The document summarizes the results of calculations for various components of a refrigeration system. It provides the mass flow rates, enthalpy values, heat loads, capacities, and coefficients of performance for the evaporator, condenser, compressors, and expansion valves. It also lists the total cooling load of 19.7874 kW and recommends a refrigerating capacity of 23.7449 kW (6.7515 tons of refrigeration) for the system.

Uploaded by

EVA BUENAFE
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
34 views

Tablessss

The document summarizes the results of calculations for various components of a refrigeration system. It provides the mass flow rates, enthalpy values, heat loads, capacities, and coefficients of performance for the evaporator, condenser, compressors, and expansion valves. It also lists the total cooling load of 19.7874 kW and recommends a refrigerating capacity of 23.7449 kW (6.7515 tons of refrigeration) for the system.

Uploaded by

EVA BUENAFE
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 6

Evaporator

Calculation Results for Evaporator


Parameters Values Unit

Mass Flow Rate (ṁb) 0.1002846109 kg/s

Enthalpy Entering the 195.6352565 kJ/kg


Evaporator (h8)

Enthalpy Leaving the 1430.3 kJ/kg


Evaporator (h1)

Capacity 61.90893669 kW
Condenser

Calculation Results for Condenser

Parameters Values Unit

Mass Flow Rate (ṁa) 0.112894207 kg/s

Enthalpy Entering the Condenser (h4) 1713 kJ/kg

Enthalpy Leaving the Condenser (h5) 336.933 kJ/kg

Capacity 155.3499932 kW

Compressors

Calculation Results for Compressors 1


Parameters Values Unit

Mass Flow Rate (ṁb) 0.1002846109 kg/s

Enthalpy Entering the Compressor (h1) 1430.3 kJ/kg

Enthalpy Leaving the Compressor (h2) 1564 kJ/kg

Capacity 13.40805248 kW

Calculation Results for Compressors 2


Parameters Values Unit

Mass Flow Rate (ṁb) 0.1128942073 kg/s

Enthalpy Entering the Compressor (h9) 1552.459723 kJ/kg

Enthalpy Leaving the Compressor (h4) 1713 kJ/kg

Capacity 18.12406731 kW
Expansion Valve
Calculation Results for Expansion Valve 1
Parameters Values Unit
State Point 5 Pressure (Pressure h5) 11.343 bar
State Point 6 Pressure (Pressure h6) 4.15452 bar
Pressure Drop (Pressure Drop 1) 7.08848 bar

Calculation Results for Expansion Valve 2


Parameters Values Unit

State Point 7 Pressure (Pressure h7) 0.1002846109 bar

State Point 8 Pressure (Pressure 8) 195.6352565 bar

Pressure Drop (Pressure Drop 2) 2.53287 bar

Summary of Calculations for the Equipment


Parameters Values

Evaporator 61.90893669 kW

Condenser 155.3499932 kW

Compressor 1 13.40805248 kW

Compressor 2 18.12406731 kW

Expansion Valve 1 (Pressure Drop) 7.08848 bar

Expansion Valve 2 (Pressure Drop) 2.53287 bar

COP 3.926722156
SUMMARY OF HEAT LOAD CALCULATION

Type of Load Values Units

Total Transmission Load 5.6188 kW

Product Load 5 kW

Infiltration Load 7.02 kW

Human Occupancy Load 0.496 kW

Lightning Device Load 0.0027 kW

Equipment Load 1.65 kW

Internal Load 2.1487 kW

Total Cooling Load 19.7874 kW

Safety Factor 1.2

Refrigerating Capacity 23.7449 kW

Tons of Refrigeration 6.7515 TR


Refrigeration Cycle Calculation (Design Option 1)

Parameters Values Units

Mass Flow Rate 0.1401 Kg/s

h2 266.4912

Work Done by Compressor 2.3768 kW

Heat Rejected by Condenser 26.1217 kW

Refrigerating Effect 23.7449 kW

Coefficient of Performance 9.9905

Refrigeration Cycle Calculation (Design Option 2)

Parameters Values Units

Mass Flow Rate (m1) 0.1401 kg/s

Mass Flow Rate (m3) 0.1881 kg/s

Work Done by Compressor 2.0241 kW


(Wc1)

Work Done by Compressor 8.9535 kW

(Wc2)

QA 23.7449 kW

QR 34.7224 kW

Coefficient of Performance 2.1630

QA = 23.7449
QR = 34.7224

WCT = 10.9776

Refrigeration Cycle Calculation (Design Option 3)

Parameters Values Units

Enthalpy 249.53 kJ/kg

Mass Flow Rate 0.3003 kg/s

h1 250.0955 kJ/kg

h2 266.4912 kJ/kg

Work Done by Compressor 4.9232 kW

Heat Rejected by Condenser 52.4130 kW

Refrigerating Effect 23.7449 kW

Coefficient of Performance 4.8231