict a maximum negative peak pressure of 320 Pa. This pressure is less than the specified
maximum enclosure pressure limit of 500 Pa, therefore the enclosure PASSES this part of the procedure.
Page 2 of 12 4/15/2023
C:\Users\user\Desktop\NFPA 2023-04-14 0015 [2023-04-14 0243] BBVA TRUJILLO CEDE PRINCIPAL.docx
Assumptions and warnings
While FanTestic Integrity software may identify clean agent peak pressure and hold time risks, use of this
software does not in any way guarantee the elimination of those risks.
• The initial extinguishing agent concentration as indicated in the test report will be achieved.
• Ductwork connected to air-handling systems that are outside this enclosure will be either isolated with
dampers or will be shut down during the hold time.
• If air handlers are used to provide continuous mixing, they will be dedicated to this enclosure and will
not create significant flows across the enclosure boundaries.
• An adequate return path for the air flow was provided during the enclosure integrity door fan tests.
• All intentional openings will be sealed during the enclosure leakage for hold time tests.
• Design temperature inside the tested enclosure during discharge is 20.0 C.
• There are NO fans that continue running during the hold time or heat sources that will produce enough
air circulation to cause a ‘continuous mixing’ condition within the entire enclosure.
• All other non-integrity tests, as outlined in the NFPA standard, will be satisfactorily completed.
Calculations for peak pressure were performed using equations from the Fire Suppression Systems Association
(FSSA) “Pressure Relief Vent Guide”.
• All intentional openings will be set to the operating condition expected during the agent discharge for
positive peak pressure relief when enclosure leakage is tested for positive vent area.
• In addition, for halocarbons only, all intentional openings will be set to the operating condition expected
during the agent discharge for negative peak pressure relief when enclosure leakage is tested for
negative vent area.
• Adequate air flow was provided along a path leading to outdoors for the test fan but the doors
surrounding the enclosure were set in the position that provide the lowest air flow required to establish
the required test pressures.
• Design temperature inside the tested enclosure during discharge is 20.0 C.
• Relative humidity in the enclosure will range between 56% and 100%.
Page 3 of 12 4/15/2023
C:\Users\user\Desktop\NFPA 2023-04-14 0015 [2023-04-14 0243] BBVA TRUJILLO CEDE PRINCIPAL.docx
Background
Hold time prediction, Descending Interface Model
This procedure predicts the hold time for the extinguishing agent/air interface to drop to the specified minimum
protected height, based on the variables shown in this report. Due to the conservative assumptions regarding
leakage distribution, this prediction model usually predicts a shorter retention time as compared to an actual
discharge, but not always.
This prediction only applies to conditions as found at the time of the test. Additional penetrations, weather,
open doorways, HVAC modifications, malfunctions and the inherent assumptions in the enclosure integrity
procedure could all combine to give very different results in a real discharge.
Page 4 of 12 4/15/2023
C:\Users\user\Desktop\NFPA 2023-04-14 0015 [2023-04-14 0243] BBVA TRUJILLO CEDE PRINCIPAL.docx
Discussion of Results – CUARTO IT
Hold Time
Compliance with Annex C of NFPA 2001 (2012 Edition)
It is predicted that a Total Enclosure Leakage measurement of 172 cm² maintains the minimum concentration of
3.825% at the minimum protected height of 2.1 m for 18.9 minutes. This hold time is greater than the specified
minimum of 10 minutes, therefore the enclosure PASSES this acceptance procedure. It was assumed that there
was no ‘continuous mixing’ condition during the hold time. Predicted hold time was therefore calculated based
on a descending interface model.
The maximum leakage allowed in the enclosure that will still maintain a hold time of 10 minutes is 325 cm²
(calculated at a reference pressure of 10Pa).
Peak Pressure
Compliance with section 5 of NFPA 2001 (2012 Edition)
5.3.7: The protected enclosure shall have the structural strength and integrity necessary to contain the agent
discharge. If the developed pressures present a threat to the structural strength of the enclosure, venting shall
be provided to prevent excessive pressures.
And that the following shall be submitted for approval to the authority having jurisdiction:
5.1.2.2 (10): maximum positive and the maximum negative pressure... expected to be developed upon the
discharge of agent
5.1.2.2 (28): pressure relief vent area… to prevent development of a pressure difference across the enclosure
boundary that exceeds a specified enclosure pressure limit.
Calculations for peak pressure, based on leakage area of Enclosure Only at a standard reference condition of
125 Pa and using no pressure relief vent (PRV), determined:
• The enclosure would represent a free vent area during discharge of 457 cm² with the enclosure set up in
the condition expected to occur during the positive pressure pulse caused by the agent discharge which
is predicted to be 85 Pa. This pressure is less than the specified maximum of 500 Pa, therefore the
enclosure PASSES this part of the procedure
• The enclosure would represent a free vent area during discharge of 457 cm² with the enclosure set up in
the condition expected to occur during the negative pressure pulse caused by the agent discharge which
is predicted to be 320 Pa . This pressure is less than the specified maximum of 500 Pa, therefore the
enclosure PASSES this part of the procedure.
Vents should be installed high in the enclosure so that mostly air is exhausted, instead of the heavier
extinguishing agent. Additionally, the vents should be rated to fully open between 80-130 Pa. Once a vent is
installed or it is decided to use leakage of the enclosure only to relieve pressures during discharge, the chosen
venting situation is used to calculate expected peak pressure, and the available free vent area must be enough
to relieve this peak pressure in order to pass. All leakage areas are extrapolated to a standard reference
condition of 125 Pa which is representative of conditions where most of the peak pressure will be relieved.
