Wheelock Sp40s Safepath Install Sheet P84714
Wheelock Sp40s Safepath Install Sheet P84714
Multi-Function Facility
Communication System
Installation, Testing,
Operation and
Maintenance Manual
1. Forward 13
1.1 Intended use .................................................................................................... 13
1.2 Design Change Disclaimer ............................................................................. 13
1.3 User Operation Assistance.............................................................................. 13
1.4 Product Model Descriptions ........................................................................... 13
1.5 Typographical Notation Conventions ............................................................. 13
2. Safety Precautions 15
2.1 Read This Manual........................................................................................... 15
2.2 Operational Safety .......................................................................................... 15
2.2.1 Expected Equipment Lifecycle ............................................................ 16
2.2.2 Periodic Testing ................................................................................... 16
2.3 Compliance with Applicable Codes, Regulations, Laws, Standards, and
Guidelines ...................................................................................................... 16
2.4 Insurance Recommendation ........................................................................... 17
2.5 Audio Output Considerations ......................................................................... 17
2.6 RF Interference ............................................................................................... 18
2.7 General ........................................................................................................... 18
3. Overview 19
3.1 Compatibility with Existing Safepath Products.............................................. 19
3.2 Standard Features ........................................................................................... 19
3.3 Enclosure and Configuration .......................................................................... 21
3.4 Nominal Electrical Data ................................................................................. 21
3.5 User Interface ................................................................................................. 22
3.5.1 Basic Operation of User Interface ........................................................ 23
3.5.2 Overview .............................................................................................. 23
3.6 Additional Drawings....................................................................................... 25
3.7 User Settings ................................................................................................... 30
3.7.1 Switch Descriptions ............................................................................. 30
3.7.2 Jumper Descriptions............................................................................. 32
3.8 LED Descriptions ........................................................................................... 33
4. Installation 34
4.1 Introduction .................................................................................................... 34
4.2 Fire Alarm Control Panel Wiring Applications .............................................. 34
4.3 General Installation Instructions ..................................................................... 35
4.4 Preparing the System Wiring Diagram ........................................................... 38
4.4.1 Unpacking and Taking Inventory......................................................... 38
4.4.2 Locating the Panel................................................................................ 38
4.4.3 Installing Field Wiring Connections .................................................... 40
4.4.4 Installing Strobe Connections .............................................................. 41
4.4.5 Installing Audio Output Connections................................................... 42
4.4.6 Installing Auxiliary Circuit Connections ............................................. 43
1. Forward
1.1 Intended use
This manual is designed to serve the installers and operators of the SP40S Multi-Function
Facility Communication System. All operating instructions, product illustrations,
troubleshooting/error messages, and other relevant information are contained in this
manual. It is the user’s responsibility to ensure that all instructions in this manual are
applied strictly.
application, operation, installation, and testing is used at the sole risk of the user
and Cooper Notification will not have any liability for such use.
Certain information contained in this manual has been extracted from the NFPA 72
Manual and the Life Safety Code 101™ Manual.
2. Safety Precautions
2.1 Read This Manual
1. Cooper Notification recommends that, before performing any actions to specify,
apply, install, maintain, and operationally test the SP40S Multi-Function Facility
Communication System, personnel properly qualified in the application and use of
life safety equipment read this manual carefully.
2. Keep this manual with the SP40S Multi-Function Facility Communication System
for reference during the life of the product. Make this manual available to all
qualified personnel who operate, test, maintain, or service the SP40S Multi-Function
Facility Communication System. It is strongly recommend that such personnel read
and understand the entire manual.
NOTE: In areas prone to lighting strikes, using a surge protection device is recommended.
NOTE: This SP40S Multi-Function Facility Communication System will not work without
power. The SP40S Multi-Function Facility Communication System is powered by 120 or 240
VAC, depending on model. 24VDC re-chargeable batteries provide backup power, should
be purchased separately. If both sources of power are cut off for any reason, the SP40S
Multi-Function Facility Communication System will not operate.
1. DO NOT assume any installation, operation, and testing details not shown in this
manual.
It is recommended that the local Authority Having Jurisdiction (AHJ) inspect and approve
the proposed placement of all the notification appliances.
CAUTION: The output of the audio system may not be heard in all cases. Sound can be
blocked or reduced by walls, doors, carpeting, wall coverings, furniture, insulation, bed
coverings, and other obstacles that may temporarily or permanently impede the output
of the audio system. Sound is also reduced by distance and masked by background noise.
The output of the audio system may not be sufficient to alert all occupants, especially
those who are asleep, those who are hearing-impaired, those who are wearing devices
that plug or cover the ears, and those who have recently used drugs or alcohol.
The output of the audio system may not be heard by an alert person if the output device
is placed in an area which is isolated by a closed door, or is located on a different floor
from the person in a hazardous situation or is placed too far away to be heard over
ambient noise such as, but not limited to, running water, traffic, air conditioners,
machinery or musical appliances.
If live microphone announcements, audible tones and/or voice messages cannot be
readily heard and understood clearly within the protected areas as intended, increase
the number and/or sound output intensity of speakers within those areas so that they are
heard and understood clearly when activated.
2.6 RF Interference
The SP40S Multi-Function Facility Communication System has been tested and found to
comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules.
These limits are designed to provide reasonable protection against harmful interference
when the equipment is operated in a commercial environment. This equipment generates,
uses, and can radiate radio frequency energy and, if not installed and used in accordance
with the instruction manual, may cause harmful interference to radio communications.
Operation of this equipment in a residential area is likely to cause harmful interference, in
which case the user is required to correct the interference at their own expense.
2.7 General
Each manufacturer's panel and notification appliances operate differently and have different
features. Before specifying, installing, operating, testing, maintaining, or servicing a
system, carefully read the installation, operation, and testing manual for each piece of
equipment and applicable codes.
Additional copies of this manual may be obtained from:
Cooper Notification
273 Branchport Ave.
Long Branch, N.J. 07740
Tel: (800) 631-2148
Fax: (732) 222- 2588
E-mail: [email protected]
3. Overview
The SP40S Multi-Function Facility Communication System is capable of supplying the
following:
• 40 Watts of audio power
• 2 Amps of strobe power
• There is an additional 0.5 Amps of auxiliary power at 28 Volts that can be used to power
other Safepath Products.
The SP40S Multi-Function Facility Communication System is used for Alarm and Non
Alarm Announcements.
The SP40S-D and SP40SE-D models do not have the option of carbon monoxide (CO)
annunciation. If you have either of these models, ignore any reference to that option.
Feature Description
Audio NAC circuit wiring -- open and short conditions during standby
AND active (Alarm and BGM) Ground Fault detection
Strobe NAC circuit wiring -- open and short conditions
Full supervision with on-board PTT Microphone -- not installed or damaged
diagnostics and trouble reporting Amplifier -- operation
circuits for: Digital Voice Section
Input voltage/low battery
Tone generator operation
Feature Description
MOTHERBOARD
AC Wiring
(NON-POWER* Wiring to Battery
(NON-POWER
LIMITED) LIMITED)
Message 1
Message 2
Message 3
Message 4
Message 5
Message 6
Message 7
Message 8
Message 1 - 8 (there are 8 messages, 1 through 8) Button manually actives Messages 1- 8. Illuminated
steady means contact closure is on a DV input.
Illuminated blinking means DV is activated via button
push.
ALARM ACTIVE indicator Indicates PTT MIC (push to talk microphone), AUX
(auxiliary), or DV (digital voice) has been initiated.
STROBE ACTIVE indicator Indicates the strobe circuit has been initiated.
RECORD button and indicator For message recording process, see section 6.3.
