Bulletin 193-EF Solid-State Overload Relays: Features
Bulletin 193-EF Solid-State Overload Relays: Features
Features
Standards Compliance
IEC 60947-4
CSA C22.2 No. 14
UL 508
Certifications
CE
CSA Certified (File No. LR13908)
UL Listed (File No. E33916, Guide NKCR)
Features
193 – EF 1 A KP – R F L
a b c d e
a b c d
C§ 160…630 KY 48V AC
KF 230V AC
KA 240V AC
KN 400V AC
KG 415V AC
KB 440V AC
ZJ 24V DC
ZY 48V DC
Factory Modifications
Code Description
R Automatic reset
F Remote reset
L External indication
∆ Contactor mounting requires the use of a bus bar mounting kit (Cat. Nos. 825-MVS or 825-MVS2).
‡ 0.5…20 A can be achieved by looping the motor supply cables. (Refer to the Specifications on Test Button for Thermal Overload Protection
Pressing the test button will verify thermal tripping operation time at 6x/e without the motor being connected. The test button must be held for longer than the set trip time t6x/e.
Device Installation and Commissioning
The operating instructions enclosed with the device provide all of the information necessary to set and commission it.
Surface Mounting
193-EF_A Snap-on fixing to standard DIN Rail or screw fixing
193-EF_B Screw fixing
193-EF_C Screw fixing
Mounting position: optional.) Use cable support Cat. No. 193-HD.
♣ Device ships with the External Indication Module accessory (Cat. No. 193-LB1) included.
The catalog number as listed is incomplete. Select a coil voltage code from the table below for completion.
Example: Cat. No. 193-EF1AÄ becomes Cat. No. 193-EF1AKP.
DC ZJ — ZY — — — — — — —
Remote Reset§ -F
External Indication♣ -L
⋆ Refer to the Catalog Number explanation on Catalog Number Explanation for the proper suffix code sequence.
§ Device ships with the Remote Reset Module accessory (Cat. No. 193-RB1) included.
♣ Device ships with the External Indication Module accessory (Cat. No. 193-LB1) included.
Add-On Modules
Mounting Materials
Connecting Components
Mounting Materials — Bus Bars
Set of 3 busbars, includes terminal and fixing screws. Suitable for use with Cat. No. 193-EF1A and 193-EF2A overload relays.
M8 connections 3 825-MVM2
Set of three
4 x 20 x 117 mm (1/8 x 25/32 x 4-39/64 in.) (180 A max.)
Universally applicable
Uniform labeling materials for contactors, motor starting equipment, timing relays, and circuit breakers
Reset — Manual
The reset button resets all protection functions. Resetting from any location is possible with the 193-RB1 remote reset module.
Reset — Automatic
Automatic resetting of thermal overload and thermistor overtemperature functions is an optional feature. All other protection functions must be reset manually.
Surface Mounting
193-EF_A Snap-on fixing to standard DIN Rail or screw fixing
193-EF_B Screw fixing
193-EF_C Screw fixing
Mounting position: optional
Setting the Rated Current (0.5…20 A) (193EF1A and 193EF2A Requires 193HD)
The motor supply cables are looped through the current transformer twice, thereby doubling the rated motor current. The setting on the Bulletin 193-EF overload relay is
the product of:
Recommended for Ie [A] Motor Supply Cables Cable Cross Section (Flexible Strand)
Motor supply wire looped twice Motor supply wire looped 4 times 0.5…2.5 looped 40 times 0.5…0.75 ‡
‡ CSA, UL: for I e = 0.5…2.5 A, only factory‐assembled wound devices should be installed
Rated Voltage Motor Circuit (primary circuit of current measuring device)
Control Circuit
AC 50/60 Hz [V] 24, 36, 48, 110, 120, 230, 240, 400, 415, 440, (0.8…1.1US)
Terminal Cross-section
Rated operating voltage per UL/CSA: pilot duty 240V [V] 24 110…125 220…250 380… 440
Ambient temperature
Operation ‐5…+60 °C
Storage ‐50…+60 °C
Transport ‐50…+85 °C
Weights
Overload Relay
Bus bars
Approvals
‡ Type of wiring: insulated control leads, screened > 200 m (shield connected with 1T1)