• At the highest humidity of 100%, a peak positive pressure of approximately 85 Pa would form.
• At the lowest humidity of 56%, a peak negative pressure of approximately –320 Pa would form.
Page 5 of 12 4/15/2023
C:\Users\user\Desktop\NFPA 2023-04-14 0015 [2023-04-14 0243] BBVA TRUJILLO CEDE PRINCIPAL.docx
Free vent area required calculation detail
Assuming an Enclosure Pressure limit of ±500 Pa, this enclosure requires a total vent free area of 82 cm² in the
positive direction and 297 cm² in the negative direction to maintain the enclosure’s structural integrity.
• 457 cm² for the Enclosure Only with the enclosure set up in its Positive Discharge Period Condition,
where any dampers or installed PRV were fixed in the position they would assume under +125 Pa.
• 457 cm² for the Enclosure Only with the enclosure set up in its Negative Discharge Period Condition,
where any dampers or installed PRV were fixed in the position they would assume under -125 Pa.
The Enclosure Only provides 457 cm² of negative venting area. Since this is more than the required total of 297
cm², this enclosure does not require any additional PRV area to maintain structural integrity and pass the peak
pressure procedure in the negative direction.
Page 6 of 12 4/15/2023
C:\Users\user\Desktop\NFPA 2023-04-14 0015 [2023-04-14 0243] BBVA TRUJILLO CEDE PRINCIPAL.docx
Test Data Appendix– CUARTO IT
The following table represents the results from the enclosure integrity procedure carried out on the whole
enclosure, with all intentional openings sealed.
Test conditions
Inside temperature,
Test date 2023-04-14 20 C
Te [C]
Outside temperature,
Test time 00:20:14 20 C
To [C]
Operator location Inside Bias pressure, Pbt [Pa] -0.43
Range C4
Fan #1,
Fan #1,
Page 7 of 12 4/15/2023
C:\Users\user\Desktop\NFPA 2023-04-14 0015 [2023-04-14 0243] BBVA TRUJILLO CEDE PRINCIPAL.docx
Page 8 of 12 4/15/2023
C:\Users\user\Desktop\NFPA 2023-04-14 0015 [2023-04-14 0243] BBVA TRUJILLO CEDE PRINCIPAL.docx
Page 9 of 12 4/15/2023
C:\Users\user\Desktop\NFPA 2023-04-14 0015 [2023-04-14 0243] BBVA TRUJILLO CEDE PRINCIPAL.docx
Venting data for Enclosure Only
There was no PRV installed for pressure relief so the Total Enclosure Leakage measured was extrapolated to the
reference pressure of 125 Pa and used in further calculations as the only available leakage for peak pressure
relief.
In the case where the leakage area of the PRV only was to be used for pressure relief, but leakage area for
enclosure and vent was entered as the venting area dataset, to determine leakage area for pressure relief by
PRV alone, the leakage of the enclosure would have been subtracted from the leakage of the venting dataset.
In the case where the leakage area of the enclosure and PRV was to be used for pressure relief, but leakage area
for vent only was entered as the venting area dataset, to determine leakage area for pressure relief by the
enclosure and PRV, the leakage of the enclosure would have been added to the leakage of the venting dataset.
The leakage of the Enclosure Only in the positive direction was obtained by measuring, and this leakage was
manipulated as necessary to determine the leakage area of the Enclosure Only required for positive pressure
relief.
The leakage of the Enclosure Only in the negative direction was obtained by measuring, and this leakage was
manipulated as necessary to determine the leakage area of the Enclosure Only required for negative pressure
relief.
Design details
Enclosure pressure limit, [Pa]: 500
Discharge time, [s]: 10
Pressure relief vent type: no pressure relief vent (PRV)
Peak Pressure relief using: Enclosure Only
Page 10 of 12 4/15/2023
C:\Users\user\Desktop\NFPA 2023-04-14 0015 [2023-04-14 0243] BBVA TRUJILLO CEDE PRINCIPAL.docx
Peak Negative Pressure Venting summary – Negative Direction
Peak negative pressure, [Pa] 320 Minimum required leakage, [cm²] 297
Venting area used, [cm²], (describes
Leak to volume ratio, LVRneg [cm²/m³] 4.1 457
Enclosure Only)
Additional PRV area needed, [cm²] 0
Page 11 of 12 4/15/2023
C:\Users\user\Desktop\NFPA 2023-04-14 0015 [2023-04-14 0243] BBVA TRUJILLO CEDE PRINCIPAL.docx
Test Equipment
The following test equipment was used in the performance of the enclosure integrity tests.
Gauge
Fan Fan serial Fan location Gauge Gauge Calibration
serial
#1 Retrotec 3000SR PH001019 LIMA DM32 416306 2023-01-24
Range n K K1 K2 K3 K4 MF
Fan Pressure (FP) is the measured fan pressure when using a self-referenced fan or when Room Pressure (RP) is
negative. If using a fan which is not self-referenced, and Room Pressure is positive, Fan Pressure is calculated by
subtracting the measured Room Pressure from the Absolute Value of the Fan Pressure.
Flow calculations are not valid if Fan Pressure is less than either MF or (K2 x |RP|).
Flow in CFM using the flow equation parameters shown above is calculated as follows for standard Ranges:
Page 12 of 12 4/15/2023
C:\Users\user\Desktop\NFPA 2023-04-14 0015 [2023-04-14 0243] BBVA TRUJILLO CEDE PRINCIPAL.docx