The document summarizes a gas pressure regulator series called the F series. It has the following key features: 1) It is a spring loaded, diaphragm controlled regulator with a balanced valve design suitable for low, medium, and high outlet pressures. 2) It has a high flow rate coefficient, high accuracy even at maximum flows, and reduced response times with no internal leakage at zero flow. 3) It can be fitted with safety shut-off valves for overpressure or under and overpressure protection that can easily be adjusted independently of the regulator set point.
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
191 views

GASTECH

The document summarizes a gas pressure regulator series called the F series. It has the following key features: 1) It is a spring loaded, diaphragm controlled regulator with a balanced valve design suitable for low, medium, and high outlet pressures. 2) It has a high flow rate coefficient, high accuracy even at maximum flows, and reduced response times with no internal leakage at zero flow. 3) It can be fitted with safety shut-off valves for overpressure or under and overpressure protection that can easily be adjusted independently of the regulator set point.
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 16

Gas Pressure Regulators

F Series
Direct-acting Gas Pressure Regulator with
Incorporated SSV According to 2014/68/EU
Directive, EN334+A1 and EN 14382
ct1-2019
PRODUCT DESCRIPTION

The ‘’F" series of spring loaded, diaphragm controlled, balanced valve design regulators are suitable
for low, medium and high outlet pressure. The ‘’F" series regulators are supplied with internal
sensing lines and are preset for an optional connection to an external sensing line by the customer.
The special regulator design combined with a balanced valve results in:

* High flow rate coefficient,


* High accuracy, even at maximum flow rates,
* Reduced response times,
* No internal leakage at zero flow rate,
* Periodical maintenance without disassembling the body from the pipework,

Suitable for gas


pressure regulator all
small and medium
Suitable for stations in capacity boiler plant Suitable for process
gas transmission, LPG, (Hot water boiler,steam combustion system and
LNG and CNG facilies. boiler, hot oil heaters, all pre-burner gas
etc…) trains
ACTUATOR
DESING

BALANCED
DESING

AP BP - MP

Technical Features
Desing Pressure, PS 25 bar 2500 kPa 362.5 PSIG
Inlet Pressure Range, bPu 0.2 – 25 bar 20 – 2500 kPa 2.9 – 362.5 PSIG
Type DS on request IS
Fail Mode Fail to Open
BP Model 10 - 85 mbar 1 – 8.5 kPa 0.14 – 1.23 PSIG
Outlet Pressure Range Wd MP Model 80 - 350 mbar 8 – 35 kPa 1.16 – 5.07 PSIG
AP Model 300 - 5000 mbar 30 – 500 kPa 4.35 – 72.5 PSIG
Operating Temparature -20°C to +60°C / -4°F to 140 °F on req. -40°C / 40 °F
Ambiente Temperature -30°C to +60°C / -22°F to 140 °F
up to AC5 / up to SG10
Accuracy & lock-up pressure (AC-SG)
BP Model AC5, SG20 – MP-AP Model AC5, SG10
Lock-up Zone Qmin, Pu / Qmax, Pu = 2,5 / 100
Natural gas, Town gas, Propane, Butane, Air, Nitrogen or any noncorrosive and filtered dry
Type of Fluid
gases. Group1,2,3
DN25 - DN40 - DN50 PN 16/25 according to ISO 7005-1, ISO 7005-2; class ANSI 150RF
Diameter
according to ANSI B16.5, ASME B16.42 and class ANSI 125 FF according to ASME B16.1 -
Safety Devices Over Pressure Shutoff and Under Pressure Shutoff. On request Int. Safety Relief Valve
Options Monitor Regulator, Silencer.

Materials
Body Cast Spheroidal Graphite Iron EN GJS 500-7 (GGG50) on request Cast steel ASTM A216 WCB
Head Die cast aluminium on request Steel
Seat Brass on request Stainless Steel
Diaphgram Nitril Rubberized canvas with hot pressing
Sealing NBR
Internal Parts Brass, Stainless Steel and Nickel coated on sealing surfaces

ct1-2019
SAFETY SLUM SHUT VALVE

The F series of regulators can be fitted with safety shut-off valve for overpressure (OPSO) orcombined
under-and-over pressure (UPSO/OPSO) protection. Shut-off gas flow when the outlet pressure of the
regulator increases or/and decreases. The Slum shut valve trip pressure can easily be adjusted
independently of the regulator set point. Built internal bypass, for balancing pressure before
relatching the safety shut-off valve, is operated by pulling the valve stem. Possibility of application of
devices for remote signal and remote control.

