0% found this document useful (0 votes)
31 views12 pages

Tarjeta de Expansión Neptronic - CMMB106 - 10162022

Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
31 views12 pages

Tarjeta de Expansión Neptronic - CMMB106 - 10162022

Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 12

Remote I/O Communication Module

Specification and Installation Instructions

Models
CMMB106

Description
The CMMB extends your BACnet or Modbus network when your
application requires additional inputs and outputs on a physical
controller. Combining the 20 inputs and outputs of the CMMB with your
Building Automation System provides simple expansion of a new or
existing controller and reduces unnecessary costs of additional
components.

Features
Power & Communication
 24Vac or 30Vdc supply CMMB106
 BACnet® MS/TP or Modbus communication port (selectable)
 Up to 2 STLD24 thermostats
Network Communication
Inputs & Outputs  BACnet® MS/TP or Modbus communication port
 8 universal inputs (selectable via DIP switch)
 2 digital inputs  Select MAC address via DIP switch or via network
 2 universal outputs (supervised)
BACnet®
 2 analog outputs (supervised)
 MS/TP @ 9600, 19200, 38400 or 76800 bps
 6 digital outputs (supervised)
 Automatic baud rate detection
Installation  Automatic device instance configuration
 10 override switches to manually control each output  Copy & broadcast configuration to other CMMB modules
 LED status indication of each input and output
Modbus
 DIN rail mounting
 Modbus @ 9600, 19200, 38400 or 57600 bps
 Removable, non-strip, raising clamp terminals
 RTU Slave, 8 bits (configurable parity and stop bits)
 Connects to any Modbus master

Technical Specifications
Specifications CMMB106
Thermostats Up to 2 STLD24 thermostats (via independent Modbus network), via 4-wire connection
Input Voltage 24 Vac or 27-33 Vdc
Consumption 8VA (331mA @ 24 Vac)
Universal Inputs (12-bit) 8 [0-10Vdc, 10KΩ (Thermistor type III), on/off (dry contact), 4-20mA] / 12-bit resolution
Digital Inputs 2 [normally open/closed or direct/reverse] / 12-bit resolution
Universal Outputs 2 [0-10Vdc, pulsed signal (20mA drive), on/off, 4-20mA] / 12-bit resolution
Analog Outputs 2 [0-10Vdc] / 12-bit resolution
Digital Relay Outputs 6 [normally open/closed, independent common per relay, 5A resistive]
BACnet BACnet® MS/TP @ 9600, 19200, 38400 or 76800 bps (BAS-C)
Modbus RTU slave @ 9600, 19200, 38400 or 57600. Selectable parity and stop bit
configuration:
Modbus  No parity, 2 stop bit
 Even parity, 1 stop bit
 Odd parity, 1 stop bit
Communication Connections 24 AWG twisted-shield cable (Belden 9841 or equivalent)
Electrical Connections 0.8 mm2 [18 AWG] minimum
Operational Temperature 0ºC to 50ºC [32ºF to 122ºF]
Storage Temperature -30ºC to 50ºC [-22ºF to 122ºF]
Relative Humidity 5 a 95% non condensed
Weight 0.4 kg [0.9 lb]
Dimensions A C

A = 6.30” / 160 mm
B = 5.00” / 126 mm
C = 2.25” / 57 mm
B
1 2 3 4

ON
1 2 3 4 5 6 7 8

CMMB106-BACnet-Modbus-150917-ESA.docx Page | 1
Remote I/O Communication Module
Specification and Installation Instructions

Connections and Configurations


Please note that all jumper settings must also be set to the same value through BACnet. Some additional configurations are only
available through BACnet (see Network Conditionson page 4).

Network | DS1
4 Mode
OFF BACnet*
MAC Address | DS2
ON Modbus
The 8 DIP switches Baud Rate | DS1
3 Mode Options
represent a binary logic to
If BACnet 1 2 Result
calculate the MAC address.
OFF Auto Detect* OFF OFF 9,600
ON Manual (see DS1-1 & DS1-2) ON OFF 19,200
Default = all OFF
OFF ON 38,400
If Modbus
ON ON BACnet: 76,800
BACnet all OFF = 0 OFF Config via Modbus Register AO3-AO4 Signal | JP1-JP2
Modbus: 57,600
Modbus all OFF = 1 ON No parity, 2 stop bits
* default setting
0-10 Vdc*

End of Line | JP3 / JP4 4-20 mA


None* * default setting
120 Ohms 1 2 3 4 5 6 7 8 1 2 3 4 JP1 = AO4
POWER
Universal Outputs | TB1
* default setting ON ON AO4 ** Selectable **
STATUS DS2 DS1
Network Port | TB10 JP3
COM AO4: Universal Output 4
COM: Common
TX RX

A+: BACnet/Modbus A+ A+ BACnet/Modbus AO3


AO3: Universal Output 3
B-: BACnet/Modbus B- B- JP2 = AO3
JP4
Analog Outputs | TB2
TX RX