3.5.2 Overview
This section describes the behavior differences of digital voice messages between SP40S
firmware and SP40S-D firmware. The SP40S-D firmware changes are limited to the user
interface section of the SP40S panel (refer to Figure 1). All other behaviors of the SP40S,
such as strobe activation, message prioritization, and AUX input functionality have not
changed.
3.5.2.1 Operation of Digital Voice Messages with SP40S firmware
Digital voice (DV) messages on the SP40S are activated locally via the front panel interface
pushbuttons (PB) or remotely using contact closures (CC) with the SP40S firmware. An
activated DV message will remain active indefinitely until you clear the source of activation.
Activation of a particular DV message appears locally at the front panel interface by LEDs
located on each DV message PB. For the SP40S firmware, a flashing LED indicates that the
PB activated a message, and a solid LED indicates that a CC activated a message.
3.5.2.2 Operation of the Digital Voice Messages with the SP40S-D firmware
Each PB and CC for DV messages 1 through 6 are individual inputs each having their own
10-minute timer. If one of the inputs goes active its associated timer starts, the associated
message starts playing, and if the input does not restore, the input’s timer will time out and
the message will stop playing. The input must restore before it can go active again,
triggering the message to play.
Example 1: CC1 goes active, its timer starts and message1 starts playing. If CC1 does not
restore, the timer will expire and the message will stop playing in 10 minutes. Once CC1
times out, CC1 cannot trigger message1 to play again until CC1 restores. You can,
however, press PB1 and message1 will start playing again and will continue for 10 minutes
if PB1 remains active. If PB1’s timer is allowed to time out also, message one cannot be
triggered by anything now since both of its associated inputs are still in “Timeout” mode.
One or both must restore and re-activate for message1 to start playing again.
Example 2: CC1 goes active, its timer starts and message1 starts playing. 8 minutes into
the timer PB1 goes active which start PB1’s timer and message1 continues to play for
another 10 minutes. This makes the total play time 18 minutes in this example if neither
CC1 nor PB1 restores and re-activates. It is possible that lower priority messages may not
be heard at all because of a higher priority message’s inputs being restored and re-activated
while the lower priority input times out.
DV message 7 and 8’s inputs (PB & CC) do not have a timer associated with them and will
continue to play message 7 or 8 until the input restores or a higher priority input goes active.
Example 3: PB7 activates which starts message7 playing. This message will continue
playing as long as PB7 remains active. CC1 goes active, its timer starts, CC1 is a higher
priority message, so message1 is heard instead of message7 now. CC1 remains active
through the 10 minute timer and the timer times out shutting off message1. Message7 starts
playing again at this time because PB7 is still active.
The addition of the timeout functionality in the SP40S-D firmware causes the user interface
on the SP40S to indicate that a particular DV input is in timeout.
Table 3 SP40S(E)-D User interface Pushbuttons/Indicators
LED Indicator Function DV Description
Message LED
STEADY OFF Both the PB and CC input for the DV message are INACTIVE.
STEADY ON The DV message input is ACTIVE as a result of either PB or CC activation.
ONE BLINK The CC input for the DV message is in the TIMEOUT state and the PB input is
INACTIVE. Deactivating the CC input will cause the LED to turn off as both
inputs become INACTIVE.
TWO BLINKS The PB input for the DV message is in the TIMEOUT state and the CC input is
INACTIVE. Deactivating the PB input will cause the LED to turn off as both
inputs become INACTIVE.
THREE BLINKS Both the CC input and the PB input for the DV channel are in the TIMEOUT
state.
JP3
2 Wire/4 Wire Mode
(For connection
to Audio Boosters)
JP5 DV J4 AUX IN
Record Select
J6 User
J5 FACP Interface
Display
(for future use)
Interface
Connection
SW3 Strobe
Activation SW4
Tone Types
SW6
NAC/Contact
Closure Select
SW7 DV IN
Supervision
SW5 Pretone/ and Auxiliary
Postone Enable Timeout
SW9 Sync/
Nonsync
Strobe
Settings
D4 MIC
PTT MIC Missing
D1 Audio Circuit or Inoperable
Open
D3 DV
Digital D5 AMP
Amplifier Section D6 SPB
D2 Audio Circuit Voice Section Supervision Open
Trouble
Short
D8 Batteries
Missing or Low
D29
(Red) Audio
Peak/Overload
D44 AUX IN,
CC Open,
RMX or
Remote MIC
Trouble
D47 Interface
Trouble
D55 - DV1 - IN1 OPEN
D62 - DV2 - IN2 OPEN
R40 Telephone
Page Volume
Control
R92 Background
Music Volume
Control
R93 Tone
Control Treble
R73 Digital
Voice Volume
Control R94 Tone
Control Bass
R81 Digital
Voice Tone R100 AUX IN
Volume Control Volume
Control
SW9
PIN FUNCTION ON
Standard Sync
1 Sync mode (NAC input)
(OFF = PASS THRU SYNC MODE)
2 Sync mode (Alarm) Standard Sync (OFF = 28 volts)
3 unused --
4. Installation
4.1 Introduction
Remember, the lives of people depend upon the safe and proper installation of the voice
evacuation system and the SP40S Multi-Function Facility Communication System. Please
read, understand, and follow the specific installation instructions set forth in this chapter
carefully to avoid damage to the panel and equipment connected to it. Ensure that only
qualified personnel in accordance with the procedures in this manual conduct the
installation.
CAUTION: The SP40S printed circuit board is sensitive to static electricity and has
delicate components mounted on it. Before handling the board or any component on it,
discharge any static electricity from your body by touching a grounded object such as a
metal screw, which is connected to earth ground. Install the panel in a static-free area;
properly attach grounded wrist straps before touching any static-sensitive areas.
• If you or the installer have any questions about the installation, consult with the
authorities having jurisdiction (AHJ), prior to installation.
The SP40S Digital Voice Section inputs require Contact Closures to initiate. The Fire
Alarm Control Panel (FACP) supplies these dry Contact Closures.
NOTE: Do not connect a NAC or DC voltage directly to the Digital Voice Inputs. A relay
is required.
The SP40S strobe input requires 8-33VDC to initiate. The FACP NAC Circuit of 12VDC or
24VDC initiates this circuit.
TROUBLE Form C relay terminals and an internal sounder are available for monitoring the
condition of the SP40S Multi-Function Facility Communication System.
Section 2
Section 1 System Trouble Connections
Alarm Connections Section 3
AC Trouble
Connections
Section 4
Audio Output
Connections
Section 5
Night Ring, Telephone
Page, Background
Music Connections
Section 6
Auxilary Input
and 24VDC
Output
Connections
Sections 7 and 8
Internal Digital Voice
Connections
Section 9 Section 11
Section 10 Strobe Connections
Primary Power Secondary Power
(120VAC) Connections (Battery) Connections
NC Normally closed Alarm Relay contact closed to Common (COM) in non-alarm condition.
Terminal
Symbol Alarm Connections Definitions
Block
Audio Output Connections
Audio Output for 25V or 70V speakers. Supervised using UL Listed 10K
AUD Ohm, ½ W EOLR. Power Limited.
Audio Output
OUT
TB4 25V setting = Class 2; 70V setting = Class 3
Terminal
24V 24 VDC, 0.5A Continuous Output Connection, Power Limited auxiliary
Block 4 24 VDC, 0.5A Output
OUT power source. NOTE: Two 24V outputs combine for 0.5A.
Section 4
Contact Closure indicates a primary power loss on the audio booster.
SPB SAFEBAPTH4 Booster Input is supervised using 10k Ohm EOLR. Used only when AC loss is
SUP Supervision reported separately from system trouble. Active only when SW2
Position 3 is ON.
Night Ringer, Telephone Page, Background Connections
Contact Closure Input initiates chime sound for Night Ring. Non-
NR Night Ring supervised. Night Ring does not operate without VAC input and the Panel
TB5 is operating on Battery.
