Purwadi 2011
Purwadi 2011
Agus Purwadi1, Nana Heryana, Dadan Nurafiat Anang Mawardi2, Pranyoto, Muhammad Firmansyah
School of Electrical Engineering and Informatics Center of Research and Development
Institut Teknologi Bandung PT. PLN (Persero)
Bandung 40132 Indonesia Jakarta 12760, Indonesia
1
[email protected] 2
[email protected]
Abstract— This paper presents the characteristics and levels of Harmonic distortion phenomenon is not new and it
harmonics on PT. PLN's ( Indonesia state owned electric utility constitutes one of the main concerns for engineers in the
company) 150 kV/70 kV high voltage, 20 kV/380 medium and low several stages of energy utilization within the power industry.
voltage networks in West Java and Banten Area. Within this In the beginning, harmonic distortions was mainly caused by
paper a study and measurements for various types of loads in saturation of power transformer, industrial arc furnaces and
some types of industries connected to high voltage, medium other arc devices like large electric welders. The major
voltage and low voltage network are conducted and verified. This concerns was the effect that harmonic distortion could have on
paper also discuss the phenomenon of harmonics, the effects on electric machines, telephone interference, and increased risk of
the high voltage, medium voltage and low voltage networks, faults from over voltage condition developed on power factor
harmonic-producing sources, standards and recommended correction capacitors.
practice limits according to the IEEE 519 and IEC 61000
standard. The increasing use of nonlinear loads in industry is
Harmonic measurements method on high voltage network keeping harmonic distortion in distribution networks on the
was done by continuous logging for one week on two samples of rise. The most used nonlinear device perhaps the static power
150 kV big customers and one sample of 70 kV big customer to converter so widely used in industrial and residential
know the harmonics levels and their probability occurrence The applications. A situation that has raised waveform distortion
harmonic current measurements results indicated that Total levels in distribution networks even further is the application
Demand Distortion-TDD conditions for two big customers were of capacitor banks used in industrial plants for power factor
above 4% of standard limits as suggested in IEEE 519-1992. One correction and by power utilities for increasing voltage profile
customer using arc furnace load has contributed the highest
along distribution lines. The resulting reactive impedance
current harmonic pollution to the network.
Harmonic measurements methods on medium and low
forms a tank circuit with the system inductive reactance at
voltage networks were done on two types. The first method was certain frequency likely to coincide with one of the
done by continuous logging for a week duration on 8 samples of characteristic harmonics of the load. This condition will
medium voltage customer to know the harmonics levels and their trigger large oscillatory currents and voltages that may stress
probability occurrence. The second method was done by the insulation. This situation imposes a serious challenge to
instantaneous measurements for 5 minutes during peak load on industry and utility engineers to pinpoint and to correct
20 samples of low voltage distribution loads. From the excessive harmonic waveform distortion levels on the
measurement results show that harmonic current conditions- waveform because its steady increase happen to take place
THDi on the measured distribution substations are all above 5%, right at the time when the use of sensitive electronic
and 70% of customers measured have THDi more than 10%. equipment is also on the rise.
Keywords-harmonic characteristic, high voltage, medium
voltage, low voltage, networks, total demand distortion, total No doubt that the harmonic studies from the planning, the
harmonic distortion design to the operational stages of power utility and industrial
installations will prove to be effective way to keep networks
I. INTRODUCTION and equipment under acceptable operating conditions and to
Ideally, an electricity supply should have a perfectly anticipate potential problems with the installation or addition of
sinusoidal voltage signal at every customer location. However, non linear loads.[1]
for a number of reasons, utilities often find it hard to preserve
such desirable conditions. The deviation of the voltage and
current waveforms from sinusoidal is described in terms of the II. BASIC OF HARMONICS PHENOMENON
waveform distortion, which often expressed as harmonic Waveforms in a non-sinusoidal having frequencies other
distortion. than fundamental frequency are called harmonics. The
¦
1
¨ ¸
h 1 © I1 ¹
International Electro-technical Commission (IEC) is
the widely recognized organization as the curator of electric
power quality standards. IEC has introduced a series of
standards, to deal with power quality issues. Integer and inter
harmonics are included in IEC61000 series as one of D. Displacement, Distortion, and Total Power Factor
conducted low-frequency electro-magnetic phenomena. The With increasing harmonic distortion environtment, the
series also provides internationally accepted information for conventional definition of power factor as the cosine of the
the control of power system harmonic(and inter-harmonic) angle between fundamental frequency voltage and current
distortion.[2,15] has progressed to consider signal’s rms values, which make
The IEEE 519-1992 standard is a widespread up the contribution of components different frequencies.
