The document is an instruction manual for a braking resistor. It contains 3 sections: [1] Before Using This Product which describes checking the product and outlines upon receiving it. [2] Product guidance which provides product warranty information. [3] Installation which outlines proper installation environment, methods, and wiring for the braking resistor. The document provides important safety and usage instructions to ensure proper operation of the braking resistor.

Uploaded by

Luis Ramirez
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
49 views11 pages

DBR Manual 30HP and Below Instruction Manual INR-SI47-0591a-E - 2

The document is an instruction manual for a braking resistor. It contains 3 sections: [1] Before Using This Product which describes checking the product and outlines upon receiving it. [2] Product guidance which provides product warranty information. [3] Installation which outlines proper installation environment, methods, and wiring for the braking resistor. The document provides important safety and usage instructions to ensure proper operation of the braking resistor.

Uploaded by

Luis Ramirez
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 11

INSTRUCTION MANUAL

Braking Resistor
DB□□□-□C Series

gWhen an inverter is installed with the braking resistor in a device or control board and shipped, make
sure that the actual end user of the inverter receives this manual.

gThe contents of this manual are subject to changes for improvement without notice.

Fuji Electric Co., Ltd. INR-SI47-0591a-E


Preface
Thank you for purchasing our Inverter Option. Before using the option, read this manual carefully to understand how
to use the option correctly. Improper use may result in abnormal operation, reduce product life, and possible failure.
This manual does not describe how to use the inverter main unit. Refer to inverter main unit Instruction Manual for
details about the inverter main unit. Keep this manual on hand for reference when using the option.

To Use the Option Safely

Note the following items when using the option. Improper use may result in unexpected failure, electric shock, or
possible injury.

WARNING
• Wait at least five minutes after turning off the power before installing or wiring the inverter option.
Use a multimeter or similar instrument to check the voltage before performing installation or wiring.
(Check whether the charge lamp goes off.), as electric shock may occur
• Discharge statistic electricity from your body before handling the inverter option. Never touch the
Inverter option with wet hands, as accident or electric shock may occur
• No foreign matter such as screws, metal patches, lint, chips, and dust in the inverter option.
There is risk of fire or accident.
• Do not damage or stress the wiring, as accident or electric shock may occur.
• Wait at least five minutes after turning off the power before inspecting the inverter option. (Check
whether the charge lamp goes off.) There is a risk of electric shock.
• Never modify the inverter option, as electric shock or injury may occur.

CAUTION
• Do not install or operate a damaged option or one that is lacking parts, as injury may occur.

1
1 Before Using This Product

Check the items described below when you receive this product. Also check whether this product has been damaged

during transport. If anything is amiss, contact your distributor or our nearest branch office.

1-1 Type

Please confirm the form with the ratings signature board.

1-2 Outlines

Fig.1 Fig.2

Fig.3 Fig.4
Table 1-2-1 Outlines.
Size【㎜】
M odel Fig W W1 H H1 D
D B 0.75-2C /4C 1 43 - 221 215 30.5
D B 2.2-2C /4C 2 67 - 188 172 55
D B 3.7-2C /4C 2 67 - 328 312 55
D B 5.5-2C /4C 2 80 - 378 362 78
D B 7.5-2C /4C 2 80 - 418 402 78
D B 11-2C /4C 3 80 50 460 440 140
D B 15-2C /4C 3 80 50 580 560 140
D B 22-2C /4C 4 180 144 400 383 145

2
1-3 Keeping

Table 1-3-1

Item Specification

Storage -20~+70℃ Place where be dewy and freezing by rapid temperature

temperature change are not caused.

Relative 5~95%Note 1

humidity

Atmosphere There must be dust, direct sunshine, corroded gas, oil mist, steam or neither drop of water

nor a vibration. Salinity must not be included so much.

Note 1:Even if humidity meets the specification, the be dewy and freezing are caused in the place where the temperature

change is hard much. Please avoid such a place.


①Please do not put on ground.

②Please cover with the vinyl seat when atmosphere is bad.


③Please put a dry medicine internally, and, besides, wrap ②item procedure when the influence of moisture is large.

