XR70CX
Operating Manual
SAFETY PRECAUTIONS
Check the supply voltage is correct before connecting the controller.
Do not expose to water or moisture: use the controller only within the operating limits avoiding
sudden temperature changes with high atmospheric humidity to prevent formation of condensation
Warning: disconnect all electrical connections before any kind of maintenance.
The controller must not be opened.
General Description
The XR70CX, format: 32 x 74 x 60 mm, is microprocessor based controller, suitable for
applications on medium or low temperature ventilated refrigerating units. It has three relay outputs
to control compressor, fan, and defrost. It also has three NTC probes, the first one for temperature
control, the second one, to be located onto the evaporator, to control the defrost termination
temperature and to manage the fan, the third one, optional, to connect to the HOT KEY terminals
to signal the condenser temperature alarm or to display a temperature.
Regulation
The regulation is performed according to the
air temperature probe with a positive
differential from the set point: if the air
temperature increases and reaches set point
plus differential the compressor is started and
then turned off when the temperature reaches
the set point value again.
Defrost
The controller goes into defrost mode every 6 hours. It enables the electric defrost heater for 36
minutes or until the evaporator sensor reaches 60ºF—whichever happens first. Immediately after
defrost the controller waits for 1 minute before resuming normal operation. This allows time for
water droplets which may have formed on the coil to drip off into the drip pan.
1. Push and immediately release the SET key, the set point will be showed.
2. Push and immediately release the SET key or wait about 5 seconds to return to normal
operation.
1. Push the SET key for more than 2 seconds to change the Set point value.
2. The value of the set point will be displayed and the "°C" or "°F" LED starts blinking;
3. To change the set value, push the or arrows within 10 seconds.
4. To input the new set point value, push the SET key again or wait 10 seconds.
HOW TO START A MANUAL DEFROST
Push the defrost key for more than 2 seconds and a manual defrost will start
HOW TO CHANGE A PARAMETER VALUE
HOW TO MOVE A PARAMETER FROM THE SECOND LEVEL TO THE FIRST LEVEL AND
VICE VERSA.
Each parameter present in the LEVEL 2 MENU can be removed or put into "THE FIRST LEVEL"
(user level) by pressing SET + . When a parameter is present in First Level, the decimal point is
on.
Keep pressed together for more than 3 seconds the and keys till the “Pon” message will be
displayed.
Parameters
REGULATION
Hy Differential: (0,1°C to 25°C) Intervention differential for set point. Compressor cut in is
SET POINT + differential (Hy). Compressor cut out is when the temperature reaches
the set point.
LS Minimum SET POINT: (-55°CtoSET/-58°FtoSET): Sets the minimum value for the set
point..
US Maximum SET POINT: (SETto99°F/ SETto99°F). Set the maximum value for set
point.
ot First probe calibration: (-9.9to9.9°F) allows to adjust possible offset of the first
probe.
P2P Evaporator probe presence: n= not present; y= the defrost stops by temperature.
oE Second probe calibration: (-9.9to9.9°F) allows to adjust possible offset of the second
probe.
P3P Third probe presence: n=not present. ; y=present:, the terminal operates as third
probe.
O3 Third probe calibration: (-9.9to9.9°F) allows to adjust possible offset of the third
probe.
P4P Third probe presence: n=not present. ; y=present:, the terminal operates as fourth
probe.
O4 Third probe calibration: (-9.9to9.9°F) allows to adjust possible offset of the fourth
probe.
odS Outputs activation delay at start up: (0to99min) This function is enabled at the initial
start up of the instrument and inhibits any output activation for the period of time set in
the parameter.
AC Anti-short cycle delay: (0to50 min) minimum interval between the compressor stop
and the following restart.
rtr Percentage of the second and first probe for regulation (0÷100; 100 = P1, 0 =
P2): it allows to set the regulation according to the percentage of the first and second
probe, as for the following formula (rtr(P1-P2)/100 + P2).
COn Compressor ON time with faulty probe: (0to99 min) time during which the
compressor is active in case of faulty thermostat probe. With Cy=0 compressor is
always Off (Hidden).
CCt Compressor ON time during continuous cycle: (0.0to24.0hour; res. 10min) Allows to
set the length of the continuous cycle: compressor stays on without interruption for the
CCt time. This can be used, for instance, when the room is filled with new products.
FnC Fans operating mode: C-n= runs with the compressor, OFF during defrost; o-n =
continuous mode, OFF during defrost; C-Y = runs with the compressor, ON during
defrost; o-Y = continuous mode, ON during defrost;
Fnd Fans delay after defrost: (0to255min) Interval between end of defrost and evaporator
fans start.
Fct Temperature differential avoiding short cycles of fans (0to59°C; Fct=0 function
disabled). If the difference of temperature between the evaporator and the room
probes is more than the value of the Fct parameter, the fans are switched on.
FSt Fans stop temperature: (-50to50°C/122°F) setting of temperature, detected by
evaporator probe, above which fans are always OFF.
Fon Fan ON time: (0to15 min) with Fnc = C_n or C_y, (fan activated in parallel with
compressor). It sets the evaporator fan ON cycling time when the compressor is off.