STLD24 Port | TB11 A+ Up to two STLD24 AO2


** 0-10 Vdc **
** 2 STLD24 thermostats ** Thermostats COM
B-
AO2: Analog Output 2
A+: Modbus A+
AI2 AI1
AO1 COM: Common
B-: Modbus B-
AO1: Analog Output 1
AI1

Universal Inputs | TB12-15 COM


NC Digital Outputs | TB4-9
** Selectable ** AI2
NC: Normally Closed
AI1: Universal Input 1 COM DO6
AI3 COM: Common
COM: Common NO: Normally Open
NO
AI2: Universal Input 2 COM
NC
AI3: Universal Input 3 AI4
COM: Common COM DO5
AI4: Universal Input 4 AI3 AI4
NO
AI6 AI5
AI5: Universal Input 5
NC
COM: Common
AI6: Universal Input 6 AI5 COM DO4
COM NO
AI7: Universal Input 7
COM: Common AI6
AI8: Universal Input 8 NC
AI7 COM DO3
COM NO
AI8
NC
AI7 AI8
COM DO2
Digital Inputs | TB16
DI1 NO
** Configurable **
DI1: Digital Input 1 COM NC
COM: Common
DI2 COM DO1
DI2: Digital Input 2
COM NO

Voltage Input | TB17 24V


** 100mA max **
COM: Common AI1-AI8 Signal | JP5-JP12 AO1-AO4 Switches | SW1-SW4 DO1-DO6 Switches | SW5-SW10
24V: 24 Vac or 27-33 Vdc
I = 4-20mA On = 10Vdc / 20mA On = Activated (opposite state)

T*= 10K Ohms / on-off Auto* = Automatic Auto* = Automatic

V= 0-10Vdc Off = 0Vdc / 0mA Off = Deactivated (normal state)


* default setting * default setting * default setting

www.neptronic.com Page | 2
Remote I/O Communication Module
Specification and Installation Instructions

MAC Address DIP Switch (DS2)


MAC address for BACnet and Modbus communication, are selectable by DIP switch DS2 using binary logic.

BACnet
 Highest MAC address is 254.
 Default is all switches OFF = MAC address 0
 If you do not change device instance in program mode, it will be automatically modified according to the MAC address.

MAC Address DS.1 = 1 DS.2 = 2 DS.3 = 4 DS.4 = 8 DS.5 = 16 DS.6 = 32 DS.7 = 64 DS.8 = 128 Default Device Instance
0 OFF OFF OFF OFF OFF OFF OFF OFF 153000
1 ON OFF OFF OFF OFF OFF OFF OFF 153001
2 OFF ON OFF OFF OFF OFF OFF OFF 153002
3 ON ON OFF OFF OFF OFF OFF OFF 153003
4 OFF OFF ON OFF OFF OFF OFF OFF 153004
… … … … … … … … … …
126 OFF ON ON ON ON ON ON OFF 153126
… … … … … … … … … …
254 OFF ON ON ON ON ON ON ON 153254

Modbus
 Highest MAC address is 247.
 Default is all switches OFF = MAC address 1
 MAC address is binary value +1
 There is no device instance for Modbus.

MAC Address DS.1 = 1 DS.2 = 2 DS.3 = 4 DS.4 = 8 DS.5 = 16 DS.6 = 32 DS.7 = 64 DS.8 = 128
0+1 = 1 OFF OFF OFF OFF OFF OFF OFF OFF
1+1 = 2 ON OFF OFF OFF OFF OFF OFF OFF
2+1 = 3 OFF ON OFF OFF OFF OFF OFF OFF
3+1 = 4 ON ON OFF OFF OFF OFF OFF OFF
4+1 = 5 OFF OFF ON OFF OFF OFF OFF OFF
… … … … … … … … …
126+1 = 127 OFF ON ON ON ON ON ON OFF
… … … … … … … … …
246+1 = 247 OFF ON ON OFF ON ON ON ON

1 2 3 4 5 6 7 8 1 2 3 4
POWER

LEDs STATUS
ON
DS2
ON
DS1

Power
TX RX

On = Input voltage normal BACnet


Off = No power
TX RX

Status Modbus
Flashing = Normal operation (watchdog)
RX/TX (BACnet)
Flashing = Receiving (RX) and/or transmitting (TX) data.
RX/TX (Modbus)
Flashing = Receiving (RX) and/or transmitting (TX) data.
Input Status
On = Input on
Off = Input off
Flashing = Input not connected (thermistor setting only)
Analog = When Universal Inputs are set to analog values (Vdc, mA,
or 10KΩ); the LED intensity corresponds to the input value.
For example: At 10Vdc, the LED will be fully on. At 5Vdc, the
Input Status LEDs Output Status LEDs
LED will be at 50% intensity. At 0 Vdc, the LED will be off. (one per input) (one per output)
Output Status
On = Activated
Off = Deactivated
Flashing = Output pulsed
Analog = When Universal and Analog outputs are set to analog values (Vdc or mA); the LED intensity corresponds to the output
value. For example: At 10Vdc, the LED will be fully on. At 5Vdc, the LED will be at 50% intensity. At 0 Vdc, the LED will
be off.

