Ref 1 AR-1209
Ref 1 AR-1209
AR-1209
Special Report
5/18/10
Table of Contents
NERC’s Mission
The North American Electric Reliability Corporation (NERC) is an international regulatory authority for
reliability of the bulk power system in North America. NERC develops and enforces Reliability
Standards; assesses adequacy annually via a ten-year forecast and winter and summer forecasts; monitors
the bulk power system; and educates, trains, and certifies industry personnel. NERC is a self-regulatory
organization, subject to oversight by the U.S. Federal Energy Regulatory Commission (FERC) and
governmental authorities in Canada. 1
NERC assesses and reports on the reliability and adequacy of the North American bulk power system
divided into the eight Regional Areas as shown on the map below (See Table A). 2 The users, owners, and
operators of the bulk power system within these areas account for virtually all the electricity supplied in the
U.S., Canada, and a portion of Baja California Norte, México.
MRO SPP
Midwest Reliability Southern Power Pool,
Organization Inc.
NPCC
WECC
Northeast Power
Western Electricity
Coordinating Council,
Note: The highlighted area between SPP and SERC denotes overlapping Regional Coordinating Council
Inc.
area boundaries: For example, some load serving entities participate in one Region
and their associated transmission owner/operators in another.
1
As of June 18, 2007, the U.S. Federal Energy Regulatory Commission (FERC) granted NERC the legal authority to
enforce Reliability Standards with all U.S. users, owners, and operators of the BPS, and made compliance with those
standards mandatory and enforceable. In Canada, NERC presently has memorandums of understanding in place
with provincial authorities in Ontario, New Brunswick, Nova Scotia, Québec and Saskatchewan, and with the
Canadian National Energy Board. NERC standards are mandatory and enforceable in Ontario and New Brunswick as
a matter of provincial law. NERC has an agreement with Manitoba Hydro, making reliability standards mandatory
for that entity, and Manitoba has recently adopted legislation setting out a framework for standards to become
mandatory for users, owners, and operators in the province. In addition, NERC has been designated as the “electric
reliability organization” under Alberta’s Transportation Regulation, and certain reliability standards have been
approved in that jurisdiction; others are pending. NERC and NPCC have been recognized as standards setting bodies
by the Régie de l’énergie of Québec, and Québec has the framework in place for reliability standards to become
mandatory. Nova Scotia and British Columbia also have a framework in place for reliability standards to become
mandatory and enforceable. NERC is working with the other governmental authorities in Canada to achieve
equivalent recognition.
2
Note ERCOT and SPP are tasked with performing reliability self-assessments as they are regional planning and
operating organizations. SPP-RE (SPP – Regional Entity) and TRE (Texas Regional Entity) are functional entities to
whom NERC delegates certain compliance monitoring and enforcement authorities.
Table of Contents
1. Introduction ................................................................................................................................1
2.2. Time-Domain Positive Sequence Dynamic Models for Bulk Power System Stability
Analysis ........................................................................................................................................4
Acronyms .............................................................................................................................................. 47
Executive Summary
Existing state and federal energy policies including renewable portfolio standards (RPS) and
production tax credits have driven development of wind plants in the U.S. and Canada that
presently comprise in excess of 35 GW of installed capacity. This trend is projected to continue
with the addition of many other forms of renewable technologies such as photovoltaics.
Furthermore, other technologies like plug-in hybrid electric vehicles (PHEV), tidal-power
systems, etc. are also on the horizon.
Unlike traditional, non-renewable resources, the output of wind, solar, ocean and some hydro
generation resources varies according to the availability of the primary fuel (wind, sunlight and
moving water) that cannot be reasonably stored. Therefore, these resources are considered
variable, following the availability of their primary fuel source.
The North American Electric Reliability Corporation (NERC) is responsible for ensuring the
reliability of the bulk power system in North America. Anticipating the growth of variable
generation, in December 2007, the NERC Planning and Operating Committees created the
Integration of Variable Generation Task Force (IVGTF), charging it with preparing a report [1]
to identify the following:
1) Technical considerations for integrating variable resources into the bulk power
system,
One of the identified follow-up tasks from [1] was the need standard, valid, generic, non-
confidential, and public power flow and stability models for variable generation technologies,
and for a task force to review existing NERC Modeling, Data and Analysis (MOD) Standards to
ensure high levels of variable generation can be simulated and appropriately addresses through
the existing standards. This document constitutes the results of this review performed by this
Task Force. A detailed discussion is provided of model and model validation in general,
followed by an account of the current status of models for various variable generation
technologies. Then a discussion is provided of the relevant NERC MOD standards and where
they will need to be augmented to properly address variable generation.
Thorough out this report reference is made to various forms of models (standard, generic, user-
written, 3-phase, etc.). It should be emphasized that the present and imminent need is to have
models that are standard (i.e. a defined model structure used by all commercial software tools),
publicly available and not specific to any particular design (i.e. “generic” and able to reasonably
i
Executive Summary
represent key performance relevant to bulk power system studies) – this is the focus, which is
further elaborate in the report. The process and need for model validation, however, applies to
any and all levels of modeling.
An earlier draft of this report and recommendations were presented to NERC’s Planning
Committee at their March, 2010 meeting. The Committee members urged the IVGTF to pursue
NERC reliability standard development. Thus, several NERC Standards Drafting Teams
undertaking MOD Standard development will be contacted to present the recommendations from
this report for their consideration and incorporation in subsequent updates.
ii
Introduction
1. Introduction
Existing state and federal energy policies including renewable portfolio standards (RPS) and
production tax credits have driven development of wind plants in the U.S. and Canada that
presently comprise in excess of 35 GW of installed capacity. This trend is projected to continue
with the addition of many other forms of renewable technologies such as photovoltaics.
Furthermore, other technologies, like plug-in hybrid electric vehicles (PHEV), are also on the
horizon.
Unlike traditional, non-renewable resources, the output of wind, solar, ocean and some hydro
generation resources varies according to the availability of the primary fuel (wind, sunlight and
moving water) that cannot be reasonably stored. Therefore, these resources are considered
variable, following the availability of their primary fuel source. There are two overarching
attributes of variable generation that can impact the reliability of the bulk power system if not
properly addressed:
The North American Electric Reliability Corporation (NERC) is responsible for ensuring the
reliability of the bulk power system in North America. Anticipating the growth of variable
generation, in December 2007, the NERC Planning and Operating Committees created the
Integration of Variable Generation Task Force (IVGTF), charging it with preparing a report [1]
to identify the following:
3) Technical considerations for integrating variable resources into the bulk power
system
One of the identified follow-up tasks from [1] was the need for the models for variable
generation technologies. For the purpose of completeness of this document, the proposed action
item Task 1-1 from [1] is repeated below.
1
Introduction
Item Proposed
# Improvement Abstract Lead Deliverables Milestones
1.1 Standard, valid, Valid, generic, non-confidential, Ad Hoc Make ● Draft report ready
generic, non- and public standard power flow group: recommendations by December
confidential, and and stability (positive-sequence) Members and identify 2009 PC meeting
public power flow models for variable generation ● Final report with
from IVGTF changes needed to
and stability technologies are needed. Such recommendations
models (variable models should be readily validated - Planning NERC’s MOD to PC for
generation) are and publicly available to power Standards endorsement in
needed and must be utilities and all other industry February 2010
developed, stakeholders. Model parameters ● Develop SAR
enabling planners should be provided by variable with Standards
to maintain bulk generation manufacturers and a Committee if
power system common model validation standard required.
reliability across all technologies should be
adopted. The NERC Planning
Committee should undertake a
review of the appropriate
Modeling, Data and Analysis
(MOD) Standards to ensure high
levels of variable generation can be
simulated. Feedback to the group
working on NERC Standards’
Project 2007-09 will be provided.
Therefore, the goal of this document is to address the above action item and to provide:
1. The roadmap for development of valid, generic, non-confidential, and public standard
power flow and stability (positive-sequence) models for variable generation technologies.
Namely, what is available at present and what is the path forward to developing and
deploying these models.