With Fon =0 and FoF ≠ 0 the fan are always off, with Fon=0 and FoF =0 the fan are
always off.
FoF Fan OFF time: (0to15 min) with Fnc = C_n or C_y, (fan activated in parallel with
compressor). It sets the evaporator fan off cycling time when the compressor is off.
With Fon =0 and FoF ≠ 0 the fan is always off, with Fon=0 and FoF =0 the fan is
always off.
FAP Probe selection for fan management: nP = no probe; P1 =thermostat probe; P2 =
evaporator probe; P3 =configurable probe; P4 = Probe on Hot Key plug.
ALARMS
i1P Digital input polarity: oP: the digital input is activated by opening the contact; CL: the
digital input is activated by closing the contact.
i1F Digital input configuration: EAL = external alarm: “EA” message is displayed; bAL =
serious alarm “CA” message is displayed. PAL = pressure switch alarm, “CA”
message is displayed; dor = door switch function; dEF = activation of a defrost cycle;
AUS =not enabled; Htr = kind of action inversion (cooling – heating); FAn = not set it;
ES = Energy saving. did: (0to255 min) with i1F= EAL or i1F = bAL digital input
alarm delay: delay between the detection of the external alarm condition and its
signalling. with i1F= dor: door open signalling delay with i1F = PAL: time for
pressure switch function: time interval to calculate the number of the pressure
switch activation.
nPS Pressure switch number: (0 to15) Number of activation of the pressure switch,
during the “did” interval, before signalling the alarm event (I2F= PAL).If the nPS
Adr Serial address (1to244): Identifies the instrument address when connected to a
ModBUS(RTU) compatible monitoring system.
PbC Type of probe: it allows to set the kind of probe used by the instrument: PbC = PBC
probe, ntc = NTC probe.
onF on/off key enabling: nu = disabled; oFF = enabled; ES = not set it.
dP1 Thermostat probe display
dP2 Evaporator probe display
dP3 Third probe display- optional.
dP4 Fourth probe display.
rSE Real set point: it shows the set point used during the energy saving cycle or during
the continuous cycle.
rEL Software release for internal use.
Ptb Parameter table code: read only.
Installation and Mounting
Electrical Connections
The instrument is provided with screw terminal block to connect cables with a cross section up to
2.5 mm2. Before connecting cables make sure the power supply complies with the instrument’s
requirements. Separate the probe cables from the power supply cables, from the outputs and the
power connections. Do not exceed the maximum current allowed on each relay, in case of heavier
loads use a suitable external relay.
PROBES
The probes shall be mounted with the bulb upwards to prevent damages due to casual liquid
infiltration. It is recommended to place the thermostat probe away from air streams to correctly
NOTE: The "Er" message is displayed for failed programming. In this case push again key if
you want to restart the upload again or remove the "Hot key" to abort the operation.
HOW TO PROGRAM A CONTROLLER USING THE HOT KEY (DOWNLOAD)
Alarm Signaling
Message Cause Outputs
"P1" Room probe failure Compressor output according to "Cy" and "Cn"
"P2" Evaporator probe failure Defrost end is timed
“P3” Product probe failure Outputs unchanged
“P4” Not used N/A
"HA" Maximum temperature alarm Outputs unchanged
"LA" Minimum temperature alarm Outputs unchanged
“HA2” Not used N/A
“LA2” Not used N/A
"EA" External alarm(not used) Outputs unchanged
"CA" Serious external alarm(not used) All outputs off
"dA" Door open(not used) Compressor and fans restart
ALARM RECOVERY
Probe alarms P1”, “P2”, “P3” and “P4” start some seconds after the fault in the related probe; they
automatically stop some seconds after the probe restarts normal operation. Check connections
before replacing the probe. Temperature alarms “HA”, “LA” “HA2” and “LA2” automatically stop as
soon as the temperature returns to normal values. Alarms “EA” and “CA” (with i1F=bAL) recover
Technical Data
Housing: self-extinguishing ABS
Case: front 32x74 mm; depth 60mm
Mounting: panel mounting in a 71x29mm panel cut-out
Protection: IP20
Frontal protection: IP65
Connections:
1 through 8: ¼ inch spade terminal
9 through 12: screw terminal block ≤ 2.5 mm2 wiring
Power supply: according to the model: 110Vac ±10%, 50/60Hz, 230Vac +10%to-15%
Power absorption: 3VA max
Display: 3 digits, red LED, 14.2 mm high
Inputs: Up to 4 NTC
Relay outputs: compressor SPST 16(6)A 250Vac
defrost: SPDT 8(3) A, 250Vac
fan: SPST 5A, 250Vac
aux: SPDT 8(3) A, 250Vac
Data storing: on the non-volatile memory (EEPROM).
Kind of action: 1B
Pollution grade: 2
Software class: A
Rated impulsive voltage: 2500V
Over-voltage Category: II
Operating temperature: 0to60 °C (32to140°F)
Storage temperature: -30to85 °C (-22to185°F)
Relative humidity: 20to85% (non-condensing)
Measuring and regulation range: NTC -40to110°C (-40to230°F)
Resolution: 0.1 °C or 1°C or 1 °F (selectable)
Accuracy (ambient temp. 25°C): ±0.7 °C (1.3°F) ±1 digit