Slum Shut Valve Technical Futures


Type IS
Operation Class A
Response Time <2s
Maximum Pressure Set Range Wdo 35 – 5500 mbar 3.5 – 550 kPa 0.5 – 79.7 PSIG
Minimum Pressure Set Range Wdu 10 – 3200 mbar 1 – 320 kPa 0.14 – 46.6 PSIG
Accuracy (AG) BP Model AG10 – MP Model AG5 – AP Model AG5
Remote Control (Pneumatic or electromagnetic) Remote Signal (contact or inductive
Options
microswitches).

REMOTE SIGNAL and


CONTROL

ct1-2019
SET RANGE, Outlet Pressure, Springs Code [Wds]

BP MP AP D Lo De Lt Spring Spring
mbar mbar mbar Colour Code
12-16 - - 3.5 220 57 24 Grey GT1130
16-28 - - 4.0 220 58 24 Yellow GT1131
28-50 - - 4.5 220 59 20 Blue GT1132
50-75 - - 5.0 220 60 19 Black GT1133
75-85 80-120 - 5.5 220 61 17 Orange GT1134
- 120-195 - 6.0 220 62 16 Purple GT1135
- 195-300 - 6.5 220 63 15 Pink GT1136
- 220-330 - 7.0 220 63 13 Red GT1236
- 300-500 - 7.5 220 65 14 Green GT1137
- - 300-500 7.5 155 70 9.5 Silver GT1138
- - 400-600 8.0 155 70 9.5 Black GT1139
- - 600-1000 9.0 155 70 9.5 Purple GT1140
- - 800-1600 10.0 155 70 9.5 Grey GT1141
- - 1400-2400 11.0 155 70 9.5 Pink GT1142
- - 2200-3600 12.0 155 73 8.5 White GT1143
- - 3400-5000 13.0 - 7 155 - 155 74 - 45 8.5 - 10 Orange GT1144

Spring characteristics:
D : Wire diameter De: Outside Diameter Lo : Lenght Lt : of spires All dimensions in mm

SSV Maksimum Set Range, Springs Code[Wds0]

BP MP AP
Spring Code Spring Colour D Lo De
mbar mbar mbar
GT1152 Red 2.2 60 30.0 35-125
GT1153 Blue 2.5 60 30.0 65-180 170-280
GT1154 Yellow 2.7 60 30.0 80-230 240-370
GT1155 Black 3.2 60 30.0 280-490
GT1156 Purple 3.5 60 30.0 480-800 490-1000
GT1157 Silver 3.7 60 30.0 750-1250
GT1158 Pink 4.0 60 30.0 1000-1750
GT1159 White 4.5 60 30.0 1500-2500
GT1160 Orange 5.0 60 30.0 2000-5500

SSV Minimum Set Range, Springs Code [Wdsu]


Spring Code Spring Colour BP MP AP
D Lo De mbar mbar mbar

GT1145 Red 1.20 55 10.1 15-35


GT1146 Blue 1.50 55 12.2 25-40
GT1147 Yellow 2.0 55 12.2 35-110 30-100
GT1148 Black 2.3 55 12.2 60-240
GT1149 Purple 2.5 55 12.2 70-400 165-450
GT1150 Silver 2.8 60 15.0 350-900
GT1151 Pink 3.5 60 15.0 700-3200

ct1-2019
All dimensions in mm A
DIMENSIONS AND WEIGHTS
REGULATOR+SSV
Code Connec. A B C D imp Kg