2. The NERC standards implications and feedback on what further NERC action items may
be needed, if any, to address model application and validation as it relates to variable
generation.
Throughout this report reference is made to various forms of models (standard, generic, user-
written, 3-phase, etc.). The present and imminent requirement is to have models that are
standard (i.e. a defined model structure used by all commercial software tools), publicly
available and not specific to any particular design (i.e. “generic” and able to reasonably represent
key performance relevant to bulk power system studies) – this is the focus, which is further
elaborated upon this report. The process and need for model validation, however, applies to any
and all levels of modeling.
2
Characteristics of Power Systems & Variable Generation
The planning and operation of large interconnected power systems in diverse regions in the
North American continent, is a complex task which requires daily analysis and computer model
simulations. System planners and operators use simulation studies to assess the potential impact
of credible (and sometimes extreme) contingency scenarios and to assess the ability of the power
system to withstand such events while remaining stable and intact (i.e., to avoid cascading
outages). When a credible disturbance event is simulated in computer models of the power
system and the observed result is unacceptable performance, system planners and/or operators
must develop either operating strategies or planned equipment additions (e.g., line re-
conductoring, addition of shunt reactive compensation devices, etc.) to mitigate the potential
problem. To help ensure proper assessment of reliable performance and to minimize (as much as
possible) capital investment, models are required that reasonably represent actual equipment
performance in simulations.
The NERC Modeling, Data, and Analysis (MOD) Reliability Standards require Registered
Entities to create procedures needed to develop, maintain and report on models to analyze the
steady-state and dynamic performance of the power system (MOD-011 and MOD-013).
Equipment owners are required to provide steady-state and dynamic models (MOD-012) to the
Regional Entities. This information is required to build a reasonable representation of the
interconnected system for planning purposes, as stated in MOD-014 and MOD-015. 3
Specifically, models are required to perform powerflow, short circuit, and stability studies
necessary to ensure bulk power system reliability.
Therefore, system models are required for generation equipment at three levels:
1. Models for assessing the steady-state behavior of the units and their fault current
contributions for protection system analysis.
2. Models for emulating the dynamic behavior of the units for bulk power system time-
domain stability analysis.
In this chapter, the aforementioned three categories of models are described in detail focused on
variable generation technologies.
3
http://www.nerc.com/page.php?cid=2|20
3
Characteristics of Power Systems & Variable Generation
To assess the adequacy of protection system settings, faults on transmission equipment are
simulated and the settings for protection relays are evaluated, as well as the calculated fault
currents are compared to the current rating of circuit-breakers.
Both these analyses are critical to the reliable operation of the power system. To perform these
analyses, adequate models are needed for simulating the steady-state power flow and the fault
current characteristics of generation equipment.
2.2. Time-Domain Positive Sequence Dynamic Models for Bulk Power System Stability
Analysis
Time-domain simulations are a key tool for assessing the reliability of the bulk power system
assessing the stability of the system. 4
“Reliability of a power system refers to the probability of its satisfactory operation over the
long run. It denotes the ability to supply adequate electric service on a nearly continuous
basis, with few interruptions over an extended time period.
Stability of a power system refers to the continuance of intact operation following a
disturbance. It depends on the operating condition and the nature of the physical
disturbance.”
Similarly, NERC defines stability as, “The ability of an electric system to maintain a state of
equilibrium during normal and abnormal conditions or disturbances.” 5
4
The definitions listed are quoted from: P. Kundur, J. Paserba, V. Ajjarapu, G. Andersson, A. Bose, C. Canizares,
N. Hatziargyriou, D. Hill, A. Stankovic, C. Taylor, T. Van Cutsem and V. Vittal, “Definition and classification of
power system stability: IEEE/CIGRE joint task force on stability terms and definitions”, IEEE Transactions on
Power Systems, Volume 19, Issue 3, Aug. 2004, pp: 1387 – 1401. (http://ieeexplore.ieee.org)
4
Characteristics of Power Systems & Variable Generation
5
Glossary of Terms Used in Reliability Standards, http://www.nerc.com/files/Glossary_2009April20.pdf, Updated
April 20, 2009,
6
P. M. Anderson, B. L. Agrawal and J. E. Van Ness, Subsynchronous Resonance in Power Systems, IEEE Press,
New York, 1990.
P.M. Anderson and R. G. Farmer, Series Compensation of Power Systems, ISBN 1-888747-01-3, 1996
7
See Appendix I for more information on these WTG configurations.
5
Characteristics of Power Systems & Variable Generation
to large conventional synchronous generators since the typical torsional mode for a wind turbine
is quite low (around 1 to 4 Hz). Accordingly, it would be quite unlikely that the level of series
compensation in a system would be high enough to result in an electrical resonance that would
interact with a low mechanical frequency. 8 A larger concern is induction machine self-
excitation. 9 Some detailed 3-phase analysis and discussions with the wind turbine manufacturer
on a case by case basis is prudent when installing wind near series compensated lines.
Another potential phenomenon related to torsional mechanical modes is device dependant
subsynchronous oscillations, often referred to in the literature as subsynchronous torsional
interaction (SSTI). This was first observed at the Square Butte HVDC project in 1976. 10 SSTI is
a phenomenon by which controls associated with power electronic based transmission equipment
(e.g., SVC or HVDC) may introduce negative damping torques in the frequency range associated
with the torsional mechanical modes of oscillation of nearby thermal turbine-generating units.
Again, due to the relatively low frequency range for torsional modes of wind turbine, this may
not be a concern in most cases; however, where wind plants are closely coupled to a HVDC
system, analysis is prudent to ensure that control and/or torsional interaction do not occur. This
analysis will typically require detailed three-phase models for both the wind plant and the HVDC
system. Also, SSTI is not necessarily detrimental 11 because, in some cases, torsional damping
can be markedly improved through the application of power electronic devices. One thermal
power plant in the Western U.S. grid uses a dedicated SVC for this purpose as a means of
mitigating the effects of SSR. 12 A practical example of this is the Taiban Mesa wind plant
located in New Mexico. This wind plant is located electrically adjacent to a back-to-back HVDC
station – Blackwater. The detailed interconnection studies performed by ABB during the design
of the wind plant showed that there was little risk of torsional interaction between the HVDC
controls and the wind turbine generators. This analysis required detailed equipment level (3-
phase) models of the wind turbines, the HVDC and transmission network.
8
Note: The electrical resonance needs to be in the range of 56 to 59 Hz on a 60 Hz system found in North America.
9
P.M. Anderson and R. G. Farmer, Series Compensation of Power Systems, ISBN 1-888747-01-3, 1996
C. F. Wagner, “Self-Excitation of Induction Motors with Series Capacitors”, AIEE Transactions, pp.1241-1247,
Vol. 60, 1941. (http://ieeexplore.ieee.org)
10
M. Bahrman, E. Larsen, R. Piwko, H. Patel, “Experience with HVDC – Turbine Generator Torsional Interaction
at Square Butte”, IEEE Transactions on Power Apparatus and Systems, Vol. PAS-99, pp. 966-975, May/June
1980. (http://ieeexplore.ieee.org)
11
D. Dickmander, P. Pourbeik, T. Tulkiewicz and Y. Jiang-Häfner, “SSTI Characteristics of HVDC Light”, White
paper by ABB Inc., December, 2003
12
Pourbeik, A. Boström and B. Ray, “Modeling and Application Studies for a Modern Static VAr System
Installation”, IEEE Transactions on Power Delivery, Vol. 21, No. 1, January 2006, pp. 368-377.
(http://ieeexplore.ieee.org)
6
Characteristics of Power Systems & Variable Generation
Other phenomena that may expose the shaft of a WTG to cyclical and significant transient torque
pulsations may also be a concern. For example, nearby arc furnaces, or high-speed re-closing on
a transmission line emanating from the wind plant substation, or repeated commutation failures
on a nearby conventional line-commutated HVDC. As a first step, some simple transient stability
analysis may be performed to estimate the expected step change in the electrical torque on a
wind turbine generator due to the electrical event, and the wind turbine manufacturer consulted
to identify if the observed level of transient torque is a concern. Based on consultation with the
wind turbine manufacturer, more detailed analysis may be required to assess if a potential
problem exists and how it may be remedied.