Terminal
Telephone Page Input from a telephone Page Port. Non-Supervised.
Block 5
TEL Telephone Page Input Telephone Page does not operate without VAC input and the Panel is
Section 5
operating on Battery.
BGM Background Music Input Line Level, 600 Ohm Background Music Input. Automatically mutes when
any other input is in use. Non-Supervised. Background Music input does
not operate without VAC input and the panel is operating on Battery
Auxiliary Input and 24VDC Output Connections (For Connection To SPRM or SP4-RMX)
AUX Auxiliary Input Audio Line Level Audio Input, Remote MIC, or SP4-RMX Priority 2.
TB6
Terminal Contact closure or NAC will initiate AUX IN Audio. CC is supervised.
CC/NAC Contact Closure/NAC
Block 6 Connects to RMX or Remote MIC (CC Mode).
Section 6,
Regulated, 24 VDC, 0.5A Continuous Output Connection, Power Limited
24V Out 24VDC, 0.5A output auxiliary power source. NOTE: Two 24V outputs combine for 0.5A.
Connects to RMX or Remote MIC.
Terminal
Symbol Alarm Connections Definitions
Block
Internal Digital Voice Module Input Connections
Digital Voice Initiating connection for message #1 (contact closure).
IN 1 Input 1
Priority 3.
TB7
Digital Voice Initiating connection for message #2 (contact closure).
Terminal IN 2 Input 2
Priority 4.
Block 7
Section 7 Digital Voice Initiating connection for message #3 (contact closure).
IN 3 Input 3
Priority 5.
Digital Voice Initiating connection for message #4 (contact closure).
IN 4 Input 4
Priority 6.
TB12 STB 8-33 VDC, Regulated, 2A Maximum Strobe NAC Output Supervised with
Strobe Output
Terminal OUT UL Listed 10k Ohm, ½ W EOLR. (Power limited).
Block 12
Section Strobe Input Return for connecting additional strobe circuits, or UL Listed
RET Return
11 10k Ohm, ½ W EOLR.
STB IN Strobe Input 8-33 VDC, Strobe NAC Input. Triggers strobe in Alarm condition.
NOTE: All Outputs (Strobe Output, Audio Output, and 24VDC Auxiliary Power Source) are
power limited circuits.
CAUTION: To comply with the latest NFPA and UL requirements for interconnection of
fire alarm control equipment, locate the SP40S Multi-Function Facility Communication
System in the same room, and within 20 feet of, a listed compatible fire alarm control panel.
Enclose the wiring in conduit and connect it properly to such control panel.
Grounding
Points
17.00"
Ground
CAUTION: Use care when punching out knock-outs to avoid damage to internal
components.
NOTE: For power limited circuits, make sure that all input power sources (Alarm and
Trouble relay connections, NAC inputs, and auxiliary inputs) are power limited.
NOTE: The AC Power input wiring is non-power limited. Route it on the left side of the
enclosure, using one of the knockouts on the left side of the enclosure. Route all power
limited inputs and outputs on the right side and top of the enclosure.
Install field wiring in conduit when required, following the most current National Electrical
Code (NFPA-70) and local codes for the type of system being installed. Make all necessary
connections at any additional wiring or junction boxes.
CAUTION: Provide proper strain relief for all wiring not in conduit.
NOTE: Shielded wire is not required on any output circuits. If shielded wire is used, connect the
shields to the grounding points as shown in Figure 11.
Section 11
Strobe Connections
be activated during an AUX activation, turn ON SW3-position 10. (3) If the strobe output is
to be activated when one or all the digital voice messages are initiated, operate DIP switch
SW9 as explained in Section 3.7.1. (4) The fourth way is to connect a NAC circuit input from
an FACP to STB IN as described below.
2. Connect Strobe Circuit input (8 to 33VDC) from the FACP or other UL Listed
control panels to the Strobe Input circuit (STB IN) connection on TB11. Observe
correct polarity. The maximum line impedance of the strobe circuits is 40 ohms.
3. Connect the FACP EOLR, additional appliances or additional SP40S panels to RET
connection on TB11.
• The Digital Voice Initiating Connections (IN1, IN2, IN3, IN4, IN5, IN6, IN7, and
IN8) can also initiate the strobe output circuit. Strobes can be initiated by the MIC,
AUX, IN1, IN2, IN3, IN4, IN5, IN6, IN7, and IN8.
• Positions 1, 2, 3, 4, 5, 6, 7, and 8 of SW3 control the strobe initiation for inputs IN1,
IN2, IN3, IN4, IN5, IN6, IN7, and IN8, respectively. If positioned in the ON or UP
position, the strobes operate during message playback.
• Position 9 of SW3 in the ON position initiates the strobe circuit during a PTT MIC
live announcement.
• Position 10 of SW3 in the ON position initiates the strobe circuit during an AUX
activation.
• Position 2 (ON) of SW9 selects the Cooper Notification Sync Mode during an alarm
strobe activation.
Section 4
Audio Output
Connections
2. Select the proper output voltage (25V or 70V) using the Audio Output Select Jumper
J1.
Sections 7 and 8
Internal Digital Voice
Connections
• While observing correct polarity, connect the Digital Voice Initiating connections
(IN1, IN2, IN3, IN4, IN5, IN6, IN7, IN8) to the connections on TB7 or TB8 as
desired. See Figure 10 for TB7 and TB8’s locations. Figure 15 is an enlarged picture
of the referred area.
The Telephone Page input requires input from a Telephone Page Port. The Night Ring input
requires a dry contact closure. The Background Music input requires a line level, 600 Ohm,
1Vrms signal.
1. Connect Telephone Page Input (TEL) to TB5. See Figure 10 for TB5’s location.
Figure 16 is an enlarged picture of the referred area.
2. Connect Night Ring Input (NR) to TB5.
Section 5
Night Ring, Telephone
Page, Background
Music Connections
NOTE: The Night Ring (NR) input requires a contact closure from the phone system to
activate. The NR must be connected to the phone line in the same room.
NOTE: When installed in New York City, the background music feature and telephone
paging features are not permissible.
NOTE: Use a good multi-meter that provides true RMS readings in the AC voltage scale
and calculates the results through average sampling. Some multi-meters can select instant
or average sampling readings. Always do this adjustment in the “averaging” mode. Most
digital multi-meters use the average sampling method in the “AC Volts RMS” setting.
CAUTION: Do not connect input voltage to any equipment until the field wiring
has been tested, inspected and approved.
4. Check the integrity of all field wiring. Confirm that the specified cable is installed,
and that there is continuity between required points (no open circuits), with no
unwanted shorts to other conductors, chassis, or earth ground.
a) Verify that the field wiring complies with the instructions of this manual and
the detailed wiring diagram prepared for this installation.
b) Ensure that no unwanted voltages are present on circuit conductors and
ground.
c) Test all ungrounded connectors for electrical isolation from ground.
d) Measure and record the resistance of each NAC circuit. Conduct this test
reversing polarity.
5. Perform Ground Fault Installation procedure as described in Section 4.7.
6. Calculate and install properly sized backup batteries as described in Section 4.8.3.
The SP40S panel is UL approved for 24VDC for a maximum of 33 Ah. Batteries
greater than 12 Amp-Hour (Ah) are required to be installed in a UL listed battery
box. The enclosure can accommodate up to 12 Ah.
CAUTION: The National Electric Code limits the maximum number of conductors that
can be installed in conduit and wiring boxes depending on the size of the conduit, the
volume of the boxes, and the gauge of the wire used. Make sure that wiring used for
SP40S installation complies with the latest NEC, NFPA, Local, State, County, or
Province requirements. wiring has been tested, inspected and approved.
