RMS Test Block
RMS Test Block
4 M 2 0 0 | I | 3 1 / 05 / 2 0 1 9 www.rmspl.com.au rms
www.rmspl.com.au
Functional Description 4M200
System Components Features
> 14 circuit Test Block > 14 independent test groups
> Test Plug > ‘Finger safe’ test sockets suit standard or
shrouded type 4mm banana plugs for direct
access to the protection or measurement
scheme
> Auto CT shorting test plugs available
> Clear and concise front panel circuit
identification
> High current / voltage rating
> Compatible with industry standard 14 circuit
test blocks and test plugs
> Made in Australia
www.rmspl.com.au 2 rms
www.rmspl.com.au 3
Safety Features 4M200 / 4M220
Finger Safe Test Sockets Test Plug Insertion
Note the black - even numbered - equipment side sockets.
Note the yellow - odd numbered - live side sockets.
Before use the insulation of the flying leads should be visibly
checked for damage.
Flexible banana test leads with shrouded plugs are
recommended for operator safety. 2.5mm2 multi-strand wire
with PVC insulation is recommended for adequate current
rating and flexibility.
To avoid high voltage shock hazard external CT circuits must
Figure 1: Close up view of the ‘finger safe’ test plug sockets NOT be open circuited. Shorting links must be in position
that accept standard 4mm shrouded test plugs. BEFORE test plug insertion.
www.rmspl.com.au 3 rms
www.rmspl.com.au 3
Wiring Diagrams 4M200
T yp ic al ap pli ca tio n for a th r ee ph as e o ve rcu rr e n t & E F p rotec tio n s ch em e 4 M2 00 -01
* D C I so la tio n F un ction Em p lo ye d 4 M2 00 -06
4 M 2 00 - P6
C ase te r mi na l n um be rs
+ Trip
CB
1 2
Tr ip
3 4
5 6
- Tr ip
Tr ip
7 8
9 10
11 12
13 14
DC
V aux *
15 16 au xi lia ry
17 18
19 20
C
A
21 22
Ia
23 ** 24
Ib
25 26
Ic
27 28
E /F
Figure 3: Test Block Application wiring example for a three phase overcurrent and EF protection scheme
DC Fixed CT Positions **
Test Block Polarized Test Plug Comment
Isolation Designation on Test Block Facia
4M200-01 NO Operator must manually fit CT shorting
NO 4M220-00
4M200-06 links to the Test Plug in correct positions.
YES
YES Test Plug has fixed shorting positions to
4M200-P6 YES 4M220-P7
terminal 21-23-25-27
www.rmspl.com.au 4 rms
www.rmspl.com.au 3
Wiring Diagrams 4M200
Typ ica l ap p licatio n for a th r e e p h a se o ve rcu rr e n t & E F p ro tectio n sch e m e 4 M2 0 0 -0 2
4 M2 0 0 -0 7
4M 20 0- P7
C a se te rm i na l n um be rs
+ Trip
CB
1 2
3 4 Trip
5 6
- Tr i p
Trip
7 8
9 10
11 12
13 14
DC
V au x
15 16 a uxiliar y
17 18
19 20
C
A
21 22
Ia
23 ** 24
Ib
25 26
Ic
27 28
E /F
Figure 4: Test Block Application wiring example for a three phase overcurrent and EF protection scheme
DC Fixed CT Positions **
Test Block Polarized Test Plug Comment
Isolation Designation on Test Block Facia
4M200-02 NO Operator must manually fit CT shorting
NO 4M220-00
4M200-07 links to the Test Plug in correct positions.
NO
YES Test Plug has fixed shorting positions to
4M200-P7 YES 4M220-P7
terminals 21-23-25-27
www.rmspl.com.au 5 rms
www.rmspl.com.au 3
Wiring Diagrams 4M200
Typ i cal ap pli cation fo r a thre e ph as e dire ctio na l o ve rc urre nt & E/F o r di stan ce p r ote ctio n s che m e 4 M2 00 -02
4 M2 00 -07
4 M 2 00 - P7
C ase te r mi na l n um be rs
1 2
Vc
3 4
Vb
5 6
Va
7 8
9 10
- Tr ip
11 12
CB 13 14
T rip
15 16
+ Trip
17 18
O utput
19 20
Input
C
A
21 22
Ia
23 ** 24
Ib
25 26
Ic
27 28
E /F
Figure 5: Typical application for a three phase directional overcurrent & E/F or distance protection scheme
DC Fixed CT Positions **
Test Block Polarized Test Plug Comment
Isolation Designation on Test Block Facia
4M200-02 NO Operator must manually fit CT shorting
NO 4M220-00
4M200-07 links to the Test Plug in correct positions.
NO
YES Test Plug has fixed shorting positions to
4M200-P7 YES 4M220-P7
terminals 21-23-25-27
www.rmspl.com.au 6 rms
www.rmspl.com.au 3
Wiring Diagrams 4M200
Typical application for 3 Ph CT’s and core balance E/F CT 4M200-08
4M200-P8
1 2
3 ** 4 Ia
5 6
7 ** 8 Ib
9 10
11 ** 12 Ic
C
B
A
13 14
15 16
17 ** 18
E( 3Io)
19 20
21 22
23 24
25 26
27 28
DC Fixed CT Positions **
Test Block Polarized Test Plug Comment
Isolation Designation on Test Block Facia
Operator must manually fit CT shorting links
4M200-08 NO 4M220-00
to the Test Plug in the designated positions.
