Natf Reference Document Generator Specifications Open
Natf Reference Document Generator Specifications Open
Disclaimer
This document was created by the North American Transmission Forum (NATF) to facilitate
industry work to improve power system modeling. NATF reserves the right to make changes to
the information contained herein without notice. No liability is assumed for any damages arising
directly or indirectly by their use or application. The information provided in this document is
provided on an “as is” basis. “North American Transmission Forum” and its associated logo are
trademarks of NATF. Other product and brand names may be trademarks of their respective
owners. Copyright 2013. All rights reserved. This legend should not be removed from the
document.
Open Distribution
Copyright © 2013 North American Transmission Forum. Not for sale or commercial use. All rights reserved.
Generator Specifications Open Distribution
Table of Contents
Introduction........................................................................................................................................................... 3
Audience… ........................................................................................................................ ……3
Section 1. Nameplate Information .................................................................................................................... 4
Inertia ..................................................................................................................................... 5
Section 2. Continuous Gross Output Ratings ................................................................................................... 12
Section 3. Generator Reactance and Time Constants ........................................................................................ 6
The Generator Model .......................................................................................................... 6
Generator Reactances ......................................................................................................... 6
Flux patterns and saturation .............................................................................................. 6
Synchronous Reactance ...................................................................................................... 7
Transient and Subtransient Reactance ............................................................................... 7
Generator Time Constants .................................................................................................. 9
Section 4. Rotor Characteristics ....................................................................................................................... 10
Section 5. Armature Characteristics ................................................................................................................ 11
General Information ............................................................................................................. 11
Armature Short-Circuit Time Constants ................................................................................ 11
Armature Winding Resistance .............................................................................................. 11
Appendix 1 – Symmetrical Components .............................................................................................................. 12
Appendix 2 – Transient Reactance Details ........................................................................................................... 15
2
Generator Specifications Open Distribution
Introduction
This document explains the generator specifications that the generator owner provides
to the transmission planner for use in power flow, transient stability, and short-circuit
studies. It accompanies the Generator Specifications workbook.
Audience
The audiences for this document include:
1. Generator owners who provide the information to the transmission owners.
2. Transmission owners and planners who use this information in their planning
studies.
3. Operating engineers who also use this information in their operations planning
and real-time operating studies, including state estimators and contingency
analysis.
4. Anyone looking for a simple explanation of steady-state and transient generator
specifications.
3
Generator Specifications Open Distribution
Prime Mover Typical Rotor Type Rotor Speed Inertia Constant Comments
Steam Turbine Cylindrical High: 1800 or 3600 RPM High Stand-alone or back
end of combined cycle
generator
Combustion Cylindrical High: 1800 or 3600 RPM Fairly high
Turbine
Hydro Turbine Salient-pole Low: 120 RPM ± Highest
Diesel Engine ??? Low ???
Wind Turbine ??? Turbine: Low Lowest
Generator: High (geared)
4
Generator Specifications Open Distribution
Inertia
The inertia of the generator is the mechanical Figure 2 – Salient, multiple-pole generator.
energy stored in its rotating parts—the
turbine, generator, exciter1, and shaft. The generator’s inertia affects how it responds
mechanically (and, hence, electrically) to a disturbance on the transmission system. The
total inertia of all on-line generators, and where the generators are located, determines
the transient response of the entire transmission system.
Moment of inertia, J (Lb-ft2). The mechanical resistance of the generator to change its
state of rotation. The moment of inertia is related to the total mass of the rotating
components and their rotational speed, not the electrical rating of the generator.
Inertia constant, H (MW-seconds/MVA). The ratio of the total rotational energy stored
in the rotating components divided by the generator’s nameplate MVA rating:
1⁄ 𝐽𝜔2
2
𝐻= .
MVA
1Assuming the exciter is driven by the same prime mover as the generator. Exciters driven by a separate turbine do not
contribute to the inertia of the turbine-generator connected to the transmission system.
2 This should be fairly obvious given the size of the different kinds of prime movers.
5
Generator Specifications Open Distribution
Generator Reactances
Flux patterns and saturation
The concepts of flux, flux saturation, and how the flux can be
represented along the direct and quadrature axes of the
armature and rotor are important key to understanding the
generator reactances.
Flux saturation
Flux saturation refers to the degree to which the rotor field or
armature “teeth” can accommodate additional magnetic flux,
which, in turn affects the value of the machine’s transient and
sub-transient reactances. When the generator’s flux paths are
unsaturated, a sudden change in armature current (either due to
a sudden load change or short circuit) is met with increased
reactance due to the additional flux produced in the rotor or
armature fields. Conversely, if the flux path is highly saturated, Figure 6 - Generator reactance can be depicted as having
changes in the armature current cannot contribute to the flux two components along the direct and quadrature axes of
build-up, which means the generator’s reactance is reduced. the windings. The coils shown in this diagram serve only
to represent the model of the generator and do not have
Direct and Quadrature Axes reactance values per se.