CAUTION: Do not loop wire under terminals. Break wire run to provide supervision
of the connection.
CAUTION: Do not loop wire under terminals. Break wire run to provide supervision
of the connection.
CAUTION: Do not loop wire under terminals. Break wire run to provide supervision
of the connection.
Section 1
Alarm Connections
Section 2
System Trouble Connections
5. If applicable, connect the strobe circuit to TB12 STB OUT. Verify that the strobe
circuit has a UL Listed 10K Ohm, ½ W EOLR.
6. If Strobe synchronization is to be defeated, turn OFF positions 1 and 2 of SW9
Strobe Synchronization Defeat.
NOTE: All terminal blocks, jumpers, switches, LEDs, Fuses, and Potentiometers are
illustrated in Figure 4 thru Figure 8.
• Connect the interface ribbon cable to J6.
• Connect AC power, then connect the batteries.
When the AC power source is applied to the panel, the battery voltage check circuitry
is activated. If batteries are not connected within 20 seconds, the panel trouble circuit
activates. The battery voltage check circuitry re-checks for batteries every two
minutes. If the batteries are installed during the two-minute period, the panel remains
in trouble mode until the next re-check.
• D100 PWR LED and POWER ON (Interface) LED should be “ON” to indicate
normal operation.
• If SYSTEM TROUBLE (Interface) LED (Yellow) is “ON,” and the internal sounder
is operating, a trouble condition is indicated.
• In such a case, STOP TESTING. Refer to Chapter 8 of this manual, then
troubleshoot and correct the problem before you resume testing. See Figure 7 for
location of LEDs.
• Perform the following tests:
4.6.2.1 A Microphone Test
1. Press the push-to-talk Button on the microphone and speak into the microphone.
2. Ensure your voice can be heard on the output speaker circuit.
4.6.2.2 B Auxiliary Test
1. If a Remote MIC or RMX is being used, initiate a Remote MIC and speak into the
microphone.
2. Ensure your voice can be heard on the output speaker circuit.
4.6.2.3 C Digital Voice Message Test
Message 1
1. Press the top message button. The message should be heard on output speaker
circuit. The top message button/LED on the interface should blink to indicate the
button has been pressed.
2. Test the strobe circuit associated with the first message by switching DIP switch
SW3 (DV/Strobe Select), position 1 “ON.” The STB LED on the interface (Red)
turns “ON.” If the strobe circuit is attached to TB11, strobes flash.
3. Turn OFF message 1 by pressing the top message button again or removing contact
closure from IN1. The message plays to completion at least three times. If DIP
switch SW2 (DV/Strobe Select) position 1 is ON, the strobe circuit is ON until the
message is complete.
4. Turn DIP switch SW3, position 1 OFF.
5. Apply contact closure activation to TB7 (IN1) connection (Figure 15). The message
should be heard from output speaker circuit. The top message button/LED on the
interface should illuminate steadily to indicate contact closure is present.
6. Test the strobe circuit associated with the first message switching DIP switch SW3
(DV/Strobe Select), position 1 “ON.” The STB LED (Red) turns “ON.” If the strobe
circuit is attached to TB2, strobes flash.
7. Remove the contact closure from TB7 (IN1). The message plays to completion at
least three times. If DIP switch SW3 (DV/Strobe Select) position 1 is “ON,” the
strobe circuit is ON until the message is complete. The top message button/LED on
the interface should turn OFF once the contact closure is removed.
8. Turn DIP switch SW3, position 1 OFF.
9. Perform Steps 3 through 10 on Messages 2 and 3. Use Table 5.
Table 5 Digital Voice Message Tests
Message SW3 DV/Strobe
TB4 Interface Button
Number Select
Use Guidelines
• Avoid installation and/or operation in close proximity to heat sources. While the
operating temperature range is 0 to 49 degrees C (32-120 degrees F), battery life is
maximized at an ambient temperature of 20 degrees C (68 degrees F).
• Batteries may generate ignitable gases. Because of this, install batteries in a well-
ventilated location, away from spark producing equipment.
• DO NOT install batteries in an atmosphere where organic solvents or adhesives may
be present. DO NOT clean the batteries with oils, thinners, or similar substances.
The case and cover of the batteries are ABS plastic resin, which may suffer damage
from these chemicals.
• DO NOT install batteries in a heavy vibration or shock location.
• ALWAYS wear insulated gloves when handling batteries.
• DO NOT use together batteries of different capacities, age, or manufacture.
WARNING: DO NOT CRUSH, INCINERATE, OR DISMANTLE BATTERIES. THE
ELECTROLYTE CONTAINS SULFURIC ACID, WHICH CAN CAUSE SERIOUS
DAMAGE TO EYES AND SKIN. IF CONTACT DOES OCCUR, FLUSH WITH
WATER AND SEEK IMMEDIATE MEDICAL ATTENTION.
2. Calculate speaker output current by totaling all the speaker wattage settings.
Multiply the sum by 0.054. The result is the current draw in Amps.
3. Add the strobe current, the speaker current, and auxiliary current together. The result
is the total Alarm Current in Amps.
4. Alarm circuits are required to operate for 15 minutes on battery power. Multiply Step
3 by 0.25 hrs. The result is the total Alarm Capacity Required in Amp-Hours.
4.8.3.3 Battery Calculations
Good engineering practices recommend the total Amp-hours required for backup should not
exceed 90% of the Backup Battery capacity. The SP40S Multi-Function Facility
Communication System has been UL approved for a maximum of 33 Ah batteries. The
enclosure can accommodate up to 12 Ah. Batteries greater than 12 Amp-Hours (Ah) are
required to be installed in a UL listed battery box.
1. Add the total Standby Capacity Required to the total Alarm Capacity Required.
2. Multiply Step 1 by 1.25. This is the minimum Backup Battery requirement for this
panel.
3. Record results on worksheet.
CAUTION: Always apply AC voltage before applying battery backup voltage. Failure
to do so may cause damage to the SP40S Multi-Function Facility Communication
System.
AC Field Wiring
(non-power limited)
LINE, GROUND
and NEUTRAL
To Negative To Positive
(-) of battery (+) of battery
terminal terminal
(Black) (Red)
CAUTION: Always install the two batteries with the battery terminals pointing to the
center and in the upright position as shown in Figure 24. Failure to do so may cause a
short circuit which may damage the SP40S panel or batteries and cause the panel to fail
to operate in an emergency condition.
Short Jumper
(Supplied)
+
-
-
+
To Negative (-)
of Battery
Terminal (TB10)
on bottom of
motherboard
To Positive (+)
of Battery
Terminal (TB10)
on bottom of
motherboard
Figure 24 Battery Alignment and Jumper Connection
4. Connect the short jumper (included) to the back terminals (negative to positive) of
the two batteries as shown in Figure 24. This connects the 12VDC batteries in series
in order to produce 24VDC.
5. Place the batteries in the battery compartment with the battery terminals and jumper
facing “UP” or toward the top of the SP40S panel. Make sure that the red and black
battery jumpers are clear of the batteries.
6. Attach the red and black battery wires (red to (+), black to (–)) to the proper battery
terminals.
5. Operation
5.1 Introduction
This chapter describes the operating characteristics of the SP40S Multi-Function Facility
Communication System. Included is information about the following panel features:
• Supervision
• Audio Notification Appliance Output Circuit Supervision
• Amplifier Supervision
• Actions that Initiate Alarms
5.3 Supervision
A SYSTEM TROUBLE LED indicates that the supervisory functions have detected a
malfunction in the panel. When a trouble condition is detected, the panel may not be able to
receive and/or broadcast messages from the control panel.