www.neptronic.com Page | 3
Remote I/O Communication Module
Specification and Installation Instructions

Network Conditions
Please note that all jumper settings must also be set to the same value through BACnet or Modbus. The following is a list of
conditions and additional BACnet or Modbus objects.
Universal Inputs (AI1-AI8)
 When the jumper is set to Thermistor, you can select either °C or °F or you can set the input as a digital on/off input.
 If the universal input is set as a digital on/off input, you can also set the polarity to direct or reverse. For example, in Reverse an
“on” signal would be recognized as an “off” signal.
 When the jumper is set to 0-10 Vdc, you can also set the range to 0-5 Vdc.
Digital Inputs (DI1-DI2)
 You can set the polarity to direct or reverse. For example, in Reverse an “on” signal would be recognized as an “off” signal.
Universal/Analog Outputs (AO1-AO4)
 You can set the polarity to direct or reverse. For example, in reverse the output range would be 10-0 Vdc instead of 0-10 Vdc.
The polarity applies to all settings 0-10Vdc, 4-20mA, on/off and pulsed.
 You can also set the outputs to pulsed or digital on/off.
 A fixed output value can only be modified via BACnet when the override switch is in the “Automatic” position.
Digital Outputs (DO1-DO6)
 A fixed output (open/closed) can only be modified via BACnet when the override switch is in the “Automatic” position.
 The displayed text can be set to either Open/Closed, On/Off, or Alarm/Normal (BACnet only).
Supervised Outputs
 All outputs are fully supervised via BACnet. This provides the actual state of the output including any manual overrides done
using the on-board switches.

BACnet Objects Table

1
ID Name Description Writable? Notes (* = default)

Universal input 1 0-10Volt or -40-100ºC or -40-212ºF or 0-1


AI.1 UniversalInput1 Out of service
mode selected by MSV.1 Resolution 0.01Volt or 0.01ºC/0.02ºF
Universal input 2 0-10Volt or -40-100ºC or -40-212ºF or 0-1
AI.2 UniversalInput2 Out of service
mode selected by MSV.12 Resolution 0.01Volt or 0.01ºC/0.02ºF
Universal input 3 0-10Volt or -40-100ºC or -40-212ºF or 0-1
AI.3 UniversalInput3 Out of service
mode selected by MSV.15 Resolution 0.01Volt or 0.01ºC/0.02ºF
Universal input 4 0-10Volt or -40-100ºC or -40-212ºF or 0-1
AI.4 UniversalInput4 Out of service
mode selected by MSV.48 Resolution 0.01Volt or 0.01ºC/0.02ºF
Universal input 5 0-10Volt or -40-100ºC or -40-212ºF or 0-1
AI.5 UniversalInput5 Out of service
mode selected by MSV.57 Resolution 0.01Volt or 0.01ºC/0.02ºF
Universal input 6 0-10Volt or -40-100ºC or -40-212ºF or 0-1
AI.6 UniversalInput6 Out of service
mode selected by MSV.58 Resolution 0.01Volt or 0.01ºC/0.02ºF
Universal input 7 0-10Volt or -40-100ºC or -40-212ºF or 0-1
AI.7 UniversalInput7 Out of service
mode selected by MSV.59 Resolution 0.01Volt or 0.01ºC/0.02ºF
Universal input 8 0-10Volt or -40-100ºC or -40-212ºF or 0-1
AI.8 UniversalInput8 Out of service
mode selected by MSV.60 Resolution 0.01Volt or 0.01ºC/0.02ºF
AV.52 AnalogOutput1Min Min. voltage of analog output 1 Present Value 0* Volt to AV.54 | Resolution 0.1 Volt
AV.53 AnalogOutput2Min Min. voltage of analog output 2 Present Value 0* Volt to AV.55 | Resolution 0.1 Volt
AV.54 AnalogOutput1Max Max. voltage of analog output 1 Present Value AV.52 to 10.0* Volt | Resolution 0.1 Volt
AV.55 AnalogOutput2Max Max. voltage of analog output 2 Present Value AV.53 to 10.0* Volt | Resolution 0.1 Volt
AV.72 AnalogOutput1 Analog output 1 value Present Value 0-100% | Resolution 0.1%
AV.73 AnalogOutput2 Analog output 2 value Present Value 0-100% | Resolution 0.1%
AV.118 AnalogOutput3Min Min. voltage of analog output 3 Present Value 0* Volt to AV.120 | Resolution 0.1 Volt
AV.119 AnalogOutput4Min Min. voltage of analog output 4 Present Value 0* Volt to AV.121 | Resolution 0.1 Volt
AV.120 AnalogOutput3Max Max. voltage of analog output 3 Present Value AV.118 to 10.0* Volt | Resolution 0.1 Volt
AV.121 AnalogOutput4Max Max. voltage of analog output 4 Present Value AV.119 to 10.0* Volt | Resolution 0.1 Volt
AV.124 AnalogOutput3 Analog output 3 value Present Value 0-100% | Resolution 1%
AV.125 AnalogOutput4 Analog output 4 value Present Value 0-100% | Resolution 1%
-5.00 to 5.00 ºC/ºF/Volt/mA (default 0*)
AV.226 UniversalInput1Offset Universal input 1 offset Present Value
Resolution: 0.01 ºC/ºF/Volt/mA
-5.00 to 5.00 ºC/ºF/Volt/mA (default 0*)
AV.227 UniversalInput2Offset Universal input 2 offset Present Value
Resolution: 0.01 ºC/ºF/Volt/mA
-5.00 to 5.00 ºC/ºF/Volt/mA (default 0*)
AV.228 UniversalInput3Offset Universal input 3 offset Present Value
Resolution: 0.01 ºC/ºF/Volt/mA

