CyberPower UM OR1500PFCLCD
CyberPower UM OR1500PFCLCD
OR750PFCLCD / OR1000PFCLCD / OR1500PFCLCD (DO NOT plug a laser printer, paper shredder,
copier, space heater, vacuum, sump pump or
User Manual other large electrical devices into any outlet.
K01-0000408-00 The power demands of these devices may
overload and damage the unit.)
IMPORTANT SAFETY INSTRUCTIONS 2 USB Port
The USB port allows connection and
(SAVE THESE INSTRUCTIONS)
communication between the USB port on the
This manual contains important safety instructions. Please read and follow all instructions carefully during installation and operation of the unit.
computer and the UPS unit.
Read this manual thoroughly before attempting to unpack, install, or operate your UPS.
3 Dry Contact (DB-9 Port)
CAUTION! To prevent the risk of fire or electric shock, install in a temperature and humidity controlled indoor area free of conductive
The dry contact provides specific information for equipment that can utilize dry contact signals. The DB-9 port is not designed for
contaminants. (Please see specifications for acceptable temperature and humidity range).
communication between the UPS and a computer. The USB ports needs to be used for this function.
CAUTION! To reduce the risk of electric shock, do not remove the cover except to service the battery. Turn off and unplug the unit before
4 Wiring Fault Indicator (red)
servicing the batteries. There are no user serviceable parts inside except for the battery.
This LED indicator will illuminate to warn the user that a wiring problem exists, such as bad ground, missing ground or reversed wiring. If this
CAUTION! Hazardous live parts inside can be energized by the battery even when the AC input power is disconnected.
is illuminated, disconnect all electrical equipment from the outlet and have an electrician verify the outlet is properly wired. The UPS will
CAUTION! The UPS must be connected to an AC power outlet with fuse or circuit breaker protection. Do not plug into an outlet that is not
operate normally and provide battery backup even if the indicator illuminates. However, the unit will not provide surge protection without
grounded. If you need to de-energize this equipment, turn off and unplug the unit.
being plugged into a grounded and properly wired outlet
CAUTION! To avoid electric shock, turn off the unit and unplug it from the AC power source before servicing the battery.
5 AC Input Power Cord
CAUTION! Not for use in a computer room as defined in the Standard for the Protection of Electronic Computer/Data Processing Equipment,
Heavy-duty power cord.
ANSI/NFPA 75
6 Input Circuit Breaker
CAUTION! To reduce the risk of fire, connect only to a circuit provided with 20 amperes maximum branch circuit over current protection in
Located on the back of the UPS, the circuit breaker provides overload and fault protection.
accordance with the National Electric Code, ANSI/NFPA 70.
DO NOT USE FOR MEDICAL OR LIFE SUPPORT EQUIPMENT! CyberPower Systems does not sell products for life support or medical
REPLACING THE BATTERY
applications. DO NOT use in any circumstance that would affect the operation and safety of life support equipment, medical applications, or
Replacement of batteries located in an OPERATOR ACCESS AREA.
patient care.
1. When replacing batteries, replace with the same number of the following battery: CyberPower / RB1270X2D for the OR750PFCLCD,
DO NOT USE WITH OR NEAR AQUARIUMS! To reduce the risk of fire or electric shock, do not use with or near an aquarium. Condensation
CyberPower / RB1290X2A for the OR1000PFCLCD and CyberPower / RB1290X2B for the OR1500PFCLCD. Contact CyberPower
from the aquarium can cause the unit to short out.
Systems about replacement batteries.
DO NOT USE THE UPS ON ANY TRANSPORTATION! To reduce the risk of fire or electric shock, do not use the unit on any transportation
2. CAUTION! Risk of Energy Hazard, 24V, maximum 9 Ampere-hour battery. Before replacing batteries, remove conductive jewelry such
such as airplanes or ships. The effect of shock or vibration caused during transit and the damp environment can cause the unit to short out.
as chains, wrist watches, and rings. High energy conducted through these materials could cause severe burns.
3. CAUTION! Do not dispose of batteries in a fire. The batteries may explode.
4. CAUTION! Do not open or mutilate batteries. Released material is harmful to the skin and eyes. It may be toxic.
INSTALLING YOUR UPS SYSTEM CAUTION - RISK OF EXPLOSION IF BATTERY IS REPLACED BY AN INCORRECT TYPE. DISPOSE OF USED BATTERIES ACCORDING
TO LOCAL REGULATIONS.
INTRODUCTION
Thank you for selecting a CyberPower Systems UPS product. This UPS is designed to provide unsurpassed power protection, operation and
BATTERY REPLACEMENT PROCEDURE:
performance during the lifetime of the product.