If a trouble condition is detected by any of the supervisory functions, the internal sounder
operates the panel Form C TROUBLE relay (normally energized), changes state, and the
yellow SYSTEM TROUBLE LED turns “ON.” The Trouble Status Relay (TB2) must be
properly connected to and used by the control panel to indicate a system trouble. At the
same time, one of the yellow trouble location LEDs identifies the location of the trouble
condition. The internal sounder can be silenced for 20 hours by depressing the “Trouble
Acknowledge” Switch (SW1, on the User Interface). Any subsequent troubles cause the
sounder to be re-activated. If a trouble condition is indicated, follow the procedures in
Chapter 8 "Troubleshooting.”
An AC Loss can be selected to be reported as a system trouble after 170 minutes (SW2-
Position 2 = ON). This is desirable for off-premise trouble reporting. If SW2-Position 2 is
OFF, AC Loss is reported as a system trouble after 30 seconds.
6. Operating Procedures
6.1 Making Live Announcements
1. Hold the on board or remote microphone within 2 inches from your mouth, press the
Push-To-Talk (PTT) switch and begin speaking. (For best results, hold the
microphone within a half inch from your mouth.)
2. When finished, release the PTT switch and return the microphone to its holder.
NOTE: If the on-board microphone push-to-talk button is depressed and remains depressed
for two and a half minutes, the microphone circuit switches automatically to the selected
supervision tone.
6.3 NOTE: If the Digital Voice Section fails, the SP40S panel plays the
selected tone (Code 3 Tone or Slow Whoop). See Figure 6 for the location of
SW3-position 9. Recording Messages on the Digital Voice Section
CAUTION: Recording of any new message permanently erases the previous message.
If a Cooper Notification factory prerecorded fire or emergency message or a tailored
message is accidentally or intentionally erased, a new factory recorded message kit
must be purchased to restore the message.
1. Remove the DV Record Jumper JP5 (see Figure 5). Place jumper in a secure place;
this is replaced at the end of the recording procedure.
2. Connect 1/8” line level audio to audio jack (J2) on the left side of the SP40S unit.
3. Press and hold the RECORD button on the user interface.
4. Determine which one of the eight messages you wish to record.
5. Press the message button on the interface corresponding to the message you wish to
record. The Record LED illuminates and recording begins. You may release the
record button at this point.
6. When the message concludes, press the illuminated message button again. Recording
then stops.
7. Check the recorded message by pressing the proper DV message button. The
message plays in its entirety at least three times.
8. For additional message recording, repeat steps 2 through 7.
9. When recording is done, replace DV Record Jumper (JP5).
Message 1
Message 2
Message 3
Message 4
Message 5
Message 6
Message 7
Message 8
1. Press the button of the desired DV message. The message will begin playback and
the corresponding DV message LED will blink (LED will be steady with model
SP40S(E)-D).
2. Press the blinking button again to deactivate the DV message. The message plays in
its entirety a minimum of three times.
7.2.2 Equipment
The following equipment needs to be tested to ensure that equipment is operating properly:
• SP40S Multi-Function Facility Communication System
• All notification appliances
8. Troubleshooting
8.1 Introduction
CAUTION: Make sure that only qualified personnel in accordance with the procedures
in this manual conduct troubleshooting and servicing. Do not attempt to make other
adjustments, modifications, or repairs. Never use water, steam, cleaning liquids or
sprays on the panel.
8.2 General
The SP40S Multi-Function Facility Communication System monitors system integrity.
Items monitored for integrity are:
• Visual appliance circuit field wiring
• Audio appliance circuit field wiring
• Input voltage
• Battery voltage level
• Battery circuit field wiring
• Amplifier functionality
• Digital Voice Section functionality
• Battery charge voltage
• Tone generators
• Audio chain
System status is indicated to the visual indicators on the user interface, the internal Trouble
Sounder, and the Trouble and AC Trouble Form "C" relay contacts. If the AC (primary
power) is removed or low, the trouble the panel responds as follows:
• Turns "ON" the AC Trouble LED indicator on the user interface.
• Turns "ON" the System Trouble LED indicator on the user interface.
• Turns "ON" the internal sounder.
• Changes the state of the Form C AC Trouble contact to the TROUBLE position.
• Changes the state of the Form C General Trouble contact to the TROUBLE position.
(After 170 minutes if SW2-Position 2=ON or after 30 seconds if SW2-Position
2=OFF)
Any other trouble detected by the panel is reported as follows:
• Turns "ON" the System Trouble LED indicator on the user interface.
• Turns "ON" the internal sounder.
• Changes the state of the Form C General Trouble contact to the TROUBLE position.
When there are no trouble conditions detected, the user interface has the POWER ON
indicator illuminated while the SYSTEM TROUBLE and AC TROUBLE indicators are
OFF. If the POWER ON indicator is not illuminated, check to see if D100 and/or D109 (on
the PC board) are illuminated.
Figure 26 shows the location of all trouble location LED indicators within the SP40S. Table 7
cross-references the trouble location LED indicators on the PC board to the proper
troubleshooting procedure.
NOTE: When the System Trouble indicator is ON, indicating a panel Trouble, at least one
of the other yellow LED indicators is also ON, indicating the trouble location.
Troubleshooting
Condition Trouble Description
Procedure
D109 (POWER ON LED) is
AC and Battery power are missing or Low Section 8.2.1 (A)
OFF
D96 AND D97 are ON Strobe Over current Protection is active Section 8.2.2 (B)
D8 (BAT) is ON Battery voltage is below 20.4 VDC or battery is missing Section 8.2.3 (C)
AC TROUBLE (of display)
AC input voltage missing or low Section 8.2.4 (D)
is ON
D3 (DV) is ON Digital Voice Signal is too low or missing Section 8.2.5 (E)
D4 (MIC) is ON steady Push-to-Talk Microphone inoperable or missing Section 8.2.6 (F)
D5 (AMP) is ON steady Audio Over current Protection is active Section 8.2.7 (G)
D96 (STB SHT) is ON Strobe Notification Appliance Circuit is shorted Section 8.2.8 (H)
D97 (STB OPEN) is ON Strobe Notification Appliance Circuit is open Section 8.2.9 (I)
Auxiliary input is open, RMX is in trouble, or remote
D44 (AUX IN) is ON Section 8.2.10 (J)
MIC is in trouble
Audio Notification Appliance Circuit is Shorted, Splitter
D2 (AUD SHT) is ON Section 8.2.11(K)
is in trouble, or Audio Booster is in trouble
D1 (AUD OPEN) is ON Audio Notification Appliance Circuit is Open Section 8.2.12 (L)
D67 (GF) is ON Ground Fault Trouble Section 8.2.13 (M)
D47 (INT TRB) is ON User Interface is incorrectly connected or damaged Section 8.2.14 (N)
D6 (EXT AC WIR) is ON SPB SUP is open or Audio Booster has AC failure Section 8.2.15 (O)
D5 (AMP) is blinking Auxiliary preamp failure Section 8.2.16 (P)
D4 (MIC) is blinking Microphone preamp failure Section 8.2.17 (Q)
D93 (CHG TRB) is ON Battery voltage is below 18.5 VDC or battery is missing Section 8.2.18 (R)
D55 (DV1) is ON IN1 (DV input 1) is open Section 8.2.19 (S)
D62 (DV2) is ON IN2 (DV input 2) is open Section 8.2.19 (S)
D58 (DV3) is ON IN3 (DV input 3) is open Section 8.2.19 (S)
D65 (DV4) is ON IN4 (DV input 4) is open Section 8.2.19 (S)
D75 (DV5) is ON IN5 (DV input 5) is open Section 8.2.19 (S)
D84 (DV6) is ON IN6 (DV input 6) is open Section 8.2.19 (S)
D78 (DV7) is ON IN7 (DV input 7) is open Section 8.2.19 (S)
D87 (DV8) is ON IN8 (DV input 8) is open Section 8.2.19 (S)
EXCESSIVE NOISE FROM MOTHERBOARD MAY NOT BE PROPERLY
Section 8.2.20 (T)
SPEAKERS GROUNDED TO ENCLOSURE
Before performing any of the following troubleshooting procedures, make sure that
you read, understand, and follow the preliminary troubleshooting information at the
beginning of this “troubleshooting” chapter.