Another issue that may be of concern is the stability and behavior of variable generators in
extremely weak short-circuit nodes of the power system and regions of the system that may be
highly susceptible to islanding. Again, more detailed models than positive sequence stability
representations may be needed to study these scenarios (e.g., to accurately review the potential
for temporary over voltages upon islanding, etc.). Also, in some cases and designs (e.g., Type 3
WTG), the behavior of the unit as it pertains to voltage-ride through during fault scenarios can be
more onerous on the controls (i.e., controlling the DC bus voltage in the Type 3 WTG) for
unbalanced fault scenarios as opposed to a balance 3-phase faults. Thus, 3-phase detailed
equipment models are needed to assess these phenomena.
Finally, transient stability studies should be completed to ensure that basic control loops in the
variable generation plants (e.g., central voltage control systems often deployed in doubly-fed and
full-converter based wind plants that regulate voltage at the interconnecting substation by
adjusting the reactive output of all wind turbines in the wind plant) do not interact or interfere
with other nearby transmission and generation controls. This often requires proper tuning of the
controls.
This brief section illustrates the need for the availability of detailed 3-phase equipment level
models, which cannot be generic. These models are likely to be proprietary and may need to be
used under non-disclosure agreements between the vendor and the plant developer/utility.
Therefore, it is important to recognize the need for these models so that they are developed and
available to be easily deployed and used when such specialized studies are needed.
2.4. Summary
This chapter has outlined the basic power generation plants models required power system
analysis related to reliability assessment. In addition, these models need to be generic (i.e., the
model structure applicable to any vendor’s equipment, with only the variation of the model
parameters to represent various vendor equipment) and non-proprietary (i.e., publicly available
to all stakeholders). Adequate models readily exist for conventional synchronous generators, but,
until recently, have been unavailable for any variable generation technology. In the next chapter
the current status of models for all variable generation technologies is discussed.
7
Transmission Planning & Resource Adequacy
This chapter provides an overview of the models and modeling capability presently available. In
the summary of this chapter the gaps are identified and areas requiring further work are
identified. The modeling and model development discussed here is primarily for power system
power flow, short-circuit and stability analysis.
Switching Transients
Subsynchronous Resonance
Transient Stability
Long-term Dynamics
TIME (seconds)
Figure 3.1: Times of various phenomena of interest in power system studies (GE).
8
Transmission Planning & Resource Adequacy
of several 100 MW and larger are being proposed. By some projections, 13 as much as 300 GW
(20% penetration) of wind generation capacity is forecast in the U.S. by 2030 and NERC
projects an increase of 229 GW of new wind generation installed capacity by 2018. 14 The
increased penetration of renewable energy generation poses significant questions concerning the
ability of the power system to maintain reliable operation.
Presently, most wind turbine technologies use power electronics and advanced reactive power
compensation as an integral part of wind turbine generator and wind power plant. Under
dynamic transients, the behavior of modern wind turbines must be accurately simulated to
predict the response of the wind power plant. Misrepresentation of WTGs in transmission studies
may threaten the reliability of power systems by either resulting in excessive overbuild of
transmission systems due to pessimistic models, or in deficient transmission system investment
based on optimistic models.
Turbine manufacturers have developed dynamic models for their wind turbines. These dynamic
models are typically user-written models in commercially available power system simulation
software platforms (e.g., Siemens PTI PSSTME, GE PSLFTM, DigSILENT PowerFactory, etc.).
Detailed three-phase equipment level models of WTGs used for internal design purposes are also
often developed by manufacturers in either their own simulation platforms or commercial
software tools including PSCAD® or Matlab® Simulink.
Unfortunately, both these categories of models (the user-written positive-sequence models and
the three-phase detailed equipment models) require significant input data/parameters considered
to be proprietary by the turbine manufacturers and therefore are not freely available to the
general public. Access to these models usually requires a non-disclosure agreement (NDA)
between the dynamic model user and the turbine manufacturers. This agreement is only valid for
a specific turbine model, for a given period of time.
In many cases, it takes months to negotiate and to finalize the NDA. Furthermore, in some cases
there are incompatibilities among turbine models developed by different turbine manufacturers
which results in numerical interactions if multiple user-written models are incorporated into a
single power system model for system analysis. This makes the work of power system planners
almost impossible. The NDA are also usually bilateral, which renders it impossible to share the
information among the manufacturers to help resolve incompatibility problems. Finally, the
NDAs make it difficult, at best, and impossible, in some cases, to share the models thereby
potentially violating the NERC requirements for submitting models for system planning studies.
13
http://www.nrel.gov/docs/fy07osti/40482.pdf
14
http://www.nerc.com/files/2009_LTRA.pdf
9
Transmission Planning & Resource Adequacy
With this back drop, the WECC Wind Generator Modeling Group (WGMG) initiated the
development of generic wind turbine models of the four (4) different types of wind turbines (see
Appendix I for these four WTG designs). These four types of turbines currently hold the largest
market share throughout the world. WECC is interested in providing accurate and validated
models of standard wind turbines that will be available in their database, including the datasets to
be used for testing the models, and the methods for representing a wind power plant in power
system studies. These goals are being accomplished through the development and validation of
standard models. The standard models must be generic in nature – that is, they must not require
nor reveal proprietary data from the turbine manufacturers. These improved standard (generic,
non-proprietary) dynamic models enable planners, operators and engineers to perform the
necessary transmission planning studies required to ensure system reliability.
Currently, the first generation of these generic WTG models, for all four turbines types, have
been developed and are available as part of the main model library for the two most widely used
commercial power system simulation tools in North America (i.e., Siemens PTI PSSTME, GE
PSLFTM) 15. As a continuation of, and in parallel with, the WECC effort, the Institute of
Electronic and Electrical Engineers (IEEE), Power & Energy Society (PES) has also established
a Working Group to investigate WTG modeling issues: The IEEE Working Group on Dynamic
Performance of Wind Power Generation, under the Power System Dynamic Performance
Committee. This Working Group is actively expanding the efforts of generic dynamic modeling
for wind power plants, focusing on modeling specifications, disseminating methods and model
validation.
To date, the first generation of generic models developed and released have focused on capturing
the response of the units to electrical voltage disturbances on the transmission grid (grid faults).
One deficiency, particularly for the Type 1 and 2 models, is the proper representation of unit
responses to large system frequency excursions. These models have not been verified due to the
lack of data on actual turbine behavior under such circumstances and will require further
development, in consultation with turbine manufacturers.
Finally, as with all modeling exercises, model development and validation are iterative
processes, requiring:
15
PSS®E-32.0 Program Application Guide: Volume II, Chapter 21.
PSS®E-32.0 Model Library, Chapters 17 through 21
GE PSLF User's Manual. v.17.0_04. October, 2009.
10
Transmission Planning & Resource Adequacy
• Generic wind turbine models must be validated before release and public
dissemination, which is being pursued in WECC, IEEE, International
Electrotechnical Commission (IEC) and other forums.
• Data from field measurement and monitoring for model validation can be a
vital resource.
A somewhat unique need in modeling variable generation (e.g., wind) is the need for methods
required to develop equivalent models for large wind power plant. In contrast to conventional
fossil fuel and hydro power plants, where plants are constituted by either a single large unit or, at
most, a few large units, a wind power plant can be made up of tens to more than a hundred
WTGs. For large scale power system simulations, particularly in North America where the
power system models are quite large, it is often preferred to reduce the wind power plant to a
single equivalent unit. Accordingly, techniques are needed for model aggregation and testing
their validity – some significant progress has been made in this regard. For example, Figure 3.2
shows the technique developed for reducing the impedance of the wind power plant collector
system into a single, equivalent feeder impedance for representation of the wind power plant
(WPP) by an aggregated single equivalent unit in power system studies.
