MONG DUONG II THERMAL POWER PLANT DOC. No:
REV. No: 0
CALCULATION FOR SCAFFOLDING
PAGE:
CONTENTS
1. DESIGN CRITERIA
1.3 DEFORMATION
4. STRUCTURE ANALYSIS
4.1 MODELING
4.2 ANYLYSIS RESULT
Page 2
MONG DUONG II THERMAL POWER PLANT DOC. No:
-
CALCULATION FOR SCAFFOLDING REV. No: 0
PAGE:
1. DESIGN CRITERIA
1.1 DESIGN CODE AND STANDARD
Codes and Standards applied for design of farm tank foundation shall be follows:
TCVN 2737:1995 Design Standard for Load and Load Effect
AISC 360-05 (ASD) Specification for Structural Steel Buildings
ASCE 7-05 Minimum Design Loads for Buildings and other Structures
1.2 MATERIAL SPECIFICATION
Steel structure
All steel materials are JIS G 3101 (SS400) or ASTM A36 or equivalent
The minimum yield strength for shape steel fy = 245 MPa
The minimum yield strength for steel plate t <=16mm fy = 245 MPa
16< t <=40mm fy = 235 MPa
High Strength Bolt
High Strength Bolt shall be in accordance with ASTM A325 or equivalent.
The minimum tensile strength fu = 830 MPa
1.3 DEFORMATION
1) Deformation of moment member shall not be more than values in Table 1
14-JUN-2022
2) Lateral allowable movement for 1-storey industrial building without crane under standard wind load
is limited as below:
- For steel sheet wall : H/100
- For light weight wall : H/150
- For brick or concrete wall : H/200
Where : H is the column height
Page 3
MONG DUONG II THERMAL POWER PLANT DOC. No:
-
CALCULATION FOR SCAFFOLDING REV. No: 0
PAGE:
3. LOAD COMBINATION
1. Combination load for Steel design (ASD)
101 1.0 DL
102 1.0 DL + 1.0 LL
EVN1 Envelope (101~102)
Where:
DL: Dead Load
LL: Live load
4. STRUCTURE ANALYSIS
4.1 MODELING
SCAFFOLDING FRAME
Page 4
MONG DUONG II THERMAL POWER PLANT DOC. No:
-
CALCULATION FOR SCAFFOLDING REV. No: 0
PAGE:
SECTION FRAME
LIVE LOAD
Page 5
MONG DUONG II THERMAL POWER PLANT DOC. No:
-
CALCULATION FOR SCAFFOLDING REV. No: 0
PAGE:
2XD48.3*3.2
RATIO PM
Page 6
MONG DUONG II THERMAL POWER PLANT DOC. No:
-
CALCULATION FOR SCAFFOLDING REV. No: 0
PAGE:
2XD48.3*3.2
Page 7
MONG DUONG II THERMAL POWER PLANT DOC. No:
-
CALCULATION FOR SCAFFOLDING REV. No: 0
PAGE:
2) Deflection check
Unit #1
Maximum lateral deflection u3 = 0.0563 mm
Limit lateral deflection [u3] = L/250 = 600/250= 2,4 mm
=> OK