PRODUCT DESCRIPTION
The ‘’F" series of spring loaded, diaphragm controlled, balanced valve design regulators are suitable
for low, medium and high outlet pressure. The ‘’F" series regulators are supplied with internal
sensing lines and are preset for an optional connection to an external sensing line by the customer.
The special regulator design combined with a balanced valve results in:
BALANCED
DESING
AP BP - MP
Technical Features
Desing Pressure, PS 25 bar 2500 kPa 362.5 PSIG
Inlet Pressure Range, bPu 0.2 – 25 bar 20 – 2500 kPa 2.9 – 362.5 PSIG
Type DS on request IS
Fail Mode Fail to Open
BP Model 10 - 85 mbar 1 – 8.5 kPa 0.14 – 1.23 PSIG
Outlet Pressure Range Wd MP Model 80 - 350 mbar 8 – 35 kPa 1.16 – 5.07 PSIG
AP Model 300 - 5000 mbar 30 – 500 kPa 4.35 – 72.5 PSIG
Operating Temparature -20°C to +60°C / -4°F to 140 °F on req. -40°C / 40 °F
Ambiente Temperature -30°C to +60°C / -22°F to 140 °F
up to AC5 / up to SG10
Accuracy & lock-up pressure (AC-SG)
BP Model AC5, SG20 – MP-AP Model AC5, SG10
Lock-up Zone Qmin, Pu / Qmax, Pu = 2,5 / 100
Natural gas, Town gas, Propane, Butane, Air, Nitrogen or any noncorrosive and filtered dry
Type of Fluid
gases. Group1,2,3
DN25 - DN40 - DN50 PN 16/25 according to ISO 7005-1, ISO 7005-2; class ANSI 150RF
Diameter
according to ANSI B16.5, ASME B16.42 and class ANSI 125 FF according to ASME B16.1 -
Safety Devices Over Pressure Shutoff and Under Pressure Shutoff. On request Int. Safety Relief Valve
Options Monitor Regulator, Silencer.
Materials
Body Cast Spheroidal Graphite Iron EN GJS 500-7 (GGG50) on request Cast steel ASTM A216 WCB
Head Die cast aluminium on request Steel
Seat Brass on request Stainless Steel
Diaphgram Nitril Rubberized canvas with hot pressing
Sealing NBR
Internal Parts Brass, Stainless Steel and Nickel coated on sealing surfaces
ct1-2019
SAFETY SLUM SHUT VALVE
The F series of regulators can be fitted with safety shut-off valve for overpressure (OPSO) orcombined
under-and-over pressure (UPSO/OPSO) protection. Shut-off gas flow when the outlet pressure of the
regulator increases or/and decreases. The Slum shut valve trip pressure can easily be adjusted
independently of the regulator set point. Built internal bypass, for balancing pressure before
relatching the safety shut-off valve, is operated by pulling the valve stem. Possibility of application of
devices for remote signal and remote control.
ct1-2019
SET RANGE, Outlet Pressure, Springs Code [Wds]
BP MP AP D Lo De Lt Spring Spring
mbar mbar mbar Colour Code
12-16 - - 3.5 220 57 24 Grey GT1130
16-28 - - 4.0 220 58 24 Yellow GT1131
28-50 - - 4.5 220 59 20 Blue GT1132
50-75 - - 5.0 220 60 19 Black GT1133
75-85 80-120 - 5.5 220 61 17 Orange GT1134
- 120-195 - 6.0 220 62 16 Purple GT1135
- 195-300 - 6.5 220 63 15 Pink GT1136
- 220-330 - 7.0 220 63 13 Red GT1236
- 300-500 - 7.5 220 65 14 Green GT1137
- - 300-500 7.5 155 70 9.5 Silver GT1138
- - 400-600 8.0 155 70 9.5 Black GT1139
- - 600-1000 9.0 155 70 9.5 Purple GT1140
- - 800-1600 10.0 155 70 9.5 Grey GT1141
- - 1400-2400 11.0 155 70 9.5 Pink GT1142
- - 2200-3600 12.0 155 73 8.5 White GT1143
- - 3400-5000 13.0 - 7 155 - 155 74 - 45 8.5 - 10 Orange GT1144
Spring characteristics:
D : Wire diameter De: Outside Diameter Lo : Lenght Lt : of spires All dimensions in mm
BP MP AP
Spring Code Spring Colour D Lo De
mbar mbar mbar
GT1152 Red 2.2 60 30.0 35-125
GT1153 Blue 2.5 60 30.0 65-180 170-280
GT1154 Yellow 2.7 60 30.0 80-230 240-370
GT1155 Black 3.2 60 30.0 280-490
GT1156 Purple 3.5 60 30.0 480-800 490-1000
GT1157 Silver 3.7 60 30.0 750-1250
GT1158 Pink 4.0 60 30.0 1000-1750
GT1159 White 4.5 60 30.0 1500-2500
GT1160 Orange 5.0 60 30.0 2000-5500
ct1-2019
All dimensions in mm A
DIMENSIONS AND WEIGHTS
REGULATOR+SSV
Code Connec. A B C D imp Kg
C
F25/S BP DN25 PN or ANSI 280 222 410 242 10 22
DN
F40/S MP DN40 PN or ANSI 280 222 410 242 10 23
D
F50/S MP DN50 PN or ANSI 280 254 420 255 10 30
A All dimensions in mm
PACKAGING WEIGHTS
F25/S 75 x 30 x 30 0.07 24
F40/S 75 x 30 x 30 0.07 25
F50/S 75 x 30 x 30 0.07 32
ct1-2019
LABELING
Ps : Design Pressure
Pin: Inlet Pressure Range,
Pout: Outlet Pressure Range,
Wds: Outlet Set Pressure ,
AC: Accuracy Class,
SG: Lock up Class,
Temp: Operation Temperature
Where forecast, the connections between the equipment and the piping have
to be carried out using a stainless steel or copper pipe, having a minimum
internal diameter of 8 mm.