Figure 3.2: Example shows the method for reducing the impedance of a wind power plant
collector system into a single equivalent impendence. 16
16
“WECC Wind Generator Power Flow Modeling Guide”
(http://www.wecc.biz/library/WECC%20Documents/Documents%20for%20Generators/Generator%20Testing%2
0Program/Wind%20Generator%20Power%20Flow%20Modeling%20Guide.pdf)
11
Transmission Planning & Resource Adequacy
Figure 3.3 shows an example for dynamic simulations of aggregating the WPP into a single
equivalent unit and an equivalent single impedance representing the entire collector system as
compared to a detailed model representing the whole WPP unit-by-unit – the example shown
assumes that all WTGs in the WPP are identical, in cases where this is not true multiple
equivalent units may be needed one for each WTG type. As can be seen in this figure, the results
from the two simulations compare very well at the point of interconnection (which is what is
shown); thus, the equivalent aggregate is adequate for power system studies. 17
P34.5 kV
Q34.5 kV
17
Figure is from J. Brochu, R. Gagnon and C. Larose, “Validation of the WECC Single-Machine Equivalent Power
Plant”, Presented at the IEEE PES DPWPG-WG Meeting at IEEE PSCE, March 2009.
12
Transmission Planning & Resource Adequacy
The objectives of the project, which will commence in early 2010 and run for a period of two
years, are to:
• Defining proposed enhancements to the generic wind turbine model structures that would
allow representation of more advanced features including power control, automatic
curtailment, inertial and governor response;
• Comparative testing of the generic models against more detailed (and sometimes
proprietary) versions developed by turbine vendors;
• Developing recommended parameters for the generic models to best mimic the
performance of specific commercial wind turbines;
• Acquiring test data from all available sources for the purpose of validating the
performance of the appropriately specified generic models in actual case studies;
18
The UWIG was established in 1989 to provide a forum for the critical analysis of wind technology for utility
applications and to serve as a source of credible information on the status of wind technology and deployment.
The group’s mission is to accelerate the development and application of good engineering and operational
practices supporting the appropriate integration of wind power into the electric system. It currently has more than
150 members spanning the United States, Canada, and around the world including investor-owned, public power,
and rural electric cooperative utilities; transmission system operators; and associate member corporate,
government, and academic organizations http://www.uwig.org/aboutuwig.htm
13
Transmission Planning & Resource Adequacy
Maintaining communication and coordination with other ongoing activities and agencies
engaged in this topic is another objective of the effort which will be critical for success.
Part 2 of this work will be focused on extending the modeling to allow for modeling of the entire
wind power plant, including wind power plant control and auxiliary equipment.
Several members of this IEC Working Group are also members of the WECC and IEEE
Working Groups (and this NERC Task Force). The three groups are clearly working in close
collaboration to ensure maximum benefit to the industry globally and maximum sharing of
knowledge already gained through the WECC and IEEE efforts.
19
http://www.iec.ch/dyn/www/f?p=102:14:0::::FSP_ORG_ID:5613
14
Transmission Planning & Resource Adequacy
Figure 3.4: Current-Voltage characteristics of a solar cell for various insolation levels at a
constant temperature (source [11] 21).
20
The photo-voltaic effect is the process by which an electric potential difference (voltage) is created in a material
exposed to light (electromagnetic radiation), which then leads to the flow of electric current. This process is
directly related to the photo-electric effect, but distinct from it in that in the case of the photo-electric effect
electrons are ejected from the material surface upon being exposed to high enough frequency (energy) light,
whereas in the photo-voltaic effect the generated electrons are transferred across a material junction (e.g., PN
junction in a photo-diode) resulting in the buildup of a voltage between two electrodes and the flow of direct
current electricity.
21
Solar Radiation Research Laboratory at the National Renewable Energy Laboratory
(http://www.nrel.gov/midc/srrl_rsp/)
15
Transmission Planning & Resource Adequacy
Figure 3.5 shows that the current is limited when the cell is short-circuited (Voltage=0).
+
Ibus Iload
PV
ARRAY Icap Vbus
(d)
Figure 3.5: The concept of a solar array: (a) a single solar cell, (b) a series connection of
solar cells (Nser = 3 and Npar = 1), and (c) a solar array (Nser = 3 and Npar = 2).
The solar cell array(s) is then connected to a DC bus (d).
Figure 3.5 shows the concept of the solar cell up to the solar array. To use the DC power
generated by the PV array in an AC power system, the DC power must be converted to 60 Hz
AC in North America (50 Hz in some other regions in the world, like Europe). There are several
power electronic based converter concepts that can achieve this, which can be classified into two
general categories: line-commutated converters (LCC) and self-commutated or more commonly
16
Transmission Planning & Resource Adequacy
referred to as voltage-source converters (VSC). These technologies have been applied for
decades and are well understood. LCC use thyristors as their controlled switching device. The
switching on of a thyristors can be controlled, while the turn-off time cannot be controlled and
happens at the next AC waveform current zero crossing. LCC systems must be operated in a
network with an AC source and cannot operate to serve an isolated load. In contrast, VSC
systems are self-commutating, that is the power electronic switching devices used (e.g.,
integrated gate-commutated thyristors or IGCTs and insulated-gate bipolar transistors or IGBTs)
are able to be completely controlled for both turn-on and turn-off and allow the VSC to
completely control the AC waveform produced and adjust the power factor as seen on the AC
side to within the current rating of the device. Due to advances in the technology, most power
electronic converters employed in PV systems are of the VSC type. 22
From a modeling standpoint for power system studies, there are some user-written manufacturer-
specific models in existence as developed by various PV manufacturers. Presently, no generic or
standard models exist.
The WECC Working Group, which has been addressing the development of generic WTG
models, will be extending its effort in 2010 to review developing generic PV models for dynamic
simulations in stability studies. As a starting point, the grid side structure of the Type 4 WTG
model may be used since it represents a VSC. This is because PV is typically connected to the
grid with a VSC and it will behave electrically similar to a Type 4 WTG that has a similar
electrical interface with the grid—this is from a grid perspective looking at the electric response
and neglects any of the effects of the energy source.
From a steady-state, power flow and short-circuit analysis perspective, the behavior of the PV
technologies will behave in a similar fashion to a Type 4 WTG because of the VSC interface,
and because its power factor can be controlled based on the control functionality of the VSC
design. Its short-circuit response will be limited to the current limit effected by the VSC under
grid fault conditions.
The development of generic and standard PV models is presently a topic for further research.
This should be pursued imminently and much of what has been learnt from the WTG model
development process should be leveraged.
22
IEA-PVPS: Grid-Connected Photovoltaic Power Systems: Survey of Inverter and related Protection Equipment;
Report IEA PVPS T5-05: 2002, December 2002 (http://www.iea-pvps.org/products/download/rep5_05.pdf).
17
Transmission Planning & Resource Adequacy
1. Concentrating Solar Power (CSP) plants – in this case solar radiation is typically
collected through a large number of mirrors (thus a large amount of solar radiation)
which is then focused on a small area – the mirrors have tracking systems to follow the
Sun. The concentrated solar radiation heats a high temperature working fluid, which then
feeds a conventional steam-turbine generator. From an electrical grid perspective, the
models needed to simulate the steady-state, short-circuit and transient time-domain
dynamics of such a generating unit, are typically no different than standard synchronous
generating units for fossil fuel plants.
2. The Stirling Engine concept 23 – in this design a parabolic mirror assembly concentrates
the collected solar radiation on a sterling engine that sits at the focal point of the mirror
assembly. A Stirling engine is a reciprocating heat engine that operates based on the
concept of cyclical compression and expansion of a working fluid. As the working fluid
expands/contracts it drives a piston that then turns a generator. The engine is connected
to an electrical generator that produces electric energy. Once again for power system
studies the units may be modeled using standard generator models. However, in this case
a power plant would be constituted by a large number of small units (the typical Stirling
engine is about 25 kW) in a large electrical collector system that collects the power and
injects it into the utility grid – much like the collector system of a wind power plant.
Thus, modeling the collector system (e.g. see Figure 3.2 for an aggregate model of a wind
collector system) and any other devices in the collector system, such as shunt reactive
devices etc. must be properly modeled
23
http://www.stirlingenergy.com/ Y. Zhang and B. Osborn, “Solar Dish-Stirling Power Plants and Related Grid
Interconnection Issues”, IEEE PES General Meeting, 24-28 June 2007.