C
F25/S BP DN25 PN or ANSI 280 222 410 242 10 22

F25/S MP DN25 PN or ANSI 280 222 410 242 10 22

F25/S AP DN25 PN or ANSI 210 222 400 250 10 23

F40/S BP DN40 PN or ANSI 280 222 410 242 10 23

DN
F40/S MP DN40 PN or ANSI 280 222 410 242 10 23

F40/S AP DN40 PN or ANSI 210 222 400 250 10 24

F50/S BP DN50 PN or ANSI 280 254 420 255 10 30

D
F50/S MP DN50 PN or ANSI 280 254 420 255 10 30

F50/S AP DN50 PN or ANSI 210 254 400 260 10 31

A All dimensions in mm

DIMENSIONS AND WEIGHTS


REGULATOR
Code Connec. A B C D imp Kg
C

F25 BP-MP DN25 PN or ANSI 280 222 410 85 10 18

F25 AP DN25 PN or ANSI 210 222 400 85 10 19

F40 BP-MP DN40 PN or ANSI 280 222 410 85 10 19

F40 AP DN40 PN or ANSI 210 222 400 85 10 20


DN

F50 BP-MP DN50 PN or ANSI 280 254 420 90 10 27


D

F50 AP DN50 PN or ANSI 210 254 400 90 10 28


B

PACKAGING WEIGHTS

Code Dimensions Volume (m³) Weight

F25/S 75 x 30 x 30 0.07 24

F40/S 75 x 30 x 30 0.07 25

F50/S 75 x 30 x 30 0.07 32

ct1-2019
LABELING

Ps : Design Pressure
Pin: Inlet Pressure Range,
Pout: Outlet Pressure Range,
Wds: Outlet Set Pressure ,
AC: Accuracy Class,
SG: Lock up Class,
Temp: Operation Temperature

CONNECTING THE EQUIPMENT

Where forecast, the connections between the equipment and the piping have
to be carried out using a stainless steel or copper pipe, having a minimum
internal diameter of 8 mm.
Regulator sensing line: Rp ¼’’ with compression fitting for 10 mm pipe
Regulator vent line: Rp ¼’’
SSV sensing line: ¼’’ with compression fitting for 10 mm pipe
SSV vent line: Rp ¼’’

MOUNTING POSITION

ct1-2019
STANDARD INSTALLATION

Regulator continuously monitors outlet pressure. Regulator reduce


high and unstable pressure.

INLET PRESSURE OUTLET PRESSURE ATMOSPHERE

MONITOR and ACTIVE INSTALLATION

Monitor regulator is generally installed upstream of the active regulator. Although the function of
the monitor regulator is different, the two regulators are virtually identical from the point of view
of their mechanical components. The only difference is that the monitor is set at a higher pressure
than the active regulator. Flow coefficients of the regulator plus line monitor system are about 15%
lower than those of the active regulator alone.

MONITOR ACTIVE
REGULATOR REGULATOR

ct1-2019
FLOW CALCULATIONS

Outlet Pressure Type BP / MP Desing AP Desing

Nominal Diameter (mm) DN25 DN40 DN50 DN25 DN40 DN50


Size (inches) 1” 11/2” 2” 1” 11/2” 2”
Cg Flow Coefficient 270 650 780 314 690 772
KG Flow Coefficient 284 683 820 330 725 810
K1 Body Shape Factor 96 96

Sizing of regulators is usually made on the basis of Cg valve and KG flow rate coeffcients. Flow rates
at the fully open position and the various operating conditions are related by the following formula

Descriptions

Q = Flow rate in Scm/h


Pe = Absolute Upstream Pressure in bar (abs)
Pa = Absolute Downstream Pressure in bar (abs)

A. When the Cg and KG values of the regulator are known, as well as Pe and Pa, the flow rate can be
calculate as follows:

A-1 In non-critical conditions: (Pe < 2 x Pa)

Pe - Pa
Q = 0,52 x Cg x Pe x sen(K1 x ) Q = KG x Pa x (Pe - Pa)
Pe

A-2 In critical conditions: (Pe ≥ 2 x Pa)

Q= KG x Pe
2
In order to limit the noise emission
Q = 0,52 x Cg x Pe it is recommended not toexceed a
gas velocity of 150 m/s at the
regulator outlet flanged.

ct1-2019
FLOW RATE TABLES AC5 for natural gas, ρn=0,83 kg/m3
F25/S
Outlet Inlet Pressure (bar)
Pressure
(mbar)
0.5 1.0 1.5 2 2.5 3 3.5 4 6 10 12 16 19 25