1. Turn off and unplug all connected equipment.
UNPACKING
2. Turn the UPS off and unplug it from the AC power source.
Inspect the UPS upon receipt. The box should contain the following:
®
3. Remove the front panel of the UPS.
(a) UPS unit (b) User’s manual (c) PowerPanel Business Edition software CD (d) Serial cable (e) USB A+B type cable (f) Function Setup Guide
4. Remove two screws from the battery compartment cover and slide the cover completely off of the unit.
OVERVIEW
5. Disconnect the black battery wire from the batteries.
The OR750/1000/1500PFCLCD UPS provides complete power protection from utility power that isn't always consistent. The
6. Press the POWER button for 3 seconds.
OR750/1000/1500PFCLCD features surge protection against power surges and maintenance free
7. Disconnect the red battery wire from the batteries.
batteries for long lasting battery backup during power outages. In addition to ensuring consistent power
8. Remove the batteries from the compartment.
to your computer system and the OR750/1000/1500PFCLCD also includes software that will
9. Install the replace batteries by connecting the red wire (+) and black wire (-) to the same color connectors from the battery pack.
automatically save your open files and shutdown your computer system during a utility power loss.
10. Put the batteries back into the compartment.
AUTOMATIC VOLTAGE REGULATOR
11. Re-install the battery compartment cover and tighten the retaining screws.
The OR750/1000/1500PFCLCD stabilizes inconsistent utility power voltage to nominal levels that are
12. Put the front panel back on the UPS.
safe for equipment. Inconsistent utility power may be damaging to important data files and hardware, but
13. Connect to AC power and charge the new batteries for up to 16 hours to ensure a full charge.
with Automatic Voltage Regulation (AVR), damaging voltage levels are corrected to safe levels. AVR
REMINDER: Batteries are considered HAZARDOUS WASTE and must be disposed of properly. Most retailers that sell lead-acid batteries
automatically increases low utility power and decreases high utility power to a safer level closer to
110/120V.
HOW TO DETERMINE THE POWER REQUIREMENTS OF YOUR
EQUIPMENT
1. Ensure that the equipment plugged into the outlets does not exceed the UPS unit’s rated capacity (750VA/525W for
OR750PFCLCD, 1000VA/700W for OR1000PFCLCD, 1500VA/1050W for OR1500PFCLCD). If the rated capacities
of the unit are exceeded, an overload condition may occur and cause the UPS unit to shut down or the circuit breaker
to trip.
HARDWARE INSTALLATION GUIDE
OR750PFCLCD
1. Your new UPS may be used immediately upon receipt. However, to ensure the battery’s maximum
charge capacity, it is recommended that you charge the battery for at least 8 hours. Your UPS is equipped with collect used batteries for recycling, as required by local regulations.
an auto-charge feature. When the UPS is plugged into an AC outlet, the battery will automatically charge
whether the UPS is turned on or off.
Note: This UPS is designed with a safety feature to keep the system from being turned on during shipment. The
first time you turn the UPS on, you will need to have it connected to AC power or it will not power up.
DEFINITIONS FOR ILLUMINATED LCD INDICATORS
2. With the UPS unit turned off and unplugged, connect your computer, monitor, and any other peripherals OR1000/1500PFCLCD 1. ONLINE: The UPS is supplying utility power to connected equipment.
requiring battery backup into the battery power supplied outlets. DO NOT plug a laser printer, paper shredder, copier, space heater, 2. BATTERY: During a severe brownout or blackout, this icon appears and an alarm
vacuum, sump pump or other large electrical devices into any outlet. The power demands of these devices may overload and sounds (two short beeps followed by a pause) to indicate the UPS is operating from its
damage the unit. internal batteries. During a prolonged brownout or blackout, the alarm will sound
3. Plug the UPS into a 2 pole, 3 wire grounded receptacle (wall outlet). Make sure the wall branch outlet is continuously to indicate the UPS’s batteries are nearly out of power. You should save files
protected by a fuse or circuit breaker and does not service equipment with large electrical demands (e.g. air and turn off your equipment immediately or allow the software to shut the system down.
conditioner, copier, etc…). The warranty prohibits the use of extension cords, outlet strips, and surge strips. 3. Energy-Saving: The UPS in energy-saving bypass mode. When the utility power is
4. Press the power switch to turn the unit on. The Power On indicator light will illuminate and the unit will “beep”. normal and the battery is fully charged, the UPS will go into energy-saving bypass mode
If an overload is detected, an audible alarm will sound and the unit will emit one long beep. To correct this, turn the UPS off and unplug at automatically. See “CyberPower GreenPower UPSTM Technology” section for more
least one piece of equipment from the battery power supplied outlets. Make sure the circuit breaker is depressed and then turn the UPS on. information.