1
ID is equal to ObjectType.Instance

www.neptronic.com Page | 4
Remote I/O Communication Module
Specification and Installation Instructions

1
ID Name Description Writable? Notes (* = default)

-5.00 to 5.00 ºC/ºF/Volt/mA (default 0*)


AV.229 UniversalInput4Offset Universal input 4 offset Present Value
Resolution: 0.01 ºC/ºF/Volt/mA
-5.00 to 5.00 ºC/ºF/Volt/mA (default 0*)
AV.230 UniversalInput5Offset Universal input 5 offset Present Value
Resolution: 0.01 ºC/ºF/Volt/mA
-5.00 to 5.00 ºC/ºF/Volt/mA (default 0*)
AV.231 UniversalInput6Offset Universal input 6 offset Present Value
Resolution: 0.01 ºC/ºF/Volt/mA
-5.00 to 5.00 ºC/ºF/Volt/mA (default 0*)
AV.232 UniversalInput7Offset Universal input 7 offset Present Value
Resolution: 0.01 ºC/ºF/Volt/mA
-5.00 to 5.00 ºC/ºF/Volt/mA (default 0*)
AV.233 UniversalInput8Offset Universal input 8 offset Present Value
Resolution: 0.01 ºC/ºF/Volt/mA
Remote sensor model and Modbus
AV.235 SD1_Type_ADD See STLD24 document for information
address
Remote sensor baud rate of Modbus
AV.236 SD1_Baudrate Present Value See STLD24 document for information
communication
AV.237 SD1_Firmware_version Remote sensor version See STLD24 document for information
AV.238 SD1_Status_Config Remote sensor config and status Present Value See STLD24 document for information
AV.239 SD1_Intern_Temp Remote sensor internal temp. See STLD24 document for information
AV.240 SD1_Temp_SetPoint Remote sensor temp. setpoint Present Value See STLD24 document for information
AV.241 SD1_Min_Temp_SetPoint Remote sensor min. setpoint Present Value See STLD24 document for information
AV.242 SD1_Max_Temp_SetPoint Remote sensor max. setpoint Present Value See STLD24 document for information
Remote sensor internal temperature
AV.243 SD1_Int_Temp_Offset Present Value See STLD24 document for information
offset
AV.249 SD1_Extern_Temp Remote sensor external temp. See STLD24 document for information
Remote sensor external
AV.250 SD1_Extern_Temp_Offset Present Value See STLD24 document for information
temperature offset
Remote sensor button configuration
AV.251 SD1_Button_Cfg_Status Present Value See STLD24 document for information
and status
Remote sensor text
AV.252 SD1_Let76 Present Value See STLD24 document for information
characters 7 and 6
Remote sensor text
AV.253 SD1_Let54 Present Value See STLD24 document for information
characters 5 and 4
Remote sensor text
AV.254 SD1_Let32 Present Value See STLD24 document for information
characters 3 and 2
Remote sensor text
AV.255 SD1_Let1 Present Value See STLD24 document for information
character 1
Remote sensor digit
AV.256 SD1_Digit43 Present Value See STLD24 document for information
number 4 and 3
Remote sensor digit
AV.257 SD1_Digit21 Present Value See STLD24 document for information
number 2 and 1
AV.258 SD1_Icon1 Remote sensor icon to display Present Value See STLD24 document for information
AV.259 SD1_Icon1_Blink Remote sensor icon to blink Present Value See STLD24 document for information
AV.260 SD1_Icon2 Remote sensor icon to display Present Value See STLD24 document for information
AV.261 SD1_Icon2_Blink Remote sensor icon to blink Present Value See STLD24 document for information
AV.262 SD1_Icon3 Remote sensor icon to display Present Value See STLD24 document for information
AV.263 SD1_Icon3_Blink Remote sensor icon to blink Present Value See STLD24 document for information
Remote sensor model and Modbus
AV.264 SD2_Type_ADD See STLD24 document for information
address
Remote sensor baud rate of Modbus
AV.265 SD2_Baudrate Present Value See STLD24 document for information
communication
AV.266 SD2_Firmware_version Remote sensor version See STLD24 document for information
AV.267 SD2_Status_Config Remote sensor config and status Present Value See STLD24 document for information
AV.268 SD2_Intern_Temp Remote sensor internal temp. See STLD24 document for information
AV.269 SD2_Temp_SetPoint Remote sensor temp. setpoint Present Value See STLD24 document for information
AV.270 SD2_Min_Temp_SetPoint Remote sensor min. setpoint Present Value See STLD24 document for information
AV.271 SD2_Max_Temp_SetPoint Remote sensor max. setpoint Present Value See STLD24 document for information
Remote sensor internal temperature
AV.272 SD2_Int_Temp_Offset Present Value See STLD24 document for information
offset
AV.278 SD2_Extern_Temp Remote sensor external temp. See STLD24 document for information
Remote sensor external
AV.279 SD2_Extern_Temp_Offset Present Value See STLD24 document for information
temperature offset

www.neptronic.com Page | 5
Remote I/O Communication Module
Specification and Installation Instructions