Regulator sensing line: Rp ¼’’ with compression fitting for 10 mm pipe
Regulator vent line: Rp ¼’’
SSV sensing line: ¼’’ with compression fitting for 10 mm pipe
SSV vent line: Rp ¼’’
MOUNTING POSITION
ct1-2019
STANDARD INSTALLATION
Monitor regulator is generally installed upstream of the active regulator. Although the function of
the monitor regulator is different, the two regulators are virtually identical from the point of view
of their mechanical components. The only difference is that the monitor is set at a higher pressure
than the active regulator. Flow coefficients of the regulator plus line monitor system are about 15%
lower than those of the active regulator alone.
MONITOR ACTIVE
REGULATOR REGULATOR
ct1-2019
FLOW CALCULATIONS
Sizing of regulators is usually made on the basis of Cg valve and KG flow rate coeffcients. Flow rates
at the fully open position and the various operating conditions are related by the following formula
Descriptions
A. When the Cg and KG values of the regulator are known, as well as Pe and Pa, the flow rate can be
calculate as follows:
Pe - Pa
Q = 0,52 x Cg x Pe x sen(K1 x ) Q = KG x Pa x (Pe - Pa)
Pe
Q= KG x Pe
2
In order to limit the noise emission
Q = 0,52 x Cg x Pe it is recommended not toexceed a
gas velocity of 150 m/s at the
regulator outlet flanged.
ct1-2019
FLOW RATE TABLES AC5 for natural gas, ρn=0,83 kg/m3
F25/S
Outlet Inlet Pressure (bar)
Pressure
(mbar)
0.5 1.0 1.5 2 2.5 3 3.5 4 6 10 12 16 19 25
21 185 205 221 232 245 269 297 305 344 344 - - - -
BP 50 215 295 319 341 365 392 420 442 505 505 - - - -
80 227 342 428 502 560 628 690 740 863 863 - - - -
100 232 357 455 528 580 655 702 745 870 870 - - - -
150 189 271 368 440 505 560 592 628 707 707 - - - -
200 183 302 375 438 507 580 651 718 870 870 - - - -
MP
250 171 305 394 436 578 680 772 864 1109 1109 - - - -
300 158 322 368 435 592 691 785 866 1155 1155 - - - -
350 - 310 378 435 602 735 845 955 1276 1276 - - - -
500 - 260 355 410 515 620 755 865 1190 1240 1540 1540 1540 1540
1000 - - 390 445 554 638 789 935 1306 1320 1580 1580 1580 1580
AP 2000 - - - - 554 638 789 935 1306 1510 1640 1640 1640 1640
• Order to limit the noise emission it is recommended not to exceed a gas velocity of 150 m/s at the regulator outlet.
• With noice silencer approximately 10 % loss of capacity
• SSV does not reduce capacity
Butane 0.55
In the tables above, the flow is in (n)m3/h natural gas with a
Oxygen 0.76
density 0.61 and temperature 15°C. To convert to othergas
flow, using the following formula: Air 0.78
Nitrogen 0.81
Type F
ct1-2019
FLOW RATE TABLES AC5 for natural gas, ρn=0,83 kg/m3
F40/S
Outlet Inlet Pressure (bar)
Pressure
(mbar)
0.5 1.0 1.5 2 2.5 3 3.5 4 6 10 12 16 19 25
21 310 465 630 742 865 990 1045 1109 1109 1109 - - - -
BP 50 306 460 625 736 859 986 1040 1103 1103 1103 - - - -
80 304 459 623 734 857 985 1039 1101 1101 1101 - - - -
100 302 457 620 730 855 983 1035 1100 1100 1100 - - - -
150 300 455 615 728 850 981 1033 1096 1096 1096 - - - -
200 295 450 612 724 843 978 1028 1094 1094 1094 - - - -
MP
250 280 435 608 719 838 976 1022 1092 1092 1092 - - - -
300 278 425 575 717 830 975 1018 1089 1089 1089 - - - -
350 275 422 572 715 826 972 1015 1088 1088 1088 - - - -
500 - 340 490 630 763 985 1120 1245 1760 1760 1760 1760 1760 1760
1000 - - 420 620 751 985 1110 1235 1810 1810 1810 1810 1810 1810
AP 2000 - - - - 680 910 975 1085 1655 1655 2680 2680 2680 2680
• Order to limit the noise emission it is recommended not to exceed a gas velocity of 150 m/s at the regulator outlet.