18
Transmission Planning & Resource Adequacy
Presently, in North America tidal power is not a significant source of power in any region. Some
pilot programs exist for introducing the technology. In April 2009, one was announced in
Snohomish County Public Utility District in Washington State. 24
There are several options for harnessing tidal power. One method is the use of turbines similar to
wind turbines; however the fluid (water) is much denser and requires a turbine with smaller and
bulkier blades, as shown in Figure 3.6. Most of these technologies typically use AC/DC/AC
converter technology, similar to a Type 4 wind turbine, to convert the low frequency generated
electricity to grid frequency AC electricity and interface with the power system. Once this
technology becomes more prevalent a starting point for development of a suitable model
structure may be the Type 4 generic wind turbine models. Understandably, the energy source
characteristics are quite different from wind power and significantly more predictable.
Figure 3.6: One of the many concepts for tidal generation systems (courtesy of Marine
Current Turbines Limited, www.marineturbines.com).
24
http://www.snopud.com/PowerSupply/tidal/tidalpress.ashx?p=1516&756_na=46
19
Transmission Planning & Resource Adequacy
energy storage technologies etc. With respect to static VAr systems (SVCs and STATCOMs),
there is an active WECC working group imminently addressing the issue of generic models for
these devices. 25 The group has made substantial progress with the models defined and
developed, but currently undergoing testing and validation. With regards to the other emerging
technologies, most tend to be power converter based (i.e., connected to the grid through a back-
to-back frequency converter) and so their electrical behavior (neglecting the characteristics of the
energy source) will be similar to Type 4 wind turbines. Until these technologies mature, the basic
structure of other more mature converter based generation technologies can be a good starting
point.
3.6. Summary
This section has briefly presented the various types of variable generation and the present status
of models and model development for power system studies. Wind generation technologies,
being the most prevalent world-wide, have the most mature models. Through efforts started by
WECC and being continued by IEEE and IEC, generic standard models for the four main types
of WTG technologies are being developed. The first generation of these models has been
released in two power system simulation software platforms most commonly used in North
America. Other emerging technologies (e.g., PV, tidal power, etc.) can build on this effort to start
developing generic models. For example, the WECC effort will be extending its scope in 2010 to
look at PV model.
1. To emphasize and support efforts by WECC, IEEE and IEC to develop and standardize
generic models for these technologies for power system planning studies.
2. To encourage manufacturers to familiarize themselves with the generic models being
developed and be willing an able to supply parameters for these generic models to
reasonably represent their equipment for power system stability studies. As highlighted in
Chapter 2, more detailed manufacturer specific models may be needed in special cases
and for specialized studies.
3. To encourage efforts aimed at model validation.
4. To consider any augmentation or additions to reliability standards related to Modeling,
Data and Analysis (MOD) with respect to modeling and model validation of variable
generation. This is discussed in greater detail in section 5 of this report.
25
http://www.wecc.biz/committees/StandingCommittees/PCC/TSS/MVWG/SVCTF/default.aspx
20
Present Status of Model Validation
This chapter gives an overview of the model validation work that has been done hitherto as it
relates to models for variable generation. Necessarily, the primary focus of this section is on
wind turbine generator models, since models for this resource are presently the most mature.
Model validation is often achieved through some form of testing, either in a laboratory/factory or
in field. There is a range of reasons for conducting tests for wind generation. Each test has a
unique set of objectives guiding the design of adequate testing practices.
• Performance Compliance: Compliance to contractual requirements and grid codes are one
reason to perform tests. Interconnection requirements (usually included in plant Power
Purchase Agreements and Interconnection Contracts) and grid codes typically outline
specific technical criteria that must be met to allow a power plant to connect and operate
on the grid. Since these criteria point out specific levels to be met, (for example, voltage,
power factor, and response time) tests may be designed with binary “pass/fail” objectives.
• Model Validation: In much of the world, power plants above a pre-defined size must be
accurately represented with a dynamic simulation model used in stability analysis for
operations and planning purposes. As variable generation sources such as WPP are
growing in size, it is becoming increasingly important to have accurate variable
generation specific models. Tests may be performed to tune and verify simulation models
to closely match the performance of actual equipment. In the western U.S. and Canada,
WECC has mandated that any plant with 20 MVA aggregate generation must be tested
for model validation, including large wind power plants. For North America, the
imminent NERC MOD-026 standard presently under development will enforce model
validation requirements throughout the North American region.
21
Present Status of Model Validation
To achieve the goals of model validation, there are three categories of tests that may be
performed:
• Type Tests: These are tests performed by the manufacturer or independent third-parties of
representative equipment. The intent is to demonstrate that a particular design of
equipment exhibits specific performance, and all other equipment of that same design is
assumed to have the same performance. Type tests can be:
o Factory: A systemic test of a major assembly (i.e., a drive train) or entire turbine-
generator is performed under a controlled environment like a manufacturing
facility to verify performance and validate assembly design.
• Field Tests 26: Tests performed by the power plant asset owner, developer, host utility,
manufacturer and/or independent third-parties of specific operating equipment. These
tests are to demonstrate that a particular implementation, design and installation of
equipment exhibit specific performance.
26
See for example: WSCC Control Work Group and Modeling & Validation Work Group, “Test Guidelines for
Synchronous Unit Dynamic Testing and Model Validation”, February 1997. (www.wecc.biz), and IEEE Task
Force on Generator Model Validation Testing, “Guidelines for Generator Stability Model Validation Testing”,
Proceedings of the IEEE PES General Meeting, Tampa, FL, June 2007 (http://ieeexplore.ieee.org)
22
Present Status of Model Validation
o Periodic Codes & Standards Validation: Tests performed periodically after the
plant is in commercial operation to benchmark and validate plant performance per
contractual requirements. These tests are typically performed to obtain a
permanent operating license for the power plant.
• On-Line Monitoring 27: Other information of interest is from continuous data gathering
based on ongoing performance of an operating power plant. Data collected from external
and unscheduled events, including grid disturbances or in the case of WTG large changes
in wind is particularly useful. Monitoring also benchmarks performance under normal
operation.
With these general concepts in mind, the following subsections present some example cases
studies of model validation and validation approaches for variable generation sources. The
examples emphasize WPP and WTG, since wind generation is the present dominant variable
generator sources in the North America continent.
27
See for example: P. Pourbeik, “Automated Parameter Derivation for Power Plant Models From System
Disturbance Data”, Proceedings of the IEEE PES General Meeting, Calgary, Canada, July 2009
(http://ieeexplore.ieee.org). This reference shows actual application of on-line disturbance monitoring to power
plant model validation for conventional fossil fuel generation. It may be feasible to apply similar algorithms and
approaches for continuous re-validation of WTG and other variable generation technologies once generic
standard models have been developed. This is a current topic for research.
23
Present Status of Model Validation
from the closest major load centers. With this configuration, the system transfer capability is
mainly limited by stability constraints (transient stability and voltage stability) rather than
congestion or thermal capacity of equipment; hence the need for reliable models for wind power
plants and all other generation.
Stability studies are critical to determine the compensation equipment required to maintain the
reliability of the power system when integrating new generation. They are also essential for
operation planning studies including control system design and tuning and determination of
transfer capabilities.
So far, Hydro-Québec has faced two major difficulties regarding user-written models provided
by the wind turbine manufacturers. First, models often lack robustness and do not represent
accurately some important features (convergence problems in low short-circuit network, do not
take into account frequency excursions, do not represent secondary voltage regulation, etc.).
Second, model validation by the manufacturers is often incomplete, not available, or difficult to
translate to real projects (different settings or software versions, design of the collector system,
etc.). In some cases, these difficulties have lead Hydro-Québec to build its own models (see
Hypersim section below).