alternative to the IEC series. It identifies the major sources of Total power factor thus becomes the product of distortion
harmonic in power systems, effects of harmonic distortion on and true power factors:
the operation of various device or loads, guidelines for
Ptotal
measurement of harmonic distortion in the power system, PFtotal DPF u TPF cos T1 G1 u
recommendation on useful suggestion for both individual Stotal
consumers and utilities for controlling the harmonic distortion § f ·
to tolerable levels.[2,8] ¨ ¦ Vh I h cos T h G h ¸
§ P1 · ¨ h 1 ¸
A. Total Harmonic Distortion (THD) ¨ ¸¨ ¸
© V1 I1 ¹ ¨ f f
(4)
Total harmonic distortion (THD) is an important index ¦ ¦
2 2
¨ V h I h
¸¸
widely used to describe power quality issues in transmission © h1 h 1 ¹
and distribution systems. It considers the contribution of every
individual harmonic component on the signal. THD is defined § P1 · 1
¨ ¸ 2
for voltage and current signals, respectively, as follows: © V1 I1 ¹ § THD1 ·
1 ¨ ¸
f f © 100 ¹
¦V h
2
¦I 2
h
(1)
THDv h 2
u100% THDi h 2
u100%
V1 I1
IV. METHODS AND MEASUREMENT RESULTS
B. Total Demand Distortion (TDD) Harmonic measurements method on high voltage network
Harmonic distortion is most meaningful when monitored at was done by continuous logging for one week on two samples
the point of common coupling (PCC)- usually the customer’s of 150 kV Main Substation (MS) big customers and one
metering point- over period that can reflect maximum sample of 70 kV Main Substation (MS) big customer to know
customer demand, typically 15 to 30 minutes as suggested in the harmonics levels and their probability occurrence [17-18].
Standard IEEE-519 . Weak sources with a larger demand
current relative to their rated current will tend to show greater Harmonic measurements methods on medium and low
waveform distortion. Conversely, stiff sources characterized voltage networks were done on two types. The first method
for operating at low demand currents will show decreased was done by continuous logging for one week duration on 8
waveform distortion. The TDD is based on the demand samples of 20 kV medium voltage Distribution Substation (DS)
current, over the monitoring period: costumer to know the harmonics level and their probability
occurrence. The second method was done by instantaneous
measurements for 5 minutes during peak load on 20 samples of
f low voltage distribution loads.
¦I 2
h
(2)
TDD h 2
u100%
Il
TABLE I. MEASUREMENT LOCATION AND INSTRUMENT USED
3
2,5
2
1,5
1
0,5
0
PT. Toyo PT. Asia Mall PT Polifin Out Going Transf. 1 Feeder PT PT LOC Sucofindo
Giri Gunung 20 KV Kahatex Cijedil Asahimas
Garuda
2 3 4 5 6 7 8 9 10 11
12 13 14 15 16 17 18 19 20 21
22 23 24 25 26 27 28 29 30 31
32 33 34 35 36 37 38 39 40 41
42 43 44 45 46 47 48 49 50 THD
14
12
10
8
6
4
2
0
PT. Toyo PT. Asia Mall PT Polifin Out Going Transf. 1 Feeder PT PT LOC Sucofindo
Giri Gunung 20 KV Kahatex Cijedil Asahimas
Garuda
2 3 4 5 6 7 8 9 10 11
12 13 14 15 16 17 18 19 20 21
22 23 24 25 26 27 28 29 30 31
32 33 34 35 36 37 38 39 40 41
42 43 44 45 46 47 48 49 50 THD