D4 MIC
PTT MIC Missing
D1 Audio Circuit or Inoperable
Open
D3 DV
Digital D5 AMP
Amplifier Section D6 SPB
D2 Audio Circuit Voice Section Supervision Open
Trouble
Short
D8 Batteries
Missing or Low
D29
(Red) Audio
Peak/Overload
D44 AUX IN,
CC Open,
RMX or
Remote MIC
Trouble
D47 Interface
Trouble
D55 - DV1 - IN1 OPEN
D62 - DV2 - IN2 OPEN
8.2.1 Procedure A
If the green PWR LED is “OFF” and all other LEDs are “OFF,” a power loss condition has
occurred. A power loss condition may be caused by:
• Loss of AC input voltage and battery back-up voltage.
• Faulty wiring of the AC power cord and batteries missing or low.
• Faulty motherboard.
Perform the following:
1. Check for AC voltage at TB9 on the motherboard. If voltage is not present, check for
AC input wiring. If AC voltage is present, check to see if fuse (F2) is blown. If F2 is
blown, replace the fuse (250V, 10A)
2. Check for at least 18.5 VDC at TB10 (Battery terminals). If sufficient voltage is
present, check to see if fuse (F1) is blown. If F1 is blown, replace the fuse (125V,
8A).
3. If the problem persists, replace the motherboard.
NOTE: Mark all wires before removing components. When the trouble is repaired, and
before testing, replace all wires to the proper locations and replace all covers.
8.2.2 Procedure B
If the green PWR LED is “ON,” the yellow SYSTEM TROUBLE LED is “ON,” and both
D96 and D97 are ON, the SP40S panel is in an Over current state.
• Check the strobe output for excessive current calculation. (2.0A for strobe circuit).
Perform the following:
1. If excessive current is calculated, remove appliances until the strobe current is below
2.0 Amps.
2. If excessive current does not exist, and strobe output is not operating, reset the
SP40S by removing AC and battery power.
3. Wait 30 seconds and reapply power. AC first and then batteries.
8.2.3 Procedure C
If the green PWR LED is “ON,” the yellow SYSTEM TROUBLE LED is “ON,” and D8,
BAT LED is “ON,” Battery Voltage is below 18.5 VDC or the battery is missing. A Battery
Trouble condition might be caused by:
• Batteries are missing.
• Battery wiring is incorrect.
• Batteries are defective.
• Battery charging section of the motherboard is inoperable.
Perform the following:
1. Check the battery compartment for the presence of batteries. If batteries are not
installed, install them.
2. Ensure that batteries are properly wired. See Figure 23 and Figure 24 for reference.
3. With the batteries NOT connected to the SP40S measure the series voltage of the
batteries. If the battery voltage is below 18.5VDC allow the SP40S more time to
charge the batteries.
4. With the batteries NOT connected, check for 24VDC at (+, -) BAT connection at
TB10 on the motherboard. If the voltage is below 18.5VDC, the battery charging
section of the motherboard is inoperable. Replace the motherboard.
5. If Steps 1 through 4 are satisfied, replace the batteries.
NOTE: The Batteries could take up to 24 hours to charge to capacity.
8.2.4 Procedure D
If the green PWR LED is “ON,” the yellow SYSTEM TROUBLE LED is “ON,” the AC
TROUBLE LED is “ON,” and the D93 CHG TRB LED is “ON” the AC is low or missing.
An AC Trouble condition might be caused by:
• AC input missing or low.
• AC fuse (F2) is blown.
• A faulty motherboard.
Perform the following:
1. Check fuse F2 on the motherboard. Replace if necessary (250V, 10A).
2. Check for AC voltage at TB9
- If voltage is not present, check the wiring and circuit breaker.
- If voltage is present AND fuse F2 is not open, replace the motherboard.
8.2.5 Procedure E
If the green PWR LED is “ON,” the yellow SYSTEM TROUBLE LED is “ON,” D3 DV
LED is “ON,” the Digital Voice messages are missing or the DV output voltage is too low.
A DV Low Output Voltage condition might be caused by:
• Missing or incorrectly installed memory chip.
• Digital Voice volume control (R73) set too low.
• No messages recorded on memory chip.
Perform the following:
1. Check memory chip (U31) to ensure it is installed properly.
2. Verify that messages are recorded on the chip by activating them using the display
buttons.
3. Check Digital Voice volume control (R73) for proper volume level.
4. If messages were field recorded, make sure the message(s) were recorded properly
and at the proper volume.
5. Replace the motherboard.
8.2.6 Procedure F
If the green PWR LED is “ON,” the yellow SYSTEM TROUBLE LED is “ON,”D4 MIC
LED is “ON” steadily, the push-to-talk microphone is missing, improperly plugged in, or
defective.
Perform the following:
1. Install the microphone.
2. Remove the microphone plug and plug it back in.
3. Replace the microphone.
4. Replace the motherboard.
8.2.7 Procedure G
An Amplifier Trouble is present, if the green PWR LED is “ON,” the yellow SYSTEM
TROUBLE LED is “ON,” and D5 AMP LED is “ON” steady. An Amplifier Trouble
condition may be caused by:
• Short on the audio output.
• Overloaded audio output.
• Over current circuit protection mode from improper power up.
Perform the following:
1. Check the TB4, Audio Out terminals and speaker wiring for shorts.
2. Check to ensure the speakers are tapped correctly.
3. Check to ensure the Output Select jumper (J1) is installed at the proper voltage
level.
4. Reset the SP40S by removing AC and Battery power. Wait 30 seconds and
reapply power. AC first and then batteries.
5. Replace the motherboard.
8.2.8 Procedure H
If the green PWR LED is “ON,” the yellow SYSTEM TROUBLE LED is “ON,” and D96,
STB SHORT LED is “ON,” a short condition exists on the STB OUT NAC output circuit.
A STB SHORT trouble condition might be caused by:
• Shorted appliance on STB OUT (TB12).
• Faulty wiring between STB OUT and strobe notification appliance circuit is causing
a short.
Perform the following: Check the wiring and strobe notification appliances for a short circuit
condition.
8.2.9 Procedure I
If the green PWR LED is “ON,” the yellow SYSTEM TROUBLE LED is “ON,” and D97
STB OPEN LED is “ON,” an open condition exists on the STB OUT NAC output circuit. A
STB OPEN trouble condition might be caused by:
• Missing UL Listed 10K OHM, ½ W EOLR on the STB OUT circuit (TB12).
• Faulty wiring causing an open on the Strobe Notification Appliance Circuit.
8.2.10 Procedure J
If the green PWR LED is “ON,” the yellow SYSTEM TROUBLE LED is “ON,” and D44
AUX IN LED is “ON,” an open condition exists on the CC/NAC input circuit. An AUX IN
trouble condition might be caused by:
• A Remote Microphone or RMX trouble being reported to the SP40S panel (if a
remote MIC or RMX is connected).
• Faulty wiring is causing an open on the CC/NAC input circuit (TB6).
• Jumper JP2 being removed and missing a UL Listed 10K Ohm, ½ W EOLR on the
CC/NAC circuit (TB6) (if a remote MIC is not connected).
Perform the following:
1. Check the Remote Microphone and/or RMX wiring for an open condition.
2. Check the jumper setting (JP4) if a Remote Microphone or RMX is not
connected to the SP40S panel.
