Thermal Overload Motor Relay Protection
Thermal Overload Motor Relay Protection
com/thermal-
overload-motor-relay-protection
The generally accepted rule is that insulation life is halved for each 10° C rise in
temperature above the rated value, modified by the length of time spent at the
higher temperature. As an electrical machine has a relatively large heat storage
capacity, it follows that infrequent overloads of short duration may not adversely
affect the machine.
However, sustained overloads of only a few percent may result in premature
ageing and insulation failure. Furthermore, the thermal withstand capability of the
motor is affected by heating in the winding prior to a fault.
This is the principle behind the ‘thermal replica’ model of a motor used for
overload protection.
where:
Tmax = final steady state temperature
τ = heating time constant
where:
IR = current which, if flowing continuously, produces temperature Tmax in the
motor
Therefore, it can be shown that, for any overload current I, the permissible
time t for this current to flow is:
In general, the supply to which a motor is connected may contain both positive
and negative sequence components, and both components of current give rise
to heating in the motor.
Therefore, the thermal replica should take into account both of these
components, a typical equation for the equivalent current being:
where:
I1 = positive sequence current
I2 = negative sequence current
and
Finally, the thermal replica model needs to take into account the fact that the
motor will tend to cool down during periods of light load, and the initial state of
the motor. The motor will have a cooling time constant τr, that defines the rate of
cooling.
where:
Equation 1 takes into account the ‘cold’ and ‘hot’ characteristics defined in IEC
60255, part 8.
Some relays may use a dual slope characteristic for the heating time constant,
and hence two values of the heating time constant are required. Switching
between the two values takes place at a pre-defined motor current. This may be
used to obtain better tripping performance during starting on motors that use a
star-delta starter. During starting, the motor windings carry full line current, while
in the ‘run’ condition, they carry only 57% of the current seen by the relay.
Similarly, when the motor is disconnected from the supply, the heating time
constant τ is set equal to the cooling time constant τr.
Since the relay should ideally be matched to the protected motor and be capable
of close sustained overload protection, a wide range of relay adjustment
is desirable together with good accuracy and low thermal overshoot.