21 185 205 221 232 245 269 297 305 344 344 - - - -

BP 50 215 295 319 341 365 392 420 442 505 505 - - - -

80 227 342 428 502 560 628 690 740 863 863 - - - -

100 232 357 455 528 580 655 702 745 870 870 - - - -

150 189 271 368 440 505 560 592 628 707 707 - - - -

200 183 302 375 438 507 580 651 718 870 870 - - - -
MP
250 171 305 394 436 578 680 772 864 1109 1109 - - - -

300 158 322 368 435 592 691 785 866 1155 1155 - - - -

350 - 310 378 435 602 735 845 955 1276 1276 - - - -

500 - 260 355 410 515 620 755 865 1190 1240 1540 1540 1540 1540

1000 - - 390 445 554 638 789 935 1306 1320 1580 1580 1580 1580

AP 2000 - - - - 554 638 789 935 1306 1510 1640 1640 1640 1640

3000 - - - - - - 789 935 1306 1940 1680 1680 1680 1680

4000 - - - - - - - - 1306 1788 1730 1730 1730 1730

• Order to limit the noise emission it is recommended not to exceed a gas velocity of 150 m/s at the regulator outlet.
• With noice silencer approximately 10 % loss of capacity
• SSV does not reduce capacity

Flow with Other Gases Correction Factor Fc at 15°C


Propane 0.64

Butane 0.55
In the tables above, the flow is in (n)m3/h natural gas with a
Oxygen 0.76
density 0.61 and temperature 15°C. To convert to othergas
flow, using the following formula: Air 0.78

Nitrogen 0.81

Q (Scm/h Naturalgas) x Fc = Q (Scm/h Xgas) Biogas 0.85


Example:
Towngas 1.23
Q (Scm/h Naturalgas) x 0.78 = Q (Scm/h Air)
1 Scm/h Naturalgas = 0.78 Scm/h Air Hydrogen 3.04

Type F
ct1-2019
FLOW RATE TABLES AC5 for natural gas, ρn=0,83 kg/m3
F40/S
Outlet Inlet Pressure (bar)
Pressure
(mbar)
0.5 1.0 1.5 2 2.5 3 3.5 4 6 10 12 16 19 25

21 310 465 630 742 865 990 1045 1109 1109 1109 - - - -

BP 50 306 460 625 736 859 986 1040 1103 1103 1103 - - - -

80 304 459 623 734 857 985 1039 1101 1101 1101 - - - -

100 302 457 620 730 855 983 1035 1100 1100 1100 - - - -

150 300 455 615 728 850 981 1033 1096 1096 1096 - - - -

200 295 450 612 724 843 978 1028 1094 1094 1094 - - - -
MP
250 280 435 608 719 838 976 1022 1092 1092 1092 - - - -

300 278 425 575 717 830 975 1018 1089 1089 1089 - - - -

350 275 422 572 715 826 972 1015 1088 1088 1088 - - - -

500 - 340 490 630 763 985 1120 1245 1760 1760 1760 1760 1760 1760

1000 - - 420 620 751 985 1110 1235 1810 1810 1810 1810 1810 1810

AP 2000 - - - - 680 910 975 1085 1655 1655 2680 2680 2680 2680

3000 - - - - - - 748 925 2210 2590 2750 2750 2750 2750

4000 - - - - - - - - 2260 2260 2910 2910 2910 2910

• Order to limit the noise emission it is recommended not to exceed a gas velocity of 150 m/s at the regulator outlet.
• With noice silencer approximately 10 % loss of capacity
• SSV does not reduce capacity

Flow with Other Gases Correction Factor Fc at 15°C


Propane 0.64

Butane 0.55
In the tables above, the flow is in (n)m3/h natural gas with a
density 0.61 and temperature 15°C. To convert to othergas Oxygen 0.76
flow, using the following formula: Air 0.78
Nitrogen 0.81
Biogas 0.85
Q (Scm/h Naturalgas) x Fc = Q (Scm/h Xgas)
Example: Towngas 1.23
Q (Scm/h Naturalgas) x 0.78 = Q (Scm/h Air)
1 Scm/h Naturalgas = 0.78 Scm/h Air Hydrogen 3.04

ct1-2019
FLOW RATE TABLES AC5 for natural gas, ρn=0,83 kg/m3
F50/S
Outlet Inlet Pressure (bar)
Pressure
(mbar)
0.5 1.0 1.5 2 2.5 3 3.5 4 6 10 12 16 19 25

21 375 665 794 940 1075 1110 1110 1110 1110 1110 - - - -

BP 50 362 574 788 932 1069 1101 1101 1101 1101 1101 - - - -

80 357 568 787 931 1067 1098 1098 1098 1098 1098 - - - -

100 298 623 778 1075 1251 1441 1615 1804 1804 1804 - - - -

150 291 619 781 1078 1252 1444 1618 1807 1807 1807 - - - -

200 288 615 784 1081 1257 1448 1622 1809 1809 1809 - - - -
MP
250 284 608 788 1084 1260 1452 1628 1812 1812 1812 - - - -

300 280 602 790 1090 1263 1455 1631 1816 1816 1816 - - - -

350 276 599 796 1096 1268 1461 1637 1821 1821 1821 - - - -

500 - 556 720 968 1190 1340 1610 1815 1940 1790 1790 1790 1790 1790

1000 - - 540 890 1190 1452 1614 1815 2190 2355 2355 2355 2355 2355

AP 2000 - - - - 881 899 1260 1480 2014 3415 3415 3415 3415 3415

3000 - - - - - - 880 1079 1918 4680 4680 4680 4680 4680

4000 - - - - - - - - 2467 3840 4480 5540 5540 5540

• Order to limit the noise emission it is recommended not to exceed a gas velocity of 150 m/s at the regulator outlet.
• With noice silencer approximately 10 % loss of capacity
• SSV does not reduce capacity

Flow with Other Gases Correction Factor Fc at 15°C


Propane 0.64

Butane 0.55
In the tables above, the flow is in (n)m3/h natural gas with a
density 0.61 and temperature 15°C. To convert to othergas Oxygen 0.76
flow, using the following formula:
Air 0.78
Nitrogen 0.81
Biogas 0.85
Q (Scm/h Naturalgas) x Fc = Q (Scm/h Xgas)
Example: Towngas 1.23
Q (Scm/h Naturalgas) x 0.78 = Q (Scm/h Air)
1 Scm/h Naturalgas = 0.78 Scm/h Air Hydrogen 3.04

Type F
ct1-2019
A
D
OPERATION OF THE REGULATOR F SERIE B
1. Check pressure gauge, that inlet pressure should be suitable for
the gas system.
2. Check the filter cartridge, cartridges must be clean and
undeformed.
3. Check if the manual relief valve is in the closed position.
4. Open inlet main valve slowly. C
5. Check outlet pressure gauge,

if the gas pressure is not at the desired level;

‘A’ Turn the cap and remove. Outlet pressure can be adjusted by
appropriately turning the internal adjustment ring nut ‘B’ clockwise to
increase it and counterclockwise to decrease it with tube Spanner
24mm. For outlet pressures outside the specified range, ‘C’ spring
change will be required. Place ‘A’ aluminum cap back onto the
regulator top, make sure to put the ‘D’ O-ring.

Type F
ct1-2019
SSV SETTING

Shut-off setting in case of overpressure;


1. ‘E’ Turn the cap and remove.
2. ‘B’ Turn the external adjusting screw, using a tube spanner 22mm.
3. ‘B’ Turning clockwise: increase in the upper shut down pressure.
4. Turning counter-clockwise: reduction in the upper shut down
pressure.

Shut-off setting in case of overpressure;


1. ‘E’ Turn the cap and remove.
2. Turn the internal adjusting screw ‘D’ using a tube spanner 17mm. A
3. Turning clockwise: increase in the lower shut down pressure.
4. Turning counter-clockwise: reduction in the lower shut down
pressure.
5. Screw on the cap ‘E’ again.
B

Type F
ct1-2019
POSTER

Inlet Pressure

Outlet Pressure

Outlet Pressure

Type F
ct1-2019
REMARKS:
………………………………………………………………………………………………….
…………………………………………………………………………….......................
………………………………………………………………………………………………….
…………………………………………………………………………….......................
………………………………………………………………………………………………….
…………………………………………………………………………….......................
………………………………………………………………………………………………….
…………………………………………………………………………….......................
………………………………………………………………………………………………….
…………………………………………………………………………….......................
………………………………………………………………………………………………….
…………………………………………………………………………….......................

High Pressure Gas Filters

Safety Relief Valves

GASTECH LTD.
34800 – İstanbul -TURKEY Zero Gas Governor
Phone : +90 216 465 14 74
Fax : +90 216 465 14 77
E-mail : [email protected]
Web : www.gastech.com.tr

ct1-2019