Since 2006, Hydro-Québec has performed validation tests on WPP connected to its transmission
system and a general validation test program was established in 2009. 28 The power producer has
the obligation to perform validation tests in order to demonstrate that its facilities meet the
Transmission Provider requirements. The purposes of this program are:
2. To validate numerical models and parameters associated with the WPP, specifically
those given to the Transmission Provider by the power producer, by comparing the
model response to recordings taken during field tests;
28
http://www.hydroquebec.com/transenergie/fr/commerce/pop_raccordement_transport.html
24
Present Status of Model Validation
3. Inertial response
5. Power factor
7. Power quality
The tests for the primary voltage regulation are performed on a single WTG and consist in
producing instantaneous voltage variations of low amplitude on the terminal of the WTG and
small voltage steps of limited duration injected directly into the WTG voltage control system.
Three-phase voltages and currents are recorded at the wind generator to measure the local
dynamic response of a wind generator to a rapid voltage change and to verify that the response
meets voltage regulation requirements. The results are also used to set the model parameters
(time constant and gain) used in dynamic simulations. The tests regarding the secondary voltage
regulation are similar but are conducted for the entire power plant.
The validation test program includes LVRT tests on one generating unit to verify that
requirements during undervoltage conditions are met. The power producer has the responsibility
to conduct the tests or to provide a complete report describing tests performed on an identical
generating unit (same software version) to demonstrate that the requirements are met. So far, no
LVRT tests were performed on site on WPP integrated on the Hydro-Québec network. However,
monitoring equipment has been installed at three locations in wind plants: at their point of
interconnection, on a 34.5 kV feeder of the collector system and on one generating unit. The
monitoring system records signals either continuously or upon detecting variations occurring at
the point of interconnection: active power variations, voltage sags and swells and system
frequency excursions. These signals are primarily voltages and currents but may also be
mechanical variables or other signals.
The field recordings recorded on the network can thereafter be used to validate the dynamic
response of the models. This is a time consuming effort that requires the collaboration of the
manufacturers to modify the models if necessary. Event recordings to-date have made possible
suitable validation of two Hydro-Québec Siemens PTI PSS®E models and one ElectroMagnetic
Transients Program (EMTP) model.
Inertial response requirements were not in defined for the projects started before 2005.
Consequently, existing wind plants do not have to fulfill them. However, the requirements have
to be met for WPP to be commissioned in 2011 and after. The corresponding validation tests
consist in emulated frequency steps and ramps of limited duration. Besides verifying the
25
Present Status of Model Validation
requirements, the test results will be used to validate the parameters of the models and their
dynamic response.
The power factor and the maximum ramp rates modules are tested with all WTGs in service to
verify that the requirements are met. Power factor tests consist in supplying and absorbing a
maximum amount of reactive power at different levels of active power. Maximum ramp rate
tests consist in performing a power plant shutdown sequence followed by a startup sequence.
These tests are not really used to validate the models but are rather helpful to fix model
parameters.
The last module regarding the power quality is not covered by scheduled testing but by means of
a monitoring system that verifies harmonics and emission limits. The recordings are compared to
the report provided by the developers to verify if the requirements are met. However, they are
not useful to validate the EMTP model since the WPP is represented by a single-wound
generator and does not simulate the detailed collector bus system and individual wind turbine
generators.
Hydro-Québec field-testing department (UMES) conducts a wide range of special tests and
measurements for Hydro-Québec and has done so for 30 years.
To test WPP, UMES installs a monitoring systems to record three-phase voltages and currents
generally at three locations within the plant: at the point of interconnection, at the starting point
of a 34.5 kV feeder of the collector system and at the terminals of a WTG connected to the same
monitored feeder. For extended model validation, other signals within the wind turbine are
monitored including the rotor side converter voltages and currents, the network side converter
currents, and the DC bus voltage.
High speed recorders with anti-aliasing filters are used. Normally, the sampling rate is 5 kHz
with at least a 200 second window per event. The monitoring system is reachable via an Ethernet
connection for remote trigger and data retrieval. UMES has also the responsibility to perform the
data processing and analysis of the recordings in order to verify the compliance with the
interconnection requirements and to extract relevant data for model validation.
26
Present Status of Model Validation
Hypersim
The Hydro-Québec Research Institute (IREQ) 29 also has an important expertise in control system
and wind generation modeling for extensive studies of electrical networks. The simulation
environment used is Hypersim, a real-time simulator and powerful simulation tool that uses a
highly detailed representation of the Hydro-Québec network. A full-transient detailed model of a
Type 3 WTG was developed at IREQ using the MATLAB® SimPower Systems Toolbox. The
model was also implemented in EMTP and in the Hypersim real-time simulator. 30 This model is
in the process of being validated with data processed by the UMES team. The range of events
recorded does not make it possible to validate the model completely and the design and
parameters will continue to be adjusted to improve the representation of the wind turbines. The
validation of the MATLAB® model developed by IREQ was very useful to validate and improve
Hydro-Québec’s Siemens PTI PSS®E user model. 31
29
http://www.hydroquebec.com/technology/index.html
30
R. Gagnon, G. Sybille, S.Bernard, D. Paré, S. Casoria and C. Larose, “Modeling and Real-Time Simulation of a
Doubly-Fed Induction Generator Driven by a Wind Turbine,” IPST Conf., Paper No. IPST05-162, Montréal,
Canada, 2005.
C. Larose, R. Gagnon, G. Turmel, P. Giroux, J. Brochu, D. McNabb and D. Lefebvre, “Large Wind Farm
Modeling Techniques for Power System Simulation Studies,” in Proc. 8th International Workshop on Large-Scale
Integration of Wind Power into Power Systems, Bremen, Germany, Oct. 14-15, 2009.
31
C. Langlois, D. Lefebvre, L. Dube and R. Gagnon, “Developing a Type-III Wind Turbine Model for Stability
Studies of the Hydro-Québec Network,” in Proc. 8th International Workshop on Large-Scale Integration of Wind
Power into Power Systems, Bremen, Germany, Oct. 14-15, 2009.
27
Present Status of Model Validation
turbines is multi-modal: a fast initial response to address severe perturbations as well as a slower,
grid friendly refinement. For purposes of this test, the automatic control of the capacitor bank by
WindCONTROL® was disabled and manual switching was used as a stimulus to record
individual WTG response.
The detailed plot in Figure 4.2 shows a zoomed view of the response to step change in voltage at
the WTG. The very fast initial response will dominate and saturate the controls for big events.
The wind plant will do everything as quickly as it can to mitigate a large disturbance. In this
case, the fast response took approximately 200 milliseconds. The slow, refined control then takes
over to allow for coordination with other equipment and maintain post-disturbance stability. This
aggregate response also allows for a very abrupt action when needed, and a grid-friendly
refinement that maintains stability in less severe cases.
The green curve in Figure 4.3 shows that when the capacitor is switched off-line, the measured
voltage at the point of interconnection (or POI) decreases due to reduced reactive power flowing
into the grid. The response of the individual WTGs is to rapidly increase reactive output to make
up for the loss of reactive power supplied by the shunt capacitor. The plant level control then
responds to this initial under-voltage condition and attempts to restore the POI voltage by
increasing each wind generator’s reactive output by equal amounts until the plant voltage settles
to the control set point determined by the operator. The lower traces in Figure 4.3 show a gap
during the period when the capacitor bank is online between total plant Q (Q_ACTUAL) and
summation of Q out of each WTG (Q_TURBINES). This gap represents the capacitive reactance
added by the shunt bank. When the capacitor is switched offline, the gap between Q_ACTUAL
and Q_TURBINES closes and all reactive power is supplied solely from the WTGs. The initial
loss in plant reactive power is mitigated within approximately 15 seconds as each WTG settles to
a new, increased level operating point of reactive power. This new, increased reactive level for
each WTG, is the total Q increase from all units on-line in the plant, divided by the total number
of units online at the time of the test.
Figure 4.4 shows a comparison between these measured values and the simulation results of the
PSLF model. Model outputs Qg, Qplant, Qcmd and Vreg correspond to measured Q_TURBINES,
Q_ACTUAL, Q_CMD and U_LINELINE respectively. This plot shows the model performance
adequately represents what is happening in the field. The response matches closely, with a
difference immediately following the switching operation being due to lower sampling rate in the
measurement than in the GE PSLF® simulation.
