This document provides evaluation criteria for building materials, including: 1. Technical specifications for items like submersible pumps, engines, cables, inverters, solar panels, stopcocks, pipes, and reinforcement. 2. Requirements for items to meet standards like ISO, BS, DIN, and performance specifications. 3. Requirements for suppliers to provide samples, catalogues, manufacturer information, and warranties.

Uploaded by

social media
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
58 views1 page

Evaluation Criteria For The Quality of Building Materials

This document provides evaluation criteria for building materials, including: 1. Technical specifications for items like submersible pumps, engines, cables, inverters, solar panels, stopcocks, pipes, and reinforcement. 2. Requirements for items to meet standards like ISO, BS, DIN, and performance specifications. 3. Requirements for suppliers to provide samples, catalogues, manufacturer information, and warranties.

Uploaded by

social media
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 1

Evaluation Criteria for the quality of Building materials ‫مع&ايير ت &&قييم& ج&ودة مواد ا&&لبناء‬ Offered Specifications &‫ا&&لموا&صفاتا&&لمع&روضه‬

Catalogue attached
Sample Provided
(Yes/No)
NO. Sample according to specs. ‫ العينة حسب المواصفات‬Building Materials (BMs) technical specifications Offered Specifications T‫روضه‬T‫لمع‬TT‫لمواصفاتا‬TT‫ا‬ Manufacturer T‫لمصنع‬TT‫ا‬ Country of origin ‫لمنشأ‬TT‫لد ا‬TTT‫ب‬ (Yes/No)
‫الكاتالوج أجب بنعم او ال اذا كان‬
‫العينات أجب بنعم او ال‬
‫مرفق‬

Submersible pump with same Lifting capacity, quantity of water and Watt as the specification detailed
in the BOQs.
The pump should be made from Stainless steel according to the Universal standard ISI 304 as well as
1 Submersible pump ‫المضخة الغاطسة‬
the column made from stainless steel according to the global standard ISI 316 .
The pump efficiency must be more than 70% efficiency.
Fans material is bronze / stainless steel.

Submersible engine with a casing must be made from stainless steel according to the Universal
standard ISI 304 as well as the cover should be made of stainless steel according to the global standard
ISI 316 . It should work at a variable frequency of (30 -50) Hz and the RPM is not less than 2900 rpm.
2 Submersible engine ‫ المحرك الغاطس‬The temperature resistance is at least 35 °c and the degree of protection of IP68 and 50 °c depending
on the water temperature in the ground of water source. The Submersible Engine can be operated with
the solar power source and the power source . The submersible pump capacity is as per the BOQs and
the voltage is 380/415 volts.

Waterproof copper cables, can resist moisture and high temperature, and insulated from water leakage.
Cable connection from
‫ الكابل من نظام التشغيل إلى المحرك‬The cable should be elastic and double Insulating HO7RN-F type, has 2 layers and with size as
3 operating system to
‫ الغاطس‬mentioned in the BOQs. The voltage test should be from 450 to 1000 volts of the operating system to the
submersible Engine
submersible Engine

The capacity of the Converter should be as mentioned in the BOQs with warranty at least for 1 year.
The Converter should has a variable frequency that fits with the pump, can resist the maximum point of
the panels stress. In addition, the converter should has the follow specifications :
4 Inverter ‫ المحول او االنفرتر‬1- Works on the DC voltage system at least 750 volts.
2- Works on voltage system for the entering DC 500 – 650 v.
3- Works on voltage system for the exit AC 380 – 415 V.
4- Frequency between 0 – 60 Hz.

The solar panels should be with total capacity as mentioned in the BoQs and meeing the below
specifications:
 The Solar panels efficient must be more than 21% .
 The Solar panels type must be(Mono).
 The Solar panels Category must be (class A).
 The Solar panel stress can reach to 1000 Volt.
5 Solar panels ‫األلواح الشمسية‬
 The Solar panels can Resist temperature 40 ° to 85 °c.
 The Solar panels can resist a mechanical pressure more than 5,400 Pascal.
 The Supplier must attach guarantee for 25 years to ensures that the performance decrease
percentage is not less than 80% after 25 years, and guarantee for 10 years for any defect.
The Solar panels,must be meet the universal standards IEC 61215, IEC 61730-(1) and ICE617302
(2).

Withstands high pressures of more than 24 bar, and is in conformity with the British specifications
BS1414, and the thermal pressure is in accordance with the specifications of BS1560. The valves shall
6 Stopcock/Valves ‫محابس‬
be solid, manufactured from the materials mentioned in BS1560 specifications and the valve body shall
be made of stainless steel or ductile iron.
Made of polyethylene according to the diameters shown in the BOQs. They must conform to German
7 Polyethylene pipes ‫ماسورة البولي يوريثين‬
.specifications (DIN-8075, DIN-8074) and bear the required pressure of 16 kg/cm2
Galvanized pipe 3” pressure 35 ‫ انش ضغط‬3 ‫ماسورة حديد مجلفن‬
8 The pipes are made of galvanized iron with 3"or 110mm diameters and with pressure of 35 kg/cm2.
35kg/cm2 2
‫ سم‬/‫كجم‬
Galvanized pipe 2” pressure 16 ‫ انش ضغط‬2 ‫ماسورة حديد مجلفن‬
9 The pipes are made of galvanized iron with 2"or 75mm diameters and with pressure of 20 kg/cm2.
20kg/cm2 2
‫ سم‬/‫كجم‬
All reinforcement shall be free of loose mill scale or rust, grease, paint, or other substances likely to
reduce the bond between the steel and concrete.
Reinforcement should be in accordance with B.S 4466 (1969). Reinforcement must be not having
10 Steel Reinforcement ‫ حديد التسليح‬welded joints.
Unless otherwise agreed the Contractor will be required to submit a test certificate of the rolling.
Reinforcement shall be stored on racks above ground level.

50 Kg Bag portland composite cement, the minimum compressive strength of cement should be 175 kg/
m². Portland cement must be of the best grades of modern production, and fulfill the requirements
stipulated in British Standards No. 12 of 1958 where portland cement must have the following chemical
11 Cement ‫ اسمنت‬compositions: aluminum oxide, ferric oxide, magnesium oxide, sulfur trioxide, tricalcium silicate,
dicalcium silicate, tricalcium aluminate, and tetracalcium aluminofernite. The cement that harden or
whose production date has passed 12 months according to the factory certificate that must be secured
by the contractor, are not used.