1 SB 2002-4
Rev MR2002
Service Bulletin [2002-4]
SLC-500 Error Codes
If this bit is ever set upon execution of the
END, TND, or REF instruction, major error
(0020) will be declared. To avoid this type
of major error from occurring, examine the
state of this bit inside your fault routine,
take appropriate action, and then clear bit
S:5/3 using an OTU instruction with S:5/3
or a CLR instruction with S:5.
Application example:
Suppose you are executing your
fault routine for a fault code 0016H
Startup Protection. At rung 3 inside
this fault routine, a TON containing a
negative preset is executed. When
rung 4 is executed, fault code 0016H
is overwritten to indicated code 0034H,
and S:5/3 is set. If your fault routine did not
determine that S:5/3 was set, major error
0020H would be declared at the end of the
first scan. To avoid this problem, examine
S:5/3, followed by S:6, prior to returning
from your fault routine. If S:5/3 is set, take
appropriate action to remedy the fault,
then clear S:5/3.
S:5/4 Dynamic M0-M1 Referenced on Disabled Slot
Config Bit This bit is set whenever any instruction
references an M0 or M1 module file
element for a slot that is disabled (via its
I/O slot enable bit). When set, the bit
indicates that an instruction could not
execute properly due to the unavailability
of the addressed or M0 or M1 data.
If this bit is ever set upon execution
of the END, TND, or REF instruction,
major error (0020) is declared. To avoid this
type of major error from occurring,
examine the state of this bit following a
M0-M1 referenced instruction, take
appropriate action, and then clear bit S:5/4
using and OTU instruction with S:5/4 or a
CLR instruction with S:5.
S:5/5 to N/A Reserved for minor errors that revert to
S:5/7 major errors at the end of the scan.
S:5/8 Status Memory Module Boot Bit
When this bit is set by the processor,
it indicates that a memory module program
has been transferred to the processor. This
bit is not cleared by the processor. Your
program can examine the state of this bit
2 SB 2002-4
Rev MR2002
Service Bulletin [2002-4]
SLC-500 Error Codes
on entry into the REM Run mode to
determine if the memory module content
has been transferred.
Bit S:1/15 will be set to indicate REM Run
mode entry. This information is useful
when you have an application that contains
retentive data and a memory module that
has only bit S:1/10 set (Load Memory
Module on Memory error). Use this bit to
indicate that retentive data has been lost.
This bit is also helpful when using bits
S:1/11 (Load Memory Module Always) or
S:1/12 (Load Memory Module Always and
Run) to distinguish a power up REM Run
mode entry from a REM Program (or REM
Test) mode to REM run mode entry.
Status Memory Module Password
Mismatch
Bit This bit is set on REM Run mode entry,
whenever loading from the memory
module is specified (word 1, bits 11 or 12)
and the processor user program is
password protected, and the memory
module program does not match that
password. Use this bit to inform your
application program that an autoloading
memory module is installed but did not
load due to password mismatch.
S:5/10 Status STI (Selectable Timed Interrupt) Overflow
Bit
This bit is set whenever the STI timer
expires while the STI routine is either
executing or disabled and the pending bit is
already set.
S:5/11 Status Battery Low Bit
This bit is set whenever the Batter Low LED
is on. The bit is cleared when the Batter
Low LED is off.
S:5/12 Status Discrete Input Interrupt Overflow Bit
This bit is set whenever the DII interrupt
occurs while still executing the DII
subroutine or whenever the DII interrupt
occurs while pending or disabled.
S:5/13 Dynamic Unsuccessful Operating System
Config Load Was Attempted
This bit is set whenever an operating
system memory module load is attempted
and is unsuccessful. Unsuccessful loads can
occur when either the protection jumper is
3 SB 2002-4
Rev MR2002
Service Bulletin [2002-4]
SLC-500 Error Codes
in the protect position or is missing, or if
the operating system memory module is
incompatible with the SLC 5/03, SLC
5/04, or SLC 5/05 processors’ hardware
platform. Examine the state of this bit with
your user program to diagnose the
condition
S:5/14 Status Channel 0 Modem Lost
This bit indicates the status of the modem
connected to Channel 0 (RS232 serial port).