5. To maintain optimal battery charge, leave the UPS plugged into an AC outlet at all times. 4. LOAD capacity / Sensitivity setup: This meter displays the approximate output
6. To store the UPS for an extended period, cover it and store with the battery fully charged. While in storage, recharge the battery every three load level (in 20% increments) of the UPS battery outlets. It can also be sensitivity
months to ensure battery life. setup meter if you are in Setup mode. It is to control the sensitivity of the UPS to switch to Battery Mode by selecting UPS shutdown voltage
7. Ensure the wall outlet and UPS are located near the equipment being attached for proper accessibility. range. When the sensitivity is increased, the UPS will switch to Battery Mode with less input power variation.
5. BATTERY capacity: This meter displays the approximate charge level (in 20% increments) of the UPS’s internal battery. During a
BASIC OPERATION blackout or severe brownout, the UPS switches to battery power, the BATTERY icon appears, and the charge level decreases.
6. FAULT: This icon appears if there is a problem with the UPS. Press the POWER button to turn off the UPS.
DESCRIPTION E22: Battery Mode or AC/Utility Power Mode Overload fault (Unplug at least one piece of equipment from battery outlets and turn the
UPS on again.)
Front Panel E21: Battery Output Short fault (Unplug at least one piece of equipment from battery outlets and turn the UPS on again.)
1 Power Switch E01: Charger Fault (Contact CyberPower Systems for support.)
Used as the master on/off switch for equipment connected to the battery power E24: Internal Fault (Contact CyberPower Systems for support.)
supplied outlets. E23: Fan Abnormal (Contact CyberPower Systems for support.)
2 Power On Indicator 7. OVER LOAD: This icon appears and an alarm sounds to indicate the battery-supplied outlets are overloaded. To clear the overload,
This LED is illuminated when the utility power is normal and the UPS outlets are unplug some of your equipment from the battery-supplied outlets until the icon turns off and the alarm stops.
providing power, free of surges and spikes. ®
8. SCHEDULE: Users can setup the schedule to turn on and shut down the computer and UPS through PowerPanel Business Edition
3 LCD Module Display software. The LCD display will show how much time is left before the UPS will turn back on or shut down.
Intelligent LCD display shows all the UPS information using icons and messages. 9. ESTIMATED RUNTIME: This displays the run time estimate of the UPS with current battery capacity and load.
For more information please review the “Definitions for Illuminated LCD Indicators” 10. OUTPUT meter: This meter measure, in real time, the AC voltage that the UPS system is providing to the computer, such as normal AC
section below. line mode, AVR mode, and battery backup mode. (Note: The OUTPUT meter shows the status of the battery backup outlets in terms of load,
4 Down/Display Button frequency, and voltage.)
The button can be used to select the LCD display contents including Input Voltage, Output Voltage, and Estimated Run Time. Short press 11. INPUT meter: This meter measures the AC voltage that the UPS system is receiving from the utility wall outlet. The UPS is designed,
the button to scroll down the function menu. Pressing the button for 2 seconds will keep the LCD display always on or turn the LCD display through the use of automatic voltage regulation, to continuously correct output voltage to connected equipment to a safe 110/120 voltage
off while in AC/Utility power mode. For more information about the Down/Display Button, please refer to the Function Setup Guide. output range. In the event of a complete power loss, severe brownout, or over-voltage, the UPS relies on its internal battery to supply
5 Up/Mute Button consistent 110/120 output voltage. The INPUT voltage meter can be used as a diagnostic tool to identify poor-quality input power.
Short press the button to scroll up the function menu. Holding the button for more than 2 seconds will silence the alarm. For more 12. EVENT: This meter records the number of power outages.
information about the Up/Mute Button, please refer to the Function Setup Guide. 13. MUTE: This icon appears whenever the UPS is in silent mode. The alarm does not beep during silent mode.
6 Enter/Setup Button 14. AVR (Automatic Voltage Regulation): This icon appears whenever your UPS is automatically correcting low AC line voltage without
Press the button for 2 seconds to enter the setup menu and then select the functions for configuration. For more information about the using battery power. This is a normal, automatic operation of your UPS, and no action is required on your part.
Enter/Setup Button, please refer to the Function Setup Guide.
For more information about functions setup, please refer to the Function Setup Guide.
How Do You Open A Connected Equipment Claim?