3. If the Remote Microphone or RMX is in a trouble condition, refer to that
installation manual to troubleshoot that particular product.
8.2.11 Procedure K
If the green PWR LED is “ON,” the yellow SYSTEM TROUBLE LED is “ON,” and D2,
AUDIO SHORT LED is “ON,” a short condition exists on the AUDIO OUT circuit. An
AUDIO SHORT trouble condition might be caused by:
• Shorted speaker appliance on AUDIO OUT (TB4).
• Faulty wiring between AUDIO OUT and Speaker Notification Appliance Circuit is
causing a short.
• A trouble being reported from an Audio Splitter or Audio Booster.
Perform the following:
• Check the wiring and Audio Notification Appliances for a short circuit condition.
• If a Splitter or Audio Booster is in a trouble condition, refer to that manual to
troubleshoot that particular product.
8.2.12 Procedure L
If the green PWR LED is “ON,” the yellow SYSTEM TROUBLE LED is “ON,” and D1
AUDIO OPEN LED is “ON,” an open condition exists on the STB OUT NAC output
circuit. A STB OPEN trouble condition might be caused by:
• Missing UL Listed 10K OHM, ½ W EOLR on the AUDIO OUT circuit (TB4).
• Faulty wiring is causing an open on the speaker notification appliance circuit.
Perform the following:
1. Check for proper EOLR.
2. Check the speaker notification appliance circuit wiring for an open condition.
8.2.13 Procedure M
If the green PWR LED is “ON,” the yellow SYSTEM TROUBLE LED is “ON,” and D67
GF LED is “ON,” a ground fault condition exists on the output wiring. A GF trouble
condition might be caused by:
• Appliance wiring touching conduit.
• Improper Installation of an appliance(s).
Perform the following:
1. Disconnect appliances from the strobe (TB12) and speaker (TB4) connection on
the motherboard.
2. Troubleshoot the NAC circuits by checking for a resistance reading other than
infinity between the appliance leads and the conduit.
8.2.14 Procedure N
If the green PWR LED is "ON," the yellow SYSTEM TROUBLE LED is "ON," and D47
INT TRB is "ON," an Interface Trouble exists. An Interface trouble might be caused by:
• The 30 pin ribbon cable being removed from the display or motherboard
• The 30 pin ribbon cable being connected to the wrong header.
• The 30 pin ribbon cable being damaged.
Perform the following:
1. Ensure that the ribbon cable is properly installed to the user interface and to the
motherboard at J6 (Display Interface).
2. Check to see if the ribbon cable has been damaged in any way. If the ribbon
cable is damaged, replace it.
8.2.15 Procedure O
If the green PWR LED is "ON," the yellow SYSTEM TROUBLE LED is "ON," and D6
EXT AC WIR is "ON," an open condition exists on the SPB SUP terminals (TB4). This
trouble can be caused by:
• Switch SW2 position 1 is ON despite the SPB SUP terminals not being used.
• UL Listed 10k OHM ½ W EOLR not detected by the SUB SUP terminals.
Perform the following:
1. If AC is being reported separately from the Audio Booster, make sure that a 10k
Ohm ½ W EOLR is properly installed at the Audio Booster and the Audio
Booster is operating properly.
2. If AC is NOT being reported separately, make sure there is nothing on the SPB
SUP terminals (TB4) AND Switch SW2 - position 1 (SPB SUP) is OFF.
8.2.16 Procedure P
If the green PWR LED is "ON," the yellow SYSTEM TROUBLE LED is "ON," and D5
AMP LED is blinking, an Auxiliary preamp trouble has occurred.
Perform the following:
1. Turn Aux Volume Pot (R100) fully clockwise.
2. Initiate the AUX input if it is being used (via Remote MIC).
3. Reset power to the SP40S board by turning it OFF and reenergizing it. Remove
battery power first, then remove AC power. Wait 30 seconds. Apply AC Power
first, then apply battery power.
4. Replace the motherboard.
8.2.17 Procedure Q
If the green PWR LED is "ON," the yellow SYSTEM TROUBLE LED is "ON," and D4
MIC LED is blinking, a Mic preamp trouble has occurred.
Perform the following:
1. Initiate the MIC input to verify its functionality.
2. Reset power to the SP40S board by turning it OFF and reenergizing it. Remove
battery power first, then remove AC power. Wait 30 seconds. Apply AC Power
first, then apply battery power.
3. Replace the motherboard.
8.2.18 Procedure R
If the green PWR LED is "ON," the yellow SYSTEM TROUBLE LED is "ON," and D93
BATT CHG TRB LED is "ON," a battery charger trouble has occurred.
NOTE: The CHG TRB LED turns ON during an AC TROUBLE. Restoring the AC Voltage
turns OFF the CHG TRB LED.
Perform the following:
1. Remove batteries and measure the voltage at the battery terminals (TB10). If
voltage is present, above 20 Volts there is no problem with the battery charger.
2. If there is no voltage at the battery terminals (TB10) while the SP40S is running
on AC power, then there is a problem with the battery charger. Replace the
motherboard.
8.2.19 Procedure S
If the green PWR LED is "ON," the yellow SYSTEM TROUBLE LED is "ON," and one of
the IN# LEDs (D55, D58, D62, D65, D75, D78, D84, or D87) are "ON," a DV Contact
Closure Wiring Trouble exists.
Perform the following:
1. If a particular Contact Closure is not being used, make sure nothing is on the
corresponding terminal block (TB7 or TB8) and the corresponding IN CC
Supervision is turned OFF at switch SW7.
2. If a particular Contact Closure is being used, make sure that a UL approved 10k
Ohm ½ W EOLR is installed on the proper terminals.
8.2.20 Procedure T
If the unit is in normal standby mode yet excessive noise is being heard from the speakers,
the unit may not be properly grounded to the enclosure.
Perform the following:
1. Verify that the 4 metal standoffs are installed and securely fastened. Refer to
figure 3-9 for location of the grounding standoffs.
2. Verify that the 4 screws are installed and securely fastened. Refer to figure 3-9
for location of the grounding screws.
9. Technical Data
9.1 Mechanical
Parameter Description
Dimensions (H x W X D) 21 x 16 x 6 inches
Weight 36 lb
Finish Red or Black
Enclosure Enclosure Door: 16 Gauge (.060) CRS
Construction Type Enclosure Backbox: 16 Gauge (.060) CRS
Mounting Indoor surface mount
Wiring Top, left, right, and bottom knockouts (3/4”-1”) (18 total)
Entry Top (2” - 2 ½” - 3”) (2 total)
Door Lock Standard Cooper Notification key-lock
1 Motherboard
PC Boards
1Keypad board
9.2 Environmental
Parameter Description
Operating Temperature 0 to 49 °C (32 to 120 °F)
Storage Temperature -20 to 70 °C (-4 to 158 °F)
Humidity, Non-condensing 93% at 30 ± 2 °C (86 ± 4 °F)
9.3 Electrical
9.3.1 Input
Parameter Description
Primary Input Voltage SP40S 120VAC, 2.4A, 60Hz
Primary Input Voltage SP40SE 240VAC, 1.5A, 50/60Hz
Secondary (Battery) Voltage 20.4-27.5VDC (33Ah)
9.3.3 Activation
There are nine ways to activate the SP40S panel. The table below lists these activation
sources in order of priority.
9.3.4 Outputs
Parameter Description
Visual Notification Appliance Output 1 output circuit. 2.0 amps at 24VDC. Supervised.
1 output circuit.
Selectable 25 or 70.7 Volt RMS output at 40W max.
Central Amplified Audio Output Supervised.
25V setting = Class 2
70V setting = Class 3
Form C contact normally energized. Contacts transfer
Trouble Contact during trouble: 2.0 amps at 24VDC max, resistive load
(see following warning). Non-Supervised.