To accommodate the flux path patterns, we can represent the
electro-mechanical equivalents of the generator reactances by assuming they lie in two
directions: one along the direct axis of the rotor and armature windings and a second
one along the quadrature axis, which is at right angles to the direct axis. (See Figure 8).
6
Generator Specifications Open Distribution
Synchronous Reactance
Xdv Xqv
Xdi Xqi Synchronous reactance is the generator’s steady-
state reactance caused by a combination of the
armature winding leakage reactance plus the
reactance used to represent the armature reaction
to a short circuit. As shown in Figure 9, in the
linear part of the open circuit voltage curve, the
unsaturated synchronous reactance is constant. As
the machine saturates, synchronous reactance falls.
Synchronous reactance at a given field current (or
excitation voltage) can be estimated from the
gradient of the open circuit voltage and short circuit
current curves.3
The armature winding leakage reactance is
Xlm caused by the flux in the armature winding caused Figure 7 – The generator’s synchronous reactance is a function of the
by the armature (load) current, and its magnetic armature’s open-circuit voltage and short-circuit current.
path is normally not saturated.
3Excerpt from course taught by Professor Andy Knight, Energy Systems Group, University of Alberta. Used with
permission.
7
Generator Specifications Open Distribution
The subtransient
Subtransient – saturated X”dv 0.1448 X”qv 0.1432 reactance, X”, for the
direct and quadrature
Subtransient – unsaturated X”di 0.1680 X”qi 0.1661 axis are almost equal for
Transient – saturated X’dv 0.1968 X’qv 0.3726 both saturated and
unsaturated conditions.
Transient – unsaturated X’di 0.2236 X’qi 0.4234
Per-unit
Reactance
Negative Sequence – saturated X2v 0.1440
Negative Sequence – unsaturated X2i 0.1670
Zero Sequence – saturated X0v 0.0794
Zero Sequence – unsaturated X0i 0.0835
8
Generator Specifications Open Distribution
opening of the generator’s terminals (open circuit), after which we follow the armature
voltage decay to its steady-state condition, and three types of short circuits from which
we follow the armature current decay. The three short circuits comprise a balanced, 3-
phase fault, and two unbalanced line-to-line and line-to-neutral (ground) faults.
Typical Values
The following table shows typical values for a 230 MVA, air-cooled round rotor
generator. Note that the subtransient time periods (T”) are on the order of cycles along
both the direct and quadrature axes, while the transient time periods (T’) are in seconds
along the direct axis, and tenths of a second along the quadrature axis.
9
Generator Specifications Open Distribution
10
Generator Specifications Open Distribution
Figure 14 - Delta-connected
armature.
11
Generator Specifications Open Distribution
12
Generator Specifications Open Distribution
Figure 16 - The generator's continuous ratings are measured at the generator terminal bus.
13
Generator Specifications Open Distribution
The following table lists four types of short circuits and the current (or voltage or
impedance) component(s) that result.
Three-Phase Yes No No
14
Generator Specifications Open Distribution
From transfer functions (1) and (3), we see that the effective d and q-axis inductances of
the generator looking into the stator terminals will vary with time as functions of the
open-circuit and short-circuit time constants. For these time constants, the sub-
transient quantities, denoted by ", are normally much smaller than the transient
quantities, denoted by '. During steady state conditions, with s = 0, we see from transfer
functions (1) and (3) that Ld(0) = Ld and Lq(0) = Lq which are the d and q-axis
synchronous inductances of the generator. During a rapid transient, as s tends to
infinity in transfer functions (1) and (3), the limiting values of L d(s) and Lq(s) are given
by the following:
These are just the d and q-axis subtransient inductances of the generator and represent
the machine's effective inductances immediately following a sudden change. For the
transient time period, as the machine is transitioning to a steady state from a sudden
change, if we ignore the sub-transient time constants in (1) and (3) and let s tend to
infinity, then the limiting values of Ld(s) and Lq(s) are given by:
These are just the d and q-axis transient inductances of the generator and represent the
machine's effective inductances during the time period when it is transitioning to steady
state following a sudden change.
Typically, the open-circuit time constants determine the rates of change of currents and
voltages when the machine is open circuited at its stator terminals. The short-circuit
time constants likewise determine the rates of change when the machine is short-
15
Generator Specifications Open Distribution
circuited at its terminals. The short-circuit time constants are always smaller than their
associated open-circuit values.
Another interesting observation from transfer functions (4) and (5) during open-circuit
conditions follows:
For open circuit conditions, ∆id and ∆iq = 0. Therefore from transfer functions (4) and
(5), we see that only the d-axis stator flux, Yd, is nonzero for open circuit conditions.
This means that the terminal voltage of the generator will only have a d-axis component
and from transfer function (4), this component will respond to changes in field voltage,
efd, with time constants Td0' and Td0". (Remember that voltage is just the time derivative
of flux which is the same as multiplying transfer function (4) by the Laplace operator, s.)
16