BMS 485 Instruction
BMS 485 Instruction
and BMS
Version information
version The date of describe The author
V20191124 The first draft
V20200325 Update some description information, change 0xA10 to 0xD2,
dedicated charger switch refers to
make
V20200325 Determine the transmitted data baud rate of 115200
V20200329 Update the optimization instruction table and redefine the data
identifier
V20200329 Added instruction to read all data at once.
V20200427 Write ID write factory date for description
V20200429 Add 0xB7 address software version number
V20200429 The address 0x8B 0x8C is described in detail
10 The checksum 4 Accumulated checksum (high 2 bytes for CRC not yet
enabled to fill 0, low 2
Byte for cumulative check)
0x05 Pair code instruction To modify the parameters, the first command is
correct before the change
0x06 Read all the data Read all the data in the ID code table at one time
9 End of 1 0x68
identity
10 The 4
checksum
BMS reply
9 End of 1 0x68
identity
10 The 4
checksum
BMS reply
Note :(The background data identification code is 0x00 when reading all data)
Ex. :
0x0001: Represents the low volume alarm value
0x0001 ----> Low Capacity
Alarm
0-bit charging MOS tube state 1 on 0 off T h i s i s f o r u p l o a d i n g p r o m p t s
1 bit discharge MOS tube state 1 on 0 off T h i s i s f o r u p l o a d i n g
prompts.
2 bit equalization switching state 1 on,0 off this is for the upload prompt
R 0X8c Battery status 2
The 3-bit battery is down 1 normal.0 dropped, this is the upload prompt,
information
4-15 bits:
reserved
example:
00 01: The charging MOS tube is turned on
RW 0x8e Total voltage overvoltage 2 HEX 1000-15000. (10mV) Minimum unit: 10mV
protection
RW 0x8f Total voltage under 2 HEX 1000-15000. (10mV) Minimum unit: 10mV
voltage protection
0 - 1000 MV
RW 0x96 Core differential pressure 2 Hex
protection value
RW 0 xae Guard plate address 1 Hex This one is reserved, used for cascading,
RW 0 xaf The battery type 1 HEX 0: lithium iron phosphate, 1: ternary, 2: lithium titanate
W 0 x BC factory data reset 1 He X 1: Restore (only restore the factory base parameters)
W 0 x BD Remote Upgrade 1 He X 1 Start (wait for identification reply when sending the file)
Identification
W 0 x BE The cell turns off GPS 2 Hex Unit: MV (turn off the power supply to GPS when low voltage is detected)
with low voltage
W 0 x BF Cell low voltage 2 Hex Unit: MV (turn on the power to GPS when the recovery
recovery GPS voltage value is detected)
Default: 0 x 00
0 x 01: Redefine the 0 x 84 current data as 10 mA, with the highest bit being 0 for
R 0xC0 Agreement version 1 Hex discharge and 1 for charge
number If the discharge is 20A, the transmitted data is 2000 (0 x 07 D 0)
If the charge is 20A, then the transfer data is 34768 (0 x 87 D 0)
【 note 】
1. All fields marked with R or RW in 0x79 ~ 0XB9 should be reported. For those not reported in the shipped old version, try to
upgrade.If it is not convenient to upgrade, please contact our technical support at 13755639263/13480924112
2. Name 0xBA manufacturer ID. This field is mainly used for the electric changing cabinet. If there is a demand for the electric
changing cabinet, this field must be added.