2 Product guidance

2-1 Product Warranty

This product is guaranteed against defects in workmanship for 18 months from the manufacturing date indicated on the
nameplate. However, the troubles caused by the following reasons are not covered by this warranty even in warranty
period.
(1) Problems caused by incorrect operation or by unauthorized repairs or modifications.
(2) Problems resulting from using the inverter in the range outside the standard specification.
(3) Damage to the inverter after purchase or during delivery.

(4) Damage caused by earthquakes, fire, floods, lightning, abnormal voltage fluctuations or other natural disasters.

3
3 Installation

3-1 Installation Environment


The installation environment for the inverter in which this product is being installed is listed Table 3-1-1
Table 3-1-1 Installation Environment.
Item Specifications Remarks
Location Indoors -
Ambient
-10 to 50°C -
temperature
Ambient relative
5 to 95% -
humidity
Environment The place should be away from direct sunlight and free from dust, corrosive gases,
inflammable gases, oil mists, steam, dripping water or vibration. Salty environments
-
should preferably be avoided. Avoid places where sudden changes in temperature occur
which could cause condensation or freezing.
Altitude Up to 1000m -

3-2 Installation method

①Please set up so that power terminal may become the lower side.Please set up vertically on a strong building with the

bolt.Please do not turn upside down and do not set up in a horizontal plane.
②This option generates heat, and install space more than each of 100 ㎜ the top and bottom and the right and left to

secure the passage of the cooling style, please.The generated heat is radiated up. Please do not install under a weak

equipment to heat.Moreover, installation respect must use the one of the material that the temperature rise can be

endured enough.

③Please consider enough to ventilation so that the ambient temperature of the inverter and the braking resistor should

not exceed the specification value when storing in the control board etc.Please do not store in a small sealing up box

where heat radiation is bad.

WARNING
• The surface temperature of resistance becomes 400℃ or less by the use state.
There is risk of fire or burn.
• Please install in a nonflammable thing such as the metals.
There is risk of fire.
• Please do not arrange the combustible in surroundings.
There is risk of fire.

4
3-3 Wiring

CAUTION
•Check the wiring again before operating the inverter. Improper wiring may cause unexpected inverter operation or
device operation. There is a risk of accident or injury.
• Since noise is generated by the inverter, motor, and wiring, carefully monitor surrounding sensors
and devices for abnormal operation. There is a risk of accident.

Applicable Table 3-3-1

Model Use electric wire size

DB0.75-2C 2mm2

DB2.2-2C/DB3.7-2C 2mm2

DB5.5-2C/DB7.5-2C 3.5mm2

DB11-2C~DB22-2C 5.5mm2

DB0.75-4C 2mm2

DB2.2-4C~DB22-4C 2mm2

Note 1:The size of the use electric wire is based on 600V vinyl electric wire.(Please use heatproof 75℃ or more.)

Note 2:The wiring length is assumed to be 5m or less.


Recommended connection method

Terminal for braking resistor connection Table 3-3-2

Type Terminal form Connection method

0.75mm2Electric wire
DB0.75-2C
(CFGE) Please connect the terminal with wiring.
DB0.75-4C
The wiring for 500mm is attached.

DB2.2-2C/DB3.7-2C
Connected bar
DB2.2-4C/DB3.7-4C
Board thickness2mm
DB5.5-2C/DB7.5-2C Please connect wiring in connected bar with the bolt
Φ4.3mm Installation hole
DB5.5-4C/DB7.5-4C and the nut.

Connected bar
DB11-2C~DB22-2C
Board thickness2mm
DB11-4C~DB22-4C
Φ6mm Installation hole

Earth terminal Table 3-3-3

Type Terminal form Connection method

M4 Terminal Please connect wiring with the earth terminal.


All models
(With screw)

5
Connection diagram

DB0.75-2C/4C~DB7.5-2C/4C

Inverter
Braking

Resistor P(+)

(Note2)
(Note1)
DB

Please detach connected line of a built-in resistor.

Please insulate the detached line.


DB11-2C/4C~DB22-2C/4C

Braking Braking unit Inverter


Resistor
P(+) P(+)

(Note2) P(+)
N(-) N(-)
(Note1)
DB
(Note3)
1 THR

(Note4)
2
CM

(Note1)A green screw terminal is an earth. G

(Note2)The wiring for the braking resistor, there is no polarity.

