Course Material 2
Course Material 2
Beams are structural members that receives load from slab and transfers same to the columns. Structural
design of steel beams and joists primarily involves predicting the strength of the member. This requires
the designer to imagine all the ways in which the member may fail during its design life. Modes of failure
of Beams are discussed thus:
1. Bending
Fig. 6 Shear and shear buckling failures: (a) shear failure; (b) shear buckling.
4. Shear buckling
During the shearing process described above, if the web is too thin it will fail by buckling or rippling in the
shear zone, as shown in Fig. 6b.
5. Web bearing and buckling
Due to high vertical stresses directly over a support or under a concentrated load, the beam web may
actually crush, or buckle as a result of these stresses, as illustrated in Fig. 7.
6. Lateral torsional buckling
When the beam has a higher bending stiffness in the vertical plane compared to the horizontal plane,
the beam can twist sideways under the load. This is perhaps best visualised by loading a scale rule on
its edge, as it is held as a cantilever – it will tend to twist and deflect sideways. This is illustrated in
Fig. 8. Where a beam is not prevented from moving sideways, by a floor, for instance, or the beam is not
nominally torsionally restrained at supports, it is necessary to check that it is laterally stable under load.
Nominal torsional restraint may be assumed to exist if web cleats, partial depth end plates or fin plates, for
example, are present as shown in figure 9.
Fig. 9 Nominal torsional restraint at beam support supplied by (a) web cleats ( b) end plate (c) fin plate.
7. Deflection
Although a beam cannot fail as a result of excessive deflection alone, it is necessary to ensure that
deflections are not excessive under unfactored imposed loading. Excessive deflections are those resulting
in severe cracking in finishes which would render the building unserviceable.
Mc = PyS
Where
S > M/Py
This can be used to select suitable universal beam sections from steel tables with the plastic modulus of
section S greater than the calculated value of moment M.
CLASSIFICATION OF SECTION
Having selected a suitable section, or proposed a suitable section fabricated by welding, it must be
Classified.
Strength classification
In making the initial choice of section, a steel strength will have been assumed. If grade S275 steel is to be
used, for example, it may have been assumed that the strength is 275 N/mm2. By referring to the flange
thickness T from the steel tables, the design strength can be obtained from Table 9 of BS 5950, If the
section is fabricated from welded plate, the strength of the web and flange may be taken separately from
Table 9 of BS 5950 as that for the web thickness t and flange thickness T respectively. Having selected a
suitable section, or proposed a suitable section fabricated by welding, the section must be classified to
determine if it is plastic or otherwise.
Section classification
As discussed earlier, the bending strength of the section depends on how the section performs in bending.
If the section is stocky, i.e. has thick flanges and web, it can sustain the formation of a plastic hinge. On
the other hand, a slender section, i.e. with thin flanges and web, will fail by local buckling before the yield
stress can be reached.
Four classes of section are identified in clause 3.5.2 of BS 5950: with the aid of figure 10 below, the
sections are explained.
SHEAR
According to clause 4.2.3 of BS 5950, the shear force, Fv, should not exceed the shear capacity of the
Fv ≤ Pv
Where Pv = 0.6 Py Av
In which Av is the shear area = tD for rolled I-, H- and channel sections. The code gives other formula for
If the co-existent shear force Fv is less than 0.6 Pv, then this is a low shear load. Otherwise, if
When the shear load is low, the moment capacity of the section is calculated according to clause
4.2.5.2 of BS 5950 as follows:
For class 1 plastic or class 2 compact sections, the moment capacity
Where
Py = design strength of the steel
is 1.5PyZ
Mc = PyZ
where Seff is the effective plastic modulus mentioned in clause 3.5.6 of BS 5950.
Note that whereas the equation: Mc = PyZ provides a conservative estimate of the moment capacity of
class 3 compact sections, use of the equation below it is more efficient but requires additional
computational effort.
For class 4 slender sections
Mc = PyZeff
Where Zeff is the effective elastic modulus as stated in clause 3.6.2 of BS 5950.
In practice the above considerations do not prove to be much of a problem. Nearly all sections in grade
S275 steel are plastic, and only a few sections in higher strength steel are semi-compact. No British rolled
universal beam sections in pure bending, no matter what the strength class, are slender or have plastic or
compact flanges and semi-compact webs.
The simply supported beam in Fig. above supports uniformly distributed characteristic dead and imposed
loads of 5 kN/m each, as well as a characteristic imposed point load of 30 kN at mid-span. Assuming the
beam is fully laterally restrained and there is nominal torsional restrain at supports, select a suitable UB
section in S275 steel to satisfy bending and shear considerations.
Example 2 Selection of a beam section in grade S275 steel to BS 5950 For High Shear
A proposed cantilever beam 1 m long is to be built into a concrete wall as shown above. It supports
characteristic dead and imposed loading of 450 kN/m and 270 kN/m respectively. Select a suitable UB
section in S275 steel to satisfy bending and shear criteria only.
SERVICEABILITY
DEFLECTION
A check should be carried out on the maximum deflection of the beam due to the most adverse realistic
combination of unfactored imposed serviceability loading. In BS 5950 this is covered by clause 2.5.2 and
Table 8 which outlines recommended limits to these deflections, compliance with which should avoid
significant damage to the structure and finishes.
Calculation of deflections from first principles can be done using the area-moment method, Macaulay’s
method, or some other similar approach. Students should refer to a suitable structural analysis textbook for
more detail on this. However, many calculations of deflection are carried out using formulae for standard
cases, which can be combined as necessary to give the answer for more complicated situations. Figure 11
summarizes some of the more useful formulae.
Fig. 11 Deflections for standard cases. E = elastic modulus of steel (205 kN/mm2) and
I = second moment of area (x–x) of section.
Project 1
The floor shown below with an overall depth of 225 mm is to be designed to carry an imposed load of 3
kN/m2 plus floor finishes and ceiling loads of 1 kN/m2. Calculate the design loads acting on beams B1–
C1, B2–C2 and B1–B3. Assume that the beam weight is 70 kg/m run.
Also,
1. Analyze the beams to determine the bending moments, shear forces at ctitical points as well as the
maximum deflection
2. Design the beams for ultimate and serviceability limit states to BS 5950, making references to
relevant sections of the code