NO YES
Test Plug has fixed shorting positions to
4M200-P8 YES 4M220-P8
terminals 1-3, 5-7, 9-11, 15-17
www.rmspl.com.au 7 rms
www.rmspl.com.au 3
Wiring Diagrams 4M200
Typ ica l ap p l icati on for differe nti al pro te cti on of tran sfor m ers 4 M2 00 -09
4 M 2 00 - P9
C ase te r mi na l n um be rs
1 2
Ic
3 4
Ib
5 ** 6
Ia
7 8
N
C
A
9 10
11 ** 12
E /F
13 14
15 16
17 18
19 ** 20 E /F
21 22
Ic
C
A
23 24
Ib
25 ** 26
Ia
27 28
N
C a se ea rt h 4M 20 0 - 0 9 ** Pro te ctio n s ch e m e
4 M 20 0 -P9 **
Te st Blo c k
(R E AR VIE W)
4 M 2 2 0- 0 0 Te s t P lu g
( FR O N T V IE W )
DC Fixed CT Positions **
Test Block Polarized Test Plug Comment
Isolation Designation on Test Block Facia
Operator must manually fit CT shorting links
4M200-09 NO 4M220-00
to the Test Plug in the designated positions.
NO YES
Test Plug has fixed shorting positions to
4M200-P9 YES 4M220-P9
terminals 1-3-5-7, 9-11, 17-19, 21-23-25-27
www.rmspl.com.au 8 rms
www.rmspl.com.au 3
Test Block Case Details 4M200
Front View Rear View
51
P/N 263-635-008
17 7
27 28
2 holes of 3.7
www.rmspl.com.au 9 rms
www.rmspl.com.au 3
Test Block Technical Data 4M200
ELECTRICAL ENVIRONMENT
www.rmspl.com.au 10 rms
www.rmspl.com.au 3
Test Block Technical Data 4M200
ATMOSPHERIC ENVIRONMENT MECHANICAL ENVIRONMENT
Temperature Vibration - Sinusoidal
Standard IEC 60068-2-1, IEC 60068-2-2 Standard IEC 60255-21-1 Class 1
Auxiliary power Test Identification Test specification Variation
Test Identification Test specification
Supply voltage
Vibration Response 0.035 mm/0.5 gn peak
Operating Range -10 to +55°C Min and Max ≤5%
in each of 3 axes 1 sweep cycle 10-150 Hz
Storage Range -25 to +70°C Non-energized Vibration Endurance 1.0 gn peak Non-
in each of 3 axes 20 sweep cycles 10-150 Hz energized
Test duration 16 hours at top and bottom temperatures
Operating Range 40°C and 93% RH non condensing Shock Response 5 gn, 11 ms, 3 pulses
≤5%
in each of 3 axes in each direction
Test duration 16 hours
Shock Withstand 15 gn, 11 ms, 3 pulses Non-
in each of 3 axes in each direction energized
IP Rating Bump Test 10 gn, 16 ms, 1000 bumps Non-
Standard IEC 60529 in each of 3 axes in each direction energized
Test Identification Test specification
Installed IP5x Seismic
Standard IEC 60255-21-3 Class 2
Test Identification Test specification Variation
Performance Standard Seismic Response 7.5 mm/2.0 gn,
≤5%
Horizontal, on each axis 1 sweep cycle 1-35Hz
Low-voltage switchgear and control gear
Seismic Response 3.5 mm/1.0 gn,
Part 7.1: Ancillary equipment – Terminal blocks for copper ≤5%
Vertical 1 sweep cycle 1-35Hz
conductors
Standard IEC 60947-7-1 Mechanical Classification
Durability 103 insertions of the Test Plug
www.rmspl.com.au 11 rms
www.rmspl.com.au 3
Test Plug Dimensions 4M220
4M220 Multi Finger Test Plug
28 test sockets suitable for 4mm shrouded banana plugs.
Securing screws are integrated to retain the Test Plug during
testing operations.
www.rmspl.com.au 12 rms
www.rmspl.com.au 3
Test Leads 4M220
Shrouded Test Leads
Two types of shrouded ‘finger safe’ test leads are available:
Quantity
Part Number Description supplied per
4M220
www.rmspl.com.au 13 rms
www.rmspl.com.au 3
Order Codes 4M200 / 4M220
4M200 Test Block Order Code
Generate the required ordering code as follows: e.g. 4M200-02
4M200 -
01 Vx isolation 13-14
02 Vx isolation not required
06 Vx isolation 13-14, CT's 21-23-25-27, non-polarized
07 No Vx isolation, CT's 21-23-25-27, non-polarized
08 CT's 1-3, 5-7, 9-11, 15-17, non-polarized
09 CT's 1-3-5-7, 9-11, 17-19, 21-23-25-27, non-polarized
P6 Vx isolation 13-14, CT's 21-23-25-27, polarized
P7 No Vx isolation, CT's 21-23-25-27, polarized
P8 CT's 1-3, 5-7, 9-11, 15-17, polarized
P9 CT's 1-3-5-7, 9-11, 17-19, 21-23-25-27, polarized
4M220 -
CT Shorting Links 00 External links to be fitted by operator – Must be Fitted Manually by Tester
P7 Internal links fitted between contacts 21-23-25-27, polarized
P8 Internal links fitted between contacts 1-3, 5-7, 9-11, 15-17, polarized
P9 Internal links fitted between contacts 1-3-5-7, 9-11, 17-19, 21-23-25-27, polarized
www.rmspl.com.au 14 rms
www.rmspl.com.au 3
www.rmspl.com.au
6 Anzed Court
Mulgrave, Victoria 3170 ISO9001 Quality Accreditation
AUSTRALIA RMS holds BSI (British Standards Institution) registration number FS
Ph: +61 3 8544 1200 604860 for the certification of a quality system to AS/NZS ISO9001:2008.
Fax +61 3 8544 1201
Sales: [email protected] Due to RMS continuous product improvement policy the information
www.rmspl.com.au contained in this document is subject to change without prior notice.