The state of the bit is determined by:
• the protocol Channel 0 is configured
for,
• the Control Line selected, and
• the states of DCD (Data Carrier
Detect) and DSR (Data Set Ready).
If the bit is set, then the modem is not
properly connected to Channel 0 or it is in a
state where unreliable communication
exchanges may take place via Channel 0.
The following conditions apply:
• If Channel o is disabled or configured
for DH485, the bit is always cleared.
• If Channel 0 is configured for one of
the DF-1 protocols in System Mode or
Generic ASCII in User Mode, then the
Control Line selection determines
how DCD and DSR affect the modem
status:
o If Control Line=NO
HANDSHAKING: The bit is always
set.
o If Control Line=FULL-DUPLEX or
HALF-DUPLEX WITHOUR
CONTINUOUS CARRIER: The bit
is set if DSR goes inactive and
cleared when DSR goes active.
(DCD has no effect on modem
status in this case).
o If Control Line=HALF-DUPLEX
WITH CONTINUOUS CARRIER:
The bit is set is either DSR goes
inactive or DCD remain inactive
for more than 10 seconds. This
bit is cleared when both DSR and
DCD go active.
S:5/15 Status ASCII String Manipulation Error
This bit applies to SLC5/03 (OS301and
higher), SLC 5/04, and SLC 5/05 processors.
4 SB 2002-4
Rev MR2002
Service Bulletin [2002-4]
SLC-500 Error Codes
This bit is set to 1 when an attempt is made
to process a string using an ASCII
instruction that exceeds 82 characters in
length.
S:6 Status Major Error Fault Code
A hexadecimal code is entered in this word
by the processor when a major error is
declared. Refer to S:1/13. The code defines
the type of fault, as indicated on the
following pages. This word is not cleared by
the processor. Error codes are presented,
stored and displayed in a hexadecimal
format. Refer to appendix G for more
information on the hexadecimal numbering
system.
If you enter a fault code as a parameter in
an instruction in your ladder program, you
must convert the code to decimal. For
example, if you program an EQU
instruction to go true when the error 0016
occurs, enter S:6 as source A and 22, the
5 SB 2002-4
Rev MR2002
Service Bulletin [2002-4]
SLC-500 Error Codes
condition of the processor).
Recoverable User Fault
The fault routine may clear the fault by
clearing bit S:1/13.
6 SB 2002-4
Rev MR2002
Service Bulletin [2002-4]
SLC-500 Error Codes
SAFETY BULLETIN
This notice is issued to advise you that some previously accepted shop practices may not be
keeping up with changing Federal and State Safety and Health Standards. Your current shop
practices may not emphasize the need for proper precautions to insure safe operation and use
of machines, tools, automatic loaders and allied equipment and/or warn against the use of
certain solvents or other cleaning substances that are now considered unsafe or prohibited by
law. Since many shop practices may not reflect current safety practice and procedures,
particularly with regard to the safe operation of equipment, it is important that you review your
practices to ensure compliance with Federal and State Safety and Health Standards.
IMPORTANT
The operation of any machine or power-operated device can be extremely hazardous unless
proper safety precautions are strictly observed. Observe the following safety precautions:
ALWAYS:
Be sure proper guarding is in place for all pinch, catch, shear, crush, and nip points.
Be sure that all personnel are clear of the equipment before starting it.
Turn the main electrical panel off and lock it out in accordance with published
lockout/tagout procedures prior to making adjustments, repairs, and maintenance.
Wear appropriate protective equipment such as safety glasses, safety shoes, hearing
protection, and hard hats.
Keep chemical and flammable material away from electrical or operating equipment.
Maintain a safe work area that is free from slipping and tripping hazards.
Be sure appropriate safety devices are used when providing maintenance and repairs to
all equipment.
7 SB 2002-4
Rev MR2002
Service Bulletin [2002-4]
SLC-500 Error Codes
NEVER:
Modify machinery in any way without prior written approval of the Besser Engineering
Department.
Operate any equipment while any part of the body is in the proximity of potentially
hazardous areas.
It is important that you review Federal and State Safety and Health Standards on a continual
basis. All shop supervisors, maintenance personnel, machine operators, tool operators, and any
other person involved in the setup, operation, maintenance, repair or adjustment of Besser-
built equipment should read and understand this bulletin and Federal and State Safety and
Health Standards on which this bulletin is based.