(Note3)Please connect with either of inverter side control terminal X1-X9 for the G11 series. At this time, please set the

connected terminal function data in 9 among function codes E01-E09.


(Note4)Please use the shield line for the wiring for the braking unit. Please connect the shield of the shield line with the

earth terminal of the inverter. (Another shield edge side is opened.)

6
4 Specification

4-1 Electric characteristic


For 200V series
Model No. DB0.75-2C DB2.2-2C DB3.7-2C DB5.5-2C DB7.5-2C DB11-2C DB15-2C DB22-2C
FRN0.2G11S-2 FRN1.5G11S-2 FRN3.7G11S-2 FRN5.5G11S-2 FRN7.5G11S-2 FRN11G11S-2 FRN15G11S-2 FRN18.5G11S-2
Applicable Inverter FRN0.4G11S-2 FRN2.2G11S-2 FRN5.5P11S-2 FRN7.5P11S-2 FRN11P11S-2 FRN15P11S-2 FRN18.5P11S-2 FRN22G11S-2
FRN0.75G11S-2 FRN22P11S-2
Resistance Capacity(kW) 0.2 0.4 0.4 0.8 0.9 1.4 1.4 1.8
Resistance
100 40 33 20 15 10 8.6 5.8
Value(Ω)
22 22
Motor output(kW) 0.2 0.4 0.75 1.5 2.2 3.7 5.5 5.5 7.5 7.5 11 11 15 15 18.5 18.5 (G11S) (P11S)
Allowable Allowable brake
braking duty cycle(%) 10 10 10 10 10 10 7 10 7 10 7 10 7 10 7 10 10 7
characteristics
Allowable
continuous
braking time(sec) 90 45 45 45 30 20 15 10 15 10 7 10 7 10 7 10 10 7

Braking unit required NO Yes


7

For 400V series


Model No. DB0.75-4C DB2.2-4C DB3.7-4C DB5.5-4C DB7.5-4C DB11-4C DB15-4C DB22-4C
FRN0.4G11S-4 FRN2.2G11S-4 FRN3.7G11S-4 FRN5.5G11S-4 FRN7.5G11S-4 FRN11G11S-4 FRN15G11S-4 FRN18.5G11S-4
Applicable Inverter FRN0.75G11S-4 FRN5.5P11S-4 FRN7.5P11S-4 FRN11P11S-4 FRN15P11S-4 FRN18.5P11S-4 FRN22G11S-4
FRN22P11S-4
Resistance Capacity(kW) 0.2 0.4 0.4 0.8 0.9 1.4 1.4 1.8
Resistance
200 160 130 80 60 40 34.4 22
Value(Ω)
22 22
Motor output(kW) 0.4 0.75 1.5 2.2 3.7 5.5 5.5 7.5 7.5 11 11 15 15 18.5 18.5 (G11S) (P11S)
Allowable Allowable brake
braking duty cycle(%) 10 10 10 10 10 7 10 7 10 7 10 7 10 7 10 10 7
characteristics
Allowable
continuous
braking time(sec) 45 45 45 30 20 15 10 15 10 7 10 7 10 7 10 10 7

Braking unit required NO Yes

7
Note 1:The use rate will decrease because of the undermentioned model when Electric thermal O/L relay setting (for

braking resistor).
1.5~7.5G11S-2/4 7%ED

5.5~11P11S-2/4 5%ED

T1
D u ty c y c le [% E D ] = * 100
T0 ( 1 0 0 s e c A s fo llo w s )

Braking interval
Braking T0
power Braking time

T1

100%

Time

8
4-2 Supplementation
*Duty cycle(%ED)

Frequency which can be repeatedly used.


*Continuous braking time

Time which can be continuously braked.(Use of limit from state of normal temperature once.)

*Surface temperature of resistance by use rate.

The surface temperature is 230 ℃ or less (50 ℃ in surroundings temperature time). I will describe the surface

temperature rise value by the use rate of DB22-2C as a reference value.

200

180
Temperature
rise value 160
[K]
140

120

100
5 6 7 8 9 10
Duty cycle
[%ED]

9