Response to grid events demands relatively rapid control action. Manual grid or plant operator
changes in operating set-points do not normally demand fast response, and indeed, system
behavior ought not to be rapidly disturbed by moving set-points. Figure 4.5 shows the response
of GE plant to 2% step in voltage reference. The blue trace in the figure shows a well mannered
response to the reference step. The red trace is from the simulation model, which matches very
28
Present Status of Model Validation
well. In the blue trace, after, the perturbation occurring about 8 seconds after the reference
change the plant supervisory control switched on a shunt capacitor to retain dynamic range on
the wind turbines. The switching perturbation is rapidly balanced by the turbines, allowing the
response to continue smoothly.
29
Present Status of Model Validation
30
Present Status of Model Validation
Figure 4.4: 10 MVar capacitor removal field test vs. simulation results
31
Present Status of Model Validation
+ 2%
Measured = Blue Simulat ed = Red
Vref
Step
QPOI
VPOI
- 2%
Vref
Step
32
Present Status of Model Validation
Figure 4.6: GE 2.5 WTG Fault Test vs. PSS/e Model Performance
The discussion provide above is solely geared to hardware testing and validation, however,
another highly valuable and legitimate means of providing validation of simulation models (for
planning and otherwise) is to use more complex simulation software to validate simpler
planning models. Manufacturers normally have highly complex, and highly proprietary, models
of their equipment. These models are used, among other things, to design equipment and are
normally physically based and must have sufficient fidelity for original equipment
manufacturers (OEMs) to make sound engineering judgments for equipment design and
application. The OEMs are highly motivated to have these detailed high fidelity equipment level
models. These detailed models therefore can often be used to design, test and validate simpler
planning models to be used by the industry.
There is a long, accepted history in the power industry of this practice. For example, a typical
(GE) gas turbine has on the order of 4,000 state variables in the design model; planning models
typically have on the order of four state variables: simplification is necessary and expected.
These design codes have been used to develop planning models of gas turbines. Figure 4.7
below shows a comparison between a fault simulation using a GE design code (GE WindTrap®)
and the planning model in GE PSLF® for a GE 1.5 (double fed machine) WTG.
33
Present Status of Model Validation
3.0
Windtrap
PSLF
2.0
Single WTG Real Power (M
1.0
0.0
-1.0
0 0.5 1 1.5 2
Time (Seconds)
Figure 4.7: Detailed Design Simulation (GE WindTRAP®) vs. GE PSLF® Model Performance
(active power during a severe fault for a GE 1.5 WTG)
34
Summary & Recommended Actions
This document has presented a general overview of modeling and model validation as it pertains
to variable generation resources. Clearly, to date, the bulk of the experience and work has been
on wind turbine generators. Never-the-less, similar approaches for modeling and model
validation are being pursued for other variable generator technologies such as PV.
Non-proprietary and publicly available models for the simulation of steady-state (power flow),
short-circuit (fault calculations) and dynamic (time-domain simulations) behavior of such
generation resources must be made readily available for use by power system planners.
Furthermore, these models should be routinely validated to ensure proper representation of
variable generation power plants in bulk power system studies. A model is valid if its dynamic
behavior is close enough to reality so that its influence on the network of interest (i.e. used for
power system studies) is consistent with the fidelity of model structures and available data for
the power system and other generation, as it pertains to the phenomena of interest (i.e. in stability
studies). That is, perfect curve fitting is not necessary, but to the extent possible erroneous model
dynamics must not result in a notable over-design or under-design of the network.
Each of the NERC standards discussed below in Section 5.2 address to aspects of meeting a
standard: (i) the technical requirement, i.e. the need to define, measure validate a model, its
parameters etc., and (ii) the procedural requirements, i.e. the functional model of how this
technical requirement should be met, reported and monitored. The bulk of this working group’s
recommendations stated below address the technical requirements. Variable generation is a new
and quickly evolving technology and consideration should be given to the timing with which
standards be implemented.
Section 5.1 below first gives a summary of the planning process based on NERC standards to put
the discussions in this report into context with the NERC standards. Then in Section 5.2 we
provided our recommendations and comments on the NERC existing and developing standards.
35
Summary & Recommended Actions
GO signs
Interconnection
Generator Interconnection Interconnection
Agreement and is
Interconnection Evaluation Study Facility Study
put in-service
Request
TO develops Facility
Interconnection requirements
and requests models and data
of the GO at each process stage
FAC-001
36
Summary & Recommended Actions
The generic model with associated parameters feed into the NERC model building process
shown in Figure 5.2. As an example, for WTG, presently there is insufficient evidence of the
accuracy of presently available generic models for WTG 32 for all the various WTG
manufacturers. Some confirmation tests during commissioning or type tests or comparison
simulation tests with a detailed model are necessary to get buy in from the Transmission
Owner/Planner. As the technology matures, and generic models are enhanced, and associated
data parameter sets are developed for specific machine types, the new generic models will
become more accepted as is the case with models of hydro or thermal plants.
Reliability Region
defines data
requirements
MOD-11
Reliability Region
defines data
requirements
MOD-13
32
PSS®E-32.0 Program Application Guide: Volume II, Chapter 21.
PSS®E-32.0 Model Library, Chapters 17 through 21
GE PSLF User's Manual. v.17.0_04. October, 2009.
37
Summary & Recommended Actions
The regional model building manuals developed as part of MOD-11 and MOD-13 must provide
sufficient clarity to model variable generation. These manuals may ask for best available models
or generic models. These models cover the operational time frame and the 10-year planning
horizon. The manuals do not currently cover the frequency for revalidating model data.
While not included in the standards, more emphasis is currently being placed on meeting the
Eastern Interconnection Reliability Assessment Group (ERAG) model building manual
requirements in addition to regional requirements.
MOD-24
Verify reactive
power capability
MOD-25
GO
Verify generator
excitation control
model
MOD-26
Verify turbine
governor model
MOD-27
38
Summary & Recommended Actions
“R.1.2 Generating Units (including synchronous condensers, pumped storage, etc.): location,
minimum and maximum Ratings (net Real and Reactive Power), regulated bus and voltage
set point, and equipment status.”
This statement could be read to equally apply to variable generation as a source of generation.
However, it may be prudent to explicitly include variable generation in this statement. For
example, to change the sentence to:
This MOD equally applies to variable generation and needs no augmentation. The requirements
in the MOD are quite generic. The requirements of this standard are dependent on and point to
MOD 13, discussed below.
This MOD explicitly discusses synchronous type generation. It would be beneficial to include an
explicit statement to cover variable generation. For example,
“Plant-specific dynamics data shall be reported for variable generating units (e.g. wind turbine
generators, PV etc.) such as the type of generating unit, its interface with the grid and the
appropriate model and model parameters to adequately represent unit dynamic response for
bulk power system studies. The typical size of a single variable generating unit (e.g. wind
turbine generators, PV array, etc.) is several hundreds of kilo-watts to several mega-watts.
Thus, it may be acceptable for the total plant to be represented by an adequate aggregated
model of the collector system and a single equivalent generating unit scaled up to represent
the total name-plate capacity for each type of generating technology employed in the plant.
Furthermore, models may need to be provided for other equipment installed in the collector
system or at the point of interconnection such as reactive compensation devices.”
39
Summary & Recommended Actions
This latest posting of this MOD, posted for commenting on January 18th, 2010, exempts variable
generation from this requirement. It states:
“Variable energy units such as wind generators, solar, and run of river hydro are exempt
from the requirements of this Standard.”
For a variable generation plant the definition of Real Power Capability can be slightly
challenging. One way to view it is to see the total gross capability as the sum of the nameplate
rating of all individual units within the plant, e.g. for a wind power plant the total sum of the
nameplate rating of all wind turbine generators in the plant. However, there must be two
realizations (i) the amount of actual power injected into the grid at the point of interconnection
requires a suitable representation of losses on the collector system and auxiliary loads, and (ii) by
its very nature variable generation is a highly variable energy source and thus it is quite rare to
find point in time when all units in the plant are coincidentally at their peak nameplate capacity.
