Chapter-4 Apparatus Protection
Chapter-4 Apparatus Protection
ü Prime movers
ü Excitation system
ü Voltage regulation
ü Cooling systems etc
Thus protection of generator must consider the presence of
these other equipment also.
1. Stator faults
2. Rotor faults
3. Abnormal running conditions
1. Stator faults
A. Phase to ground faults
B. Phase to phase faults
C. Stator inter-turn faults
Over speeding
loss of excitation
The loss of excitation or reduced excitation is possible due to the field
failure (opening of Field winding or due to short circuit in field )
The failure of cooling system also causes sever overheating to rise the
temperature above safe limit it may lead insulation failure.
1. Differential protection
2. Inter-turn fault protection
3. Stator earth fault protection
4. Over current & earth fault protection
5. Rotor earth fault protection
6. Reverse power protection
7. Field failure protection
8. Negative phase-sequence protection
9. Over load protection
10. Over voltage protection
11. Pole slipping protection
12. Back up impedance protection
13. Under frequency protection
Cases & Consequences of Stator Insulation Failure
Ø The produced fault current does not affect the entering and
leaving current to the CTs .
Such protection (by o/c and e/f relay) is ineffective when the
main breaker is open or if the system has no other generating
source.
The relay detects the earth faults for most of the rotor circuit.
Reverse power protection is provide against the failure of
prime mover of an alternator.
ü loss of synchronism
ü Slightly increase the generator speed.
4.Through faults
Through faults are the external faults which occur outside
The protected zone through faults are not detected by the
differential protection if the through faults stay for long
period of time the transformer may subjected to thermal and
mechanical stress
Ø When more sever fault occur with high pressure strike the
lower mercury switch energize the trip ckt of the circuit
breaker break the transformer from the system
üanother hinged flap valve is locked in the lower part which
is directly in the path of oil b/n tank and the conservator.
2. Primary full load current should be considered while setting the over
current relay.
Ø Power transformer are provided with restricted e/f
protection
1. System voltage
2. Reliability of supply
Causes of faults
i insulation failure due to the deterioration of the material
In the event of fault at F in the fig the relay 2 will operate and
the fault will be isolated before the relays at 3,4 and 5 have
sufficient time to operate.
If fault at point F1, If will be via AF1 & CDF1 (hence BF1 in
opposite direction).
The long time delay occurring in the time grading system can
be partly avoided.
inductive component
Resistive component
Capacitive component
Ø Impedance of the system become impedance of source
plus impedance of part of the Trx line before the fault
Fault 4 Z2 Z1 Z2 Z1
2. Unit type of protection
i) Wire pilot
ii) Carrier current pilot
Similarly
under normal conditions the currents, leaving zone A and B
are equal,
making the relay to be inactive by the current balance
2.Balance-voltages systems: