PowerFlex 4 (User Manual)
PowerFlex 4 (User Manual)
FRN 6.xx
User Manual
www.abpowerflex.com
Burn Hazard labels may be located on or inside the equipment (e.g., drive or motor) to alert people that surfaces may be at dangerous temperatures.
PowerFlex is a registered trademark of Rockwell Automation, Inc. DriveExplorer, DriveExecutive, and SCANport are trademarks of Rockwell Automation, Inc. PLC is a registered trademark of Rockwell Automation, Inc.
Summary of Changes
The information below summarizes changes made for the September 2010 PowerFlex 4 User Manual, Publication 22A-UM001I-EN-E.
Description of New or Updated Information See Page(s) Parameters A117 [Bus Reg Mode] and A118 [Comm Write Mode] added. 3-13
The information below summarizes changes made for the July 2010 PowerFlex 4 User Manual, Publication 22A-UM001H-EN-E.
Description of New or Updated Information Start and Speed Reference Control See Page(s) 1-18
The information below summarizes changes made for the March 2007 PowerFlex 4 User Manual, Publication 22A-UM001G-EN-E.
Description of New or Updated Information Minimum Mounting Clearances clarified. Footnote (2) on Bulletin 140M catalog edited. Graphic for Analog Input, PTC wiring example corrected. Stop Drive icon and related warning text removed for parameter A110 [Anlg In 0-10V Lo]. New information on reading register address 8192 added. New information on reading register address 8193 added. See Page(s) 1-2 1-7 1-14 3-25 C-3 C-4
The information below summarizes changes made for the September 2005 PowerFlex 4 User Manual, Publication 22A-UM001F-EN-E.
Description of New or Updated Information Attention statement clarified. 240V AC 3-Phase 3.7 kW (5.0 Hp) drive fuse rating revised to 30 amps. Analog Input, PTC wiring example added. Attention statement added to Multiple Digital Input Connections wiring example. Parameter P043 [Motor OL Ret] added. Attention statement added to parameter A082 [DB Resistor Sel]. External Comm Options, Compact I/O added to Table B.G. Modbus function code 16 added. See Page(s) 1-3 1-7, A-2 1-14 1-17 3-12 3-18 B-4 C-2
soc-2
Table of Contents
Preface
Overview
Who Should Use this Manual? . . . . . . . . . Reference Materials . . . . . . . . . . . . . . . . . Manual Conventions . . . . . . . . . . . . . . . . . Drive Frame Sizes . . . . . . . . . . . . . . . . . . . General Precautions . . . . . . . . . . . . . . . . . Catalog Number Explanation . . . . . . . . . . P-1 P-1 P-2 P-2 P-3 P-4
Chapter 1
Installation/Wiring
Opening the Cover . . . . . . . . . . . . . . . . . . 1-1 Mounting Considerations . . . . . . . . . . . . . 1-2 AC Supply Source Considerations . . . . . . 1-3 General Grounding Requirements . . . . . . 1-4 Fuses and Circuit Breakers . . . . . . . . . . . . 1-6 Power Wiring . . . . . . . . . . . . . . . . . . . . . . 1-8 I/O Wiring Recommendations . . . . . . . . 1-11 Start and Speed Reference Control . . . . . 1-18 EMC Instructions . . . . . . . . . . . . . . . . . . 1-20
Chapter 2
Start Up
Prepare For Drive Start-Up . . . . . . . . . . . . 2-1 Integral Keypad . . . . . . . . . . . . . . . . . . . . . 2-3 Viewing and Editing Parameters . . . . . . . . 2-4
Chapter 3
Chapter 4
Troubleshooting
Drive Status . . . . . . . . . . . . . . . . . . . . . . . . Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Fault Descriptions . . . . . . . . . . . . . . . . . . . Common Symptoms and Corrective Actions . . . . . . . . . . . . . . . . 4-1 4-1 4-3 4-5
Appendix A Appendix B
ii
Appendix C
Appendix D
Index
Preface
Overview
The purpose of this manual is to provide you with the basic information needed to install, start-up and troubleshoot the PowerFlex 4 Adjustable Frequency AC Drive.
For information on Who Should Use this Manual? Reference Materials Manual Conventions Drive Frame Sizes General Precautions Catalog Number Explanation See page P-1 P-1 P-2 P-2 P-3 P-4
Reference Materials
The following manuals are recommended for general drive information:
Title Wiring and Grounding Guidelines for Pulse Width Modulated (PWM) AC Drives Preventive Maintenance of Industrial Control and Drive System Equipment Safety Guidelines for the Application, Installation and Maintenance of Solid State Control A Global Reference Guide for Reading Schematic Diagrams Guarding Against Electrostatic Damage Publication Available Online at DRIVES-IN001 DRIVES-SB001 SGI-1.1 www.rockwellautomation.com/ literature
0100-2.10 8000-4.5.2
P-P-2
Overview
Manual Conventions
In this manual we refer to the PowerFlex 4 Adjustable Frequency AC Drive as: drive, PowerFlex 4 or PowerFlex 4 Drive. Parameter numbers and names are shown in this format:
P031 [Motor NP Volts] Name Number Group d = Display Group P = Basic Program Group A = Advanced Program Group
The following words are used throughout the manual to describe an action:
Word Can Cannot May Must Shall Should Should Not Meaning Possible, able to do something Not possible, not able to do something Permitted, allowed Unavoidable, you must do this Required and necessary Recommended Not Recommended
Overview
P-3
General Precautions
ATTENTION: The drive contains high voltage capacitors which take time to discharge after removal of mains supply. Before working on drive, ensure isolation of mains supply from line inputs [R, S, T (L1, L2, L3)]. Wait three minutes for capacitors to discharge to safe voltage levels. Failure to do so may result in personal injury or death. Darkened display LEDs is not an indication that capacitors have discharged to safe voltage levels.
! !
ATTENTION: Only qualified personnel familiar with adjustable frequency AC drives and associated machinery should plan or implement the installation, start-up and subsequent maintenance of the system. Failure to comply may result in personal injury and/or equipment damage. ATTENTION: This drive contains ESD (Electrostatic Discharge) sensitive parts and assemblies. Static control precautions are required when installing, testing, servicing or repairing this assembly. Component damage may result if ESD control procedures are not followed. If you are not familiar with static control procedures, reference A-B publication 8000-4.5.2, Guarding Against Electrostatic Damage or any other applicable ESD protection handbook. ATTENTION: An incorrectly applied or installed drive can result in component damage or a reduction in product life. Wiring or application errors, such as, undersizing the motor, incorrect or inadequate AC supply, or excessive ambient temperatures may result in malfunction of the system. ATTENTION: The bus regulator function is extremely useful for preventing nuisance overvoltage faults resulting from aggressive decelerations, overhauling loads, and eccentric loads. However, it can also cause either of the following two conditions to occur. 1. Fast positive changes in input voltage or imbalanced input voltages can cause uncommanded positive speed changes; 2. Actual deceleration times can be longer than commanded deceleration times However, a Stall Fault is generated if the drive remains in this state for 1 minute. If this condition is unacc eptable, the bus regulator must be disabled (see parameter A117). In addition, installing a properly sized dynamic brake resistor will provide equal or better performance in most cases.
! !
P-P-4
Overview
1-3
Drive
6-8
10
11
13-14
1P5
4
Code Version 3 No Brake IGBT 4 Standard
AA
Optional
Code V A B D
Ph. 1 1 3 3
Code Rating 0 Not Filtered 1 Filtered Code Interface Module 1 Fixed Keypad Code Purpose AA Reserved for thru custom firmware ZZ
Code N F H
Enclosure Panel Mount - IP 20 (NEMA Type Open) Flange Mount - IP 20 (NEMA Type Open) Replacement Plate Drive - IP 20 (NEMA Type Open) - Contact factory for ordering information.
kW (HP) 0.2 (0.25) 0.4 (0.5) 0.75 (1.0) 1.5 (2.0) 2.2 (3.0)
kW (HP) 0.2 (0.25) 0.4 (0.5) 0.75 (1.0) 1.5 (2.0) 2.2 (3.0) 3.7 (5.0)
kW (HP) 0.4 (0.5) 0.75 (1.0) 1.5 (2.0) 2.2 (3.0) 3.7 (5.0)
Position 12 of the Catalog Number now indicates drive type. All PowerFlex 4 drives are equipped with RS485 communication.
Chapter 1
Installation/Wiring
This chapter provides information on mounting and wiring the PowerFlex 4 Drive.
For information on Opening the Cover Mounting Considerations AC Supply Source Considerations See page 1-1 1-2 1-3 For information on Fuses and Circuit Breakers Power Wiring I/O Wiring Recommendations EMC Instructions See page 1-6 1-8 1-11 1-20
Most start-up difficulties are the result of incorrect wiring. Every precaution must be taken to assure that the wiring is done as instructed. All items must be read and understood before the actual installation begins. ATTENTION: The following information is merely a guide for proper installation. Rockwell Automation, Inc. cannot assume responsibility for the compliance or the noncompliance to any code, national, local or otherwise for the proper installation of this drive or associated equipment. A hazard of personal injury and/or equipment damage exists if codes are ignored during installation.
1-2
Installation/Wiring
Mounting Considerations
Mount the drive upright on a flat, vertical and level surface. Install on 35 mm DIN Rail. or Install with screws.
Table 1.A Screw Mounting Recommendations Minimum Panel Thickness Screw Size 1.9 mm (0.0747 in.) M4 (#8-32) Mounting Torque 1.56-1.96 N-m (14-17 lb.-in.)
Protect the cooling fan by avoiding dust or metallic particles. Do not expose to a corrosive atmosphere. Protect from moisture and direct sunlight.
25 mm (1.0 in.)
Closest object that may restrict air flow through the drive heat sink and chassis
Mounting Option B
Table 1.B Enclosure and Clearance Requirements Enclosure Rating IP 20/Open Type Maximum 40C (104F) Minimum Mounting Clearances Use Mounting Option A Use Mounting Option B
Rating requires installation of the PowerFlex 4 IP 30/NEMA 1/UL Type 1 option kit.
Debris Protection
A plastic top panel is included with the drive. Install the panel to prevent debris from falling through the vents of the drive housing during installation. Remove the panel for IP 20/Open Type applications.
Installation/Wiring
1-3
Storage
Store within an ambient temperature range of -40 to +85C. Store within a relative humidity range of 0% to 95%, non-condensing. Do not expose to a corrosive atmosphere.
1-4
Installation/Wiring
Remove MOV jumper to ground. or Install Isolation Transformer with grounded secondary if necessary.
SHLD
Installation/Wiring
1-5
Safety Ground -
(PE)
This is the safety ground for the drive that is required by code. One of these points must be connected to adjacent building steel (girder, joist), a floor ground rod or bus bar. Grounding points must comply with national and local industrial safety regulations and/or electrical codes.
Motor Ground
The motor ground must be connected to one of the ground terminals on the drive.
1-6
Installation/Wiring
Fusing
The PowerFlex 4 has been UL tested and approved for use with input fuses. The ratings in the table that follows are the minimum recommended values for use with each drive rating. The devices listed in this table are provided to serve as a guide.
Installation/Wiring
Table 1.D Minimum Recommended Branch Circuit Protective Devices Voltage Rating 120V AC 1-Phase Drive Rating kW (HP) 0.2 (0.25) 0.4 (0.5) 0.75 (1.0) 1.1 (1.5) Fuse Rating(1) Amps 10 15 30 40 6 10 15 25 30 10 10 15 30 3 6 10 15 25 30 3 6 10 15 15 140M(2) Catalog No. 140M-C2E-C10 140M-C2E-C16 140M-D8E-C20 140M-D8E-C25 140M-C2E-B40 140M-C2E-B63 140M-C2E-C16 140M-C2E-C16 140M-D8E-C25 140M-C2E-B63 140M-C2E-B63 140M-C2E-C16 140M-D8E-C20 140M-C2E-B25 140M-C2E-B40 140M-C2E-C10 140M-C2E-C16 140M-C2E-C16 140M-F8E-C25 140M-C2E-B25 140M-C2E-B40 140M-C2E-B63 140M-C2E-C10 140M-C2E-C16
1-7
Recommended MCS Contactors Catalog No. 100-C09 100-C12 100-C23 100-C37 100-C09 100-C09 100-C12 100-C16 100-C23 100-C09 100-C09 100-C12 100-C23 100-C09 100-C09 100-C09 100-C12 100-C16 100-C23 100-C09 100-C09 100-C09 100-C09 100-C16
240V AC 0.2 (0.25) 1-Phase 0.4 (0.5) NO BRAKE 0.75 (1.0) 1.5 (2.0) 2.2 (3.0) 240V AC 1-Phase 0.2 (0.25) 0.4 (0.5) 0.75 (1.0) 1.5 (2.0) 0.2 (0.25) 0.4 (0.5) 0.75 (1.0) 1.5 (2.0) 2.2 (3.0) 3.7 (5.0) 0.4 (0.5) 0.75 (1.0) 1.5 (2.0) 2.2 (3.0) 3.7 (5.0)
240V AC 3-Phase
480V AC 3-Phase
(1) (2)
Recommended Fuse Type: UL Class J, CC, T or Type BS88; 600V (550V) or equivalent. The AIC ratings of the 140M are based on a maximum 100 kA AIC with the exception of 140M-D and 140M-F which have a maximum of 50 kA AIC. Refer to the selection guide for Bulletin 140M motor protectors for other ratings suitable for your particular application.
1-8
Installation/Wiring
Power Wiring
! !
ATTENTION: National Codes and standards (NEC, VDE, BSI, etc.) and local codes outline provisions for safely installing electrical equipment. Installation must comply with specifications regarding wire types, conductor sizes, branch circuit protection and disconnect devices. Failure to do so may result in personal injury and/or equipment damage. ATTENTION: To avoid a possible shock hazard caused by induced voltages, unused wires in the conduit must be grounded at both ends. For the same reason, if a drive sharing a conduit is being serviced or installed, all drives using this conduit should be disabled. This will help minimize the possible shock hazard from cross coupled power leads.
Standard (Option 2)
Tray rated 600V, 75C or 90C (167F or 194F) RHH/RHW-2 Shawflex 2ACD/3ACD or equivalent Class I & II; Tray rated 600V, 75C or Division I & II 90C (167F or 194F) RHH/RHW-2
Installation/Wiring
1-9
Motor Cable Only(1) 15 meters (49 feet) 40 meters (131 feet) 170 meters (558 feet)
Longer cable lengths can be achieved by installing devices on the output of the drive. Consult factory for recommendations.
Output Disconnect
The drive is intended to be commanded by control input signals that will start and stop the motor. A device that routinely disconnects then reapplies output power to the motor for the purpose of starting and stopping the motor should not be used. If it is necessary to disconnect power to the motor with the drive outputting power, an auxiliary contact should be used to simultaneously disable drive control run commands.
1-10
Installation/Wiring
BR+ BR-
Terminal R/L1, S/L2 R/L1, S/L2, T/L3 U/T1 V/T2 W/T3 BR+, BR-
Description 1-Phase Input 3-Phase Input To Motor U/T1 To Motor V/T2 = To Motor W/T3 Dynamic Brake Resistor Connection Safety Ground - PE
Maximum Wire Size (1) Minimum Wire Size (1) Torque 3.3 mm2 (12 AWG) 5.3 mm2 (10 AWG) 0.8 mm2 (18 AWG) 1.3 mm2 (16 AWG) 1.7-2.2 N-m (16-19 lb.-in.)
Maximum/minimum sizes that the terminal block will accept - these are not recommendations.
Installation/Wiring
1-11
! !
Important: I/O terminals labeled Common are not referenced to the safety ground (PE) terminal and are designed to greatly reduce common mode interference. ATTENTION: Driving the 4-20mA analog input from a voltage source could cause component damage. Verify proper configuration prior to applying input signals.
1-12
Installation/Wiring
Description 0.8 mm2 (18AWG), twisted pair, 100% shield with drain. (1) 0.8 mm2 (18AWG), 3 conductor, shielded for remote pot only.
If the wires are short and contained within a cabinet which has no sensitive circuits, the use of shielded wire may not be necessary, but is always recommended.
Table 1.H I/O Terminal Block Specifications Maximum Wire Size (1) Minimum Wire Size (1) 0.13 mm2 (26 AWG) Torque 0.5-0.8 N-m (4.4-7 lb.-in.)
Maximum/minimum sizes that the terminal block will accept - these are not recommendations.
Installation/Wiring
Figure 1.5 Control Wiring Block Diagram
Important: I/O Terminal 01 is always a coast to stop input except when P036 [Start Source] is set to 3-Wire control. In three wire control, I/O Terminal 01 is controlled by P037 [Stop Mode]. All other stop sources are controlled by P037 [Stop Mode]. Important: The drive is shipped with a jumper installed between I/O Terminals 01 and 11. Remove this jumper when using I/O Terminal 01 as a stop or enable input. Two wire control shown. For three wire control use a momentary input on I/O Terminal 02 to command a start. Use a maintained input for I/O Terminal 03 to change direction. Relay N.O.
Relay Common Relay N.C.
1-13
(1)
Stop
(1)
Start/Run FWD (2) Direction/Run REV Digital Common Digital Input 1 Digital Input 2 +24V DC +10V DC 0-10V In Analog Common 4-20mA In RS485 Shield
Potentiometer must be 1-10k ohm 2 Watt Min.
(2)
01 02 03 04 05 06 R1 R2 R3
30V DC 125V AC 240V AC Resistive Inductive 3.0A 0.5A 3.0A 0.5A 3.0A 0.5A
SNK SRC
11
12 13 14 15 16
RS485 (DSI) 8 1
(1)
No.
R1 R2 R3
Signal
Relay N.O. Relay Common Relay N.C.
Default
Fault Fault Source (SRC) Coast Not Active Not Active Preset Freq Preset Freq Not Active Not Active
Description
Normally open contact for output relay. Common for output relay. Normally closed contact for output relay.
Param.
A055 A055
Inputs can be wired as Sink (SNK) or Source (SRC) via DIP Switch setting. The factory installed jumper or a normally closed input must be present for the drive to start. P036 (1)
Stop (1) Start/Run FWD Direction/Run REV Digital Common Digital Input 1 Digital Input 2 +24V DC +10V DC 0-10V In (3) Analog Common 4-20mA In (3) RS485 (DSI) Shield
P036, P037 Command comes from the integral keypad by default. To disable reverse operation, see A095 [Reverse Disable]. P036, P037, A095 For digital inputs. Electronically isolated with digital inputs from analog I/O. Program with A051 [Digital In1 Sel]. Program with A052 [Digital In2 Sel]. Drive supplied power for digital inputs. Maximum output current is 100mA. Drive supplied power for 0-10V external potentiometer. Maximum output current is 15mA. For external 0-10V input supply (input impedance = 100k ohm) or potentiometer wiper. For 0-10V In or 4-20mA In. Electronically isolated with analog inputs from digital I/O. For external 4-20mA input supply (input impedance = 250 ohm). Terminal should be connected to safety ground - PE when using the RS485 (DSI) communications port. P038 A051 A052
P038 P038
Only one analog frequency source may be connected at a time. If more than one reference is connected at the same time, an undetermined frequency reference will result.
1-14
Installation/Wiring
12 13 14
Analog Input 0 to +10V, 100k ohm impedance 4-20 mA, 100 ohm impedance
Voltage Current P038 [Speed Reference] = 2 0-10V P038 [Speed Reference] = 3 Input 4-20mA Input
+ Common
13 14
Common +
14 15
Wire the PTC and External Resistor (typically matched to the PTC Hot Resistance) to I/O Terminals 12, 13, 14. Wire R2/R3 Relay Output (SRC) to I/O Terminals 5 & 11. A051 [Digital In1 Sel] = 3 Aux Fault A055 [Relay Out Sel] = 10 Above Anlg V A056 [Relay Out Level] = % Voltage Trip
R2 R3 11 12 13 14 05
Re RPTC
VTrip =
100
Installation/Wiring
Input Connection Example 2 Wire SRC Control Internal Supply (SRC) Non-Reversing P036 [Start Source] = 2, 3 11 or 4 Input must be active for Stop-Run the drive to run. When input is opened, the drive will stop as specified by P037 [Stop Mode]. If desired, a User Supplied 24V DC power source can be used. Refer to the External Supply (SRC) example. 2 Wire SNK Control Internal Supply (SNK) Non-Reversing
Stop-Run
1-15
Stop-Run
01 02 04
2 Wire SRC Control Internal Supply (SRC) Run FWD/Run REV P036 [Start Source] = 2, 3 11 or 4 Input must be active for Stop-Run Forward the drive to run. When input is opened, the drive will stop as specified by Stop-Run Reverse P037 [Stop Mode]. If both Run Forward and Run Reverse inputs are closed at the same time, an undetermined state could occur. 2 Wire SNK Control Internal Supply (SNK) Run FWD/Run REV
01 02 03 04
1-16
Installation/Wiring
Connection Example Internal Supply (SRC)
Input 3 Wire SRC Control Non-Reversing P036 [Start Source] = 1 A momentary input will start the drive. A stop input to I/O Terminal 01 will stop the drive as specified by P037 [Stop Mode].
Stop
11
01 02
Stop
01 02 04
Start
Start
+24V
Common
Each digital input draws 6 mA. 3 Wire SNK Control Non-Reversing Internal Supply (SNK)
Stop 01 02 03 04
Start
3 Wire SRC Control Reversing P036 [Start Source] = 1 A momentary input will start the drive. A stop input to I/O Terminal 01 will stop the drive as specified by P037 [Stop Mode]. I/O Terminal 03 determines direction.
11
Start Direction
01 02 03 04
Each digital input draws 6 mA. 3 Wire SNK Control Reversing Internal Supply (SNK)
Stop 01 02 03 04
Start Direction
Installation/Wiring
1-17
!
Multiple Analog Connections
12 13 14
13 14
13 14
13 14
Remote Potentiometer
When connecting a single potentiometer to multiple drives it is important to connect I/O Terminal 14 common together for all drives. I/O Terminal 14 common and I/O Terminal 13 (potentiometer wiper) should be daisy-chained to each drive. All drives must be powered up for the analog signal to be read correctly.
1-18
Installation/Wiring
Yes
Yes
Yes
No
Yes
Start, Speed and Direction commands come from RS485 (DSI) port.
No Run as specified by P038 [Speed Reference]. Start and Direction commands come from P036 [Start Source].
Yes
No Run as specified by A071-A073 [Preset Freq 1-3]. Start and Direction commands come from P036 [Start Source].
Yes
No Run as specified by P038 [Speed Reference]. Start and Direction commands come from P036 [Start Source].
Installation/Wiring
1-19
Accel/Decel Selection
The selection of Accel/Decel rates can be made through digital inputs, RS485 (DSI) communications and/or parameters.
Yes
No
Yes
Active when A067 [Accel Time 2]/A068 [Decel Time 2] is selected by RS485 (DSI) port.
No
Yes
A067 [Accel Time 2]/A068 [Decel Time 2] is active when input is active.
No P039 [Accel Time 1]/P040 [Decel Time 1]; A067 [Accel Time 2]/A068 [Decel Time 2] determined by the active Preset Frequency. See A070-A073 [Preset Freq 0-3] on page 3-16.
Yes
1-20
Installation/Wiring
EMC Instructions
CE Conformity
Conformity with the Low Voltage (LV) Directive and Electromagnetic Compatibility (EMC) Directive has been demonstrated using harmonized European Norm (EN) standards published in the Official Journal of the European Communities. PowerFlex Drives comply with the EN standards listed below when installed according to the User Manual. CE Declarations of Conformity are available online at: http://www.ab.com/certification/ce/docs.
General Notes
Installation/Wiring
1-21
(1)
(2)
First Environment Unrestricted Distribution installations require a shielded enclosure. Keep wire length as short as possible between the enclosure entry point and the EMI filter. Integral EMI filters are available on 240V, 1-Phase drives.
1-22
Installation/Wiring
EN61000-3-2
0.75 kW (1 HP) 240V 1-Phase and 3-Phase drives and 0.37 kW (0.5 HP) 240V 1-Phase drives are suitable for installation on a private low voltage power network. Installations on a public low voltage power network may require additional external harmonic mitigation. Other drive ratings meet the current harmonic requirements of EN61000-3-2 without additional external mitigation.
Chapter 2
Start Up
This chapter describes how to start up the PowerFlex 4 Drive. To simplify drive setup, the most commonly programmed parameters are organized in a single Basic Program Group. Important: Read the General Precautions section before proceeding. ATTENTION: Power must be applied to the drive to perform the following start-up procedures. Some of the voltages present are at incoming line potential. To avoid electric shock hazard or damage to equipment, only qualified service personnel should perform the following procedure. Thoroughly read and understand the procedure before beginning. If an event does not occur while performing this procedure, Do Not Proceed. Remove All Power including user supplied control voltages. User supplied voltages may exist even when main AC power is not applied to the drive. Correct the malfunction before continuing.
1. Confirm that all inputs are connected to the correct terminals and are
secure.
2. Verify that AC line power at the disconnect device is within the rated
value of the drive.
3. Verify that any digital control power is 24 volts. 4. Verify that the Sink (SNK)/Source (SRC) Setup DIP Switch is set to
match your control wiring scheme. See Figure 1.5 on page 1-13 for location. Important: The default control scheme is Source (SRC). The Stop terminal is jumpered (I/O Terminals 01 and 11) to allow starting from the keypad. If the control scheme is changed to Sink (SNK), the jumper must be removed from I/O Terminals 01 and 11 and installed between I/O Terminals 01 and 04.
5. Verify that the Stop input is present or the drive will not start.
Important: If I/O Terminal 01 is used as a stop input, the jumper between I/O Terminals 01 and 11 must be removed.
2-2
Start Up
6. Apply AC power and control voltages to the drive. 7. Familiarize yourself with the integral keypad features (see page 2-3)
before setting any Program Group parameters.
Start Up
2-3
Integral Keypad
PROGRAM
FAULT
Menu
Description
Display Group (View Only) Consists of commonly viewed drive operating conditions. Basic Program Group Consists of most commonly used programmable functions.
Advanced Program Group Consists of remaining programmable functions. Fault Designator Consists of list of codes for specific fault conditions. Displayed only when fault is present.
LED State Steady Red Flashing Red Steady Red Flashing Red Steady Red Steady Red Flashing Red Steady Green
Alphanumeric Display Displayed Units Program Status Fault Status Pot Status
Description Indicates drive is running and commanded motor direction. Drive has been commanded to change direction. Indicates actual motor direction while decelerating to zero. Indicates parameter number, parameter value, or fault code. Single digit flashing indicates that digit can be edited. All digits flashing indicates a fault condition. Indicates the units of the parameter value being displayed. Indicates parameter value can be changed. Indicates drive is faulted. Indicates potentiometer on Integral Keypad is active. Indicates Start key on Integral Keypad is active. The Reverse key is also active unless disabled by A095 [Reverse Disable]. Description Back one step in programming menu. Cancel a change to a parameter value and exit Program Mode. Advance one step in programming menu. Select a digit when viewing parameter value. Scroll through groups and parameters. Increase/decrease the value of a flashing digit. Advance one step in programming menu. Save a change to a parameter value. Used to control speed of drive. Default is active. Controlled by parameter P038 [Speed Reference]. Used to start the drive. Default is active. Controlled by parameter P036 [Start Source]. Used to reverse direction of the drive. Default is active. Controlled by parameters P036 [Start Source] and A095 [Reverse Disable]. Used to stop the drive or clear a fault. This key is always active. Controlled by parameter P037 [Stop Mode].
No. Key
2-4
Start Up
Example Displays
VOLTS AMPS HERTZ PROGRAM FAULT
or or
PROGRAM
FAULT
or or
PROGRAM FAULT VOLTS AMPS HERTZ
or
PROGRAM FAULT
or
11. Press Esc to return to the parameter list. Continue to press Esc to back out of the programming menu. If pressing Esc does not change the display, then d001 [Output Frequency] is displayed. Press Enter or Sel to enter the group menu.
The Basic Program Group (page 3-8) contains the most commonly changed parameters.
Chapter 3
About Parameters
To configure a drive to operate in a specific way, drive parameters may have to be set. Three types of parameters exist: ENUM ENUM parameters allow a selection from 2 or more items. Each item is represented by a number. Numeric Parameters These parameters have a single numerical value (i.e. 0.1 Volts). Bit Parameters Bit parameters have four individual bits associated with features or conditions. If the bit is 0, the feature is off or the condition is false. If the bit is 1, the feature is on or the condition is true.
Some parameters are marked as follows. = Stop drive before changing this parameter.
32
= 32 bit parameter. Parameters marked 32 bit will have two parameter numbers when using RS485 communications and programming software.
3-2
Parameter Organization
B Progr asic am G roup Ad Progrvanced am G roup
Displa
y Gro
up
See page 3-3 Output Freq Commanded Freq Output Current Output Voltage DC Bus Voltage Drive Status Fault 1 Code Fault 2 Code Fault 3 Code Process Display Control Source Contrl In Status Dig In Status Comm Status Control SW Ver Drive Type Elapsed Run Time Testpoint Data Analog In 0-10V Analog In 4-20mA Drive Temp
d001 d002 d003 d004 d005 d006 d007 d008 d009 d010 d012 d013 d014 d015 d016 d017 d018 d019 d020 d021 d024
See page 3-8 Motor NP Volts Motor NP Hertz Motor OL Current Minimum Freq Maximum Freq Start Source Stop Mode Speed Reference Accel Time 1 Decel Time 1 Reset To Defalts Motor OL Ret
P031 P032 P033 P034 P035 P036 P037 P038 P039 P040 P041 P043
See page 3-13 Digital In1 Sel Digital In2 Sel Relay Out Sel Relay Out Level Accel Time 2 Decel Time 2 Internal Freq Preset Freq 0 Preset Freq 1 Preset Freq 2 Preset Freq 3 Jog Frequency Jog Accel/Decel DC Brake Time DC Brake Level DB Resistor Sel S Curve % Boost Select Maximum Voltage Current Limit Motor OL Select PWM Frequency Auto Rstrt Tries Auto Rstrt Delay Start At PowerUp Reverse Disable Flying Start En Compensation SW Current Trip Process Factor Fault Clear Program Lock Testpoint Sel Comm Data Rate Comm Node Addr Comm Loss Action Comm Loss Time Comm Format Anlg In 0-10V Lo Anlg In 0-10V Hi Anlg In 4-20mA Lo Anlg In 4-20mA Hi Slip Hertz @ FLA Process Time Lo Process Time Hi Bus Reg Mode Comm Write Mode
A051 A052 A055 A056 A067 A068 A069 A070 A071 A072 A073 A078 A079 A080 A081 A082 A083 A084 A088 A089 A090 A091 A092 A093 A094 A095 A096 A097 A098 A099 A100 A101 A102 A103 A104 A105 A106 A107 A110 A111 A112 A113 A114 A115 A116 A117 A118
3-3
Display Group
d001 [Output Freq]
Values Default Min/Max: Display: Related Parameter(s): d002, d010, P034, P035, P038 Read Only 0.0/P035 [Maximum Freq] 0.1 Hz Output frequency present at T1, T2 & T3 (U, V & W).
Value of the active frequency command. Displays the commanded frequency even if the drive is not running. Important: The frequency command can come from a number of sources. Refer to Start and Speed Reference Control on page 1-18 for details. Values Default Min/Max: Display: Read Only 0.0/P035 [Maximum Freq] 0.1 Hz
3-4
Values
32 bit parameter.
The output frequency scaled by A099 [Process Factor] or by A115 [Process Time Lo] and A116 [Process Time Hi].
Output Process Process Freq x Factor = Display
Values
3-5
Start Command Digit 0 0 = Keypad 1 = 3-Wire 2 = 2-Wire 3 = 2-Wire Level Sensitive 4 = 2-Wire High Speed 5 = RS485 (DSI) Port 9 = Jog Speed Command Digit 1 0 = Drive Potentiometer 1 = A069 [Internal Freq] 2 = 0-10V Input/Remote Potentiometer 3 = 4-20mA Input 4 = A070 - A073 [Preset Freq x] (A051 - A052 [Digital Inx Sel] must be set to 4) 5 = RS485 (DSI) Port 9 = Jog Freq Reserved Digit 2 Reserved Digit 3
Values
Status of the control terminal block control inputs. Important: Actual control commands may come from a source other than the control terminal block.
1 = Input Present, 0 = Input Not Present Start / Run FWD Input (I/O Terminal 02) Bit 0 Direction / Run REV Input (I/O Terminal 03) Bit 1 Bit 2 Stop Input(1) (I/O Terminal 01) Reserved Bit 3
(1)
The stop input must be present in order to start the drive. When this bit is a 1 the drive can be started. When this bit is a 0 the drive will stop.
Values
3-6
1 = Input Present, 0 = Input Not Present Digital In1 Sel (I/O Terminal 05) Bit 0 Digital In2 Sel (I/O Terminal 06) Bit 1 Reserved Bit 2 Reserved Bit 3
Values
1 = Condition True, 0 = Condition False Receiving Data Bit 0 Transmitting Data Bit 1 RS485 (DSI) Based Option Connected Bit 2 (Allen-Bradley devices only.) Communication Error Occurred Bit 3
Values
3-7
The present value of the current at I/O Terminal 15 (0.0% = 4mA, 100.0% = 20mA).
3-8
Set to the maximum allowable motor current. The drive will fault on an F7 Motor Overload if the value of this parameter is exceeded by 150% for 60 seconds. Values Default Min/Max: Display: Based on Drive Rating 0.0/(Drive Rated Amps 2) 0.1 Amps
Related Parameter(s): d001, d002, d013, P035, A110, A112, A115 0.0 Hz 0.0/240.0 Hz 0.1 Hz Related Parameter(s): d001, d002, d013, P034, A078, A111, A113, A115
Stop drive before changing this parameter. Sets the highest frequency the drive will output. Values Default Min/Max: Display: 60 Hz 0/240 Hz 1 Hz
3-9
4 2-W Hi Speed
Important: When commanding Jog via the RS485 communications port on drives with firmware version 1.02 or earlier, the Jog command will follow the commanded direction from I/O Terminal 03. On firmware versions 1.03 and later, the commanded direction will be provided via the RS485 communications port. Important: When sending a continuous start command via the RS485 communications port on drives with firmware version 1.02 or earlier, a maintained stop input is required to stop the drive. Once the stop input is inactive, the drive will restart. On firmware versions 1.03 and later, once a stop input is received, the start command must transition from high to low to high for the drive to start.
3-10
Coast to Stop. Stop command clears active fault. DC Injection Braking Stop. Stop command clears active fault. DC Injection Braking Stop with Auto Shutoff. Standard DC Injection Braking for value set in A080 [DC Brake Time]. OR Drive shuts off if the drive detects that the motor is stopped. Stop command clears active fault.
3 DCBrkAuto,CF(1)
Ramp to Stop. Coast to Stop. DC Injection Braking Stop. DC Injection Braking Stop with Auto Shutoff. Standard DC Injection Braking for value set in A080 [DC Brake Time]. OR Drive shuts off if current limit is exceeded.
(1)
3-11
5 Comm Port
Values
ratio
cele
ele
Speed
ratio
Acc
0 0
Time
3-12
Values
0 0
Acc ele
Speed
ratio
Time
Enables/disables the Motor Overload Retention function. When Enabled, the value held in the motor overload counter is saved at power-down and restored at power-up. A change to this parameter setting resets the counter. Options 0 Disabled (Default) 1 Enabled
3-13
2 Jog
3 Aux Fault
4 Preset Freq (Default) Refer to A070 - A073 [Preset Freq x]. Important: Digital Inputs have priority for frequency control when programmed as a Preset Speed and are active. Refer to the flowchart on 1-18 for more information on speed reference control priority. 5 Local 6 Comm Port When active, sets integral keypad as start source and potentiometer on the integral keypad as speed source. When active, sets communications device as default start/ speed command source. Can only be tied to one input. When active, clears an active fault. Causes drive to immediately ramp to a stop regardless of how P037 [Stop Mode] is set. Causes drive to immediately coast to a stop regardless of how P037 [Stop Mode] is set. Causes drive to immediately begin a DC Injection stop regardless of how P037 [Stop Mode] is set. Drive accelerates to A078 [Jog Frequency] according to A079 [Jog Accel/Decel] and ramps to stop when input becomes inactive. A valid start will override this command. Drive accelerates to A078 [Jog Frequency] according to A079 [Jog Accel/Decel] and ramps to stop when input becomes inactive. A valid start will override this command.
12 Jog Reverse
3-14
A051 & 13 10V In Ctrl A052 Options 14 20mA In Ctrl (Cont.) 15 - 25 26 Anlg Invert
Sets the condition that changes the state of the output relay contacts.
3-15
32 bit parameter.
Sets the trip point for the digital output relay if the value of A055 [Relay Out Sel] is 6, 7, 8, 10 or 20.
A055 Setting 6 7 8 10 20 A056 Min/Max 0/240 Hz 0/180% 0/815 Volts 0/100% 0/1
Values
When active, sets the rate of acceleration for all speed increases except jog. Refer to the flowchart on page 1-19 for details.
Values
ratio
cele
ele
Speed
ratio
Acc
0 0
Time
When active, sets the rate of deceleration for all speed decreases except jog. Refer to the flowchart on page 1-19 for details.
Values
ratio
cele
ele
Speed
ratio
Acc
0 0
Time
3-16
A070 [Preset Freq 0](1) A071 [Preset Freq 1] A072 [Preset Freq 2] A073 [Preset Freq 3]
Values A070 Default A071 Default A072 Default A073 Default Min/Max: Display:
Provides a fixed frequency command value when A051 - A052 [Digital Inx Sel] is set to 4 Preset Frequencies. An active preset input will override speed command as shown in the flowchart on page 1-19.
(1)
To activate A070 [Preset Freq 0] set P038 [Speed Reference] to option 4 Preset Freq 0-3.
Input State of Digital In 2 (I/O Terminal 06) 0 0 1 1
Frequency Source A070 [Preset Freq 0] A071 [Preset Freq 1] A072 [Preset Freq 2] A073 [Preset Freq 3]
Accel / Decel Parameter Used(2) [Accel Time 1] / [Decel Time 1] [Accel Time 1] / [Decel Time 1] [Accel Time 2] / [Decel Time 2] [Accel Time 2] / [Decel Time 2]
When a Digital Input is set to Accel 2 & Decel 2, and the input is active, that input overrides the settings in this table.
Sets the output frequency when a jog command is issued. 0.0/P035 [Maximum Freq] 0.1 Hz
3-17
Sets the length of time that DC brake current is injected into the motor. Refer to parameter A081 [DC Brake Level].
Defines the maximum DC brake current, in amps, applied to the motor when P037 [Stop Mode] is set to either Ramp or DC Brake. Drive Rated Amps 0.05 0.0/(Drive Rated Amps 1.8) 0.1 Amps
DC Injection Braking Mode Voltage Volts/Speed
Vo
lta
Volts/Speed
Spe
ge
ed
Speed
Stop Command
Time
Stop Command
! !
ATTENTION: If a hazard of injury due to movement of equipment or material exists, an auxiliary mechanical braking device must be used. ATTENTION: This feature should not be used with synchronous or permanent magnet motors. Motors may be demagnetized during braking.
3-18
The drive is able to provide full braking indefinitely. Braking power is limited by the external DB resistor. When this parameter is set to 1 Normal RA Res and an appropriate RA resistor is used (see selection Table B.C), the drive provides calculated resistor overload protection. However, the drive cannot protect against a brake IGBT failure. ATTENTION: A risk of fire exists if external braking resistors are not protected. The external resistor package must be self-protected from over temperature or the protective circuit shown in Figure B.7 on page B-9, or equivalent, must be supplied.
!
Values
0 0/99 1
A083 [S Curve %]
Sets the percentage of acceleration or deceleration time that is applied to the ramp as S Curve. Time is added, 1/2 at the beginning and 1/2 at the end of the ramp. Values Default Min/Max: Display: Example: Accel Time = 10 Seconds S Curve Setting = 50% S Curve Time = 10 0.5 = 5 Seconds Total Time = 10 + 5 = 15 Seconds 0% (Disabled) 0/100% 1%
50% S Curve Target
Target/2
3-19
Sets the boost voltage (% of P031 [Motor NP Volts]) and redefines the Volts per Hz curve.(1) Drive may add additional voltage unless option 5 is selected. 2 35.0, VT 3 40.0, VT 4 45.0, VT 5 0.0 no IR 6 0.0 7 2.5, CT [Default for 3.7kW (5HP) Drives] 8 5.0, CT (Default) 9 7.5, CT 10 10.0, CT 11 12.5, CT 12 15.0, CT 13 17.5, CT 14 20.0, CT
100
Constant Torque
50
Settings 5-14 0
100
3-20
Drive provides Class 10 motor overload protection. Settings 0-2 select the derating factor for the I2t overload function.
100 80 60 40 20 0 0
Max Derate
10 11 12 13 14 15 16
3-21
!
Values
Sets the time between restart attempts when A092 [Auto Rstrt Tries] is set to a value other than zero.
3-22
A097 [Compensation]
Enables/disables correction options that may improve problems with motor instability. Options 0 Disabled 1 Electrical (Default) 2 Mechanical Some drive/motor combinations have inherent instabilities which are exhibited as non-sinusodial motor currents. This setting attempts to correct this condition. Some motor/load combinations have mechanical resonances which can be excited by the drive current regulator. This setting slows down the current regulator response and attempts to correct this condition.
3 Both
Values
3-23
Important: Power to drive must be cycled before any changes will affect drive operation. Options 0 1200 1 2400 2 4800 3 9600 (Default) 4 19.2K 5 38.4K
Sets the drive node address for the RS485 (DSI) port if using a network connection. Important: Power to drive must be cycled before any changes will affect drive operation. Values Default Min/Max: Display: 100 1/247 1
3-24
Sets the time that the drive will remain in communication loss before implementing the option selected in A105 [Comm Loss Action].
3-25
Sets the analog input level that corresponds to P034 [Minimum Freq] if a 0-10V input is used by P038 [Speed Reference]. Analog inversion can be accomplished by setting this value larger than A111 [Anlg In 0-10V Hi] or by setting A051 - A052 [Digital Inx Sel] to option 26 Anlg Invert Values Default Min/Max: Display:
P035 [Maximum Freq]
en ce
Sp
ee
e dR
fer
P034 [Minimum Freq] 0 0 A110 [Anlg In 0-10V Lo] A111 [Anlg In 0-10V Hi]
Sets the analog input level that corresponds to P035 [Maximum Freq] if a 0-10V input is used by P038 [Speed Reference]. Analog inversion can be accomplished by setting this value smaller than A110 [Anlg 0-10V In Lo] or by setting A051 - A052 [Digital Inx Sel] to option 26 Anlg Invert. Values Default Min/Max: Display: 100.0% 0.0/100.0% 0.1% Related Parameter(s): d021, P034, P038, A051, A052
Sets the analog input level that corresponds to P034 [Minimum Freq] if a 4-20mA input is used by P038 [Speed Reference]. Analog inversion can be accomplished by setting this value larger than A113 [Anlg In4-20mA Hi] or by setting A051 - A052 [Digital Inx Sel] to option 26 Anlg Invert. Values Default Min/Max: Display: 0.0% 0.0/100.0% 0.1% Related Parameter(s): d021, P035, P038, A051, A052
Sets the analog input level that corresponds to P035 [Maximum Freq] if a 4-20mA input is used by P038 [Speed Reference]. Analog inversion can be accomplished by setting this value smaller than A112 [Anlg In4-20mA Lo] or by setting A051 - A052 [Digital Inx Sel] to option 26 Anlg Invert. Values Default Min/Max: Display: 100.0% 0.0/100.0% 0.1%
3-26
Compensates for the inherent slip in an induction motor. This frequency is added to the commanded output frequency based on motor current.
Scales the time value when the drive is running at P034 [Minimum Freq]. When set to a value other than zero, d010 [Process Display] indicates the duration of the process.
Scales the time value when the drive is running at P035 [Maximum Freq]. When set to a value other than zero, d010 [Process Display] indicates the duration of the process.
ATTENTION: Risk of equipment damage exists. If a controller is programmed to write parameter data to Non-Volatile Storage (NVS) frequently, the NVS will quickly exceed its life cycle and cause the drive to malfunction. Do not create a program that frequently uses configurable outputs to write parameter data to NVS unless A164 [Comm Write Mode] is set to option 1.
3-27
No.
P039 A067 d020 d021 A111 A110 A113 A112 A093 A092 A084 A117 A103 A107 A105 A106 A104 d015 A118 d002 A097 d013 d012 d016 A089 A082 A081 A080 d005 P040 A068 d014 A051, A052 d006 d024 d017 d018
Group
Basic Program Advanced Program Display Display Advanced Program Advanced Program Advanced Program Advanced Program Advanced Program Advanced Program Advanced Program Advanced Program Advanced Program Advanced Program Advanced Program Advanced Program Advanced Program Display Advanced Program Display Advanced Program Display Display Display Advanced Program Advanced Program Advanced Program Advanced Program Display Basic Program Advanced Program Display Advanced Program Display Display Display Display
Parameter Name
Fault x Code Fault Clear Flying Start En Internal Freq Jog Accel/Decel Jog Frequency Maximum Freq Maximum Voltage Minimum Freq Motor NP Hertz Motor NP Volts Motor OL Current Motor OL Ret Motor OL Select Output Current Output Freq Output Voltage Preset Freq x Process Display Process Factor Process Time Hi Process Time Lo Program Lock PWM Frequency Relay Out Level Relay Out Sel Reset To Defalts Reverse Disable S Curve % Slip Compensation Speed Reference Start At PowerUp Start Source Stop Mode SW Current Trip Testpoint Data Testpoint Sel
No.
d007-d009 A100 A096 A069 A079 A078 P035 A088 P034 P032 P031 P033 P043 A090 d003 d001 d004 A070-A073 d010 A099 A116 A115 A101 A091 A056 A055 P041 A095 A083 A114 P038 A094 P036 P037 A098 d019 A102
Group
Display Advanced Program Advanced Program Advanced Program Advanced Program Advanced Program Basic Program Advanced Program Basic Program Basic Program Basic Program Basic Program Basic Program Advanced Program Display Display Display Advanced Program Display Advanced Program Advanced Program Advanced Program Advanced Program Advanced Program Advanced Program Advanced Program Basic Program Advanced Program Advanced Program Advanced Program Basic Program Advanced Program Basic Program Basic Program Advanced Program Display Advanced Program
3-28
Notes:
Chapter 4
Troubleshooting
Chapter 4 provides information to guide you in troubleshooting the PowerFlex 4 drive. Included is a listing and description of drive faults (with possible solutions, when applicable).
For information on Drive Status Faults See page For information on 4-1 Fault Descriptions 4-1 Common Symptoms and Corrective Actions See page 4-3 4-5
Drive Status
The condition or state of your drive is constantly monitored. Any changes will be indicated through the integral keypad.
LED Indications
See page 2-3 for information on drive status indicators and controls.
Faults
A fault is a condition that stops the drive. There are two fault types.
Type Fault Description Auto-Reset/Run When this type of fault occurs, and A092 [Auto Rstrt Tries] is set to a value greater than 0, a user-configurable timer, A093 [Auto Rstrt Delay], begins. When the timer reaches zero, the drive attempts to automatically reset the fault. If the condition that caused the fault is no longer present, the fault will be reset and the drive will be restarted. Non-Resetable This type of fault may require drive or motor repair, or is caused by wiring or programing errors. The cause of the fault must be corrected before the fault can be cleared.
4-2
Troubleshooting
Fault Indication
Condition Display Drive is indicating a fault. The integral keypad provides visual notification of a fault condition by displaying the following. Flashing fault number Flashing fault indicator Press the Escape key to regain control of the integral keypad.
RUN FWD REV PRGOGRAM FAULT VOLTS AMPS HERTZ
Troubleshooting
4-3
Fault Descriptions
Table 4.A Fault Types, Descriptions and Actions Type(1)
No. F2
F3
Power Loss
F4 F5
UnderVoltage OverVoltage
F6
Motor Stalled
F7
Motor Overload
F8
Heatsink OvrTmp
F12
HW OverCurrent
F13
Ground Fault
Action 1. Check remote wiring. 2. Verify communications programming for intentional fault. DC bus voltage remained below 1. Monitor the incoming AC line for 85% of nominal. low voltage or line power interruption. 2. Check input fuses. DC bus voltage fell below the Monitor the incoming AC line for low minimum value. voltage or line power interruption. DC bus voltage exceeded Monitor the AC line for high line maximum value. voltage or transient conditions. Bus overvoltage can also be caused by motor regeneration. Extend the decel time or install dynamic brake option. Drive is unable to accelerate Increase P039 - A067 [Accel Time x] motor. or reduce load so drive output current does not exceed the current set by parameter A089 [Current Limit]. Internal electronic overload trip. 1. An excessive motor load exists. Reduce load so drive output current does not exceed the current set by parameter P033 [Motor OL Current]. 2. Verify A084 [Boost Select] setting Heatsink temperature exceeds a 1. Check for blocked or dirty heat predefined value. sink fins. Verify that ambient temperature has not exceeded 40C (104F) for IP 30/NEMA 1/UL Type 1 installations or 50C (122F) for IP20/Open type installations. 2. Check fan. The drive output current has Check programming. Check for exceeded the hardware current excess load, improper A084 [Boost Select] setting, DC brake volts set limit. too high or other causes of excess current. A current path to earth ground Check the motor and external wiring has been detected at one or to the drive output terminals for a more of the drive output grounded condition. terminals.
(1)
4-4
Troubleshooting
Type(1)
No. F33
F71
Net Loss
F81
Comm Loss
1. Check the wiring between the drive and motor. 2. Check motor for grounded phase. 3. Replace drive if fault cannot be cleared. Excessive current has been 1. Check the motor and drive output detected between these two terminal wiring for a shorted output terminals. condition. 2. Replace drive if fault cannot be cleared. The drive was commanded to 1. Clear the fault or cycle power to write default values to EEPROM. the drive. 2. Program the drive parameters as needed. Programmed A098 [SW Current Check load requirements and A098 Trip] has been exceeded. [SW Current Trip] setting. Drive rating of 150% for 1 minute Reduce load or extend Accel Time. or 200% for 3 seconds has been exceeded. Failure has been detected in the 1. Cycle power. drive power section. 2. Replace drive if fault cannot be cleared. The communication network has 1. Cycle power. faulted. 2. Check communications cabling. 3. Check network adapter setting. 4. Check external network status. RS485 (DSI) port stopped 1. If adapter was not intentionally communicating. disconnected, check wiring to the port. Replace wiring, port expander, adapters or complete drive as required. 2. Check connection. 3. An adapter was intentionally disconnected. 4. Turn off using A105 [Comm Loss Action]. The checksum read from the Set P041 [Reset To Defalts] to board does not match the option 1 Reset Defaults. checksum calculated. Failure has been detected in the 1. Cycle power. drive control and I/O section. 2. Replace drive if fault cannot be cleared.
Description Drive unsuccessfully attempted to reset a fault and resume running for the programmed number of A092 [Auto Rstrt Tries]. A phase to ground fault has been detected between the drive and motor in this phase.
(1)
Troubleshooting
4-5
None
4-6
Troubleshooting Drive does not Start from Start or Run Inputs wired to the terminal block.
None Incorrect programming. P036 [Start Source] is set to option 0 Keypad or option 5 RS485 (DSI) Port. A051 - A052 [Digital Inx Select] is set to option 5 Local and the input is active. None Incorrect input wiring. See 1-14 for wiring examples. 2 wire control requires Run Forward, Run Reverse or Jog input. 3 wire control requires Start and Stop inputs Stop input is always required. Incorrect Sink/Source DIP switch None setting.
Corrective Action Clear fault. Press Stop Cycle power Set A100 [Fault Clear] to option 1 Clear Faults. Cycle digital input if A051 - A052 [Digital Inx Select] is set to option 7 Clear Fault. Check parameter settings.
Incorrect reference source is being selected via remote device or digital inputs.
None
4-7
None
Programming is preventing the None drive output from exceeding limiting values.
Corrective Action Reprogram P039 [Accel Time 1] or A067 [Accel Time 2]. Compare d003 [Output Current] with A089 [Current Limit]. Remove excess load or reprogram P039 [Accel Time 1] or A067 [Accel Time 2]. Check for improper A084 [Boost Select] setting. Verify d002 [Commanded Freq]. Check d012 [Control Source] for the proper Speed Command. Check P035 [Maximum Freq] to insure that speed is not limited by programming.
4-8
Troubleshooting
Notes:
Appendix A
Fusing
If fuses are chosen as the desired protection method, refer to the recommended types listed below. If available amp ratings do not match the tables provided, the closest fuse rating that exceeds the drive rating should be chosen. IEC BS88 (British Standard) Parts 1 & 2 (1), EN60269-1, Parts 1 & 2, type gG or equivalent should be used. UL UL Class CC, T or J must be used. (2)
Circuit Breakers
Refer to listings in the following tables for recommended circuit breakers (inverse time or instantaneous trip) and 140M Self-Protecting Motor Starters.
(1) (2)
Typical designations include, but may not be limited to the following; Parts 1 & 2: AC, AD, BC, BD, CD, DD, ED, EFS, EF, FF, FG, GF, GG, GH. Typical designations include; Type CC - KTK-R, FNQ-R Type J - JKS, LPJ Type T - JJS, JJN
A-2
Specifications
Drive Ratings Input Ratings Branch Circuit Protection Voltage 140M Motor kW (HP) Amps Range kVA Amps Fuses Protectors(2) 100 - 120V AC (10%) 1-Phase Input, 0 - 230V 3-Phase Output Catalog Number
22A-V1P5N104 22A-V2P3N104 22A-V4P5N104 22A-V6P0N104 22A-A1P4N103 22A-A2P1N103 22A-A3P6N103 22A-A6P8N103 22A-A9P6N103 22A-A1P5N104 22A-A2P3N104 22A-A4P5N104 22A-A8P0N104 22A-B1P5N104 22A-B2P3N104 22A-B4P5N104 22A-B8P0N104 22A-B012N104 22A-B017N104 22A-D1P4N104 22A-D2P3N104 22A-D4P0N104 22A-D6P0N104 22A-D8P7N104 0.2 (0.25) 0.4 (0.5) 0.75 (1.0) 1.1 (1.5) 1.5 2.3 4.5 6.0 90-126 90-126 90-126 90-126 0.75 1.15 2.25 3.0 6.0 9.0 18.0 24.0 10 15 30 40 140M-C2E-C10 140M-C2E-C16 140M-D8E-C20 140M-D8E-C25 140M-C2E-B40 140M-C2E-B63 140M-C2E-C16 140M-C2E-C16 140M-D8E-C25 140M-C2E-B63 140M-C2E-B63 140M-C2E-C16 140M-D8E-C20 140M-C2E-B25 140M-C2E-B40 140M-C2E-C10 140M-C2E-C16 140M-C2E-C16 140M-F8E-C25 140M-C2E-B25 140M-C2E-B40 140M-C2E-B63 140M-C2E-C10 140M-C2E-C16
Output Ratings
Contactors
100-C09 100-C12 100-C23 100-C37 100-C09 100-C09 100-C12 100-C16 100-C23 100-C09 100-C09 100-C12 100-C23 100-C09 100-C09 100-C09 100-C12 100-C16 100-C23 100-C09 100-C09 100-C09 100-C09 100-C16
Input/Output Ratings
Output Frequency: 0-240 Hz (Programmable) Efficiency: 97.5% (Typical)
Approvals
C
UL
Protective Features
Dynamic Braking
Internal brake IGBT included with all ratings except No Brake versions. Refer to Appendix B of the PowerFlex 4 User Manual on CD for ordering information.
(1) (2)
200-240V AC - 1-Phase drives are also available with an integral EMC filter. Catalog suffix changes from N103 to N113 and N104 to N114. Refer to the Bulletin 140M Motor Protectors Selection Guide, publication 140M-SG001 to determine the frame and breaking capacity required for your application.
A-3
Category Environment
Specification Altitude: Maximum Surrounding Air Temperature without derating: IP20: NEMA 1: Flange Mount: Cooling Method Convection: Fan: Storage Temperature: Atmosphere:
10 to 50 C (14 to 122 F) 10 to 40 C (14 to 104 F) Heatsink: 10 to 40 C (14 to 104 F) Drive: 10 to 50 C (14 to 122 F) 0.2 kW (0.25 HP) drives Flange Mount drives, all ratings All other drive ratings. 40 to 85 degrees C (40 to 185 degrees F) Important: Drive must not be installed in an area where the ambient atmosphere contains volatile or corrosive gas, vapors or dust. If the drive is not going to be installed for a period of time, it must be stored in an area where it will not be exposed to a corrosive atmosphere. 0 to 95% non-condensing 15G peak for 11ms duration (1.0ms) 1G peak, 5 to 2000 Hz 2-16 kHz. Drive rating based on 4 kHz. Within 0.05% of set output frequency. Within 0.5% of maximum output frequency. 2% of base speed across a 40:1 speed range. Multiple programmable stop modes including Ramp, Coast, DC-Brake, Ramp-to-Hold and S Curve. Two independently programmable accel and decel times. Each time may be programmed from 0 - 600 seconds in 0.1 second increments. 150% Overload capability for up to 1 minute 200% Overload capability for up to 3 seconds Class 10 protection with speed sensitive response and power-down overload retention function.
Control
Relative Humidity: Shock (operating): Vibration (operating): Carrier Frequency Frequency Accuracy Digital Input: Analog Input: Speed Regulation - Open Loop with Slip Compensation: Stop Modes: Accel/Decel: Intermittent Overload: Electronic Motor Overload Protection
A-4
200240V
380480V
Appendix B
Product Selection
Table B.A Catalog Number Description
22A Drive
Drive Ratings Input Voltage 120V 50/60 Hz 1-Phase No Filter
A
Voltage Rating
1P5
Rating
N
Enclosure
1
HIM
1
Emission Class
4
Type
(1)
Replacement Plate drives are also available. Contact factory for ordering information.
B-2
HP 0.25 0.5 1.0 1.5 0.25 0.5 1.0 2.0 0.25 0.5 1.0 2.0 3.0 5.0 0.5 1.0 2.0 3.0 5.0
Catalog Number (1) (2) AK-R2-091P500 AK-R2-091P500 AK-R2-091P500 AK-R2-091P500 AK-R2-091P500 AK-R2-091P500 AK-R2-091P500 AK-R2-091P500 AK-R2-091P500 AK-R2-091P500 AK-R2-091P500 AK-R2-091P500 AK-R2-047P500 AK-R2-047P500 AK-R2-091P500 AK-R2-360P500 AK-R2-360P500 AK-R2-120P1K2 AK-R2-120P1K2
The resistors listed in this table are rated for 5% duty cycle. Use of Rockwell resistors is always recommended. The resistors listed have been carefully selected for optimizing performance in a varity of applications. Alternative resistors may be used, however care must be taken when making a selection. Refer to the PowerFlex Dynamic Braking Resistor Calculator, publication PFLEX-AT001.
0.25 2
0.75 1.0
480V 50/60 Hz 0.4 0.5 3-Phase 0.75 1.0 1.5 2.2 3.7
(1)
Catalog numbers listed are for 3% impedance open style units. NEMA Type 1 and 5% impedance reactor types are also available. Refer to publication 1321-TD001.
B-3
22-RF9P5-AS 22-RF9P5-AS 22-RF9P5-AS 22-RF9P5-AS 22-RF021-BS 22-RF021-BS 22-RF5P7-AS 22-RF5P7-AS 22-RF5P7-AS 22-RF012-BS 22-RF012-BS
L Type Filter Catalog Number (3) 22-RF010-AL 22-RF010-AL 22-RF018-BL 22-RF025-CL (4) 22-RF010-AL 22-RF010-AL 22-RF010-AL 22-RF018-BL 22-RF010-AL 22-RF010-AL 22-RF010-AL 22-RF018-BL 22-RF025-CL (4) 22-RF9P5-AL 22-RF9P5-AL 22-RF9P5-AL 22-RF9P5-AL 22-RF021-BL 22-RF021-BL 22-RF5P7-AL 22-RF5P7-AL 22-RF5P7-AL 22-RF012-BL 22-RF012-BL
This filter is suitable for use with a cable length up to 10 meters (33 feet) for Class A and 1 meter for Class B environments. These ratings can be ordered with internal S Type filters. Refer to the Catalog Number explanation on page P-4 and Table B.B for details. This filter is suitable for use with a cable length up to 100 meters for Class A and 5 meters for Class B environments. The piggyback mounting option cannot be used with Frame B PowerFlex 4 drives and Frame C EMC Line Filters.
Table B.F Human Interface Module (HIM) Option Kits and Accessories
Item LCD Display, Remote Panel Mount Description Digital speed control CopyCat capable IP66 (NEMA Type 4X/12) indoor use only 22-HIM-C2 includes 2.9 meter cable. 22-HIM-C2S includes 2 meter cable. Catalog Number 22-HIM-C2 22-HIM-C2S (1)
LCD Display, Remote Handheld Digital speed control Full numeric keypad CopyCat capable IP30 (NEMA Type 1) Includes 1.0 meter cable Panel mount with optional Bezel Kit Bezel Kit DSI HIM Cable (DSI HIM to RJ45 cable)
(1)
22-HIM-A3
Panel mount for LCD Display, Remote Handheld unit, IP30 (NEMA Type 1) 1.0 Meter (3.3 Feet) 2.9 Meter (9.51 Feet)
The 22-HIM-C2S is smaller than the 22-HIM-C2 and cannot be used as a direct replacement.
B-4
Optional 100-240V AC Power Supply for External 20-XCOMM-AC-PS1 DSI Communications Kit. Three channel. 1769-SM2 22-SCM-232
Serial Converter Module Provides serial communication via DF1 protocol (RS485 to RS232) for use with DriveExplorer and DriveExecutive software. Includes: DSI to RS232 serial converter (1) 1203-SFC serial cable (1) 22-RJ45CBL-C20 cable (1) DriveExplorer Lite CD (1) DSI Cable Serial Cable 2.0 meter RJ45 to RJ45 cable, male to male connectors.
22-RJ45CBL-C20
2.0 meter serial cable with a locking low profile 1203-SFC connector to connect to the serial converter and a 9-pin sub-miniature D female connector to connect to a computer. For use when connecting the serial converter to DriveExplorer on a handheld PC. RJ45 one to two port splitter cable RJ45 120 Ohm resistors (2 pieces) RJ45 Two position terminal block (5 pieces) 1203-SNM AK-U0-RJ45-SC1 AK-U0-RJ45-TR1 AK-U0-RJ45-TB2P
DriveExplorer Software Windows based software package that provides 9306-4EXP01ENE (CD-ROM) Version 3.01 an intuitive means for monitoring or configuring or later Allen-Bradley drives and communication adapters online. Compatibility: Windows 95, 98, ME, NT 4.0 (Service Pack 3 or later), 2000, XP and CE(1) DriveExecutive software Windows based software package that provides 9303-4DTE01ENE (CD-ROM) Version 1.01 an intuitive means for monitoring or configuring or later Allen-Bradley drives and communication adapters online and offline. Compatibility: Windows 98, ME, NT 4.0 (Service Pack 3 or later), 2000 and XP
(1) (2)
See www.ab.com/drives/driveexplorer.htm for supported devices. For pricing information, refer to the PowerFlex 4-Class Price List, Publication 22-PL001.
IP30/NEMA 1/UL Type 1 Field installed kit. Converts drive to IP30/ Kit NEMA 1/UL Type 1 enclosure. Includes conduit box with mounting screws and plastic top panel.
(1)
For pricing information, refer to the PowerFlex 4-Class Price List, Publication 22-PL001.
B-5
Product Dimensions
Table B.I PowerFlex 4 Panel Mount Drives Ratings are in kW and (HP)
Frame 120V AC 1-Phase
0.2 (0.25) 0.37(0.5) 0.75(1.0) 1.1 (1.5)
Figure B.1 PowerFlex 4 Panel Mount Drives Dimensions are in millimeters and (inches). Weights are in kilograms and (pounds).
a d c
g e b
5.5 (0.22)
Frame
A
(1) (2)
a
80 (3.15)
b(1)
185 (7.28)
c
136 (5.35)
d
67 (2.64)
e(2)
152 (5.98)
f
59.3 (2.33) 87.4 (3.44)
g
140 (5.51) 168 (6.61)
Shipping Weight
1.4 (3.1) 2.2 (4.9)
100 (3.94) 213 (8.39) 136 (5.35) 87 (3.43) 180 (7.09) Overall height of drive with IP 30/NEMA 1/UL Type 1 option kit installed. Overall height of standard IP 20/Open Type drive.
Figure B.2 IP 30/NEMA 1/UL Type 1 Option Kit Dimensions are in millimeters and (inches)
59.2 (2.33) 40.0 (1.57) 79.1 (3.11) 64.1 (2.52) 40.6 (1.60)
20.7 (0.81)
22.2 (0.87)
25.6 (1.01)
22.2 (0.87)
Frame A - 22-JBAA
Frame B - 22-JBAB
B-6
210 (8.27)
Frame B
244 (9.61) 94.3 (3.71) 63.1 (2.48)
214 (8.43)
250 (9.84)
B-7
97.5 (3.84)
16 (0.63)
49 (1.93)
8 (0.31)
Frame B
6.5 (0.26) 145 (5.71) 23.5 (0.93)
197 (7.76) 225 (8.86) 98.5 (3.88) 5.3 (0.21) 210 (8.27)
14 (0.55)
31 (1.22)
49 (1.93)
98 (3.86)
B-8
92 (3.62)
50 (1.97)
88 (3.46)
6 (0.24)
80 (3.15)
5.3 (0.21)
Frame B
112 (4.41) 125 (4.92) 80 (3.15) 88 (3.46) 9.5 (0.37)
100 (3.94)
5.3 (0.21)
B-9
Frame A
17.0 (0.67) 30.0 (1.18) 60.0 (2.36) 31.0 (1.22) 61.0 (2.40)
Frame B
59.0 (2.32)
US
316.0 (12.44)
ROCKWELL AUTOMATION
335.0 (13.19)
US
386.0 (15.20)
405.0 (15.94)
13.0 (0.51)
Frame A B
Power Off
Power On
ROCKWELL AUTOMATION
SURFACES MAY BE
B-10
c
b 104 (4.10) 104 (4.10) 104 (4.10) 104 (4.10) 104 (4.10) 127 (5.00) 127 (5.00) 127 (5.00) 127 (5.00) 133 (5.25) c 70 (2.75) 70 (2.75) 76 (3.00) 86 (3.38) 92 (3.62) 76 (3.00) 76 (3.00) 85 (3.35) 76 (3.00) 79 (3.10) d 50 (1.98) 50 (1.98) 50 (1.98) 60 (2.35) 66 (2.60) 53 (2.10) 53 (2.10) 63 (2.48) 53 (2.10) 54 (2.13) e 37 (1.44) 37 (1.44) 37 (1.44) 37 (1.44) 37 (1.44) 51 (2.00) 51 (2.00) 51 (2.00) 51 (2.00) 51 (2.00) Weight 1.8 (4) 1.8 (4) 1.8 (4) 2.3 (5) 2.7 (6) 3.1 (7) 3.6 (8) 4.9 (11) 4.1 (9) 4.1 (9)
Catalog Number 1321-3R2-A 1321-3R2-B 1321-3R4-B 1321-3R4-C 1321-3R4-D 1321-3R8-A 1321-3R8-B 1321-3R8-C 1321-3R12-A 1321-3R18-A
a 112 (4.40) 112 (4.40) 112 (4.40) 112 (4.40) 112 (4.40) 152 (6.00) 152 (6.00) 152 (6.00) 152 (6.00) 152 (6.00)
B-11
Figure B.9 Frame A EMC Line Filters Dimensions are in millimeters and (inches) Catalog Numbers: 22-RF5P7-AS, -AL; 22-RF9P5-AS, -AL; 22-RF010-AL
29.8 (1.17) 50 (1.97) 80 60 (3.15) (2.36)
208 (8.19)
17.8 (0.70)
24 (0.94)
5.5 (0.22)
Figure B.10 Frame B EMC Line Filters Dimensions are in millimeters and (inches) Catalog Numbers: 22-RF012-BS, -BL (Series B); 22-RF018-BS; 22-RF021-BS, -BL
29.8 (1.17) 50 (1.97) 100 78 (3.94) (3.07)
217 (8.54)
17.8 (0.70)
24.0 (0.94)
5.5 (0.22)
B-12
297 (11.69)
17 (0.67)
30 (1.18)
5.5 (0.22)
Important: The piggyback mounting option cannot be used with Frame B PowerFlex 4 drives and Frame C EMC Line Filters.
B-13
Figure B.12 Remote (Panel Mount) HIM Dimensions are in millimeters and (inches) Catalog Number: 22-HIM-C2
17.6 (0.69) 104 (4.09)
220 (8.66)
2.9m
78 (3.07) 66 (2.60)
194 (7.64)
B-14
180 (7.09)
2m
67 (2.64)
60 (2.36)
154 (6.06)
77 (3.03)
23.5 (0.93)
Important: The 22-HIM-C2S is smaller than the 22-HIM-C2 and cannot be used as a direct replacement.
B-15
25.2 (0.99)
180 (7.09)
2m
67 (2.64)
60 (2.36)
154 (6.06)
77 (3.03)
23.5 (0.93)
B-16
Notes:
Appendix C
Controller
For information regarding DeviceNet or other communication protocols, refer to the appropriate usr manual.
Network Wiring
Network wiring consists of a shielded 2-conductor cable that is daisy-chained from node to node.
Figure C.1 Network Wiring Diagram
Master TxRxD+ TxRxDPowerFlex 4 Node 1
120 ohm resistor
4 5
TxRxD+ TxRxDShield
PowerFlex 4 Node 2 4 5
TxRxD+ TxRxDShield
FRONT
X X X NOTE: The shield is connected at ONLY ONE end of each cable segment.
Shield
PIN 1 PIN 8
Only pins 4 and 5 on the RJ45 plug should be wired. The other pins on the PowerFlex 4 RJ45 socket contain power, etc. for other Rockwell Automation peripheral devices and must not be connected. Wiring terminations on the master controller will vary depending on the master controller used and TxRxD+ and TxRxD- are shown for illustration purposes only. Refer to the master controllers user manual for network terminations. Note that there is no standard for the + and - wires, and consequently Modbus device manufacturers interpret them differently. If you have problems with initially establishing communications, try swapping the two network wires at the master controller.
C-2
RS485 (DSI) Protocol Standard RS485 wiring practices apply. Termination resistors need to be applied at each end of the network cable. RS485 repeaters may need to be used for long cable runs, or if greater than 32 nodes are needed on the network. Control Terminal 16 on the PowerFlex 4 must also be connected to PE ground (there are two PE terminals on the drive). See Figure 1.5 for more information.
Parameter Configuration
The following PowerFlex 4 parameters are used to configure the drive to operate on a network.
Parameter P036 [Start Source] P038 [Speed Reference] A103 [Comm Data Rate] A104 [Comm Node Addr] Details Set to 5 RS485 (DSI) Port if Start is controlled from the network. Set to 5 RS485 (DSI) Port if the Speed Reference is controlled from the network. Sets the data rate for the RS485 (DSI) Port. All nodes on the network must be set to the same data rate. Sets the node address for the drive on the network. Each device on the network requires a unique node address. Reference Page 3-9 Page 3-11 Page 3-23 Page 3-23 Page 3-24
A105 [Comm Loss Action] Selects the drives response to communication problems. A106 [Comm Loss Time] A107 [Comm Format]
Sets the time that the drive will remain in Page 3-24 communication loss before the drive implements A105 [Comm Loss Action]. Sets the transmission mode, data bits, parity and stop Page 3-24 bits for the RS485 (DSI) Port. All nodes on the network must be set to the same setting.
Important: Modbus devices can be 0-based (registers are numbered starting at 0) or 1-based (registers are numbered starting at 1). Depending on the Modbus Master used, the register addresses listed on the following pages may need to be offset by +1. For example, Logic Command may be register address 8192 for some master devices (e.g. ProSoft 3150-MCM SLC Modbus scanner) and 8193 for others (e.g. PanelViews).
C-3
C-4
Description A xxx.x decimal value where the decimal point is fixed. For example, a decimal 123 equals 12.3 Hz and 300 equals 30.0 Hz.
Returns the same data as Reading (03) Parameter d001 [Output Freq].
C-5
Additional Information
Refer to http://www.ab.com/drives/ for additional information.
C-6
Notes:
Index
A
AC Supply Ground, 1-4 Source, 1-3 Ungrounded, 1-3 Advanced Program Group Parameters, 3-13 Ambient Temperatures, 1-2 Armored Cable, 1-8 Auto Rstrt Tries Fault, 4-4 Auxiliary Input Fault, 4-3 Distribution Systems, Ungrounded, 1-3 Drive Frame Size, P-2, B-5 Drive Grounding, 1-4 Drive Overload Fault, 4-4 Drive Ratings, P-4, A-1 DriveExecutive, 3-1 DriveExplorer, 3-1
E
Earthing, see Grounding EMC/RFI Grounding, Filter, 1-5 Interference, 1-20 Enclosure Rating, Changing, 1-2 ESD, Static Discharge, P-3
B
Before Applying Power, 2-1, 2-2 Bus Capacitors, Discharging, P-3
C
Cable Length, 1-12 Cable, Power, 1-8 Capacitors, Discharging, P-3 Catalog Number Explanation, P-4 CE Conformity, 1-20 Checklist, Start-Up, 2-1, 2-2 Circuit Breakers Input, 1-6 Comm Loss Fault, 4-4 Command Sources for Start and Speed, 1-18 Contactors, Input, 1-11 Control, 2 and 3 Wire, 1-14, 1-17 Conventions, Manual, P-2 Cover, Opening, 1-1 Cross Reference, Parameter by Name, 3-27
F
Faults Auto Rstrt Tries, 4-4 Auxiliary Input, 4-3 Comm Loss, 4-4 Drive Overload, 4-4 Ground Fault, 4-3 Heatsink OvrTmp, 4-3 HW OverCurrent, 4-3 I/O Board Fail, 4-4 Motor Overload, 4-3 Motor Stalled, 4-3 OverVoltage, 4-3 Parameter Checksum, 4-4 Phase Short, 4-4 Phase to Ground Short, 4-4 Power Loss, 4-3 Power Unit, 4-4 SW OverCurrent, 4-4 UnderVoltage, 4-3 Filter, RFI, 1-5 Frame Designations, P-2, A-1, B-5 Fuses Input, 1-6 Ratings, A-1
D
Dimensions Drive, B-5 Minimum Clearances, 1-2 Discharging Bus Capacitors, P-3 Display, 2-3 Display Group Parameters, 3-3
Index-2
G
General Precautions, P-3 Ground Fault, 4-3 Grounding Filter, 1-5 General, 1-4
P
Parameter Descriptions, 3-1 Types, 3-1 Viewing and Editing, 2-4 Parameter Checksum Fault, 4-4 Parameter Cross Reference by Name, 3-27 Parameters Advanced Program Group, 3-13 Display Group, 3-3 Program Group, 3-8 PE Ground, 1-5 Phase Short Fault, 4-4 Phase to Ground Fault, 4-4 Potentiometer, Wiring, 1-14 Power Cables/Wiring, 1-8 Power Conditioning, Input, 1-4 Power Loss Fault, 4-3 Power Unit Fault, 4-4 Powering Up the Drive, 2-1, 2-2 Precautions, General, P-3 Product Selection, B-1 Program Group Parameters, 3-8 Programming, 3-1 PTC Analog Input Wiring, 1-14
H
Heatsink OvrTmp Fault, 4-3 HW OverCurrent Fault, 4-3
I
I/O Wiring, 1-11 Wiring Examples, 1-14, 1-17 I/O Board Fail Fault, 4-4 Input Contactor, 1-11 Input Fusing, 1-6 Input Potentiometer, 1-14 Input Power Conditioning, 1-4 Installation, 1-1 Integral Keypad, 2-3 Interference, EMC/RFI, 1-20
K
Keypad, 2-3
L
LEDs, 2-3
R
Ratings, A-1 Reflective Wave Protection, 1-9 Removing Cover, 1-1 Repeated Start/Stop, 1-11 Repeated Start/Stop Precautions, 1-11 RFI, see EMC/RFI RWR (Reflective Wave Reducer), 1-9
M
Minimum Clearances, 1-2 Motor Cable Length, 1-9 Motor Overload Fault, 4-3 Motor Stalled Fault, 4-3 motor starter, 1-6 Mounting Options and Clearances, 1-2 MOVs, 1-3
S
Safety Ground, 1-5 Shielded Power Cables, 1-8 Short Circuit Protection, 1-6 Software, 3-1 Start and Speed Reference Selection and Control, 1-18, 1-19
O
Opening the Cover, 1-1 Operating Temperatures, 1-2 Operator Interface, 2-3 OverVoltage Fault, 4-3
Index-3 Start/Stop, Repeated, 1-11 Start-Up Checklist, 2-1, 2-2 Static Discharge, ESD, P-3 Status LEDs, 2-3 Supply Source, AC, 1-3 SW OverCurrent Fault, 4-4 System Grounding, 1-4
T
Terminal Block I/O, 1-12 Power, 1-10 Three Wire Control, 1-14, 1-17 Two Wire Control, 1-14, 1-17
U
UnderVoltage Fault, 4-3 Ungrounded Supply, 1-3 Unshielded Power Cables, 1-8
W
Watts Loss, A-4 Wiring, 1-1 Block Diagram, 1-13 I/O, 1-11 I/O Examples, 1-14, 1-17 Potentiometer, 1-14 Power, 1-8 PTC Example, 1-14
Index-4
www.rockwellautomation.com
Power, Control and Information Solutions Headquarters
Americas: Rockwell Automation, 1201 South Second Street, Milwaukee, WI 53204-2496 USA,Tel: (1) 414.382.2000, Fax: (1) 414.382.4444 Europe/Middle East/Africa: Rockwell Automation, Vorstlaan/Boulevard du Souverain 36, 1170 Brussels, Belgium,Tel: (32) 2 663 0600, Fax: (32) 2 663 0640 Asia Pacific: Rockwell Automation, Level 14, Core F, Cyberport 3, 100 Cyberport Road, Hong Kong,Tel: (852) 2887 4788, Fax: (852) 2508 1846