Form C contact normally energized. Contacts transfer
Alarm Contact during alarm trouble: 2.0 amps at 24VDC max, resistive
load (see following warning). Non-Supervised.
Form C contact normally energized. Contacts transfer
AC Trouble Contact during AC trouble: 2.0 amps at 24VDC max, resistive load
(see following warning). Non-Supervised.
10. Warranty
LIMITED WARRANTY
Cooper Wheelock, Inc. dba Cooper Notification and Cooper Notification, Inc. (each, a “Seller”) products must be used within
their published specifications and must be PROPERLY specified, applied, installed, operated, maintained and operationally
tested in accordance with these instructions at the time of installation and at least twice a year or more often and in
accordance with local, state and federal codes, regulations and laws. Specification, application, installation, operation,
maintenance and testing must be performed by qualified personnel for proper operation in accordance with all of the latest
National Fire Protection Association (NFPA), Underwriter’s Laboratories (UL), National Electrical Code (NEC), Occupational
Safety and Health Administration (OSHA), local, state, county, province, district, federal and other applicable building and fire
standards, guidelines, regulations laws and codes including, but not limited to, all appendices and amendments and the
requirements of the local authority having jurisdiction (AHJ). Seller products when properly specified, applied, installed,
operated, maintained and operationally tested as provided above are warranted against mechanical and electrical defects for
a period of (a) three (3) years from date of manufacture with respect to MEDC and Seller Industrial Signals and Seller Fire
and Security Notification Appliances and Devices, or (b) one (1) year from date of manufacture with respect to Waves and
SafePath Voice Evacuation and Mass Notification Systems (date of manufacture is determined by date code.) Correction of
defects by repair or replacement shall be at Seller’s sole discretion and shall constitute fulfillment of all obligations under this
warranty. THE FOREGOING LIMITED WARRANTY SHALL IMMEDIATELY TERMINATE IN THE EVENT ANY PART NOT
FURNISHED BY SELLER IS INSTALLED IN THE PRODUCT. THE FOREGOING LIMITED WARRANTY SPECIFICALLY
EXCLUDES ANY SOFTWARE REQUIRED FOR THE OPERATION OF OR INCLUDED IN A PRODUCT. SELLER MAKES
NO REPRESENTATION OR WARRANTY OF ANY OTHER KIND, EXPRESS, IMPLIED OR STATUTORY WHETHER AS TO
MECHANTABILITY, FITNESS FOR A PARTICULAR PURPOSE OR ANY OTHER MATTER.
USERS ARE SOLELY RESPONSIBLE FOR DETERMINING WHETHER A PRODUCT IS SUITABLE FOR THE USER’S
PURPOSES, OR WHETHER IT WILL ACHIEVE THE USER’S INTENDED RESULTS. THERE IS NO WARRANTY AGAINST
DAMAGE RESULTING FROM MISAPPLIACATION, IMPROPER SPECIFICATION, ABUSE, ACCIDENT OR OTHER
OPERATING CONDITIONS BEYOND SELLER’S CONTROL.
SELLER DOES NOT WARRANT THAT THE OPERATION OF THE SOFTWARE WILL BE UNINTERRUPTED OR ERROR-
FREE OR THAT THE SOFTWARE WILL MEET ANY OTHER STANDARD OF PERFORMANCE, OR THAT THE
FUNCTIONS OR PERFORMANCE OF THE SOFTWARE WILL MEET THE USER’S REQUIREMENTS. SELLER SHALL
NOT BE LIABLE FOR ANY DELAYS, BREAKDOWNS, INTERRUPTIONS, LOSS, DESTRUCTION, ALTERATION, OR
OTHER PROBLEMS IN THE USE OF A PRODUCT ARISING OUT OF OR CAUSED BY THE SOFTWARE.
THE LIABILITY OF SELLER ARISING OUT OF THE SUPPLYING OF A PRODUCT, OR ITS USE, WHETHER ON
WARRANTIES, NEGLIGENCE, OR OTHERWISE, SHALL NOT IN ANY CASE EXCEED THE COST OF CORRECTING
DEFECTS AS STATED IN THE LIMITED WARRANTY AND UPON EXPIRATION OF THE WARRANTY PERIOD ALL SUCH
LIABILITY SHALL TERMINATE. SELLER IS NOT LIABLE FOR LABOR COSTS INCURRED IN REMOVAL,
REINSTALLATION OR REPAIR OF A PRODUCT BY ANYONE OTHER THAN SELLER OR FOR DAMAGE OF ANY TYPE
WHATSOEVER, INCLUDING BUT NOT LIMITED TO, LOSS OF PROFIT OR INCIDENTAL, INDIRECT, CONSEQUENTIAL,
SPECIAL, PUNTIVE OR EXEMPLARY DAMAGES. THE FOREGOING SHALL CONSTITUTE THE SOLE REMEDY OF THE
PURCHASER AND THE EXCLUSIVE LIABILITY OF SELLER.
IN NO CASE WILL SELLER’S LIABILITY EXCEED THE PURCHASE PRICE PAID FOR A PRODUCT.
LIMITATION OF LIABILITY
SELLER’S LIABILITY ON ANY CLAIM OF ANY KIND, INCLUDING NEGLIGENCE AND BREACH OF WARRNTY, FOR ANY
LOSS OR DAMAGE RESULTING FROM, ARISING OUT OF, OR CONNECTED WITH THIS CONTRACT, OR FROM THE
MANUFACTURE, SALE, DELIVERY, RESALE, REPAIR OR USE OF ANY PRODUCT COVERED BY THIS ORDER SHALL
BE LIMITED TO THE PRICE APPLICABLE TO THE PRODUCT OR PART THEREOF WHICH GIVES RISE TO THE CLAIM.
SELLER’S LIABILITY ON ANY CLAIM OF ANY KIND SHALL CEASE IMMEDIATELY UPON THE INSTALLATION IN THE
PRODUCT OF ANY PART NOT FURNISHED BY SELLER. IN NO EVENT SHALL SELLER BE LIABLE FOR ANY CLAIM
OF ANY KIND UNLESS IT IS PROVEN THAT ITS PRODUCT WAS THE DIRECT CAUSE OF SUCH CLAIM. FURTHER, IN
NO EVENT, INCLUDING IN THE CASE OF A CLAIM OF NEGLIGENCE, SHALL SELLER BE LIABLE FOR INCIDENTAL,
INDIRECT, CONSEQUENTIAL, SPECIAL, PUNITIVE OR EXEMPLARY DAMAGES. SOME STATES DO NOT ALLOW THE
EXCLUSION OR LIMITATION OF INCIDENTAL OR CONSEQUENTIAL DAMAGES, SO THE PRECEDING LIMITATION
MAY NOT APPLY TO ALL PURCHASERS.
Speaker/Strobe Combination
The following Wheelock products are LISTED compatible with the trouble audible output.
Bells
MB-G6-24
MB-G10-24
The following devices are rated per UL 2017 and UL 864 for use with the SP40S for the NFPA 72
low frequency tone sleeping area application
Speakers Speaker/Strobes
E50H E50H-241575W E50H-24MCW
E60H E50H-24MCWH E60H-24MCC
E70H E60H-24MCCH E70H-241575W
E90H E70H-24MCW E70H-24MCWH
S8-70/25 E90H-24MCC E90H-24MCCH
LSPK S8-24MCC S8-24MCCH
LSPKC LSPST3 LSPSTC3
LSPST LSPSTC
Amplifiers Accessories
SPB-80/4 SP4Z-A/B
SPB-80/4E SP4-APS
SPB-160 SP-SVC
SPB-160E
SPB-320
SPB-320E