1
ID Name Description Writable? Notes (* = default)

Remote sensor button configuration


AV.280 SD2_Button_Cfg_Status Present Value See STLD24 document for information
and status
Remote sensor text
AV.281 SD2_Let76 Present Value See STLD24 document for information
characters 7 and 6
Remote sensor text
AV.282 SD2_Let54 Present Value See STLD24 document for information
characters 5 and 4
Remote sensor text
AV.283 SD2_Let32 Present Value See STLD24 document for information
characters 3 and 2
Remote sensor text
AV.284 SD2_Let1 Present Value See STLD24 document for information
character 1
Remote sensor digit
AV.285 SD2_Digit43 Present Value See STLD24 document for information
number 4 and 3
Remote sensor digit
AV.286 SD2_Digit21 Present Value See STLD24 document for information
number 4 and 3
AV.287 SD2_Icon1 Remote sensor icon to display Present Value See STLD24 document for information
AV.288 SD2_Icon1_Blink Remote sensor icon to blink Present Value See STLD24 document for information
AV.289 SD2_Icon2 Remote sensor icon to display Present Value See STLD24 document for information
AV.290 SD2_Icon2_Blink Remote sensor icon to blink Present Value See STLD24 document for information
AV.291 SD2_Icon3 Remote sensor icon to display Present Value See STLD24 document for information
AV.292 SD2_Icon3_Blink Remote sensor icon to blink Present Value See STLD24 document for information
AV.467 NumberOfSlaveSensor Number of remote sensors Present Value 0*-2 (# of STLD24 connected to CMMB)
0-254 Address of first CMMB to copy
AV.468 CopyCfgStartAdd Copy configuration start address Present Value
Available only if BV.101 is set to No
AV.468 – (AV.468 + 64)
AV.469 CopyCfgEndAdd Copy configuration end address Present Value Address of last CMMB to copy
Available only if BV.101 is set to No
AV.468 – AV.469
Result of copy is available on Description
property and is available only if BV.101 is set to
2
AV.470 CopyCfgResult Copy configuration result Present Value Yes. Results: Succeed, Prog_Error, Type_Error,
Model_Error, FW_Error, Mem_Error,
Size_Error, Comm_Error, SlaveDevice,
InProgress, AllSucceed
0= Open / Ouvert *
BI.1 DigitalInput1 Digital input 1 status Out of service 1= Close / Fermé
Text depends of selection in MSV.76
0= Open / Ouvert *
BI.2 DigitalInput2 Digital input 2 status Out of service 1= Close / Fermé
Text depends of selection in MSV.77
0= Open / Ouvert / Off / Arret / Normal *
BV.22 ContactOutput1 Digital output 1 status Present Value 1= Close / Fermé / On / Marche / Alarm
Text depends of selection in MSV.66
0= Open / Ouvert / Off / Arret / Normal *
BV.23 ContactOutput2 Digital output 2 status Present Value 1= Close / Fermé / On / Marche / Alarm
Text depends of selection in MSV.67
0= Open / Ouvert / Off / Arret / Normal *
BV.24 ContactOutput3 Digital output 3 status Present Value 1= Close / Fermé / On / Marche / Alarm
Text depends of selection in MSV.68
0= Open / Ouvert / Off / Arret / Normal *
BV.25 ContactOutput4 Digital output 4 status Present Value 1= Close / Fermé / On / Marche / Alarm
Text depends of selection in MSV.69
0= Open / Ouvert / Off / Arret / Normal *
BV.26 ContactOutput5 Digital output 5 status Present Value 1= Close / Fermé / On / Marche / Alarm
Text depends of selection in MSV.70
0= Open / Ouvert / Off / Arret / Normal *
BV.27 ContactOutput6 Digital output 6 status Present Value 1= Close / Fermé / On / Marche / Alarm
Text depends of selection in MSV.71
0= Direct *
BV.33 DigitalInput1Polarity Polarity of digital input 1 Present Value
1= Reverse
0= Direct *
BV.34 DigitalInput2Polarity Polarity of digital input 2 Present Value
1= Reverse
0= Direct *
BV.66 AnalogOutput1Direction Polarity of analog output 1 Present Value
1= Reverse

2
Write address in present value, result will be available in description.

www.neptronic.com Page | 6
Remote I/O Communication Module
Specification and Installation Instructions