TROUBLESHOOTING 1. Call us at (877) 297-6937 or write to us at Cyber Power Systems (USA), Inc., 4241 12th Ave. E., STE 400, Shakopee, MN
55379, or send us an e-mail message at [email protected] for instructions, within 10 days of the occurrence.
Problem Possible Cause Solution 2. When you contact CyberPower, identify the Product, the Purchase Date, and the item(s) of Connected Equipment. Have
information on all applicable insurance or other resources of recovery/payment that are available to the Initial Customer and
Circuit breaker button is Turn the UPS off and unplug at least one piece of Request a Claim Number.
Circuit breaker has tripped due to an
projecting from the back of the equipment. Wait 10 seconds, reset the circuit breaker by 3. You must provide a dated purchase receipt (or other proof of the original purchase) and provide a description of the damage to
overload.
unit. pressing the button in, and then turn the UPS on. your connected equipment.
4. Pack and ship the product to CyberPower and, if requested, the item(s) of Connected Equipment, a repair cost estimate for the
Battery not fully charged. Recharge the battery by leaving the UPS plugged in. damage to the Connected Equipment, and all claim forms that CyberPower provides to you. Show the Claim Number on the
The UPS does not perform
Contact CyberPower Systems about replacement batteries shipping label or include it with the product. You must prepay all shipping costs, you are responsible for packaging and
expected runtime. Battery is worn out.
at [email protected] shipment, and you must pay the cost of the repair estimate.
The on/off switch is designed to
Turn the UPS off. Wait 10 seconds and then turn the UPS
prevent damage from rapidly turning How Long Do I Have To Make A Claim?
on.
it off and on. All claims must be made within ten days of the occurrence.
The unit is not connected to an AC
The unit must be connected to a 110/120V 60Hz outlet.
outlet. What Will We Do To Correct Problems?
The UPS will not turn on.
Contact CyberPower Systems about replacement batteries CyberPower will inspect and examine the Product.
The battery is worn out.
at [email protected] If the Product is defective in material or workmanship, CyberPower will repair or replace it at CyberPower's expense, or, if
CyberPower is unable to or decides not to repair or replace the Product (if defective) within a reasonable time, CyberPower will refund
Mechanical problem. Contact CyberPower Systems at [email protected] to you the full purchase price you paid for the Product (purchase receipt showing price paid is required).
If it appears that our Product failed to protect any equipment plugged into it, we will also send you forms for making your claim for the
Connect the USB cable to the UPS unit and an open USB
The USB cable is not connected. port on the back of the computer. You must use the cable connected equipment. We will repair or replace the equipment that was damaged because of the failure of our Product or pay you
that came with the unit. the fair market value (NOT REPLACEMENT COST) of the equipment at of the time of the damage. We will use Orion Blue Book, or
PowerPanel® Business Edition is The USB cable is connected to the Check the back of the computer for an additional USB port. another a third-party valuation guide, or eBay, craigslist, or other source to establish that amount. Our maximum liability is limited to
inactive (all icons are gray). wrong port. Move the cable to this port. $150,000 for the OR750PFCLCD, $200,000 for the OR1000PFCLCD and the OR1500PFCLCD.
Shutdown your computer and turn the UPS off. Wait 10
The unit is not providing battery
seconds and turn the UPS back on. This should reset the Who Pays For Shipping?
power.
unit. We pay when we send items to you; you pay when you send items to us.
Additional troubleshooting information can be found under “Support” at www.CPSww.com
What isn’t covered by the warranty?
1. This Warranty does not cover any software that was damaged or needs to be replaced due to the failure of the Product or any
TECHNICAL SPECIFICATIONS data that is lost as a result of the failure or the restoration of data or records, or the reinstallation of software.
2. This Warranty does not cover or apply to: misuse, modification, operation or storage outside environmental limits of the Product
or the equipment connected to it, nor for damage while in transit or in storage, nor if there has been improper operation or
Model OR750PFCLCD OR1000PFCLCD OR1500PFCLCD
maintenance, or use with items not designed or intended for use with the Product, such as laser printers, appliances, aquariums,
medical or life support devices, etc.
Capacity 750VA / 525W 1000VA / 700W 1500VA /1050W
The Product was designed to eliminate disrupting and damaging effects of momentary (less than 1ms) voltage spikes or impulses
Size (W x H x D) 5.4" x 6.4" x 13.8"
from lightning or other power transients. If it can be shown that a voltage spike lasting longer than 1ms has occurred, the occurrence
Net Weight 22.5lbs / 10.2kg 24.7lbs / 11.2kg 25.0lbs / 11.3kg will be deemed outside the rated capabilities of the Product and the Limited Warranty is void. CyberPower Does Not Cover or
Undertake Any Liability in Any Event for Any of the Following:
Typical Battery Recharge Time 8 hours 1. Loss of or damage to data, records, or software or the restoration of data or records, or the reinstallation of software.