• With noice silencer approximately 10 % loss of capacity
• SSV does not reduce capacity
Butane 0.55
In the tables above, the flow is in (n)m3/h natural gas with a
density 0.61 and temperature 15°C. To convert to othergas Oxygen 0.76
flow, using the following formula: Air 0.78
Nitrogen 0.81
Biogas 0.85
Q (Scm/h Naturalgas) x Fc = Q (Scm/h Xgas)
Example: Towngas 1.23
Q (Scm/h Naturalgas) x 0.78 = Q (Scm/h Air)
1 Scm/h Naturalgas = 0.78 Scm/h Air Hydrogen 3.04
ct1-2019
FLOW RATE TABLES AC5 for natural gas, ρn=0,83 kg/m3
F50/S
Outlet Inlet Pressure (bar)
Pressure
(mbar)
0.5 1.0 1.5 2 2.5 3 3.5 4 6 10 12 16 19 25
21 375 665 794 940 1075 1110 1110 1110 1110 1110 - - - -
BP 50 362 574 788 932 1069 1101 1101 1101 1101 1101 - - - -
80 357 568 787 931 1067 1098 1098 1098 1098 1098 - - - -
100 298 623 778 1075 1251 1441 1615 1804 1804 1804 - - - -
150 291 619 781 1078 1252 1444 1618 1807 1807 1807 - - - -
200 288 615 784 1081 1257 1448 1622 1809 1809 1809 - - - -
MP
250 284 608 788 1084 1260 1452 1628 1812 1812 1812 - - - -
300 280 602 790 1090 1263 1455 1631 1816 1816 1816 - - - -
350 276 599 796 1096 1268 1461 1637 1821 1821 1821 - - - -
500 - 556 720 968 1190 1340 1610 1815 1940 1790 1790 1790 1790 1790
1000 - - 540 890 1190 1452 1614 1815 2190 2355 2355 2355 2355 2355
AP 2000 - - - - 881 899 1260 1480 2014 3415 3415 3415 3415 3415
• Order to limit the noise emission it is recommended not to exceed a gas velocity of 150 m/s at the regulator outlet.
• With noice silencer approximately 10 % loss of capacity
• SSV does not reduce capacity
Butane 0.55
In the tables above, the flow is in (n)m3/h natural gas with a
density 0.61 and temperature 15°C. To convert to othergas Oxygen 0.76
flow, using the following formula:
Air 0.78
Nitrogen 0.81
Biogas 0.85
Q (Scm/h Naturalgas) x Fc = Q (Scm/h Xgas)
Example: Towngas 1.23
Q (Scm/h Naturalgas) x 0.78 = Q (Scm/h Air)
1 Scm/h Naturalgas = 0.78 Scm/h Air Hydrogen 3.04
Type F
ct1-2019
A
D
OPERATION OF THE REGULATOR F SERIE B
1. Check pressure gauge, that inlet pressure should be suitable for
the gas system.
2. Check the filter cartridge, cartridges must be clean and
undeformed.
3. Check if the manual relief valve is in the closed position.
4. Open inlet main valve slowly. C
5. Check outlet pressure gauge,
‘A’ Turn the cap and remove. Outlet pressure can be adjusted by
appropriately turning the internal adjustment ring nut ‘B’ clockwise to
increase it and counterclockwise to decrease it with tube Spanner
24mm. For outlet pressures outside the specified range, ‘C’ spring
change will be required. Place ‘A’ aluminum cap back onto the
regulator top, make sure to put the ‘D’ O-ring.
Type F
ct1-2019
SSV SETTING
Type F
ct1-2019
POSTER
Inlet Pressure
Outlet Pressure
Outlet Pressure
Type F
ct1-2019
REMARKS:
………………………………………………………………………………………………….
…………………………………………………………………………….......................
………………………………………………………………………………………………….
…………………………………………………………………………….......................
………………………………………………………………………………………………….
…………………………………………………………………………….......................
………………………………………………………………………………………………….
…………………………………………………………………………….......................
………………………………………………………………………………………………….
…………………………………………………………………………….......................
………………………………………………………………………………………………….
…………………………………………………………………………….......................
GASTECH LTD.
34800 – İstanbul -TURKEY Zero Gas Governor
Phone : +90 216 465 14 74
Fax : +90 216 465 14 77
E-mail : [email protected]
Web : www.gastech.com.tr
ct1-2019