1
ID Name Description Writable? Notes (* = default)

0= Direct *
BV.67 AnalogOutput2Direction Polarity of analog output 2 Present Value
1= Reverse
0= Direct *
BV.68 AnalogOutput3Direction Polarity of analog output 3 Present Value
1= Reverse
0= Direct *
BV.69 AnalogOutput4Direction Polarity of analog output 4 Present Value
1= Reverse
Polarity of universal input 1 0= Direct *
BV.93 UI1_DI_Polarity Present Value
when used in digital input mode 1= Reverse
Polarity of universal input 2 0= Direct *
BV.94 UI2_DI_Polarity Present Value
when used in digital input mode 1= Reverse
Polarity of universal input 3 0= Direct *
BV.95 UI3_DI_Polarity Present Value
when used in digital input mode 1= Reverse
Polarity of universal input 4 0= Direct *
BV.96 UI4_DI_Polarity Present Value
when used in digital input mode 1= Reverse
Polarity of universal input 5 0= Direct *
BV.97 UI5_DI_Polarity Present Value
when used in digital input mode 1= Reverse
Polarity of universal input 6 0= Direct *
BV.98 UI6_DI_Polarity Present Value
when used in digital input mode 1= Reverse
Polarity of universal input 7 0= Direct *
BV.99 UI7_DI_Polarity Present Value
when used in digital input mode 1= Reverse
Polarity of universal input 8 0= Direct *
BV.100 UI8_DI_Polarity Present Value
when used in digital input mode 1= Reverse
0= No *
1= Yes
BV.101 CopyCfgExecute Start or stop copy configuration Present Value
Start copy and give results, must be reset by
user.
1= Extern_Sensor_C *
2= Extern_Sensor_F
3= 0_10Volt
MSV.1 UniversalInput1Function Selected analog input 1 mode Present Value
4= DigitalInput
5= 0_5Volt
6= 4_20mA
1= Extern_Sensor_C *
2= Extern_Sensor_F
3= 0_10Volt
MSV.12 UniversalInput2Function Selected analog input 2 mode Present Value
4= DigitalInput
5= 0_5Volt
6= 4_20mA
1= Extern_Sensor_C *
2= Extern_Sensor_F
3= 0_10Volt
MSV.15 UniversalInput3Function Selected analog input 3 mode Present Value
4= DigitalInput
5= 0_5Volt
6= 4_20mA
1= Extern_Sensor_C *
2= Extern_Sensor_F
3= 0_10Volt
MSV.48 UniversalInput4Function Selected analog input 4 mode Present Value
4= DigitalInput
5= 0_5Volt
6= 4_20mA
1= Analog *
MSV.54 AnalogOutput1Mode Select analog output 1 mode Present Value 2= On_Off
3= Pulsing
1= Analog *
MSV.55 AnalogOutput2Mode Select analog output 2 mode Present Value 2= On_Off
3= Pulsing
1= Extern_Sensor_C *
2= Extern_Sensor_F
3= 0_10Volt
MSV.57 UniversalInput5Function Selected analog input 5 mode Present Value
4= DigitalInput
5= 0_5Volt
6= 4_20mA
1= Extern_Sensor_C *
2= Extern_Sensor_F
3= 0_10Volt
MSV.58 UniversalInput6unction Selected analog input 6 mode Present Value
4= DigitalInput
5= 0_5Volt
6= 4_20mA

www.neptronic.com Page | 7
Remote I/O Communication Module
Specification and Installation Instructions

1
ID Name Description Writable? Notes (* = default)

1= Extern_Sensor_C *
2= Extern_Sensor_F
3= 0_10Volt
MSV.59 UniversalInput7Function Selected analog input 7 mode Present Value
4= DigitalInput
5= 0_5Volt
6= 4_20mA
1= Extern_Sensor_C *
2= Extern_Sensor_F
3= 0_10Volt
MSV.60 UniversalInput8Function Selected analog input 8 mode Present Value
4= DigitalInput
5= 0_5Volt
6= 4_20mA
1= Open_Close *
2= Ouvert_Fermé
Contact output 1 inactive & active
MSV.66 ContactOutput1Text Present Value 3= On_Off
text
4= Marche_Arret
5= Alarm_Normal
1= Open_Close *
2= Ouvert_Fermé
Contact output 2 inactive & active
MSV.67 ContactOutput2Text Present Value 3= On_Off
text
4= Marche_Arret
5= Alarm_Normal
1= Open_Close *
2= Ouvert_Fermé
Contact output 3 inactive & active
MSV.68 ContactOutput3Text Present Value 3= On_Off
text
4= Marche_Arret
5= Alarm_Normal
1= Open_Close *
2= Ouvert_Fermé
Contact output 4 inactive & active
MSV.69 ContactOutput4Text Present Value 3= On_Off
text
4= Marche_Arret
5= Alarm_Normal
1= Open_Close *
2= Ouvert_Fermé
Contact output 5 inactive & active
MSV.70 ContactOutput5Text Present Value 3= On_Off
text
4= Marche_Arret
5= Alarm_Normal
1= Open_Close *
2= Ouvert_Fermé
Contact output 6 inactive & active
MSV.71 ContactOutput6Text Present Value 3= On_Off
text
4= Marche_Arret
5= Alarm_Normal