Finally, the seasonal variable generation output variations need some discussion since they are
quite different than conventional generation technologies.
R1.5.1. Verified maximum gross and net Reactive Power capability (both lagging and
leading) at Seasonal Real Power generating capabilities as reported in accordance with
Reliability Standard MOD-024 Requirement 1.5.1.
Note: the above requirements are from the existing version of the standard. MOD-025 is
currently being enhanced.
Although all of the above could equally apply to variable generation, some clarification may be
needed. Namely, variable generation reactive capability of the “power plant” is not entirely
inherent in the individual generating units. A variable generation power plant, such as a wind
power plant, may contain many reactive power sources such as the individual generating units
themselves (e.g. Type 3 or 4 WTG, see Appendix I), discretely switched shunt reactive devices
40
Summary & Recommended Actions
(e.g. shunt capacitors or reactors), smoothly controlled shunt reactive devices (e.g. SVC or
STATCOM), or a combination of these devices. Thus, care should be taken as to how the total
reactive capability of the power plant is defined and at what point (e.g. point of interconnection,
and whether this is defined as the high or low side of the substation transformer). Also, it may
not be practical under normal operating conditions to exercise the full reactive capability of the
power plant (this is a known issue, even with conventional synchronous generator plants) to test
it, thus it should suffice to demonstrate the plants reactive capability to the extent possible in the
field and to then augment this with engineering calculations to derive the plants full reactive
capability. This is particularly, true of variable generation because there is no control over the
energy resource. So for example, a typical wind power plant may only achieve its name-plate
rating for a hour or two during an entire year. Thus, it would not be possible to demonstrate the
full reactive capability of the plant in the field. Rather, it should suffice to demonstrate the
reactive capability of a single WTG and then to derive through engineering calculations
(considering all other reactive devices in the plant, such as SVC, STATCOM etc.) the total
reactive capability of the plant. These comments should be somehow used to appropriately
modify MOD 25.
MOD-026-1 — Verification of Models and Data for Generator Excitation System Functions –
SECOND POSTING (and MOD 27)
MOD 26 (and MOD 27 Verification of Models and Data for Turbine/Governor and Load
Control) are presently under development 33. These two standards deal specifically with the
routine validation of generating unit dynamic models for power system stability studies.
Presently, these standards are tailored explicitly to deal with synchronous type generators, since
much of the language revolves around technology associated with synchronous generation (e.g.
excitation system, AVR, power system stabilizers etc.). Thus, the following key items need to be
clarified in these standards, as they pertain to variable generation. In addition, the comments that
follow apply to all components in a variable generation plant that may include devices such as
the actual power generating units, shunt compensation devices, centralized control systems
spanning the entire facility, etc.:
1. Unit/Plant Size for Validation: These MOD’s specify the size of generating unit above
which model validation is required. It should be recognized that the typical size of a
33
MOD 26 and MOD 27 standards under development are found at http://www.nerc.com/filez/standards/Generator-
Verification-Project-2007-09.html.
41
Summary & Recommended Actions
2. Validation of various technologies in a single plant: Variable generation power plants can
consist of multiple generation technologies. For example, a wind power plant may
consist of WTGs of two different types. Thus, we need to consider the following points
as they pertain to variable generation:
a. For a uniform variable generation plant (i.e. all generating units are of the same
technology type) a single aggregate generator model representation should be
sufficient.
i. The size of the group is a significant proportion of the total plant size (e.g.
> 20% of plant rating).
ii. Each group should represent a unique characteristic (e.g. Type 1 WTG as
compared to a Type 3 WTG).
3. Validation of different control layers: Variable generation plants, such as wind power
plant, may have several functional layers of control. For example, in a wind power plant
with Type 3 WTGs we may have one level of closed loop voltage regulation at the
terminals of the WTG, a second slower control loop that regulates voltage at the point of
interconnection (POI), and a third layer of control that coordinates the switching of shunt
capacitors at the POI based on the reactive output of the individual WTGs. In addition,
devices such as STATCOMs may be present at the POI. Modeling and model validation
should incorporate such devices/control layers to the extent that the dynamics of these
functional layers are important for stability studies (see Figure 3.1).
4. Modeling and Model Validation: Models are an emulation of actual equipment. Not all
model parameters necessarily translate to actual physical components or measureable
features. Judgment needs to be exercised in the modeling and validation process.
42
Summary & Recommended Actions
b. Models should state clearly the type and the range of events they have been
designed to simulated and the limitation of the models beyond which the model
deviates from the actual variable generation plant performance (e.g. a model
developed to represent electrical transient behavior of a WTG may not be
adequate for studying wind fluctuations over a many minute time frame).
c. In general, the best approach to model validation is to use field (or test bench)
measurements of various disturbances that must exercise the different control
functions to a wide range of operation points. For example, a model is not
necessarily valid if the only a comparison between simulation results and field
measurements for a single voltage step response is performed at one operating
condition. Ideally, illustration of validation against recorded response to various
system disturbances (faults, frequency deviations, etc.) gives the greatest
confidence in validation.
d. A model is valid if its dynamic behavior is close enough to reality so that its
influence on the network of interest (i.e. used for power system studies) results in
relatively negligible errors for the phenomena of interest (i.e. in stability studies).
That is, perfect curve fitting is not necessary, but to the extent possible erroneous
model dynamics must not result in a notable over-design or under-design of the
network.
43
Summary & Recommended Actions
7. Issues related to the fuel source for variable generation: For variable generation one
needs to be cognizant of the variable nature of the energy source and thus the possible
impracticality of performing model validation at a desired plant output, but rather having
to accept model validation at whatever plant output can be achieved at the time of testing
or disturbance monitoring.
a. Many variable generation technologies are rapidly changing, for example in wind
power plants new control software or new setting may be uploaded every year, if
not sooner.
c. If the changes are significant, the existing dynamic models should be revalidated
– say within three months or so after the update/upgrade. The changes (which
may include a new module, new software etc.) should be reported to the local
Regional Entities.
44
Appendix I: Wind-Turbine Generation (WTG) Technologies
GRID
3
GEAR BOX
WOUND ROTOR
INDUCTION GENERATOR TRANSFORMER
GRID
3
GEAR BOX
3
Rectifier IGBT R
Control
34
(b) Type 2 Wind Turbine-Generator: Variable Slip Induction Generator
34
IGBT R control = Resistor controlled by Insulated Gate Bi-Polar Transistor
45
Appendix I: Wind-Turbine Generation (WTG) Technologies
WOUND ROTOR
INDUCTION GENERATOR TRANSFORMER
GRID
3
GEAR BOX
3
SYNCHRONOUS
GENERATOR TRANSFORMER
GRID
3 3
GEAR BOX Rectifier IGBT
Inverter
46
Acronyms
Acronyms
DFAG – Doubly Fed Asynchronous Generator (also often referred to as DFIG – Doubly Fed
Induction Generator)
PV – Photovoltaic
47
Acronyms
48
IVGTF Roster
49
IVGTF Roster
50
IVGTF Roster
51
IVGTF Roster
52
References
[2] CIGRE Technical Brochure 328, Modeling and Dynamic Behavior of Wind
Generation as it Relates to Power System Control and Dynamic Performance,
Prepared by CIGRE WG C4.601, August 2007 (available on-line at:
www.e-cigre.org)
[4] G. Lalor, A. Mullane and M. J. O’Malley, “Frequency Control and Wind Turbine
Technologies,” IEEE Transactions on Power Systems, Vol. 20, pp. 1903-1913,
2005.
[8] ESB National grid, “Dynamic modeling of wind generation in Ireland”, January
2008
53
References
[11] Bialasiewicz, J. T.; Muljadi, E.; Nix, R. G.; Drouilhet, S., "Renewable Energy
Power System Modular Simulator: RPM-SIM User's Guide," National Renewable
Energy Laboratory, March 2001, NREL/TP-500-29721.
[12] N. Miller, K. Clark, J. MacDowell and W. Barton, "Experience with Field and
Factory Testing for Model Validation of GE Wind Plants," European Wind Energy
Conference & Exhibition, Brussels, Belgium, March/April 2008
54