2. Damage from causes other than AC Power Line Transients, spikes, or surges on properly installed, grounded and
Typical Battery Life 3 to 6 years, depending on number of discharge/recharge cycles
code-compliant 120 volt power lines in the United States and Canada; transients, surges or spikes on standard telephone land
lines, PBX telephone equipment lines or Base 10T Ethernet lines, when properly installed and connected. (This exclusion
Recommended Battery Sealed Maintenance Free Lead Acid Battery
applies, for example, to fluctuations in data transmission or reception, by CATV or RF transmission or fluctuations, or by
Safety Approvals UL1778, CSA C22.2 No 107.3, FCC/DoC Class B transients in such transmission.)
3. Damage from any circumstance described as excluded above with respect to the Product.
4. Damages from fire, flood, wind, rain, rising water, leakage or breakage of plumbing, abuse, misuse or alteration of either the
SYSTEM FUNCTIONAL BLOCK DIAGRAM
product or the Connected Equipment.
EMI Surge
Input Filter Suppressor AVR Output 5. CyberPower excludes any liability for personal injury under the Limited Warranty and Connected Equipment Guarantee.
CyberPower excludes any liability for direct, indirect, special, incidental or consequential damages, whether for damage to or
loss of property [EXCEPT FOR (AND ONLY FOR) the specific limited agreement of CyberPower to provide certain warranty
Charger
AC/DC Inverter benefits regarding "Connected Equipment" under this Warranty], loss of profits, business interruption, or loss of information or
data. NOTE: Some States or Provinces do not allow the exclusion or limitation of incidental or consequential damages, so the
Normal Mode above limitation may not apply to you.
Battery Mode
6. The Product is not for use in high-risk activities or with aquariums. The Product is not designed or intended for use in hazardous
Battery
environments requiring fail-safe performance, or for use in any circumstance in which the failure of the Product could lead
directly to death, personal injury, or severe physical or property damage, or that would affect operation or safety of any medical
CYBERPOWER GREENPOWER UPS™ TECHNOLOGY or life support device (collectively, "High Risk Activities"). CyberPower expressly disclaims any express or implied warranty of
fitness for High Risk Activities or with aquariums. CyberPower does not authorize use of any Product in any High Risk Activities
Advanced Energy-Saving Patented Bypass Technology or with Aquariums. ANY SUCH USE IS IMPROPER AND IS A MISUSE OF THE PRODUCT.
CyberPower’s patented GreenPower UPS™ with Bypass Technology reduces UPS energy costs by up to
75% compared to conventional UPS models. Even when utility power is normal, conventional UPS models
constantly pass power through a transformer. By contrast, under normal conditions the advanced circuitry Where Can I Get More Information?
of a GreenPower UPS™ bypasses the transformer. As a result, the power efficiency is significantly The application of the United Nations Convention of Contracts for the International Sale of Goods is expressly excluded.
increased while decreasing waste heat, using less energy, and reducing energy costs. CyberPower is the warrantor under this Limited Warranty.
When an abnormal power condition occurs, the GreenPower UPS™ automatically runs power through its For further information please feel free to contact CyberPower at CyberPower Systems (USA), Inc. 4241 12th Ave E., STE 400,
transformer to regulate voltage and provide “safe” power. Since utility power is normal over 88% of the time, the GreenPower UPS™ Shakopee, MN 55379; call us at (877) 297-6937; or send us an e-mail message at [email protected].
operates primarily in its efficient bypass mode.
The GreenPower UPS™ is also manufactured in accordance with the Restriction on Hazardous Substances (RoHS) directive making CyberPower Systems encourages environmentally sound methods for disposal and recycling of its UPS products.
it one of the most environmentally-friendly on the market today. Please dispose and/or recycle your UPS and batteries in accordance to the local regulations of your state.
Limited Warranty and Connected Equipment Guarantee All rights reserved. Reproduction without permission is prohibited.
Read the following terms and conditions carefully before using the CyberPower OR750/1000/1500PFCLCD (the “Product”). By using
the Product you consent to be bound by and become a party to the terms and conditions of this Limited Warranty and Connected
Equipment Guarantee (together referred to as this “Warranty”). If you do not agree to the terms and conditions of this Warranty, you
should return the Product for a full refund prior to using it.
Who Is Covered?
This warranty only covers the original purchaser. Coverage ends if you sell or otherwise transfer the Product.