1= Open_Close *
MSV.76 DigitalInput1Text Digital input 1 inactive & active text Present Value
2= Ouvert_Fermé

1= Open_Close *
MSV.77 DigitalInput2Text Digital input 2 inactive & active text Present Value
2= Ouvert_Fermé

1= Analog *
MSV.81 AnalogOutput3Mode Select analog output 3 mode Present Value 2= On_Off
3= Pulsing
1= Analog *
MSV.82 AnalogOutput4Mode Select analog output 4 mode Present Value 2= On_Off
3= Pulsing

www.neptronic.com Page | 8
Remote I/O Communication Module
Specification and Installation Instructions

Modbus Registers
 Register address
o As per protocol base (base 0); for PLC add 1 to protocol base.
o As per holding register (base 40001)
 Functions :
o 03 Read Holding Register
o 06 Write Single Register
o 16 Write Multiple Registers
 Error Codes :
o 02 Illegal Data Address
o 03 Illegal Value
o 06 Slave Device Busy
 W = Writable register, [blank] = read only.
 No Real number in modbus register, use scale to calculate real number. Register = Real number * Scale => Real number = Register / Scale. Scale could be 1, 10 or 100
 Attention when writing a register that contains a bit string. If bit is writable (conditional or not), the write will always be accepted. If bit is reserved or not writable, the write will be ignored and
will keep its actual state.
 Use READ-MODIFY-WRITE sequence.

Default Value
Protocol Holding
Base Register
Description Data Type MSB/LSB Units/Values Writable
MB LB
MSB = Neptronic Device ID 105 [1..247]
0 40001 Unsigned * MAC address is writable if all DIP switches of DS2 are OFF. W* 69h 1h
LSB = MAC Address (69h) (1h- F7h)
[96] 9,600
Unsigned [192] 19,200
1 40002 Device Baud Rate W 96
Scale 0.01 [384] 38,400
[576] 57,600
COM Port Configuration
IMPORTANT: The default value is "no parity, 2 0 = no parity, 2 stop bits
stop bits". To change the value, you must set
2 40003 Unsigned [0..2] 1 = even parity, 1 stop bit W 0
DIP switch DS1-3 to OFF. If set to ON, it will
always remain at the default value. Refer to 2 = odd parity, 1 stop bit
Connections and Configurations on page 2.
3 40004 Product Name (characters 8 & 7) 2 x ASCII char 8 char 7 Valid ASCII character: 32 (20h) – 122 (7ah), Empty = 0 W 43h [C] 40h [M]
4 40005 Product Name (characters 6 & 5) 2 x ASCII char 6 char 5 Valid ASCII character: 32 (20h) – 122 (7ah), Empty = 0 W 40h [M] 42h [B]
5 40006 Product Name (characters 4 & 3) 2 x ASCII char 4 char 3 Valid ASCII character: 32 (20h) – 122 (7ah), Empty = 0 W 31h [1] 30h [0]
6 40007 Product Name (characters 2 & 1) 2 x ASCII char 2 char 1 Valid ASCII character: 32 (20h) – 122 (7ah), Empty = 0 W 36h [6] 20h [ ]
Unsigned
7 40008 Firmware Version 106 1.06 106
Scale 100
Unsigned
8 40009 Application Version 103 1.03 103
Scale 100

www.neptronic.com Page | 9
Remote I/O Communication Module
Specification and Installation Instructions

Default Value
Protocol Holding
Base Register
Description Data Type MSB/LSB Units/Values Writable
MB LB

0 = Normal
1 = Fault
9 40010 System Status 1 Bit String [B0..B15] 0000, 0001, 1111, 1110b
-------------------
B0 = System operation
10 40011 System Status 2 Bit String [B0..B15] Always 0 0000, 0000, 0000, 0000b
11 40012 Analog Input 1 32767
12 40013 Analog Input 2 T_C: Type: Signed, Scale:100, Unit:ºC, Range:-40,00 - 100,00 ºC, Resolution : 0,01 32767
T_F: Type: Signed, Scale:100, Unit:ºF, Range:-40,00 - 212,00 ºF, Resolution : 0,01
13 40014 Analog Input 3 32767
0-10V: Type: Unsigned, Scale:100, Unit: Volt, Range:0-10,00V, Resolution : 0,01
14 40015 Analog Input 4 DI: Type: Unsigned, Scale:1, Unit: n/a, Range: 0-1, Resolution : 1 32767
15 40016 Analog Input 5 0-5V: Type: Unsigned, Scale:100, Unit: Volt, Range:0-5,00V, Resolution : 0,01 32767
4-20mA: Type: Unsigned, Scale:100, Unit: mA, Range:4,00 - 20,00 mA, Resolution : 0,01
16 40017 Analog Input 6 32767
17 40018 Analog Input 7 Note: 32767 (7FFFh) = Input in fault; for temperature T_C & T_F modes only 32767
18 40019 Analog Input 8 32767
B0 = DI1
19 40020 Digital Input Bit String [B0..B1] 0000, 0000, 0000, 0000b
B1 = DI2
20 40021 Analog Output 1 0
21 40022 Analog Output 2 Unsigned 0
Scale 10
[0..1000] Unit: %, Range: 0-100,0%, Resolution : 0,1 W
22 40023 Analog Output 3 0
23 40024 Analog Output 4 0
B0 = Relay 1
B1 = Relay 2
B2 = Relay 3
24 40025 Relay Output Bit String [B0..B6] W 0000, 0000, 0000, 0000b
B3 = Relay 4
B4 = Relay 5
B5 = Relay 6
B0 = Relay 1
B1 = Relay 2
B2 = Relay 3
B3 = Relay 4
Output Overwrite Status
B4 = Relay 5
25 40026 Indicates that the output is overridden by the Bit String [B0..B10] 0000, 0000, 0000, 0000b
B5 = Relay 6
hardware switch (SW5-SW10).
B6 = AO1
B7 = AO2
B8 = AO3
B9 = AO4

www.neptronic.com Page | 10
Remote I/O Communication Module
Specification and Installation Instructions

Default Value
Protocol Holding
Base Register
Description Data Type MSB/LSB Units/Values Writable
MB LB

26 40027 Universal Input 1 Function 1


27 40028 Universal Input 2 Function 1
28 40029 Universal Input 3 Function 1 = Temperature °C 1
2 = Temperature °F
29 40030 Universal Input 4 Function 3 = 0-10V 1
Unsigned [1..4] W
30 40031 Universal Input 5 Function 4 = Digital Input 1
5 = 0-5V
31 40032 Universal Input 6 Function 6 = 4-20mA 1
32 40033 Universal Input 7 Function 1
33 40034 Universal Input 8 Function 1
34 40035 Universal Input 1 Offset 0
35 40036 Universal Input 2 Offset 0
36 40037 Universal Input 3 Offset 0
37 40038 Universal Input 4 Offset Signed 0
Scale 100
[0..100] Range: +/- 5,00, Resolution : 0,10 W
38 40039 Universal Input 5 Offset 0
39 40040 Universal Input 6 Offset 0
40 40041 Universal Input 7 Offset 0
41 40042 Universal Input 8 Offset 0
1 = Analog
2 = On/Off
42 40043 Analog Output 1 Mode Unsigned [1..4] W 1
3 = Pulse
4 = 4-20mA
43 40044 Analog Output 1 Minimum Voltage Signed Unit: Volt, Range: 0 V - Register 44, Resolution : 0,1 0
[0..100] W
44 40045 Analog Output 1 Maximum Voltage Scale 10 Unit: Volt, Range: Register 43 - 10.0V, Resolution : 0,1 100
1 = Analog
2 = On/Off
45 40046 Analog Output 2 Mode Unsigned [1..4] W 1
3 = Pulse
4 = 4-20mA
46 40047 Analog Output 2 Minimum Voltage Signed Unit: Volt, Range: 0 V - Register 47, Resolution : 0,1 0
[0..100] W
47 40048 Analog Output 2 Maximum Voltage Scale 10 Unit: Volt, Range: Register 46 - 10.0V, Resolution : 0,1 100

1 = Analog
2 = On/Off
48 40049 Analog Output 3 Mode Unsigned [1..4] W 1
3 = Pulse
4 = 4-20mA

www.neptronic.com Page | 11
Remote I/O Communication Module
Specification and Installation Instructions

Default Value
Protocol Holding
Base Register
Description Data Type MSB/LSB Units/Values Writable
MB LB

49 40050 Analog Output 3 Minimum Voltage Signed Unit: Volt, Range: 0 V - Register 50, Resolution : 0,1 0
[0..100] W
50 40051 Analog Output 3 Maximum Voltage Scale 10 Unit: Volt, Range: Register 49 - 10.0V, Resolution : 0,1 100
1 = Analog
2 = On/Off
51 40052 Analog Output 4 Mode Unsigned [1..4] W 1
3 = Pulse
4 = 4-20mA
52 40053 Analog Output 4 Minimum Voltage Signed Unit: Volt, Range: 0 V - Register 53, Resolution : 0,1 0
[0..100] W
53 40054 Analog Output 4 Maximum Voltage Scale 10 Unit: Volt, Range: Register 52 - 10.0V, Resolution : 0,1 100
0 = Direct
1 = Reverse
-------------------
B0 = AO1 polarity
B1 = AO2 polarity
B2 = AO3 polarity
B3 = AO4 polarity
System Options B4 = AI1 polarity *
54 40055 Bit String [B0..B13] B5 = AI2 polarity * W 0000, 0000, 0000, 0000b
* = digital input mode only B6 = AI3 polarity *
B7 = AI4 polarity *
B8 = AI5 polarity *
B9 = AI6 polarity *
B10 = AI7 polarity *
B11 = AI8 polarity *
B12 = DI1 polarity
B13 = DI2 polarity

Recycling at end of life: please return this product to your Neptronic local distributor for recycling. If you need to find the nearest Neptronic authorized distributor, please consult www.neptronic.com.

www.neptronic.com Page | 12

You might also like